Download Eaton Power Xpert 9395 550/275 Specifications

Transcript
CHI Control Components
Enclosures
UPS
catalogue
• Bullet 1
• Bullet 2
• Bullet 3
Eaton UPS solutions
Headline
be
nt to
Conte ided
prov
• Bullet 4
• Bullet 5
• Bullet 6
Energizing a world
that demands more.
Discover today’s Eaton.
Powering business worldwide
As a global power management company, we help
customers worldwide manage the power needed
for buildings, aircraft, trucks, cars, machinery
and businesses.
Eaton’s innovative technologies help customers manage
electrical, hydraulic and mechanical power more reliably,
efficiently, safely and sustainably.
We provide integrated
solutions that help make
energy, in all its forms,
We deliver:
•
more practical and
Electrical solutions that use less energy, improve power reliability
and make the places we live and work safer and more comfortable
•
Hydraulic and electrical solutions that enable machines
to deliver more productivity without wasting power
•
With 2012 sales
of $21.8 billion on
a pro forma basis,
Eaton has approximately
Aerospace solutions that make aircraft lighter, safer and less
costly to operate, and help airports operate more efficiently
•
accessible.
Vehicle drivetrain and powertrain solutions that deliver
more power to cars, trucks and buses, while reducing fuel consumption
and emissions
102,000 employees
around the world and
sells products in more
than 175 countries.
Eaton’s electrical business
Eaton is a global leader with expertise in:
•
Power distribution and circuit protection
•
Backup power protection
•
Solutions for harsh and hazardous environments
•
Lighting and security
•
Structural solutions and wiring devices
•
Control and automation
•
Engineering services
Eaton is positioned through its global solutions to answer
today’s most critical electrical power management challenges.
With 100 years of electrical experience behind us, we’re
energized by the challenge of powering up a world that
demands twice as much energy as today. We’re anticipating
needs, engineering products and creating solutions to energize
our markets today and in the future.
We are dedicated to ensuring that reliable, efficient and safe
power is available when it’s needed most.
Eaton.com
Eaton’s heritage in industry
-leading UPS design and
production
For more than 50 years, Eaton has been safeguarding the critical systems of businesses across the globe. Whether protecting
a single desktop or a large data centre, Eaton solutions provide
clean, uninterrupted power to keep mission-critical applications
working. We offer a comprehensive range of environmentally
sensitive, efficient, reliable UPSs, surge protective devices, power
distribution units (PDUs), remote monitoring solutions, meters,
software, connectivity solutions, enclosures, airflow management and professional services. We work with IT and facilities
managers to effectively manage power in virtually every business
segment, including data centres, retail outlets, healthcare organisations, governmental agencies, manufacturing firms, broadcasting companies, financial institutions, and a wide variety of other
areas. Our solutions provide the power to make a difference,
helping you achieve your business goals while maintaining an
environmentally sustainable enterprise.
www.eaton.eu/powerquality
5
Contents
UPS basics
Why use UPS?
6
Power protection for different needs
7
PC, Workstation and home AV UPS
Eaton Protection Box
8
Eaton Protection Station
10
Eaton 3S UPS
12
Eaton Ellipse ECO UPS
14
Eaton 5S UPS
16
Eaton Ellipse PRO UPS
18
Network and Server
Eaton 5SC UPS
20
Eaton 5P UPS
22
Eaton 5130 UPS
24
Eaton 5PX UPS
26
Eaton 9130 UPS
28
Eaton EX UPS
30
Eaton 9SX UPS
32
Eaton 9PX UPS 34
Data Center and Facility UPS
Eaton BladeUPS
36
Eaton 9155 and 9355 UPS
38
Eaton 9355 UPS
40
Eaton 93E UPS
42
Eaton 93PM UPS
44
Power Xpert 9395 UPS
46
IT racks and power distribution units
Eaton RP Series IT Rack
48
Eaton FlexPDU
50
Eaton HotSwap MBP 50
Managed ePDUs
52
Advanced Monitored ePDUs
52
Switched ePDUs
52
Monitored ePDUs
53
In-Line Monitored ePDUs
53
Basic ePDUs
53
Software & connectivity
Intelligent Power Software
54
Intelligent Power Manager
55
Intelligent Power Protector
56
Connectivity Options
57
Green life cycle
Green by design
58
Technology
Hot Sync Technology 60
ABM Technology
62
Energy Saver System
64
Variable Module Management System
66
UPS basics
Why use UPS?
An uninterruptable power supply (UPS) protects IT
equipment and other electrical loads from problems
that can affect the public electricity supply.
It performs the following three basic functions:
1. Prevents hardware damage typically caused by surges and
spikes. Many UPS models continually condition incoming power
as well.
2. Prevents data loss and corruption. Without a UPS, data stored
on devices that are subjected to a hard system shutdown may
become corrupted or even lost completely. In conjunction with
power management software, a UPS can facilitate a graceful
system shutdown.
3. Provides availability for networks and other applications while
preventing downtime. UPSs can also be paired with generators
in order to give the generators sufficient time to power up in
the event of a power cut.
Eaton UPSs address all of the nine common
power problems described below:
5. Overvoltage
1. Power failure
typically caused by lightning strike
or fault with the power company’s
equipment. Without a UPS, this will
cause a hard shutdown, putting data at
risk.
Increased supply voltage lasting from
minutes to days. Often triggered by
rapid reductions in power demands,
overvoltage can damage hardware.
6. Electrical noise
2. Power sag
Short-term voltage reduction, often
caused by start-up of nearby large
loads. Power sags can cause equipment
crashes and hardware damage.
“Interference”, typically from radio
transmitters, welding equipment
etc. Noise can cause hard-to-find
intermittent problems.
7. Frequency variation
3. Power surge
Short-term high voltage, usually caused
by lightning strike nearby. Spikes
almost always lead to data loss and/or
hardware
damage.
Changes in supply frequency, usually
only found on supplies from generators.
8. Switching transient
Instantaneous undervoltage, typically
lasting a few nanoseconds.
4. Undervoltage
Reduced supply voltage lasting from
minutes to days. Typically occurs when
supply network is overloaded. Can lead
to computers behaving unpredictably.
9. Harmonic distortion
Disortion of the normal smooth supply
waveform. Can be caused by variable
spreed drivers and even photocopiers.
Can cause communication errors,
overheating and hardware damage.
6
EATON UPS Catalogue
UPS topologies for different needs
Three common UPS topologies described below
provide varying degrees of protection for your
equipment.
Passive standby topology (off-line) is the most frequently
used UPS topology for protecting PCs against power failure, power
sag and power surge. In normal mode, the UPS supplies power to
the application directly from the mains, filtered but without active
conversion. The battery is charged from the mains. In the event of
a power cut or fluctuation, the UPS delivers stable power from the
battery. The advantages of this topology are low cost and adequacy
for office environments. Passive standby topology is not suitable
if the power supply is of low quality (industrial sites) or subject to
frequent disruptions.
Line interactive topology is used for protecting enterprise networks and IT applications against power failure, power sag, power
surge, undervoltage and overvoltage. In normal mode, the device
is controlled by a microprocessor that monitors the quality of the
supply and reacts to fluctuations. A voltage compensation circuit
is enabled to boost or reduce the supply voltage to compensate
for the fluctuations. The main advantage of this topology is that it
enables compensation of under and overvoltage without using the
batteries.
Double conversion topology (on-line) is a basis for UPSs
designed for continuous power protection of critical equipment
against all nine power problems: power failure, power sag, power
surge, undervoltage, overvoltage, switching transient, line noise,
frequency variation and harmonic distortion. It ensures a consistent
quality of power supply regardless of disturbances in the incoming
mains. The output voltage is entirely regenerated by a sequence of
AC to DC conversion followed by DC to AC conversion in order to
create power supply without any electrical interference. Double conversion UPSs can be used with any type of equipment as there are
no transients when changing over to battery power.
www.eaton.eu
7
PC, Workstation and home AV UPS
Surge protection
Eaton Protection Box
1/5/8 sockets
Surge protection
The Eaton Protection Box multi-way block with high performance
surge protection is a simple solution for protecting delicate
equipment.
Effective surge protection
The Protection Box is designed to filter the power supply for
delicate equipment to protect it against surges, interference and
the indirect effects of lightning.
Eaton Protection Box 8
The high performance of the Protection Box is based on an
advanced design with surge protection in compliance with IEC
61643-1.
Complete protection
Eaton Protection Box 5
• The Protection Box range has models with 1, 5 or 8 sockets.
Some models also provide protection for telephone connections
that can carry surges to the equipment.
• Tel@ models: with telephone / broadband Internet access
protection
• Tel@ + TV models: with telephone / broadband Internet access
protection + Audio/Video protection module (surge protection
for television and FM radio with TV and F -Type connectors)
Practical and economical:
replaceable surge protection module
(Protection Box 5 Tel@, 5 Tel@ + TV and 8 Tel@ + TV)
The surge protective components for these models are grouped
into a pluggable module for:
Eaton Protection Box 1
Advanced protection:
• Computers, peripherals and multimedia
• TV, Video and Hi-Fi equipment: Home cinema,
DVD writers, digital decoders, etc.
• Broadband modems (Internet and TV)
• IP telephony
• Household goods, etc.
• Easy replacement if the surge protective devices are destroyed
by a major surge (no need to disconnect the equipment and the
pluggable unit is an Eaton standard replacement part)
• Can be updated (adding functions, changing connectors, etc.)
Warranty for connected equipment
Eaton offers free warranty for the equipment connected (applicable
for EU countries and Norway only). This insurance is included in the
purchase price of the Protection Box and covers up to 50 000 € for
an 8 socket model to cover damage caused by a failure of the
surge protection.
And lots of features to simplify life
• Power ON and active protection indicators
• PowerLine Communications compatibility (Protection Box 5/8)
for connecting PLC adapters
• Cable ties and cable markers supplied (5 and 8 socket models)
• Sockets arranged to allow blocks to be plugged side by side
8
EATON UPS Catalogue
Eaton Protection Box
Power ON indicator
Widely spaced sockets
for transformer units,
Active protection indicator
1 PLC-ready outlet
Telephone / broadband protection
(for Protection Box 5 and 8)
Replaceable surge protection module
All outlets with safety shutters
Eaton Protection Box 8
Eaton Protection Box 5
Audio/Video protection module
available (for Protection Box 5 Tel@
+ TV and 8 Tel@ + TV only)
TECHNICAL SPECIFICATIONS
Rating (A/W)*
Voltage/frequency
IEC 61643-1 tested
PowerLine compatibility
Surge test conditions
Surge test conditions for IEC 61643-1
with 8/20μs pulse
Protective devices
Total rating
Response time
Total power absorbed
EMI/RFI filter
52dB from 100kHz to 100MHz
Telephone and audio/video line protection
RJ11/RJ45 telephone including broadband
Audio/Video line
Marking and standards
Safety
EMC
Surge protection
Dimensions and weight
Dimensions H x W x D
Weight
Customer Service & Support
2 years warranty
Replaceable surge protection module
1
1 Tel@
16 A / 3 680 W
16 A / 3 680 W
220 V – 250 V / 50/60 Hz
Yes
Yes
/
/
5
5 Tel@
5 Tel@+TV
8 Tel@+TV
10 A / 2 300 W
10 A / 2 300 W
10 A / 2 300 W
10 A / 2 300 W
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Uoc = 6.6 kV, Up = 1.5 kV, In = 2.5 kA, Imax = 8 kA
30 000 A, 3 x MOV 10 000 A
<1ns
1110 Joules
/
Yes
/
Yes
Yes
Yes
/
/
10 000 A
/
/
/
10 000 A
/
10 000 A
10 000 A
10 000 A
10 000 A
IEC 60-950, NFC 61-303
EN 55082-2, EN 55022 class B, EN 61000-4-4, level 4 IEC 61000-4-5, level X=10kV
IEC 61 643-1
67 x 70 x 105 mm
0.160 kg
67 x 70 x 105 mm
0.210 kg
65 x 120 x 255 mm 65 x 120 x 260 mm 65 x 120 x 260 mm 65 x 150 x 315 mm
0.610 kg
0.770 kg
0.840 kg
0.850 kg
Standard product exchange ; warranty for connected equipment up to 50 000 €
Standard exchange free of charge from Eaton aftersales services
* Calculated for a nominal voltage at 230 V
Part Numbers
French sockets (FR)
“Schuko” sockets (DIN)
French sockets (FR-B) for Belgium
FR
1
66 706
66 708
/
1 Tel@
66 707
66 709
/
5
66 710
66 712
66 932
5 Tel@
66 711
66 713
66 933
5 Tel@+TV
66 934
66 936
66 938
8 Tel@+TV
66 935
66 937
/
DIN
www.eaton.eu
9
PC, Workstation and home AV UPS
Surge protection & UPS
Eaton Protection Station
500/650/800 VA
Combined UPS/surge protection/
multiple socket device
Innovative solutions offering total protection for home
computers and digital leisure devices.
Protect all your equipment against power failures and
voltage fluctuationss
Eaton Protection Station can do this, offering in a single device:
• Up to 8 standard outlets
• A high performance surge suppressor
• A UPS with 20 to 30 minutes battery back-up for a typical PC
The first UPS in its class with energy-saving features
Eaton Protection Station 800
Eaton Protection Station boasts an efficient electrical design with
EcoControl function that automatically disables peripherals
when the master device (Computer, HD TV, Home network
storage, etc...) is turned off. This will help you save up to 30%
energy compared to previous generation UPSs.
A model for every application
Three versions (500 VA/250 W, 650 VA/400 W or 800 VA/500 W
backup power), to protect an internet PC, a multimedia computer
with peripherals or a hardcore gamer configuration.
Thanks to its multi-position format Eaton Protection Station can fit
anywhere.
Guaranteed peace of mind
Multi-position
Advanced protection for:
• Home computing
• Digital leisure equipment
10
EATON UPS Catalogue
• Surge suppressor compatible with IEC 61 643-1 standard
(+ status indicator)
• USB port and power management software as standard
(650 & 800 models)
• Data line protection to ensure that the internet line
(including xDSL) is protected against surges
• Unlimited warranty for the connected computer equipment
(EU countries and Norway only)
• Periodic test and battery replacement indicator
Eaton Protection Station
Surge protection status indicator
One PLC-ready outlet
Line protection for telephone/ ADSL Internet
Replaceable batteries
Spaced outlets, compatible with local standards
Reset button (circuit breaker)
Outlets with surge protection
USB port (650 & 800) and Windows/Linux/Mac software
Outlets with surge protection and back-up power
Indicator for mains/battery operation with additional
audible alarms for overload and faults
Two EcoControl outlets (650 & 800)
Eaton Protection Station 650 & 800
TECHNICAL SPECIFICATIONS 500
Technology
Application
Outlets
650
800
High frequency UPS with surge protection
6 standard outlets (3 with back-up power and surge 8 standard outlets (4 with back-up power and
surge protection + 4 with surge protection)
protection + 3 with surge protection)
Performance
Output power capacity (backup outlets)
Output power capacity (all outlets)
Input voltage range
Output voltage and frequency
Protection
500 VA - 250 W
5 A - 1150 VA
184 V - 264 V
230 V - 50 / 60 Hz auto-selection
Resettable circuit breaker
650 VA - 400 W
10 A - 2300 VA
Up to 160 V - 284 V (adjustable)
800 VA - 500 W
10 A - 2300 VA
Up to 160 V - 284 V (adjustable)
Batteries
Battery type
Battery monitoring
Battery operation
Typical application
Backup time with typical application
Replaceable sealed lead-acid batteries
Automatic battery test, battery replacement indicator, protection against deep discharges (4-hour limit)
Cold-start capable (mobile power source), battery charging even in OFF position
1 internet computer
1 multimedia computer + peripherals
1 computer high graphics power
20 min
30 min
30 min
Features
User interface
Surge protection
Performance on 8/20 wave
Operation with mains/battery power, surge suppressor status, overload, battery replacement, fault, audible alarms
Save up to 30% energy* (efficient electrical design and automatic deactivation of idle
/
peripherals)
Complete common and differential mode protection - 3 MOV – Total power: 525 Joules, compatible with IEC 61643-1 standard
Uoc = 6 kV
Uoc = 6 kV
Uoc = 6 kV
Up = 1.5 kV
Up = 1.7 kV
Up = 1.7 kV
In = 2.5 kA
In = 2.8 kA
In = 2.8 kA
I max = 8 kA
I max = 8 kA
I max = 8 kA
PowerLine compatibility
Data line protection
Installation
/
1 PLC-ready outlet
Protection for telephone/fax/modem/Internet ADSL line + Ethernet network
Requires earth connection
EcoControl
1 PLC-ready outlet
Standards
Standards
Quality and environment
IEC 62040-1, IEC 62040-2, IEC 61643-1
ISO 9001, ISO14001
Dimensions and weight
Dimensions W x H x D
Weight
155 x 304 x 137 mm
2.9 kg
185 x 327 x 149 mm
3.8 kg
185 x 327 x 149 mm
4 kg
/
/
USB port
USB port
Personal Solution-Pac software on CD, compatible with Windows Vista/XP/Mac/Linux
(power management, Automatic system shutdown, Alarm notification, Events log)
Power Management
Com port
Software
Customer service & support
2 years guarantee
Warranty+
Standard product exchange, including the battery ; warranty for the connected computing equipment for an unlimited amount (EU countries)
Optional 3 years warranty (depending on the country please visit www.eaton.com/powerquality)
*compared to UPS from the previous generations
Part Numbers
500
650
800
FR outlets
DIN outlets
66 942
66 943
61 061
61 062
61 081
61 082
FR
DIN
™
www.eaton.eu
11
PC, Workstation and home AV UPS
Single phase UPS
Eaton 3S UPS
550/700 VA
Power protection for office and
home computer equipment
Protection against power problems
• The Eaton 3S UPS helps to protect your computer equipment in
case of everyday events such as lightning strikes, storms, overdemand on the utility grid, accidents, and
natural disasters knocking out power without warning.
• In the event of a total blackout, the unit provides sufficient
battery backup time to last through most power outages.
• The 3S also protects telephone, broadband and Ethernet line
from “back door” power surges.
• The shutdown software makes it possible to automatically save
your work and shut down your application without
losing any data. Once the power is restored, you can
continue working exactly where you left off.
Easy integration and installation
Ideal for protecting:
•
•
•
•
12
Computers and peripherals
Broadband modems (internet and TV)
IP telephony equipment
Point-of-sale equipment
EATON UPS Catalogue
• Attractive design and glossy finish make the 3S a perfect fit for
the modern office environment.
• The 3S comes with either 6 Schuko (DIN) or 6 French (FR)
outlets for easy connection of typical computer configurations
with peripherals (IEC model also available with
8 outlets).
• The 3S features a HID-compliant USB port (cable supplied),
for automatic integration with common operating systems
(Windows/Mac OS/Linux).
• Compact unit fits on or under your desk or can be
mounted on a wall.
• Easy-to-replace battery helps to extend UPS service life.
Eaton 3S UPS
3 Schuko or FR outlets with surge
4 IEC outlets with surge
protection
protection
3 Schuko or FR outlets with battery 4 IEC outlets with battery
backup and surge protection
backup and surge protection
On / Off button + LED interface
On / Off button + LED interface
USB port
USB port
Dataline protection
Dataline protection
Replaceable battery
Replaceable battery
7
Reset button (circuit breaker)
8
Wall-mounting system
Eaton 3S 700 DIN
Eaton 3S 700 IEC
TECHNICAL SPECIFICATIONS
Eaton 3S 550
Eaton 3S 700
Rating (VA/W)
Application
Output connection (FR/DIN models)
Output connection (IEC models)
Characteristics
Input voltage
Output voltage
Frequency
Input protection
Battery
Battery type
Battery test
Cold start (no mains power)
Deep-discharge protection
Battery replacement indicators
50% load backup
70% load backup
Communication
Communications port
550 VA / 330 W
700 VA / 420 W
Line protection
Standards compliance
Safety
EMC
Dimensions, weight and colour
Dimensions H x W x D
Weight
Colour
Customer service & support
7
Reset button (circuit breaker)
8
Wall-mounting system
3 outlets with battery backup and surge protection + 3 outlets with surge protection
4 outlets with battery backup and surge protection + 4 outlets with surge protection
Up to 161-284 V (adjustable)
230 V (settable to 220 V, 230 V or 240 V)
50-60 Hz autoselect
Resettable circuit breaker
Compact, sealed lead-acid (replaceable)
Yes
Yes
Yes
LED
10 min
6 min
Yes
Yes
Yes
LED
9 min
6 min
HID-compliant USB port for automatic integration with most common operating systems
(Windows XP, Vista and 7, Linux, Mac OS X), cable supplied
Tel/fax/modem/internet/Ethernet
IEC/EN 62040-1, CE mark
IEC 62040-2
86 x 140 x 335 mm
2.9 kg
Black
86 x 170 x 335 mm
3.8 kg
Black
2-year warranty
Standard product exchange, including battery
Warranty+
Optional 3-year warranty (depending on the country please visit www.eaton.com/powerquality)
Part numbers
550
700
French sockets (FR)
Schuko sockets (DIN)
IEC sockets
3S550FR
3S550DIN
3S550IEC
3S700FR
3S700DIN
3S700IEC
FR
DIN
IEC
www.eaton.eu
13
PC, Workstation and home AV UPS
Single phase UPS
Eaton Ellipse ECO UPS
500/650/800/1200/1600 VA
Energy-efficient power protection for business
computers
Eaton Ellipse ECO range
• With an efficient electrical design and the EcoControl function
(USB models), which automatically disables peripherals when
the master device is turned off, the Eaton Ellipse ECO helps you
make energy savings of up to 25 per cent compared to previousgeneration UPSs.
• As well as providing a power supply backed up by a battery to
keep equipment operating during a power failure, the Ellipse
ECO also provides effective protection against damaging surges.
• The Ellipse ECO includes a high performance surge-protection
device that complies with IEC 61643-1; this device also protects
data connections such as Ethernet, internet and telephone lines.
Easy integration and installation
• The Ellipse ECO comes with either four (500/650/800 models)
or eight outlets (1200/1600 models) with Schuko (DIN) or
French (FR) format for easy connection to typical computer
configurations with peripherals. IEC models are also available.
• The Ellipse ECO’s extra-flat design makes it easy to install in
any office environment: installation options include vertical box
format, below the desk, horizontally under a monitor, 19” rackmounted (optional 2U kit) and wall-mounted (optional kit).
• The USB models are designed to be compatible with a wide
variety of different computer models. Eaton Intelligent
Power® Manager software is delivered as standard (CD and
USB cable supplied) and is compatible with all major operating
systems (Windows 7, Vista, XP, Linux and Mac OS).
Eaton Ellipse ECO easy integration
14
EATON UPS Catalogue
Complete peace of mind
• Unlimited warranty for the connected computer equipment
(EU countries and Norway only)
• Periodic battery self-test ensures early detection of a battery
that needs to be replaced.
• Easy-to-replace battery helps to extend UPS service life.
• Push-button circuit breaker enables easy recovery from an
overload or short circuit.
Eaton Ellipse ECO
Three outlets with surge protection and backup ,
Four outlets with surge protection and backup
Four outlets with surge protection
One EcoControl outlet (USB models)
two EcoControl outlets (1200 & 1600)
Tel/Internet and Ethernet protection
one socket with surge protection only
Tel/Internet and Ethernet protection
USB port (USB models)
USB port
Replaceable batteries
Replaceable batteries
Reset button (circuit breaker)
Reset button (circuit breaker)
Eaton Ellipse ECO 1200/1600
Eaton Ellipse ECO 500/650/800
TECHNICAL SPECIFICATIONS
500
650
650 USB
800 USB
1200 USB
1600 USB
Rating (VA/W)
Application
Number of outlets
Outlets with surge protection and backup /
Outlets with surge protection
Characteristics
Nominal input voltage
Input voltage
Output voltage
Frequency
Input protection
Features
Energy efficient design
500 VA / 300 W
650 VA / 400 W
650 VA / 400 W
800 VA / 500 W
1200 VA / 750 W
1600 VA / 1000 W
4
3/1
4
3/1
4
3/1
4
3/1
8
4/4
8
4/4
Yes
Yes
Yes
Yes
230 V
184 V - 264 V (adjustable to 161 V - 284 V)
230 V (adjustable to 220 V, 230 V, 240 V
50-60 Hz autoselect
Resettable circuit breaker
EcoControl function
Yes
Yes
-
-
Yes up to 20% energy saving*
Yes up to 25% energy saving*
(automatic deactivation of idle peripherals)
Surge protection device compliant with IEC 61643-1
1 PLC-ready outlet 1 PLC-ready outlet 1 PLC-ready outlet
1 PLC-ready outlet
Surge protection
PowerLine compatibility
Battery
Battery type
Automatic battery test
Cold start (start without mains)
Deep discharge protection
Battery replacement indicators
Battery runtime at 50% load
Battery runtime at 70% load
Communication
Communication port
-
-
Software
-
-
Line protection
Standards
Safety / EMC
Surge protection
Dimensions and weight
Dimensions H x W x D
Weight
Customer Service & Support
Tel/Fax/Modem/Internet and Ethernet
Replaceable sealed lead acid
Yes
Yes
Yes
Yes
4 hours
4 hours
LED + audible alarm
9 min
9 min
5 min
6 min
Yes
Yes
4 hours
Yes
Yes
4 hours
Yes
Yes
4 hours
Yes
Yes
4 hours
9 min
6 min
11 min
6 min
10 min
6 min
11 min
6 min
USB port
USB port
USB port
(cable supplied)
(cable supplied)
(cable supplied)
Eaton Intelligent Power software delivered as standard
(compatible with: Windows 7/Vista/XP, Mac OS X, Linux)
USB port
(cable supplied)
IEC 62040-1, IEC 60950-1, IEC 62040-2, CB Report, CE mark
IEC 61643-1
263 x 81 x 235 mm 263 x 81 x 235 mm 263 x 81 x 235 mm 263 x 81 x 235 mm 305 x 81 x 312 mm
2.9 kg
3.6 kg
3.6 kg
4.1 kg
6.7 kg
305 x 81 x 312 mm
7.8 kg
Standard product exchange, including the battery ; warranty for the connected computing equipment for an
unlimited amount (EU countries)
Optional 3-years warranty (depending on the country please visit www.eaton.com/powerquality)
2 years warranty
Warranty+
Part Numbers
500
650
650 USB
800 USB
1200 USB
1600 USB
French outlets (FR)
Schuko outlets (DIN)
IEC outlets
Accessories
19” rack mounting kit (2U)
Wall mounting kit
EL500FR
EL500DIN
EL500IEC
EL650FR
EL650DIN
EL650IEC
EL650USBFR
EL650USBDIN
EL650USBIEC
EL800USBFR
EL800USBDIN
EL800USBIEC
EL1200USBFR
EL1200USBDIN
EL1200USBIEC
EL1600USBFR
EL1600USBDIN
EL1600USBIEC
ELRACK
ELWALL
ELRACK
ELWALL
ELRACK
ELWALL
ELRACK
ELWALL
ELRACK
ELWALL
ELRACK
ELWALL
FR
DIN
IEC
www.eaton.eu
15
PC, Workstation and home AV UPS
Single phase UPS
Eaton 5S UPS
550/700/1000/1500VA
Affordable power protection for workstations
Performance
• The Eaton 5S UPS provides effective power protection, even
in disturbed electrical environments. Voltage fluctuations are
automatically corrected using an AVR device (booster/fader),
without needing the batteries.
• The 5S not only provides a supply with battery backup to keep
equipment operating during power cuts, but also provides
effective protection against damaging surges.
Reliability
Eaton 5S UPS product range
• The 5S protects networked equipment from “back door” power
surges coming through Ethernet, internet
or telephone lines.
• The 5S’s periodic automatic battery testing ensures
early detection if a battery needs to be replaced.
• The easy-to-replace battery helps to extend
the UPS service life.
Versatility
Eaton 5S versatility
Ideal for protecting:
Workstations
Business Telephony
Network devices
Point-of-sale equipment
16
EATON UPS Catalogue
• The 5S can be installed vertically over or under a desk, or
horizontally under a screen. Its compact, slimline form factor
even allows it to be easily integrated into environments with
space constraints.
• The 5S features an HID-compliant USB port, for automatic
integration with common operating systems (Windows/
Mac OS/Linux). The 5S is also compatible with Eaton UPS
Companion power management software.
• All models come bundled with a USB cable and
two IEC-IEC load cables.
Eaton 5S UPS
3
1 LED user interface
4
2 Battery replacement panel
4 Data line protection
5 4 IEC 10A and 4 surge
1
5
3 USB port
only IEC 10A
6 Circuit breaker reset button
2
6
Eaton 5S 1000i UPS
TECHNICAL SPECIFICATIONS
550
700
1000
1500
Rating (VA/W)
Electrical Characteristics
Technology
Input voltage range
Output voltage
Frequency
550 VA / 330 W
700 VA / 420 W
1000 VA / 600 W
1500 VA / 900 W
Line-Interactive (AVR with Booster + Fader)
175V-275V
230 V
50-60 Hz autoselect
Connections
Number of IEC outlets
Outlets with surge protection and backup /
Outlets with surge protection
Batteries
Typical backup times at 50 and 70% load*
Battery management
4
6
8
8
3/1
3/3
4/4
4/4
10/6 mn
9/5 mn
14/8 mn
11/8 mn
Automatic battery test, deep-discharge protection, cold-start capable, replaceable batteries
Communication
Data line protection
HID-compliant USB port for automatic integration with most common operating systems
(Windows Vista, 7 & 8, Linux, Mac OS X), cable supplied
Tel/Fax/Modem/Internet and Ethernet
Standards
Safety & EMC
IEC/EN 62040-1, IEC/EN 62040 -2, CB Report, CE mark
Dimensions & Weight
Dimensions H x W x D
Weight
250 x 87 x 260 mm
4.96kg
Communication Port
250 x 87 x 260 mm
5.98kg
250 x 87 x 382 mm
9.48kg
250 x 87 x 382 mm
11.08kg
Customer Service & Support
Warranty
2 years warranty including batteries
* Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.
Part Numbers
550
700
1000
1500
5S
5S550i
5S700i
5S1000i
5S1500i
In the interests of continuous product improvement, all specifications are subject to change without notice.
www.eaton.eu
17
PC, Workstation and home AV UPS
Single phase UPS
Eaton Ellipse PRO UPS
650/850/1200/1600 VA
Energy-saving power protection for workstations
and small servers
Ellipse Pro range
• The LCD screen on the Eaton Ellipse PRO UPS provides clear
information on its status and measurements. It also allows easy
configuration of UPS settings.
• The EcoControl function, which automatically disables
peripherals when the master device is turned off, can cut
energy consumption by as much as 20%.
• Automatic Voltage Regulation (AVR) instantly corrects voltage
fluctuations, meaning you can continue working through
brownouts and overvoltages without using the batteries.
• The Ellipse PRO includes a high performance surge-protection
device that complies with IEC 61643-1. This device also protects
data connections such as Ethernet, internet and telephone
lines.
Easy integration and installation
LCD screen
• The Ellipse PRO comes with either four (650/850 models) or
eight (1200/1600 models) Schuko (DIN) or French (FR) sockets
for easy connection to most common computer configurations
with peripherals. IEC models are also available.
• The Ellipse PRO’s extra-flat design makes it easy to install in
any office environment: installation options include vertical box
format, below the desk, horizontally under a monitor, 19” rackmounted (optional 2U kit) and wall-mounted (optional kit).
• The Ellipse PRO is equipped with a USB port and comes
complete with a USB cable and Eaton UPS Companion
software that enables safe system shutdown, energy usage
metering and easy configuration of UPS settings.
Complete peace of mind
Advanced protection for:
•Workstations
• Network devices
•Peripherals
18
EATON UPS Catalogue
• Three-year warranty including batteries.
• Unlimited warranty for connected computer equipment (EU
countries and Norway only).
• Battery tests itself automatically at regular intervals, ensuring
early detection when it’s time for replacement.
• Easy-to-replace battery helps to extend UPS service life.
Eaton Ellipse PRO UPS
1
3 sockets with surge protection
and backup, one socket with surge
protection only
1
4 sockets with surge protection
and backup
2 4 sockets with surge protection
2
1 EcoControl socket
3
2 EcoControl sockets (1200/1600
models)
3
Telephone, internet and Ethernet
protection
4
USB port
4
Telephone, internet and Ethernet
protection
5 Replaceable batteries
5 USB port
6
Circuit breaker reset buttons
6
Replaceable batteries
7
Circuit breaker reset button
Eaton Ellipse PRO 650i
Eaton Ellipse PRO 1600i
Technical Specifications
650
850
1200
1600
Rating (kVA/kW)
Electrical characteristics
Technology
Input voltage range
Output voltage
Frequency
Connections
Number of sockets
Sockets with surge protection and backup /
Sockets with surge protection
Features
User interface
EcoControl (automatic deactivation of idle
peripherals)
Surge protection
Batteries
Typical backup times at 50 and 70% load*
Battery management
Communication
Communication port
650 VA / 400 W
850 VA / 510 W
1200 VA / 750 W
1600 VA / 1000 W
Line-interactive (AVR with booster + fader)
165 V - 285 V (adjustable to 150 V - 285 V)
230 V (adjustable to 220 V - 230 V - 240 V)
50-60 Hz autoselect
4
4
8
8
3/1
3/1
4/4
4/4
LCD (UPS status and measurements, configuration of UPS settings)
Yes, up to 15% energy saving
Yes, up to 15% energy saving
Yes, up to 20% energy saving
Yes, up to 20% energy
saving
Surge protection device compliant with IEC 61643-1
9 / 5 mn
9 / 5 mn
9 / 5 mn
Automatic battery test, deep-discharge protection, cold-start capable, replaceable batteries
9 / 5 mn
USB port (cable supplied)
USB port (cable supplied)
USB port (cable supplied)
USB port (cable supplied)
Software
Eaton UPS Companion CD ROM (enables safe system shutdown, energy usage metering and configuration of UPS settings)
Data line protection
Tel/fax/modem/internet and Ethernet
Standards
Safety and EMC
IEC/EN 62040-1, IEC/EN 62040 -2, CB report, CE mark
Surge protection
IEC 61643-1
Dimensions H x W x D and weight
Dimensions H x W x D
260 x 82 x 285 mm
260 x 82 x 285 mm
275 x 82 x 390 mm
275 x 82 x 390 mm
11.3kg
Weight
6.6kg
7.3kg
9.9kg
Customer service and support
Warranty
3 years warranty including batteries. Unlimited warranty for connected computer equipment (EU countries and Norway only).
* Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.
Parts Numbers
French sockets (FR)
Schuko sockets (DIN)
IEC outlets
Accessories
19” rack-mounting kit (2U)
Wall-mounting kit
650
ELP650FR
ELP650DIN
ELP650IEC
850
ELP850FR
ELP850DIN
ELP850IEC
1200
ELP1200FR
ELP1200DIN
ELP1200IEC
ELRACK
ELWALL
ELRACK
ELWALL
ELRACK
ELWALL
1600
ELP1600FR
ELP1600DIN
ELP1600IEC
ELRACK
ELWALL
www.eaton.eu
19
Network and Server
Single phase UPS
Eaton 5SC UPS
500/750/1000/1500VA
Affordable and reliable protection for small business servers
Easily manageable UPS
• The new LCD interface provides clear status of the UPS key
parameters such as input and output voltage, load and battery
level, and estimated runtime. Configuration capabilities are also
offered for output voltage, audible alarm and sensitivity.
• The 5SC offers USB and serial connectivity. USB port is HID
compliant for automatic integration into Windows, Mac OS and
Linux.
• Eaton Intelligent Power Protector ® (IPP) software delivered as
standard, can be used as point to point power management
(USB/Serial) or Network based using IPP as a proxy.
Reliable power protection
5SC Range
• Pure sinewave output: When operating in battery mode the 5SC
provides a high quality output signal for any sensitive equipment
connected, such as active PFC (power factor corrected) servers.
• Buck and Boost operation corrects a wide range of input voltage
variations through continuous regulation, without the use of
batteries, and ensures consistent input voltage to the loads
protected.
• Stronger, longer battery life: Eaton ABM® battery management
technology uses an innovative three-stage charging system that
extends battery life by up to 50%.
LCD interface
Ideal for protecting:
Tower Servers
NAS, Network equipment
ATMs, Ticket machines, Kiosks
Flexible integration
• Small size for easy integration even with space constraints
(kiosks, cash machines, ticket machines etc.) and up to eight
outlets for better flexibility!
• Adjustable input waveform sensitivity to adapt the UPS to
specific environment (like Genset).
• Easy battery replacement from front panel to extend UPS life.
20
EATON UPS Catalogue
Eaton 5SC UPS
3
1 LCD Interface :
2 Panel for batteries replace-
Clear information on
ment
UPS status and measurements
1
3 1 USB port + 1 serial port
4 8 IEC 10A sockets
2
4
Eaton 5SC 1500i
TECHNICAL SPECIFICATIONS
Rating (VA/W)
Format
Electrical Characteristics
Technology
Line-Interactive High Frequency (Sinewave, Booster + Fader)
Input voltage and frequency ranges without
using batteries
184V–276V, 45–55Hz (50Hz system), 55–65Hz (60Hz system)
Output voltage and frequency
230V (+6/–10 %) (Adjustable to 220V/230V/240V), 50/60Hz +/–0.1 % (autosensing)
500
500 VA / 350 W
Tower
750
750 VA / 525 W
Tower
1000
1000 VA / 700 W
Tower
1500
1500 VA / 1050 W
Tower
Connections
Input
Outputs
1 IEC C14 (10A)
4 IEC C13 (10A)
6 IEC C13 (10A)
8 IEC C13 (10A)
8 IEC C13 (10A)
Batteries
Typical backup times at 50 and 70% load*
Battery management
13/9
13/9
13/9
13/9
ABM®, Automatic battery test, deep discharge protection
Communication
Communication ports
1 USB port + 1 RS232 serial port (USB and RS232 ports cannot be used simultaneously)
Operating conditions, Standards and Approvals
Operating temperature
0–35°C
0–35°C
0–35°C
0–35°C
Noise level
<40dB
<40dB
<40dB
<40dB
Safety
IEC/EN 62040-1, UL 1778
EMC, Performance
IEC/EN 62040-2
Approvals
CE, CB report (TUV)
Dimensions H x W x D / Weight
Dimensions
Weight
210 x 150 x 240mm
6.6kg
210 x 150 x 340mm
10.4kg
210 x 150 x 340mm
11.1kg
210 x 150 x 410mm
15.2kg
1000
5SC1000i
1500
5SC1500i
Customer Service & Support
Warranty
2 years
* Runtimes are shown at 0.7 power factor. Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.
Part Numbers
5SC
500
5SC500i
750
5SC750i
In the interests of continuous product improvement, all specifications are subject to change without notice.
www.eaton.eu
21
Network and Server
Single phase UPS
Eaton 5P UPS
650/850/1150/1550VA
Eaton 5P is an energy efficient line-interactive UPS with
advanced LCD and energy metering features.
Manageability
Available in tower and rack 1U format
• The new graphical LCD display provides clear information on
the UPS’s status and measurements on a single screen (in
seven languages). Enhanced configuration capabilities are also
available with easy-to-use navigation keys.
• The 5P can meter energy consumption providing kWh values
through the LCD and Eaton’s power management software.
• Load segment control enables prioritised shutdowns of nonessential equipment during outages in order to maximise
battery runtime for critical devices. Load segment control can
also be used to remotely reboot locked-up network equipment
or to manage scheduled shutdowns and sequential start-ups.
• The 5P offers Serial and USB connectivity, plus an extra slot for
an optional communication card (including SNMP/ Web card or
relay contact card). Eaton’s Intelligent Power® Software Suite
compatible with all major OS including virtualisation software
such as VMware and Hyper-V is included with each UPS.
Performance and efficiency
Intuitive LCD
Ideal for protecting:
Servers
Networking
Storage devices
22
EATON UPS Catalogue
• Energy efficient UPS: With an optimised electrical design,
the 5P provides up to 98% efficiency, reducing cooling
and utility costs.
• Pure sinewave output: When operating in battery mode the 5P
provides a high quality output signal for any sensitive equipment
connected, such as active PFC (power factor corrected) servers.
• Adjustable tolerance and sensitivity: Users can maximise useful
battery life by widening the input voltage window or adjustable
input waveform sensitivity (via the LCD or software) to adapt
the UPS to a specific environment (like Genset).
Availability and Flexibility
• The 5P is available in tower or Rack 1U format, providing
unmatched energy density with up to 1.1kW in only 1U.
• Stronger, longer battery life: Eaton ABM® battery management
technology uses an innovative three-stage charging technique
that extends batteries by up to 50%.
• Batteries can be hot-swapped without ever having to shut down
connected equipment. With an optional, hot-swap maintenance
bypass module, you can even replace the entire UPS.
Eaton 5P UPS
4
5
1 Graphical LCD:
- Clear information on UPS
3 One USB port + one serial
port + remote ON/OFF and
1
remote power OFF connec-
status and measurements
tor
- Energy metering
4 8 IEC 10A sockets
2
- Enhanced configuration
(including two groups of
capabilities
3
- Available in seven languages
controlled sockets)
5 Communication card slot
2 Panel for batteries
replacement (Hot swappable)
Eaton 5P 1550i UPS
TECHNICAL SPECIFICATIONS
650
850
1150
1550
Rating (VA/W)
Technology
650VA/420W
Tower or Rack 1U
850VA/600W
Tower or Rack 1U
1150VA/770W
Tower or Rack 1U
1550VA/1100W
Tower or Rack 1U
Electrical Characteristics
Technology
Input voltage and frequency ranges without
using batteries
Output voltage and frequency
Line-Interactive High Frequency (Pure Sinewave, Booster + Fader)
160V-294V (adjustable to 150V-294V) 47 to 70 Hz (50 Hz system), 56.5 to 70 Hz (60 Hz system),
40 Hz in low-sensitivity mode
230 V (+6/-10 %) Adjustable to 200V / 208V / 220V / 230V / 240V), 50/60 Hz +/- 0.1 % (autosensing)
Connections
Input
Outputs Tower model
Outputs Rack 1U model
1 IEC C14 (10A)
4 IEC C14 (10A)
4 IEC C14 (10A)
Switched Outlet Group
2 outlet groups
Battery
Typical backup times at 50 and 70% load*
Battery management
6 IEC C14 (10A)
4 IEC C14 (10A)
8 IEC C14 (10A)
6 IEC C14 (10A)
8 IEC C14 (10A)
6 IEC C14 (10A)
9/6 mn
12/7 mn
12/7 mn
13/8 mn
ABM® & Temperature compensated charging method (user selectable), Automatic battery test,
deep discharge protection
Communication
Communication Ports
Communication Slot
Operating conditions, standards and approvals
Operating temeprature
Noise level
Safety
EMC, Performance
Approvals
Dimensions H x W x D / Weight
Tower models
Rack 1U models
Customer Service & Support
Warranty
1 USB port + 1 RS232 serial port and relay contacts (USB and RS232 ports cannot be used simultaneously),
1 mini terminal block for remote ON/OFF and Remote Power Off
1 slot for Network-MS card , ModBus-MS or Relay-MS cards
0 to 35°C
0 to 35°C
<40dB
<40dB
IEC/EN 62040-1, UL 1778
IEC/EN 62040 -2 , IEC/EN 62040-3 (Performance)
CE, CB report (TUV)
0 to 35°C
<40dB
0 to 40°C
<40dB
230 x 150 x 345 mm/7.8kg
230 x 150 x 345 mm/10.4kg
230 x 150 x 345 mm/11.1kg
230 x 150 x 445 mm/15.6kg
43.2(1U) x 438 x 364 mm/8.6kg
43.2(1U) x 438 x 509 mm/13.8kg
43.2(1U) x 438 x 509 mm/14.6kg
43.2(1U) x 438 x 554 mm/19.4kg
3 years on electronics, 2 years on batteries
* Runtimes are shown at 0.7 power factor. Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.
Part Numbers
650
850
1150
1550
Tower
Rack 1U
5P650i
5P650iR
5P850i
5P850iR
5P1150i
5P1150iR
5P1550i
5P1550iR
In the interests of continuous product improvement, all specifications are subject to change without notice.
www.eaton.eu
23
Network and Server
Single phase UPS
Eaton 5130 UPS
1250/1750/2500/3000 VA
Line-interactive UPS
Highest power performance
• The 5130 protects connected equipment from five of the most
common power anomalies: failures, surges, sags, under-voltage
and overvoltage.
• 0.9 power factor: more real power to your protected load. By
delivering more real output power, the 5130 powers more
servers than another UPS of equivalent VA rating with a lower
power factor. 5130 is compatible with all modern IT equipment.
Unmatched reliability
• Load segment control enables prioritized shutdown of
nonessential equipment during outages to maximize battery
runtime for critical devices. Load segment control can also
be used to remotely re-boot locked-up network equipment or
manage scheduled shutdowns and sequential startups.
• You can extend the runtime to several hours by adding up to
four external battery modules. Each external battery module
occupies only 2U for most models (3U for reduced depth, 3000
VA models).
• With hot-swappable batteries, you can replace a battery module
without disrupting server room operations or power to protected
equipment. With an optional, hot-swap maintenance bypass
module, you can even replace the entire UPS.
Outstanding versatility
2U rackmount installation
Advanced power protection for:
• IT and networking environments
• Servers and networking gear
• Telecommunications, VoIP and security
systems
24
EATON UPS Catalogue
• The UPS offers the choice of rackmount or tower installation.
Pedestal and rail kits are included in all models at no extra
charge.
• The 2U model is optimized for rack mounting but is easily
deployed as a tower. The 3U unit is optimized for tower
deployment or short-depth racks, which makes it especially
suitable for telecom equipment racks
• The 5130 offers Serial and USB communication plus an extra
slot for optional communication card (including SNMP/Web card,
relay contact card) allowing remote monitoring in a variety of
networking environments.
• The UPS comes complete with the Eaton Software Suite CD,
including SNMP compatible power management software.
Eaton 5130 UPS
1
Access panel for battery
replacement
5
1
2
Load segments
3
USB and serial ports and
4
Communication card slot
5
LED user interface
6
EBM connector
2
3
RPO/ROO connector
4
6
TECHNICAL SPECIFICATIONS
Battery
General
LEDs
Topology
Diagnostics
Transfer time
ROO/RPO
Rail kit/tower stand
13 status-indicating LEDs
Line interactive
Full system self-test at power up
1-4 ms typical
Rear deck emergency stop connector (for remote on/off
and power off)
Included with all units
Electrical Input
Nominal voltage
230 Vac
Voltage range*
160–294 V
Frequency
50/60 Hz
47–70 Hz for 50 Hz operation
56.5–70 Hz for 60 Hz operation
700–2000 VA: 10A
3000 VA: 16A
Frequency range
Dedicated circuit
breaker rating
Battery replacement
Hot-swappable internal batteries
Start-on-battery
Allows start of UPS without utility input
Communications
Serial port
USB port
Optional communication
cards
Cables
Power management
software
RS-232 (RJ45) port
As standard (HID), for communicating with Windows
XP/Vista
MS- format cards (Network or Relay)
RS 232 and USB communications cables included
Eaton Software Suite CD-ROM (bundled with UPS)
Environmental
Electrical Output
Safety markings
CE; C-Tick; TUVus
Safety conformance
IEC/EN 62040-1, UL 1778
EMC compliance
IEC/EN 62040-2 EN 50091-2 class B
Operating temperature
0°C to +40°C
Storage temperature
-15°C to +50°C
Relative humidity
20–95% non-condensing
Audible noise
Max 45 dBA
Power factor
On utility voltage
regulation
On battery voltage
regulation
Efficiency
0.9
Over current protection
Electronic current limit
5130 model
Line mode, BTUs/hr
Battery mode, BTUs/hr
Load crest factor
3:1
Two groups of two individually controlled output receptacles
1250 VA
250
1.682
1750 VA
348
2.340
2500 VA
490
2.559
3000 VA
588
3.071
Load segments
184–265 Vac
-10%, +6% of nominal
Heat dissipation table (battery fully charged)
Normal or line mode: >94%
103006590-6591
Rating
(VA/Watts)
1250/1150
Input
connection
IEC C14-10A
PW5130i1750-XL2U
103006591-6591
1750/1600
IEC C14-10A
PW5130i2500-XL2U
103006592-6591
2500/2250
IEC C20-16A
PW5130i3000-XL2U
103006593-6591
3000/2700
IEC C20-16A
PW5130i3000-XL3U
103006594-6591
3000/2700
IEC C20-16A
PW5130N1750-EBM2U
103006587-6591
N/A
PW5130N3000-EBM2U
103006589-6591
N/A
PW5130N3000-EBM3U
103006588-6591
N/A
Description
Part number
PW5130i1250-XL2U
Output receptacles
Dimensions H x W x D, mm
Weight, kg
(8) IEC-C13-10A
86 x 441 x 509
24,3
(8) IEC-C13-10A
(1) IEC-C19-16A
(8) IEC-C13-10A
(1) IEC-C19-16A
(8) IEC-C13-10A
(1) IEC-C19-16A
(8) IEC-C13-10A
86 x 441 x 509
26,6
86 x 441 x 634
33,8
86 x 441 x 634
33,8
131 x 441 x 484
34,3
N/A
N/A
86 x 441 x 509
30,4
N/A
N/A
86 x 441 x 634
41,7
N/A
N/A
131 x 441 x 484
41,7
Extended Battery Modules
BATTERY RUNTIMES*
PW5130i1250-XL2U
PW5130i1750-XL2U
PW5130i2500-XL2U
PW5130i3000-XL2U/3U
Internal batteries
75% load
50% load
13 min
20 min
9 min
14 min
10 min
17 min
9 min
15 min
+1 EBM
75% load
50% load
52 min
105 min
33 min
60 min
50 min
85 min
38 min
60 min
+2 EBMs
75% load
50% load
90 min
175 min
55 min
100 min
80 min
130 min
70 min
100 min
+3 EBMs
75% load
50% load
125 min
225 min
80 min
145 min
130 min
210 min
90 min
150 min
+4 EBMs
75% load
50% load
175 min
300 min
105 min
180 min
180 min
290 min
120 min
210 min
www.eaton.eu
25
Network and Server
Single phase UPS
Eaton 5PX UPS
1500/2200/3000 VA
Exceptional efficiency, manageability and energy
metering capabilities for IT managers
Manageability
Rack/Tower versatile
• The new graphical LCD provides clear information on the UPS’s
status and measurements on a single screen (one of seven
languages). Enhanced configuration capabilities are also available
with easy-to-use navigation keys.
• For the first time in the industry the 5PX can meter energy
consumption right down to the managed outlet groups. kWh
values can be monitored using the LCD or Eaton’s Intelligent
Power® Software Suite.
• Load segment control enables prioritised shutdowns of
nonessential equipment to maximise battery runtime for critical
devices. Load segment control can also be used to remotely
reboot locked-up network equipment or to manage scheduled
shutdowns and sequential start-ups.
• The 5PX offers Serial and USB connectivity, plus an extra slot
for an optional communication card (including SNMP/Web card
or relay contact card). Eaton’s Intelligent Power® Software Suite
compatible with all major OS including virtualization software
such as VMware and Hyper-V is included with each UPS.
Performance and efficiency
Intuitive LCD for easy
configuration and management
Advanced protection for:
•
•
•
•
Servers
Switches
Routers
Storage devices
• With an optimised electrical design, the 5PX can provide up to
99% efficiency, reducing cooling and utility costs.
• With a power factor of 0.9, the 5PX delivers more real output
power. It powers more servers than other UPSs with equivalent
VA ratings and lower power factors. The 5PX is compatible with
all modern IT equipment.
• When operating in battery mode the 5PX provides a high quality
output signal for any sensitive equipment connected, such as
active PFC (power factor corrected) servers.
Availability and flexibility
• The 5PX is available in a rack/tower convertible version pedestal and rail kits are included with all models at no
extra charge.
• Stronger, longer battery life: Eaton ABM® battery management
technology uses an innovative three-stage charging technique
that only recharges the battery when necessary, so the battery
experiences less corrosion and service life is prolonged
by up to 50%.
• Batteries can be hot-swapped without ever having to shut down
connected equipment. With an optional, hot-swap maintenance
bypass module, you can even replace the entire UPS.
• There is also the possibility to add more runtime with up to four
external hot-swappable battery modules, able to run systems
for hours if necessary. The additional battery modules are
automatically recognised by the UPS.
26
EATON UPS Catalogue
Eaton 5PX UPS
1 USB port + 1 serial port + remote
Graphical LCD display :
- Clear information on UPS status
ON/OFF and remote power OFF
and measurements
inputs
- Enhanced configuration capabilities
External battery (EBM) connector
- Available in 7 languages
8 IEC 10A + 1IEC 16A sockets
with energy metering (including 4
Access panel for battery replacement
(Hot swappable)
programmable sockets)
Eaton 5PX 3000i RT2U
Communication card slot
TECHNICAL SPECIFICATIONS
1500
2200
3000
Rating (VA/W)
Format
1500 VA / 1350 W
RT2U (tower / rack 2U)
2200 VA / 1980 W
RT2U (tower / rack 2U)
3000 VA / 2700 W
RT2U & RT3U
Electrical characteristics
Technology
Input voltage and frequency ranges without
using batteries
Output voltage and frequency
Line-Interactive High Frequency (Pure Sinewave, Booster + Fader)
160V-294V (adjustable to 150V-294V) 47 to 70 Hz (50 Hz system),
56.5 to 70 Hz (60 Hz system), 40 Hz in low-sensitivity mode
230 V (+6/-10 %) (Adjustable to 200V / 208V / 220V / 230V / 240V), 50/60 Hz +/- 0.1 % (autosensing)
Connections
Input
Outputs
1 IEC C14 (10 A) socket
8 IEC C13 (10 A)
1 IEC C20 (16 A) socket
8 IEC C13 (10 A) sockets
1 IEC C19 (16 A) socket
1 IEC C20 (16 A) socket
8 IEC C13 (10 A) sockets
1 IEC C19 (16 A) socket
Remotely controlled sockets
Additional outputs with HS MBP
Additional outputs with FlexPDU
2 groups of 2 x IEC C13 (10 A)
4 FR/Schuko sockets or 3 BS sockets or 6 IEC 10 A sockets or terminal blocks (HW version)
8 FR/Schuko sockets or 6 BS sockets or 12 IEC 10 A sockets
Batteries
Typical backup times for 50 and 70% load*
5PX
5PX + 1 EBM
5PX + 4 EBM
Battery management
19/11 mn
15/8 mn
14/9 mn
90/54 mn
60/35 mn
66/38 mn
285/180 mn
210/125 mn
213/121 mn
ABM® & Temperature compensated charging method (user selectable), Automatic battery test, deep discharge protection, automatic recognition of external battery units
Interfaces
Communication ports
1 USB port + 1 RS232 serial port and relay contacts (USB and RS232 ports cannot be used simultaneously)
+ 1 mini terminal block for remote ON/OFF and Remote Power Off
1 slot for NMC Minislot card (included in Netpack versions) or NMC ModBus/JBus or MC Contacts/Serial
Communications card slots
Operating conditions, standards and approvals
Operating temperature
Noise Level
Performance - Safety - EMC
0 to 40°C
< 45 dBA
< 45 dBA
< 50 dBA
IEC/EN 62040-1 (Safety), IEC/EN 62040-2 (EMC), IEC/EN 62040-3 (Performance),
Approvals
CE, CB report, TÜV
Dimensions W x D x H / Weight
UPS Dimensions
441 x 522 x 86,2 (2U) mm
441 x 522 x 86,2 (2U) mm
UPS Weight
Dimensions of EBM
Weight of the EBM
27.6 kg
28.5 kg
32.8 kg
32.8 kg
441 x 647 x 86,2 (RT2U) mm
441 x 497 x 130,7 (RT3U) mm
38.08 (RT2U) - 37.33 (RT3U)
same as UPS
46.39 (RT2U) - 44.26 (RT3U)
Customer Service & Support
Warranty
3 years on electronics, 2 years on batteries
* Runtimes are shown at 0.7 power factor. Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.
Part Numbers
1500
1500 Netpack*
2200
2200 Netpack*
3000 (RT3U)
3000 Netpack* (RT2U)
UPS
5PX1500iRT
5PX1500iRTN
5PX2200iRT
5PX2200iRTN
5PX3000iRT3U
5PX3000iRTN
EBM
5PXEBM48RT
5PXEBM48RT
5PXEBM48RT
5PXEBM48RT
5PXEBM72RT3U
5PXEBM72RT2U
* Network Management Card included as standard in Netpack versions
www.eaton.eu
27
Network and Server
Single phase UPS
Eaton 9130 UPS
700/100/1500/2000/3000/5000/6000 VA
Double conversion UPS
Highest power performance
• Double conversion topology. The 9130 constantly monitors
power conditions and regulates voltage and frequency. Even
when presented with the most severe power problems, UPS’s
output remains within 3% of nominal voltage.
• More real power. High 0.9 output power factor enables the 9130
to provide its full power capability to modern IT equipment.
• Highest efficiency to reduce utility and cooling spending.
The 9130 can provide up to 95% efficiency in online double
conversion mode and up to 98% in high-efficiency mode.
Unmatched reliability
Multilingual LCD
Advanced power protection for:
•
•
•
•
•
•
•
•
•
•
28
IT and networking environments
Servers, networking gear
Telecommunications, VoIP, security systems
Medical systems
Diagnostics and medical screening
Patient record archives
Manufacturing systems
Chip fabrication
Pharmaceutical production
Chemical processing
EATON UPS Catalogue
• The internal bypass allows service continuity in case of internal
fault, a maintenance bypass is also available (as option) for
easy replacement of the UPS without powering down critical
systems.
• Stronger, longer battery life. Eaton ABM® battery management
technology uses an innovative three-stage charging technique,
that only recharges the battery when necessary, so the battery
experiences less corrosion and service life is prolonged by
up to 50%.
• Batteries can be hot-swapped without ever having to shut down
connected equipment.
• Possibility to add more runtime at any time with up to four
external hot-swappable battery modules to run systems for
hours if necessary.
• Enables prolonged runtime of essential equipment during power
outages by allowing for orderly, remote shutdown of non-critical
systems and processes thanks to a capability to control load
segments (available up to 3kVA).
Outstanding versatility
• One platform, two factors, dozens of choices. Up to 3000 VA
of UPS power is packed into only 2U of rack space. The tower
option is about the size of a modern, compact PC.
• Enhanced configuration capability through easily navigated
multilingual graphical display.
• Remote monitoring. The 9130 comes complete with the
Eaton Software Suite CD including SNMP-compatible power
management software providing control and visibility over all
your UPS systems.
• Connectivity options are available for almost any network
environment.
Eaton 9130 UPS
Multilingual graphical
1
LCD display
1
7
3
5
4
2
Panel for replacing batteries
3
One USB port + one serial port
4
One Relay Output +
6
5
EBM battery unit connector
6
Load segments
7
Communication card slot
Technical specifications
General
LEDs
Topology
Diagnostics
UPS bypass
Rail kit
Electrical Input
Nominal voltage
Voltage range
Frequency range
Electrical Output
Power factor
Voltage
Frequency regulation
Load crest factor
1
one EPO connector
2
User interface
2
Communications
Ports
Relay output
Graphical LCD with blue backlight and text in
English, French, German, Russian and Spanish
Four status-indicating LEDs
True online, double-conversion
Full system self-test
Automatic bypass
Included with all rackmount units
Optional communication
cards (BD/MS Slot)
Environmental
Safety and EMC markings
Audible noise
Ambient operating
220–240V
up to 120–276 VAC (depending on load level)
40–70 Hz (50/60 Hz)
Storage temperature
Relative humidity
0.9
±3 % of nominal regulation (on utility and battery)
±3 Hz online
3 to 1
Description
Part number
Tower Models
PW9130i700T
103006433-6591
PW9130i1000T-XL
103006434-6591
PW9130i1500T-XL
103006435-6591
PW9130i2000T-XL
103006436-6591
PW9130i3000T-XL
103006437-6591
PW9130i5000T-XL
103007841-6591
PW9130i6000T-XL
103007842-6591
Tower Extended Battery Modules
PW9130N1000T-EBM
103006438-6591
PW9130N1500T-EBM
103006439-6591
PW9130N3000T-EBM
103006440-6591
PW9130N6000T-EBM
103007843-6591
Rack Models
PW9130i1000R-XL2U
103006455-6591
PW9130i1500R-XL2U
103006456-6591
PW9130i2000R-XL2U
103006457-6591
PW9130i3000R-XL2U
103006463-6591
Rack Extended Battery Modules
PW9130N1000R-EBM2U
103006458-6591
PW9130N1500R-EBM2U
103006459-6591
PW9130N3000R-EBM2U
103006460-6591
BATTERY RUNTIMES*
Rack models
PW9130i1000R-XL2U
PW9130i1500R-XL2U
PW9130i2000R-XL2U
PW9130i3000R-XL2U
Tower models
PW9130i700T-XL
PW9130i1000T-XL
PW9130i1500T-XL
PW9130i2000T-XL
PW9130i3000T-XL
PW9130i5000T-XL
PW9130i6000T-XL
Internal batteries
75% Load 50% Load
4
6
3
7
RS-232 and USB HID port as standard
Common alarm standard
SNMP/Web card for monitoring in SNMP-based networks. Relay card for remote shutdown of IBM AS/400
systems. MODBUS for integration to industrial environment.
IEC/EN 62040-1, IEC/EN 62040-2, CE marking
<50 dB
0˚C to +40˚C
-20˚C to +40˚C with batteries and
-25˚C to +55˚C without batteries
5–90% non-condensing
Rating (VA/Watts)
Input connection
Output receptacles
Dimensions H x W x D, mm
Weight, kg
700/630
1000/900
1500/1350
2000/1800
3000/2700
5000/4500
6000/5400
C14
C14
C14
C14
C20
Hardwire
Hardwire
(6) C13
(6) C13
(6) C13
(8) C13, (1) C19
(8) C13, (1) C19
Hardwire
Hardwire
230 x 160 x 350
230 x 160 x 380
230 x 160 x 430
325 x 214 x 410
325 x 214 x 410
574 x 244 x 542
574 x 244 x 542
12.2
14.5
19.0
34.5
34.5
75.5
75.5
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
230 x 160 x 380
230 x 160 x 430
325 x 214 x 410
574 x 244 x 542
18.5
24.3
50.0
111
1000/900
1500/1350
2000/1800
3000/2700
C14
C14
C14
C20
(6) C13
(6) C13
(8) C13, (1) C19
(8) C13, (1) C19
86.5 x 438 x 450
86.5 x 438 x 450
86.5 x 438 x 600
86.5 x 438 x 600
16
19
29
29.5
NA
NA
NA
NA
NA
NA
NA
NA
NA
86.5 x 438 x 450
86.5 x 438 x 450
86.5 x 438 x 600
22.1
28.1
41.1
+1 EBM
75% Load 50% Load
+2 EBMs
75% Load 50% Load
+3 EBMs
75% Load 50% Load
+4 EBMs
75% Load 50% Load
13
11
13
8
22
18
24
14
55
47
63
34
82
81
95
62
103
83
118
70
186
143
190
92
151
126
170
96
250
208
242
156
223
195
221
130
312
262
345
211
12
13
11
21
12
20
16
19
22
18
34
20
34
27
N/A
55
47
81
49
81
66
N/A
82
81
130
79
136
107
N/A
103
83
145
90
153
120
N/A
186
143
198
143
232
194
N/A
151
126
184
134
217
178
N/A
250
208
293
180
328
267
N/A
223
195
248
165
273
231
N/A
312
262
431
240
477
372
* Runtimes are shown at a 0.7 power factor. Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.
www.eaton.eu
29
Network and Server
Single phase UPS
Eaton EX UPS
700/1000/1500/2200/3000 VA
Double conversion (online)
Maximum availability
Eaton EX 1500
• Topology: double conversion on-line UPS with automatic
by-pass and power factor correction
• Powershare: the Eaton EX output sockets are individually
controlled to provide load-shedding to maximise the backup
time and provide remote reboot and sequential start-up as
standard
• Continuous power supply: Hot swappable batteries.
The HotSwap MBP (Maintenance By-Pass) module allows the
UPS to be replaced without interrupting the power supply
• Long backup times: 1 to 4 EXB battery units can be added to
the Eaton EX. The Eaton EX 3000XL has a built-in super charger
for extra long backup times
Minimum total cost of ownership
• Easy operation: the LCD gives you access to a wide range of
measurements and set-up menus
• Remote supervision: the Eaton software suite offers a wide
range of communication option including: SNMP and HTML,
ModBus/JBus and relay outputs
Eaton EX has unmatched Flexibility.
Eaton EX versatility: rack or tower
Ideal protection for:
• Servers, data storage and network equipment
• Telephony - VoIP
• Medical equipment - Industrial processes
30
EATON UPS Catalogue
• Format: EX 700 to 1500 are available in tower format or
RT2U convertible rack/tower format (compatible with
short-depth rack). EX 2200 & 3000 are available in RT2U
format (optimised for rack mounting) or RT3U (for tower or
short-depth racks)
• Connections: with FlexPDU and HotSwap MBP, the RT2U and
RT3U models can be connected by sockets or terminal blocks.
They can be installed as required, on the side or on top of
the unit
• Compatible with high power factor loads: Eaton EX is rated
for 0.9 power factor (700 VA/630 W, 1000 VA/900 W,
1500 VA/1350 W, 2200 VA/1980 W and 3000 VA/2700 W)
• the EX includes both serial and USB ports, plus remote On/Off
connector and an extra slot for optional communication cards.
The UPS comes with a complete
Eaton software suite.
Eaton EX UPS
1 USB port + 1 serial port + remote
ON/OFF and emergency stop inputs
LCD Multilingual display
- 6 languages,
EXB battery unit connector
- displays measurements,
EXB units recognised automatically
- displays alarms,
8 IEC 10A sockets, including 4 Powershare pro
- access to control and set-up menus
grammable sockets and 1 IEC 16A socket
Panel for batteries replacement
Communication card slot
(Hot swappable)
Mountings for HotSwap MBP and FlexPDU
Eaton EX 3000
TECHNICAL SPECIFICATIONS
Rating (VA/W)
Format
Electrical characteristics
Architecture
700
700 VA / 630 W
Mini tower
Input voltage and frequency ranges
without using batteries
100/120/140/160 V to 284V - 40 to 70 Hz
for load level <20% / <33% / <66% / >=66% of rated output
Output voltage and frequency
230 V (adjustable to 200/208/220/240/250 V), 50/60 Hz auto-select or
frequency converter mode (2)
Connections
Input
1000 - 1000 RT2U
1500 - 1500 RT2U
1000 VA / 900 W (1)
1500 VA / 1350 W (1)
Mini tower or RT2U (tower/rack 2U)
On-line double conversion with automatic by-pass and power factor correction
1 IEC C14 (10A) socket
2200
3000 - 3000 XL
2200 VA / 1980 W
3000 VA / 2700 W (1)
RT2U (tower/rack 2U) and RT3U (tower/rack 3U)
100/120/160/184 V to 284V - 40 to 70 Hz
for load level <20% / <33% / <66% / >=66% of
rated output
230 V (adjustable to 200/208/220/240 V),
50/60 Hz auto-select or frequency converter mode
1 IEC C20 (16A) or terminal block on HotSwap
MBP HW (Hard-Wired)
8 IEC C13 (10A) sockets + 1 IEC C19 (16A) socket
2 groups of 2 x IEC C13 (10A) on Eaton EX
Outputs
6 IEC C13 (10A) sockets
Remotely controlled Powershare sockets
2 independent groups: 2 + 1 IEC C13 (10A) sockets
Additional outputs with
4 FR/Schuko sockets or 3 BS sockets or 6 IEC 10A sockets or terminal blocks (HW version)
HotSwap MBP FR/DIN/BS/IEC/HW
Additional outputs with
8 FR/Schuko sockets or 6 BS sockets or 12 IEC 10A sockets
FlexPDU FR/DIN/BS/IEC
Battery
Typical backup times for 50 and 70% load (5) except for Eaton EX 3000 XL (4)
EX
16 min / 10 min
18 min / 12 min
13 min / 9 min
17 min / 12 min
15 min / 10 min
EX + 1 EXB
/
75 min / 50 min
50 min / 35 min
85 min / 60 min
60 min / 40 min
EX + 4 EXB
/
250 min / 200 min
180 min / 120 min
285 min / 200 min
190 min / 150 min
Battery management
Automatic weekly test (period adjustable using LCD display or in software supplied), automatic recognition
of external battery units => continuous maximisation of backup time + deep discharge protection
Interfaces
Indicators and display
3 LEDS + adjustable multilingual display: display of measurements, access to control and set-up menus
Communication ports
1 USB port + 1 RS232 serial port and relay contacts (3) + 1 mini terminal block for remote ON/OFF and emergency stop
Communications card slots
1 slot for NMC Minislot card (included in Netpack version) or NMC ModBus/JBus or MC Contacts/Serial
Operating conditions, standards and approvals
Operating temperature noise level
0°C to 40°C continuous, 45 dBA
Performance - Safety - EMC
IEC/EN 62 040-1, IEC/EN 62 040-2, IEC/EN 62 040-3 (VFI-SS-113), IEC/EN 60 950-1 (RD)
Approvals
CE, TüV GS, CB report, cTüV-US
CE, TüV, CB Report, UL CE, TüV, CB Report, UL
Dimensions (H x W x D) / Weight
EX
242 x 153 x 440 mm /
242 x 153 x 440 mm /
242 x 153 x 490 mm /
440 x 131 x 490 mm (6) /
12.5 kg
15 kg
18 kg
30 kg (3000 XL = 18 kg)
86.5 x 438 x 483 mm / 86.5 x 438 x 483 mm /
EX (RT2U format)
/
86 x 440 x 640 mm / 31 kg
18 kg
20.5 kg
EX EXB
/
242 x 153 x 440 mm / 21 kg
440 x 131 x 490 mm (6)
EX EXB (RT2U format)
/
86.5 x 438 x 483 mm / 24.5 kg
/
/
Customer Service & Support
2 years warranty
Standard product exchange, including the battery
Warranty+
Optional 3-years warranty (depending on the country please visit www.eaton.com/powerquality)
1: Maximum rating with EXB battery units: Eaton EX 1000 = 800 W, Eaton EX 1500 =1200 W and Eaton EX 3000=2400W. 2: Derated by 15% when used as a frequency converter. 3: USB and RS232 serial
ports cannot be used simultaneously. 4: Except Eaton EX 3000 XL: UPS with high speed charger, without built-in batteries, for custom configurations: ask us for details. 5: Runtimes are shown at 0.7
power factor. Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc. 6: compatible with 600 mm deep rack
Part Numbers
700
1000
1500
2200
3000
EX
EX (RT2U format, includes rack kit)
EX HotSwap (RT3U format, includes
rack kit + HotSwap MBP)
68 180
/
/
68 181
68 182
/
68 183
68 184
/
68 400
68 401
FR: 68406 DIN: 68407 BS:
68408
IEC: 68409 HW: 68410
68 402 - XL: 68 404
68 403
FR: 68412 DIN: 68413 BS:
68414
IEC: 68415 HW: 68416
/
/
/
68 411
68 417
/
/
/
/
68 185
68 186
/
/
68 185
68 186
/
/
/
/
68 405
68 441
/
/
68 405
68 441
EX Netpack (RT2U format, includes
rack kit and NMC card)
EX EXB
EX EXB (RT2U format, includes rack kit)
EX EXB (RT3U format, includes rack kit)
EX Rack Kit 2U/3U
www.eaton.eu
31
Network and Server
Single phase UPS
Eaton 9SX UPS
5/6/8/11 kVA
High performance Online double conversion UPS
Performance and efficiency
• Double conversion topology. The Eaton 9SX constantly monitors
power conditions and regulates voltage and frequency.
• With up to 95% efficiency in online double conversion mode the
9SX provides the highest efficiency level in its class to reduce
energy & cooling costs.
• With a 0.9 power factor the 9SX delivers 28% more power than
UPS in its class. It powers more servers than other UPSs with
equivalent VA ratings and lower power factors.
Availability and flexibility
9SX 11kVA
9SX is an
Energy Star®
qualified UPS
9SX´s LCD tilts 45° for easy viewing
Advanced protection for:
• Infrastucture, Industrial and Medical
• IT, Networking, Storage and Telecom
32
EATON UPS Catalogue
• The internal bypass allows service continuity in case of
internal fault. Batteries are hot-swappable from the front panel
without powering down critical systems.
• With its rack/tower versatile form factor the 9SX can be installed
in any environment (rack kit provided as standard on
RT versions).
• Stronger, longer battery life: Eaton ABM® battery management
technology uses an innovative three-stage charging technique
that extends battery life by up to 50%.
• More runtime can be added with up to 12 external hotswappable battery modules, able to run systems for hours if
necessary. The additional battery modules are automatically
recognized by the UPS.
Manageability
• The new graphical LCD provides clear information on the
UPS’s status and measurements on a single screen (in seven
languages). LCD display position can be adjusted to offer the
best viewable angle for tower and rack usage.
• The 9SX can meter energy consumption. kWh values can be
monitored using the LCD or Eaton’s Intelligent Power® Software
Suite.
• Load segment control enables prioritised shutdowns of
nonessential equipment to maximise battery runtime for
critical devices. It can also be used to remotely reboot locked-up
equipment or to manage scheduled shutdowns and sequential
start-ups.
• The 9SX offers Serial, USB and relay (four dry contacts)
connectivity, plus an extra slot for an optional card (Modbus,
Network or Relay). 9SX also provides Remote Power off
function. Eaton’s Intelligent Power® Software Suite is included
with each UPS.
Eaton 9SX UPS
1
Remote Off/On and Remote
4DB
Power Off connectors
5
2Slot
9 with output contacts
USB and serial ports
6Input/Ouput
for Network-MS,
connections
ModBus-MS or Relay-MS
cards
3External
battery module
Eaton 9SX 11kVA
(EBM) connector with automatic detection (RJ-11)
Technical Specifications
5kVA
6kVA
8kVA
11kVA
Rating (kVA/kW)
5kVA/4.5kW
6kVA/5.4kW
8kVA/7.2kW
11kVA/10kW
Technology
On-line double conversion with Power Factor Correction (PFC) system
Input voltage range
176-276V without derating (up to 100–276V with derating)
Input frequency range/THDI
40-70Hz, 50/60Hz autoselection, frequency converter as standard, THDI < 5%
Electrical Characteristics
Nominal voltage
200/208/220/230/240V
200/208/220/230/240V/250V
200/208/220/230/240V +/– 1%; THDU <2%
200/208/220/230/240/250V +/– 1%; THDU <2%
Up to 94% in Online mode, 98% in Hi-Efficiency mode
Up to 95% in Online mode, 98% in Hi-Efficiency mode
Overload capacity
102–110% : 120s, 110–125%: 60s, 125–150%: 10s, >150%: 500ms
102–110% : 120s, 110–125%: 60s, 125–150%: 10s, >150%: 900ms
Input
Terminal block (up to 10 mm2)
Output voltage/THDU
Efficiency
Crest factor/short circuit current
Connections
Outputs
Batteries
Typical backup times at 50 and 70% load*
9SX
9SX + 1 EBM
9SX + 4 EBM
Battery management
3:1/90A
3:1/90A
3:1/120A
Terminal block (up to 16mm2)
Terminal block + 2 controlled groups of 4 IEC C13 (10A) + 2 IEC C19 (16A)
13/10 min
60/40 min
220/150 min
11/8 min
48/34 min
170/120 min
3:1/150A
Terminal block
15/10 min
9/5min
38/25 min
22/15 min
120/82 min
80/55 min
ABM® and Temperature compensated charging method (user selectable), automatic battery test, deep discharge protection, automatic
recognition of external battery units.
Communication
Communication ports
Communication slot
Operating conditions, standards and approvals
1 USB port, 1 RS232 serial port (USB and RS232 ports cannot be used simultaneously), 4 dry contacts (DB9), 1 mini terminal block for remote
On/Off and 1 for remote power Off.
1 slot for Network-MS card, ModBus-MS or Relay-MS cards.
Operating temperature
0 to 40°C continuous
Safety
IEC/EN 62040-1, UL 1778, CSA 22.2
Approvals
CE, CB report (TUV), UL
Noise level
EMC, performance
Dimensions H x W x D/Weight
UPS
EBM
<45dB
<48db
<50db
IEC/EN 62040 -2 , FCC Class A, IEC/EN 62040-3 (Performance)
440(19’’)*130(3U)*685mm/48kg
440(19’’)*130(3U)*645mm/68kg
Power module
–
Warranty
2 years warranty
Customer Service and Support
<45dB
440(19’’)*130(3U)*685mm/48kg
440(19’’)*130(3U)*645mm/68kg
–
440(19’’)*260(6U)*700mm/84kg
440(19’’)*130(3U)*680mm/65kg
440(19’’)*130(3U)*700mm/19kg
440(19’’)*260(6U)*700mm/86kg
440(19’’)*130(3U)*680mm/65kg
440(19’’)*130(3U)*700mm/21kg
* Runtimes are shown at 0.7 power factor. Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc
Parts Numbers
9SX 5kVA
9SX 6kVA
9SX 8kVA
9SX 11kVA
UPS
–
–
9SX8Ki
9SX11Ki
UPS with Rack Kit
EBM
EBM with Rack Kit
Power Module
HotSwap Maintenance ByPass
Transformer Module
Supercharger with Rack Kit
1.8m Battery Connection Cable
Battery Integration System
Rack Kit
9SX5KiRT
–
9SXEBM180RT
–
MBP6Ki
TFMR11Ki
–
EBMCBL180
BINTSYS
9RK
9SX6KiRT
–
9SXEBM180RT
–
MBP6Ki
TFMR11Ki
–
EBMCBL180
BINTSYS
9RK
9SX8KiRT
9SXEBM240
–
9SX8KiPM
MBP11Ki
TFMR11Ki
SC240RT
EBMCBL240
BINTSYS
9RK
9SX11KiRT
9SXEBM240
–
9SX11KiPM
MBP11Ki
TFMR11Ki
SC240RT
EBMCBL240
BINTSYS
9RK
www.eaton.eu
33
Network and Server
One phase UPS
Eaton 9PX UPS
5/6/8/11 kVA
Energy efficient power protection
Performance and Efficiency
Rack/Tower versatile 1:1
• Double conversion topology. The Eaton 9PX constantly monitors
power conditions and regulates voltage and frequency.
• With up to 95% efficiency in online double conversion mode
and 98% in high-efficiency mode the 9PX provides the
highest efficiency level in its class to reduce energy &
cooling costs.
• With a 0.9 power factor the 9PX delivers 28% more power than
UPS in its class. It powers more servers than other UPSs with
equivalent VA ratings and lower power factors.
• With a RT (Rack/tower) versatile form factor the 9PX is the
most compact solution in its class delivering up to 5400W in
only 3U and 10kW in only 6U.
Manageability
9PX 11kVA with Maintenance ByPass
Advanced protection for:
• Small & medium datacenter
• IT, Networking, Storage and Telecom
• Infrastucture, Industrial and Medical
34
EATON UPS Catalogue
• The new graphical LCD provides clear information on the
UPS’s status and measurements on a single screen (in seven
languages). LCD display position can be adjusted to offer the
best viewable angle for tower and rack usage.
• The 9PX can meter energy consumption. kWh values can be
monitored using the LCD or Eaton’s Intelligent Power® Software
Suite.
• Load segment control enables prioritised shutdowns of
nonessential equipment to maximise battery runtime for
critical devices. It can also be used to remotely reboot lockedup network equipment or to manage scheduled shutdowns and
sequential start-ups.
• The 9PX offers Serial, USB and relay connectivity, plus an extra
slot for an optional card (Network card delivered as standard
on Netpack version). Eaton’s Intelligent Power® Software Suite
compatible with all major OS including virtualization software
such as VMware and Hyper-V is included with each UPS.
Availability and Flexibility
• The internal bypass allows service continuity in case of
internal fault, a Maintenance ByPass is also available (as
standard on HotSwap version) for easy replacement of the UPS
without powering down critical systems.
• The Eaton 9PX can be paralleled to achieve twice the power of
unitary product using HotSync technology, without extra cost on
the initial purchase.
• Stronger, longer battery life: Eaton ABM® battery management
technology uses an innovative three-stage charging technique
that extends battery life by up to 50%.
• More runtime can be added with up to 12 external hotswappable battery modules, able to run systems for hours if
necessary. The additional battery modules are automatically
recognized by the UPS.
Eaton 9PX UPS
1
Remote Off/On and Remote
Power Off connectors
5
8 IEC 10A sockets (2 groups
of 4 manageable sockets)
with cable retention system
2
Slot for Network-MS,
ModBus-MS or Relay-MS cards
6
2 IEC 16A sockets
with cable retention system
3
Parallel operation
port (DB15)
7
DB 9 with output contacts
4
External battery module
(EBM) connector with
automatic detection (RJ11)
8
USB and serial ports
9
Input/Ouput connection
Technical Specifications
5kVA 1:1
6kVA 1:1
6kVA 3:1
8kVA 1:1 or 3:1
11kVA 1:1 or 3:1
Rating (kVA/kW)
5kVA/4.5kW
6kVA/5.4kW
6kVA/5.4kW
8kVA/7.2kW
11kVA/10kW
Technology
On-line double conversion with Power Factor Correction (PFC) system
Input voltage
200/208/220/230/240V single phase
Input voltage range
176-276V without derating (up to 100-276V with derating) single phase305V-480V without derating (up to 175V-480V with derating) three phase
Output voltage/THDU
200/208/220/230/240V +/– 1%; THDU <2%
Input frequency range/THDI
40-70Hz, 50/60Hz autoselection, frequency converter as standard, THDI < 5%
Efficiency
Up to 94% in Online mode, 98% in Hi-Efficiency mode
Electrical Characteristics
200/208/220/230/240V/250V single phase, 380/400/415 three phase
200/208/220/230/240/250V +/– 1%; THDU <2%
Up to 95% in Online mode,
98% in Hi-Efficiency mode
Crest factor/short circuit current
3:1/90A
Overload capacity
102–110% : 120s, 110–125%: 60s, 125–150%: 10s, >150%: 500ms
3:1/90A
102–110% : 120s, 110–125%: 60s, 125–150%: 10s, >150%: 900ms
3:1 / 90A
3:1 / 120A
3:1 / 150A
Terminal block (up to 10 mm2)
Terminal block + 2 controlled groups of 4 IEC C13 (10A) + 2 IEC C19
(16A)
Terminal block (up to 16mm2)
Connections
Input
Outputs
Outputs with HotSwap Maintenance Bypass
Terminal block
Terminal block
+ 4 IEC C19 (16A)
Terminal block + 3 IEC C13 (10A) + 2 IEC C19 (16A)
Batteries
Typical backup times at 50 and 70% load*
9PX
13/10 min
11/8 min
30/20min
20/15 min
13/9min
9PX + 1 EBM
60/40 min
48/34 min
70/45min
48/32 min
32/21 min
9PX + 4 EBM
220/150 min
170/120 min
210/140 min
140/100 min
100/70 min
Battery management
ABM® and Temperature compensated charging method (user selectable), automatic battery test, deep discharge protection, automatic
recognition of external battery units.
Communication
Communication ports
1 USB port, 1 RS232 serial port (USB and RS232 ports cannot be used simultaneously), 4 dry contacts (DB9), 1 mini terminal block for remote
On/Off and 1 for remote power Off, 1 DB15 for parallel operation.
Communication slot
1 slot for Network-MS card (included in Netpack versions), ModBus-MS or Relay-MS cards.
Operating conditions, standards and approvals
Operating temperature
0 to 40°C continuous
Noise level
<45dB
Safety
IEC/EN 62040-1, UL 1778 (1:1 version)
<45dB
<48db
EMC, performance
IEC/EN 62040 -2, FCC Class A (1:1 version), IEC/EN 62040-3 (Performance)
Approvals
CE, CB report (TUV), UL (1:1 version)
<48db
<50db
Dimensions H x W x D/Weight
UPS Dimensions
440(19’’)*130(3U)*685mm
440(19’’)*130(3U)*685mm
440(19’’)*260(6U)*700mm
440(19’’)*260(6U)*700mm
440(19’’)*260(6U)*700mm
UPS Weight
48kg
48kg
88kg
84kg (1ph), 88kg (3ph)
86kg (1ph), 88kg (3ph)
EBM Dimensions
440(19’’)*130(3U)*645mm
440(19’’)*130(3U)*645mm
440(19’’)*130(3U)*680mm
440(19’’)*130(3U)*680mm
440(19’’)*130(3U)*680mm/65kg
EBM Weight
68kg
68kg
65kg
65kg
65kg
Power Module Dimensions
-
-
440(19’’)*130(3U)*700mm
440(19’’)*130(3U)*700mm
440(19’’)*130(3U)*700mm
Power Module Weight
-
-
23kg
19kg (1ph), 23kg (3ph)
21kg (1ph), 23kg (3ph)
Customer Service and Support
Warranty
2 years warranty
* Runtimes are shown at 0.7 power factor. Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc
Parts Numbers
9PX 5kVA
9PX 6kVA
9PX 8kVA
9PX 6kVA 3:1
9PX 8kVA 3:1
9PX 11kVA 3:1
UPS with HotSwap Maintenance Bypass
9PX5KiBP
9PX6KiBP
9PX8KiBP
9PX6KiBP31
9PX8KiBP31
9PX11KiBP31
UPS with Network Card and Rack Kit
9PX5KiRTN
9PX6KiRTN
–
/
/
/
UPS with HotSwap MBP, Network Card
and Rack Kits
–
–
9PX8KiRTNBP
9PX6KRTNBP31
9PX8KiRTNBP31
9PX11KiRTNBP31
EBM
9PXEBM180
9PXEBM180
9PXEBM240
9PXEBM240
9PXEBM240
9PXEBM240
Power Module
–
–
9PX8KiPM
9PX6KiPM31
9PX8KiPM31
9PX11KiPM31
HotSwap Maintenance Bypass
MBP6Ki
MBP6Ki
MBP11Ki
MBP11Ki31
MBP11Ki31
MBP11Ki31
Transformer Module single phase
TFMR11Ki
TFMR11Ki
TFMR11Ki
TFMR11Ki
TFMR11Ki
TFMR11Ki
Supercharger with Rack Kit
–
–
SC240RT
SC240RT
SC240RT
SC240RT
1.8m Battery Connection Cable
EBMCBL180
EBMCBL180
EBMCBL240
EBMCBL240
EBMCBL240
EBMCBL240
Battery Integration System
BINTSYS
BINTSYS
BINTSYS
BINTSYS
BINTSYS
BINTSYS
Rack Kit
9RK
9RK
9RK
9RK
9RK
9RK
www.eaton.eu
35
Data Center and Facility UPS
Three phase UPS
Eaton BladeUPS
12/24/36/48/60 kW
Designed for data centres – to ensure maximum
uptime and efficiency
Simply scalable
• Eaton BladeUPS provides scalable double-conversion backup
power
• BladeUPS is designed for the data centre -to work in harmony
with your servers and IT equipment to ensure maximum uptime
and maximum efficiency
• Scalable architecture enables you to design, scale and grow your
data centre as your demand grows.
• BladeUPS provides from 12kW to 60kW N+1 mounted in a
single IT rack enclosure, with multiple power distribution options
• BladeUPS delivers an industry-leading 98% efficiency across the
operating range, resulting in cooler operating conditions and less
heat dissipation
™
Due to outstanding green performance, Eaton BladeUPS
has earned the “An Eaton Green Solution”™ label
Advanced power protection for:
•
•
•
•
•
•
36
Small, medium and large data centres
Blade servers
Network environments
Telephony and VoIP equipment
Networking applications such as IPTV, security
Storage devices: RAID, SAN
EATON UPS Catalogue
Highly flexible
• BladeUPS is extremely flexible and supports multiple
configurations including power protection in each rack,
centralised protection, zone protection or hybrid as required
• If your needs change or need to move your IT equipment,
simply redeploy and reuse BladeUPS as single of parallel units
elsewhere
• Multiple external batteries can be added to increase runtime
• BladeUPS has multiple power distribution options including the
Rack Power Module (RPM), ePDUs or hardwired. The 3U RPM
delivers single-phase power and can be deployed in the same
rack as the UPS and IT equipment.
Highly efficient
• Optimize your operational expenditure - Latest high efficiency
technologies provide 98% efficiency, with 65% less heat
dissipation to minimise your operational costs and reduce your
carbon footprint
• A 60kW N+1 solution could save over €20,000 in 5 years in
energy costs alone
• The small footprint of BladeUPS allows extra space for IT
equipment in the rack and data centre.
• Due to the low heat dissipation, air conditioning requirements
are reduced by up to a third and BladeUPS can be located close
to IT equipment.
• Utilises Eaton’s Advanced Battery Management system to
prolong battery life by up to 50%
Eaton BladeUPS
TECHNICAL SPECIFICATIONS
General
Power Rating
Efficiency
Heat Dissipation
Cooling
12 kW per UPS module
Up to 98,6 per cent
371W/1266 BTU/hr at 100% rated load
Fan cooled, temperature microprocessor
monitored; front air entry, rear exhaust
Audible Noise, Normal
Operation
<60 dBA at 1 meter
Altitude Before Derating
1000 meters (3300 ft ASL)
Input
Input Voltage
Voltage Range
Frequency Range
400 Vac
400V: 311 to 519 Vac, phase to phase
50 or 60 Hz, ±5 Hz
Input Current Distortion
<5% with IT loads (PFC power supplies)
Input Power Factor
Inrush Current
Input Requirements
Bypass Source
Generator
Compatibility
>0.99 with IT loads (PFC power supplies)
Load dependent
Three-phase, four-wire + ground
Same as input (single feed)
Fast sync slew rate for generator synchronisation
Output
Communications and User Interface
Software
UPS ships with Software Suite CD
Compatibility
X-Slot Bays
Two available for the cards listed below
Two lines by 20 characters
Control Panel LCD
Four menu-driven interface buttons
Four status at a glance LEDs
Multi-language
English standard; 20 languages available
Configuration
User capable, firmware auto configures
Changes
Dry Contact Inputs
Two, user-configurable
Dry Contact Outputs
One, user-configurable
Service
Installation
Preventative
Maintenance
Corrective
Maintenance
Serviceability
Features
400V: 180 to 240 Vac, Ph to N
Output Frequency (nominal)
50 or 60 Hz auto-detection on startup
EMI
Surge Protection
Hazardous
Materials (RoHS)
Frequency Regulation
0.1 Hz free running
Warranty
Lagging: 0.7
Leading: 0.9
<3% with IT loads (PFC power supplies)
Total Output Voltage Distortion
<5% non-linear or non-PFC power supplies
Load Power Factor Range
Battery
Battery Type
Battery Runtime (Internal)
VRLA - AGM
13 minutes at 50 per cent load
4.7 minutes at 100 per cent load
Battery String Voltage
240 Vdc
Battery Test
Automatic battery test standard
(remote scheduling capable)
Manual battery test from front display
Battery Recharge Profile
ABM three-stage charging technology
Battery Cut-off Voltage
Variable from 1.67 VPC at <5 min. runtime
Battery Low Condition
Announced with alarm
Extended Battery Capability
Yes, add up to four additional 3U battery enclosures
(~34 min at 100 per cent load, >1 hour at 50 per cent
load)
Physical
Dimensions (HxWxD) UPS
Note: Total Chassis Weight
without batteries or
electronics
Total Chassis Weight
with batteries or
electronics
Total UPS Weight
without Batteries
Total UPS Weight
with Batteries
EBM Weight
User capable, optional factory service available
User capable, optional factory service available
Hot-swappable batteries
Hot-swappable electronics module
Automated internal maintenance bypass
Auto-configure firmware
Flash firmware upgradeable
Certifications
Rated Output Voltage
Output
Configuration
Three-phase, four-wire + ground
User capable, located in the IT racks
Standard
Warranty Repair
IEC 62040
ANSI C62.41, Cat B-3
EU Directive 2002/95/EC Category 3 (4 of 5)
12 months
Factory depot repair or replace
Options and Accessories
Detachable input cord
Detachable input/output cord assembly
Detachable paralleling cord assembly
Extended Battery Modules (EBMs)
3U output sub-distribution module
0U to 3U rack power strips
60 kW BladeUPS Parallel Bar
Four-post rail kit
Optional X-Slot Communication Cards
Application
Web SNMP
Environment Monitoring
IBM eServer™
(i5™, iSeries™,
or AS/400), industrial
Parallel
Remote LCD Display
Card
ConnectUPS-X Web/SNMP Card
EMP Environmental Monitoring Probe
(requires Web/SNMP card)
Relay Interface Card
Hot Sync Card
ViewUPS-X
Recommended ePDU:
261 (6U) x 442 x 660 mm
Y032440CD100000
PW107BA0UC08
46 kg
PW107MI0UC08
RPM - Rack Power Module (BladeUPS in, 12xC13 + 6xC19
out) 20 ft lead
ePDU - Basic (0U, Dual 16A C20 in, 24xC13+ 8xC19 out) use
in addition to RPM
ePDU - IP Monitored (0U, Dual 16A C20 in, 24xC13+ 8xC19
out) use in addition to RPM
140 kg
61 kg
140 kg
77 kg
www.eaton.eu
37
Data Center and Facility UPS
One and Three phase UPS
Eaton 9155 and 9355 UPS
8/11/12/15 kVA
Double-conversion UPS
Premium power performance
• Double-conversion topology provides the highest level of
protection available by isolating the output power from all input
anomalies.
• With a transformer-free design and sophisticated sensing and
control circuitry the 9155/9355 delivers an efficiency
of up to 92%.
• Active power factor correction (PFC) provides unbeatable 0,99
input power factor and less than 4,5% ITHD, thus eliminating
interference with other critical equipment in the same electrical
network and enhancing compatibility with generators.
• With 0.9 output power factor, UPS is optimized to protect
modern IT equipment without need to oversize.
True reliability
Advanced power protection for:
•
•
•
•
•
•
38
Banking systems
Small server and computer rooms
Healthcare equipment
Network communications equipment
Security systems
Automation systems
EATON UPS Catalogue
• Patented Powerware HotSync® technology enables paralleling
of two or more UPS modules to increase availability or add
capacity. The technology enables load sharing without any
communication line, thus eliminating single point of failure.
• ABM® technology charges batteries only when necessary,
reducing batteries corrosion and prolonging batteries service life
by up to 50%.
• Internal batteries in all standard configurations provide an
extended runtime with the smallest footprint.
Extensive configurability
• Further runtime extension is possible with external battery
cabinets.
• A multilingual graphical LCD display makes possible to monitor
the UPS status easily.
• The 9155/9355 can also be integrated into network
management, industrial automation and building management
systems.
• Bundled Eaton Software Suite provides an orderly network
shutdown in an event of extended power outage.
Eaton 9155/9355 UPS 8-15 kVA
Technical specifications
UPS output power rating (0,9 p.f.)
kVA
8
10
12
15
kW
7,2
9
10,8
13,5
General
Efficiency in double
conversion mode (full load)
Efficiency in double
conversion mode (half load)
Efficiency in high efficiency
mode
Distributed parallelling with
Hot Sync technology
Field upgradeable
<3% (100% linear load); <5% (reference non linear
load)
0,9 (e.g. 9 kW at 10 kVA)
Output UTHD
Output power factor
Permitted load power factor
Overload on inverter
92%
Overload when bypass available
90%
0,7 lagging - 0,8 leading
10 min 100-110%; 1 min 110-125%;
5 sec 125-150%; 300 ms >150%
60 min 100-110%, 10 min 110-125%; 1 min >125150%
Battery
up to 98%
4
Type
Maintenance free VRLA batteries, NiCd
Charging method
ABM technology or Float
Optional
Inverter/rectifier topology
transformer-free IGBT with PWM
Temperature compensation
Battery nominal voltage (leadacid)
Audible noise
<50 dB
Charging current / Model
Altitude (max)
1000 m without derating (max 2000 m)
*May be limited by maximum UPS input current rating
yes
Input
Input wiring
Nominal voltage rating
(configurable)
384 V (32x12 V, 192 cells)
Default 3 A
*Max 30 A
Accessories
1 ph or 3 ph + N + PE
Isolation transformer, long-life batteries, external battery cabinets, UPS Center (input, bypass, distribution),
X-Slot connectivity (Web/SNMP, ModBus/Jbus, Relay,
Hot Sync, ViewUPS-X remote display), Hot Sync parallel tie cabinet, integrated manual bypass, external
maintenance bypass switch
220/380, 230/400, 240/415 V 50/60 Hz
Input frequency range
Low -20% at 100% load/-50% at 50% load without
battery discharge; High +10% /max +20%
45-65 Hz
Input power factor
0,99
Communications
Input ITHD
less than 4,5%
X-Slot
2 communication bays
Soft start capability
Yes
Serial ports
1 available
Internal backfeed protection
Yes
Relay inputs/outputs
2/1 programmable
Input voltage range
Output
Output wiring
Nominal voltage rating
(configurable)
Compliance with standards
1 ph or 3 ph + N + PE
Safety (CB certified)
IEC 62040-1, IEC 60950-1
220/380, 230/400, 240/415 V 50/60 Hz
EMC
IEC 62040-2
Performance
IEC 62040-3
Stand-alone UPS with 1-phase input
Part number
Description
Rating
Back-up (pf. 0.7)
Dimensions (HxWxD)
Weight
1022532
9155-8-S-10-32x7Ah
8 kVA / 7.2 kW
10 min
817x305x702 mm
155 kg
1022533
9155-8-S-15-32x9Ah
8 kVA / 7.2 kW
15 min
817x305x702 mm
160 kg
1022534
9155-8-S-28-64x7Ah
8 kVA / 7.2 kW
28 min
1214x305x702 mm
250 kg
1022535
9155-8-S-33-64x9Ah
8 kVA / 7.2 kW
33 min
1214x305x702 mm
275 kg
1022536
9155-10-S-10-32x9Ah
10 kVA / 9 kW
10 min
817x305x702 mm
160 kg
1022537
9155-10-S-20-64x7Ah
10 kVA / 9 kW
20 min
1214x305x702 mm
250 kg
1022538
9155-10-S-25-64x9Ah
10 kVA / 9 kW
25 min
1214x305x702 mm
275 kg
Stand-alone UPS with 3-phase input
Part number 9155/9355
Description
Rating
Back-up (pf. 0.7)
Dimensions (HxWxD)
Weight
1022480
9155-8-N-10-32x7Ah
8 kVA / 7.2 kW
10 min
817x305x702 mm
155 kg
1022481/1023411
9155/9355-8-N-15-32x9Ah
8 kVA / 7.2 kW
15 min
817x305x702 mm
160 kg
1022482
9155-8-N-28-64x7Ah
8 kVA / 7.2 kW
28 min
1214x305x702 mm
250 kg
1022483/1023412
9155/9355-8-N-33-64x9Ah
8 kVA / 7.2 kW
33 min
1214x305x702 mm
275 kg
1022484/1023413
9155/9355-10-N-10-32x9Ah
10 kVA / 9 kW
10 min
817x305x702 mm
160 kg
1022485
9155-10-N-20-64x7Ah
10 kVA / 9 kW
20 min
1214x305x702 mm
250 kg
1022486/1023414
9155/9355-10-N-25-64x9Ah
10 kVA / 9 kW
25 min
1214x305x702 mm
275 kg
1022487/1023415
9155/9355-12-N-8-32x9Ah
12 kVA / 10.8 kW
8 min
817x305x702 mm
160 kg
1022488
9155-12-N-15-64x7Ah
12 kVA / 10.8 kW
15 min
1214x305x702 mm
250 kg
1022489/1023416
9155/9355-12-N-20-64x9Ah
12 kVA / 10.8 kW
20 min
1214x305x702 mm
275 kg
1022490/1023417
9155/9355-15-N-5-32x9Ah
15 kVA / 13.5 kW
5 min
817x305x702 mm
160 kg
1022491
9155-15-N-10-64x7Ah
15 kVA / 13.5 kW
10 min
1214x305x702 mm
250 kg
1022492/1023418
9155/9355-15-N-15-64x9Ah
15 kVA / 13.5 kW
15 min
1214x305x702 mm
275 kg
Part number
Description
Rating
Back-up (pf. 0.7)
Dimensions (HxWxD)
Weight
1022561
9X55-BAT5-64x7Ah
2x32x7 Ah
195 kg
1022562
9X55-BAT5-96x7Ah
3x32x7 Ah
Check technical specifications
817x305x699 mm
1214x305x699 mm
310 kg
External battery cabinets
www.eaton.eu
39
Data Center and Facility UPS
Three phase UPS
Eaton 9355 UPS
20/30/40 kVA
Double-conversion UPS
Premium power performance
• Double-conversion topology provides the highest level of
protection available by isolating the output power from all input
anomalies.
• With a transformer-free design and sophisticated sensing and
control circuitry the 9355 delivers an efficiency of up to 93%.
• Active power factor correction (PFC) provides unbeatable
0,99 input power factor and less than 4,5% input ITHD, thus
enhancing compatibility with generators and eliminating
interference with other critical equipment in the same network.
• The UPS enables optimal power protection for modern 0,9 p.f.
rated IT equipment without the need to oversize.
• The 9355 design is also available with 1-phase output (9155) at
20-30kVA power ratings.
True reliability
Advanced power protection for:
•
•
•
•
•
40
Financial systems
Medium-sized servers and computers
ICT equipment
Critical building infrastructure
Industrial applications
EATON UPS Catalogue
• Patented Powerware Hot Sync® technology makes possible
to parallel two or more UPSs to increase availability or add
capacity. The technology enables load sharing without any
communication line, thus eliminating single point of failure.
• ABM® technology charges batteries only when necessary,
preventing batteries corrosion and prolonging batteries service
life by up to 50%.
• Internal batteries in all standard configurations support more
runtime than comparable UPS.
Extensive configurability
• Configurable and multilingual LCD control panel with back light
and graphical mimic screen monitors the UPS status easily.
• Connectivity options guarantee a smooth integration with
various application systems requirements.
• Bundled with Eaton Software Suite the 9355 provides an
orderly network shutdown in an event of extended power
outage. If required, the 9355 can also be integrated to network
management, industrial automation and building management
systems.
Eaton 9355 UPS
Technical specifications
Output power factor
0,9 (e.g. 27 kW at 30 kVA)
kVA
20
30
40
Permitted load power factor
kW
18
27
36
Overload on inverter
0,7 lagging - 0,8 leading
10 min 100-110%; 1 min 110-125%;
5 sec 125-150%; 300 ms >150%
60 min 100-110%, 10 min 110-125%; 1 min >125150%
UPS output power rating (0,9 p.f.)
General
Efficiency in double-conversion
mode (full load)
Efficiency in double-conversion
mode (half load)
Distributed parallelling with
Hot Sync technology
Field upgradeable
93%
Overload when bypass available
91%
Type
Maintenance free VRLA batteries, NiCd
Charging method
ABM technology or Float
Optional
Battery
4
Inverter/rectifier topology
Transformer-free IGBT with PWM
Temperature compensation
Battery nominal voltage (leadacid)
Audible noise
<50 dB
Charging current / Model
Altitude (max)
1000 m without derating (max 2000 m)
*May be limited by maximum UPS input current rating
yes
Input
432 V (36x12 V, 216 cells)
Default 3 A
*Max 60 A
Accessories
Input wiring
Nominal voltage rating
(configurable)
3 ph + N + PE
Isolation transformer, long-life batteries, external
battery cabinets, X-Slot connectivity (Web/SNMP,
ModBus/Jbus, Relay, Hot Sync, ViewUPS-X remote
display), Hot Sync parallel tie cabinet, integrated
manual bypass, external maintenance bypass switch
220/380, 230/400, 240/415 V 50/60 Hz
Input frequency range
Low -20% at 100% load/-50% at 50% load without
battery discharge; High +10%/max +20%
45-65 Hz
Input power factor
0,99
Communications
Input ITHD
less than 4,5%
X-Slot
2 communication bays
Soft start capability
Yes
Serial ports
1 available
Internal backfeed protection
Yes
Relay inputs/outputs
2/1 programmable
Input voltage range
Output
Compliance with standards
Output wiring
Nominal voltage rating
(configurable)
1 ph or 3 ph + N + PE
Safety (CB certified)
IEC 62040-1, IEC 60950-1
220/380, 230/400, 240/415 V 50/60 Hz
EMC
IEC 62040-2
Performance
IEC 62040-3
<3% (100% linear load); <5% (reference non linear
load)
Output UTHD
Standard UPS with 3-phase input
Part number 9355
Description
Rating
Runtime (pf 0.7)
Dimensions (HxWxD)
Weight
1025061/1026598
9355/9155-20-N-5-1x9Ah-MBS
20 kVA / 18 kW
5 min
1684x494x762 mm
300 kg
1025062/1026599
9355/9155-20-N-13-2x9Ah-MBS
20 kVA / 18 kW
13 min
1684x494x762 mm
400 kg
1025063/1026600
9355/9155-20-N-22-3x9Ah-MBS
20 kVA / 18 kW
22 min
1684x494x762 mm
500 kg
1025064/1026601
9355/9155-20-N-31-4x9Ah-MBS
20 kVA / 18 kW
31 min
1684x494x762 mm
600 kg
1025065/1026602
9355/9155-30-N-7-2x9Ah-MBS
30 kVA / 27 kW
7 min
1684x494x762 mm
400 kg
1025066/1026603
9355/9155-30-N-13-3x9Ah-MBS
30 kVA / 27 kW
12 min
1684x494x762 mm
500 kg
1025067/1026604
9355/9155-30-N-20-4x9Ah-MBS
30 kVA / 27 kW
20 min
1684x494x762 mm
600 kg
1025795
9355-40-N-8-3x9Ah-MBS
40 kVA / 36 kW
8 min
1684x494x762 mm
517 kg
1025796
9355-40-N-12-4x9Ah-MBS
40 kVA / 36 kW
12 min
1684x494x762 mm
617 kg
External battery cabinets 9155/9355
Part number
Description
Rating
Runtime
Dimensions (HxWxD)
Weight
1025169
9355-BAT-1x24Ah
1x36x24 Ah
1684x494x758 mm
510 kg
1025170
9355-BAT-2x24Ah
2x36x24 Ah
See separate
specification
1684x494x758 mm
870 kg
9355 20-40 kVA runtimes
Runtimes for UPS with internal batteries ...p.f. 0.7 (typical IT server/computer load)
Battery
7 Ah 12 V
9 Ah 12 V
7 Ah 12 V
9 Ah 12 V
7 Ah 12 V
9 Ah 12 V
7 Ah 12 V
9 Ah 12 V
Qty
1 x 36
1 x 36
2 x 36
2 x 36
3 x 36
3 x 36
4 x 36
4 x 36
5
24
30
60
70
103
115
152
158
10
8
12
24
28
41
46
55
63
15
5
7
14
18
26
31
40
42
20
5
10
13
17
22
26
31
25
6
10
12
16
18
23
30
7
10
13
15
20
35
5
7
10
11
15
40
5
8
9
12
www.eaton.eu
kVA
min
min
min
min
min
min
min
min
41
Data Center and Facility UPS
Three phase UPS
Eaton 93E UPS
80/100/120/160/200 kVA
Double conversion UPS
Simply effective power protection
• Double conversion provides the highest level of protection
available by isolating the output power from all input anomalies.
• With a transformer-free design and sophisticated sensing and
control circuitry the 93E UPS delivers an efficiency
of up to 98,5%.
• Active power factor correction (PFC) provides unbeatable 0,99
input power and <5% ITHD, thus eliminating interference with
other critical equipment in the same network and enhancing
compatibility with generators.
• The UPS is optimized for protecting modern 0,9 p.f. rated
IT equipment without the need to oversize.
True reliability
• Patented Powerware Hot Sync® technology makes possible
to parallel up to 3 UPSs in capacity and up to 4 UPSs in
redundancy. The technology enables load sharing without any
communication line, thus eliminating single point of failure and
increasing power availability.
• ABM testing and charging cycle helps you to prevent battery
problems and in addition lessens corrosion proloning battery
servicelife up to 50%.
Extensive configurability
Advanced power protection for:
•
•
•
•
•
•
•
Small and Medium data centers
Financial services
Building management
Telecommunications
Industrial automation equipment
Healthcare
Government
• The 93E offers up to 60% smaller footprint compared to
competitive UPS offerings.
• A multilingual graphical LCD display makes possible to monitor
the UPS status easily.
• Wide software and connectivity options provide monitoring,
management and shutdown capabilities over the network.
• Connectivity options are available to suit nearly any
communication requirements, from standard serial
communications to secure remote monitoring over the Web.
Cost savings and sustainability
• A new technical platform used in Eaton´s three-phase UPS
products guarantee easy upgrades, low MTTR, similarity on
service trainings and documentation, thus lowering total cost of
ownership.
• A range of service agreement options can be easily customized
for customers’ needs and budget.
42
EATON UPS Catalogue
Eaton 93E UPS
General
Output
80 100120160200 kVA
72 90 108144180 kW
Output wiring
3 ph + neutral
Efficiency in double conversion mode (full
load)
Efficiency in double conversion mode (half
load)
93.5%
Nominal voltage rating (configurable)
220/380, 230/400 (default),
240/415 V 50/60 Hz
Output UTHD
<2% (100% linear load)
Output power factor
0.9
Efficiency in High-Efficiency mode (HE)
98.5%
Permitted load power factor
Distributed paralleling
with Hot Sync technology
3+1
Inverter/rectifier topology
Transformer-free IGBT with PWM
Audible noise
≤65 dB (80-120kVA) and ≤70dB
(160-200kVA) at a 1m, 75 % load
Altitude (max)
1000 m without derating (max 2000 m)
0.7 lagging – 0.9 leading
10 min 102-125%load
1 min 126-150%load
150 ms >151% load
Continuous <115% load, 20 ms 1000%
peak current. Note! External bypass fuses
may limit the overload capability.
UPS output power rating (0.9 p.f.)
93.3%
Input
Input wiring
3 ph + neutral
Nominal voltage rating (configurable)
220/380, 230/400, 240/415 V 50/60 Hz
Input voltage range
+20% / -15% at 100% load
+20% / -50% at 50% load
Input frequency range
42-70 Hz
Input Power Factor
Overload on inverter
Overload when bypass available
Accessories
External battery cabinets, internal manual bypass switch up to 120 kVA,
external maintenance bypass switch, MiniSlot connectivity
(Web/SNMP, ModBus/Jbus, Relay)
Communications
MiniSlot
2 communication bays
Serial ports
USB, RS232
0,99
Relay inputs/outputs
Two Signal inputs
Input ITHD
< 5%
Compliance with standards
Soft start capability
Yes
Safety (CB certified)
IEC 62040-1
Internal backfeed protection
Yes
EMC
IEC 62040-2, EMC Category C3
Performance
IEC 62040-3
Battery
Due to continous product improvement programs, specifications are subject to change without notice.
Battery type
VRLA
Charging method
ABM technology or Float
432 V (36 x 12 V, 216 cells)
456 V (38 x 12 V, 228 cells)
480 V (40 x 12 V, 240 cells)
80 100 120160200 kVA
2020 202020
4040 408080
Battery nominal voltage (lead-acid)
Charging current / Model
Default A
Max* A
*May be limited by maximum UPS input current rating
www.eaton.eu
43
Data Center and Facility UPS
Three phase UPS
Eaton 93PM UPS
30/40/50/80/100/120/150/160/200 kW
Maximum energy efficiency.
Minimum operating costs.
Lowest total cost of ownership
• The 93PM UPS sets new standards, with an operating level of
up to 97% in double conversion mode resulting in significant
savings in operational costs.
• > 99% superior efficiency is delivered
in Energy Saver System mode (ESS).
• Maximal power and energy density ensures
a compact footprint.
Highly scalable and reliable
• Scalable, modular architecture and ‘Pay as you grow
capability minimises CapEx.
• Eaton’s unique Hot Sync wireless paralleling and internal
redundancy ensures maximum availability and high reliability.
Easy deployment
™
Due to outstanding green performance,
the Eaton 93PM UPS has earned the
“An Eaton Green Solution”™ label
Key applications
•
•
•
•
44
Small, medium and large data centres
Modular and virtualised data centres
Mission-critical applications
IT infrastructure
EATON UPS Catalogue
• Thermal management support allows for flexible installation
against the wall, in rows and in hot/cold aisle configurations.
• Easy access allows fast MTTR (mean time to repair).
Easy management
• The 93PM UPS comes with Web and SNMP interfaces as
standard.
• Intelligent Power® software integrates with leading virtualisation
management systems for monitoring and managing.
• The intuitive user LCD interface and visual data logging provides
clear information on the UPS status.
Eaton 93PM UPS
Technical specifications
General
Output wiring 3ph + N + PE
220/380, 230/400, 240/415 V 50/60 Hz
UPS output power rating (1.0 p.f.) 30, 40, 50, 80, 100, 120, 150, 160, 200 kW
Nominal voltage rating (configurable) Efficiency in double conversion mode
Up to 97%
Efficiency in Energy Saver System (ESS) > 99%
Output UTHD < 1% (100% linear load).
< 5% (reference non-linear load)
Field upgradeable Yes
Rated output power factor 1.0
Inverter/rectifier topology
Transformer-free IGBT with PWM
Permitted load power factor 0.8 lagging – 0.8 leading
Audible noise
30–50 kW:
< 60 dBA
80–200 kW:
< 65 dBA
ESS operation:
< 47 dBA
Overload on inverter 10 min 102–110%;
60 sec 111–125%;
10 sec 126–150% 300 ms > 150%.
On battery mode 300 ms > 126%
Altitude (max) 1000 m without derating (max 2000 m)
Overload when bypass available N
ote: Bypass fuses may limit the overload
Input
Continuous < 125%, 10 ms 1000%
capability!
Input wiring 3ph + N + PE
Nominal voltage rating (configurable)
220/380, 230/400, 240/415 V 50/60 Hz
Accessories
Input voltage range High +20% rectifier input, 10% bypass input.
Low –15% at 100% load, –40% at 50% load
without battery discharge
Input frequency range
Input Power Factor
40–72 Hz 0.99
Input ITHD 30 kW:
40–200 kW:
Soft start capability Yes
Internal backfeed protection Yes
< 4.5%
< 3%
External battery cabinets with long-life batteries,
External maintenance bypass switch, integrated manual bypass,
MiniSlot connectivity (Web/SNMP, ModBus/Jbus, Relay)
Communications
MiniSlot 3 communication bays
Network/SNMP interface
Yes, standard
Serial ports Built-in host and device USB
Relay inputs/outputs 5 relay inputs and dedicated EPO
1 relay output
Compliance with standarts
Battery
Battery type VRLA
Charging method ABM technology or Float
Battery nominal voltage (VRLA) 432 V (36 x 12 V, 216 cells) or
480 V (40 x 12 V, 240 cells)
N
ote: Strings with different battery
30–50 kW
80–100 kW
120–150 kW
160–200 kW
Battery start capability Yes
IEC 62040-1
EMC IEC 62040-2
Performance IEC 62040-3
Due to continuous product imrovement programmes, specifications are subject to change without notice.
voltage may not be paralleled!
Charging current maximum Safety (CB certified) 16,5 A
33 A
50 A
66 A
Output
Part number
Description Rating Full load runtime Dimension (WxDxH) P-105000007-005
93PM-30(50)-BB-6x9Ah
30 kW 20 min 560 x 914 x 1876
890 kg
P-105000007-020
93PM-40(50)-BB-6x9Ah
40 kW 15 min 560 x 914 x 1876
890 kg
P-105000007-034
93PM-50(50)-BB-6x9Ah
50 kW 10 min 560 x 914 x 1876
890 kg
Part number
Description Rating P-105000011-001
93PM-50(100)-N+1
P-105000011-005
93PM-80(100)
P-105000011-009
93PM-100(100)
P-105000014-001
93PM-100(150)-N+1
P-105000014-005
93PM-120(150)
P-105000014-009
93PM-150(150)
P-105000016-001
93PM-150(200)-N+1
P-105000016-002
93PM-160(200)
P-105000016-003
93PM-200(200)
Dimension (WxDxH) 50 kW N+1
80 kW 100 kW Weight (with battery)
Weight (without batteries)
560 x 914 x 1876
338 kg
560 x 914 x 1876
338 kg
560 x 914 x 1876
338 kg
100 kW N+1 560 x 914 x 1876
438 kg
120 kW 560 x 914 x 1876
438 kg
150 kW 560 x 914 x 1876
438 kg
150 kW N+1
760 x 914 x 1876
556 kg
160 kW 760 x 914 x 1876
556 kg
200 kW 760 x 914 x 1876
556 kg
www.eaton.eu
45
Data Center and Facility UPS
Three phase UPS
Power Xpert 9395 UPS
225/275/450/550/675/827/900/1100 kVA
Double conversion UPS
Premium power performance
™
• Double conversion provides the highest level of protection
available by isolating the output power from all input anomalies.
• With a transformer-free design and sophisticated sensing and
control circuitry the 9395 UPS delivers an efficiency
of up to 94,5%.
• Maximised UPS energy efficiencies with Energy Advantage
Architecture (EAA): Variable Module Management System
(VMMS) optimises system efficiency at low load levels and
Energy Saver System (ESS) allows dramatic increase in UPS
efficiency without sacrificing load protection.
• Active power factor correction (PFC) provides 0,99 input power
factor and below 3-5% ITHD (depends on utility UTHD), thus
eliminating interference with other critical equipment in the
same network and enhancing compatibility with generators.
• The UPS is optimized for protecting modern 0,9 p.f.
rated IT equipment without the need to oversize.
True reliability
Due to outstanding green performance, the Power
Xpert 9395 has earned the “An Eaton Green
Solution”™ label
Advanced power protection for:
•
•
•
•
•
Big data centers and server farms
Financial services
Building management
Telecommunications
Hospitals
Power Xpert 9395 SBM
(System Bypass Module)
46
EATON UPS Catalogue
• Patented Powerware Hot Sync® technology makes possible to
parallel up to five UPSs to increase availability or add capacity.
The technology enables load sharing without any
communication line, thus eliminating single point of failure.
• Robust manageability with 10-inch color touchscreen display,
superior control and connectivity and with an extensive service
offering.
• ABM® technology charges batteries only when necessary,
preventing batteries corrosion and prolonging batteries service
life by up to 50%.
Extensive configurability
• The 9395 is a completely integrated system that incorporates
multiple power modules and system switchgear on factory prewired bases.
• A multilingual graphical LCD display makes possible
to monitor the UPS status easily.
• Wide software and connectivity options provide monitoring,
management and shutdown capabilities over network
• Cost savings and sustainability
• High system efficiency reduces utility cost, extends battery run
times and ensures cooler operating conditions.
• Compared to traditional UPS design, a transformer-free
UPS is only 50% the weight and occupies just 60% the
footprint, thus reducing impact on shipping.
• The new design requires 50-80% less energy in manufacturing
due to less energy needed for testing thanks to Easy Capacity
Test.
• Pre-wired configuration reduces cabling busbar costs and
installation time. Front accessible design minimizes installation
costs and saves valuable data centre space.
• A single technical platform used in Eaton´s three-phase UPS
products guarantees easy upgrades and similarity in service,
thus lowering total cost of ownership.
• More than 90% of the materials can be recycled, further
decreasing end-of-life impact.
Power Xpert 9395 UPS
Technical specifications
UPS output power rating (0,9 p.f.)
Battery
kVA
225
275
450
550
675
825
900
1100
kW
204
250
408
500
612
750
816
1000
General
Efficiency in double
conversion mode (full load)
>94% (According to IEC 62040-3)
Efficiency in double
conversion mode (half load)
>93% (According to IEC 62040-3)
VMMS (double conversion)
significantly increased efficiency at low loads
Efficiency in Energy Saver
System (ESS)
up to 99%
Distributed parallelling with Hot
5+1
Sync technology
Internal N+1 redundance
capable
in 550 : 275 kVA
in 825 : 550 kVA
in 1100 : 825 kVA
Type
VRLA, AGM, Gel, Wet Cell (NiCd batteries and flywheel on request)
Charging method
ABM technology or Float
Temperature compensation
with EMP
Battery nominal voltage (leadacid)
480 V (40 x 12 V, 240 cells)
Charging current / Model
Default A
Max* A
275
38
83
550
76
166
825
114
249
1100
152
332
*Limited by maximum UPS input current rating
Dimensions and weights
225 kVA, 275 kVA
1350 x 880 x 1880 mm (wxdxh)
830 kg
225, 275 kVA redundant
1890 x 880 x 1880 mm
1430 kg
450, 500, 550 kVA
1890 x 880 x 1880 mm
1430 kg
450, 550 kVA redundant
2630 x 880 x 1880 mm
2030 kg
Field upgradeable
yes
Inverter/rectifier topology
transformer-free IGBT with PWM
Audible noise
<76 dB; <81 dB (825 and 1100 kVA)
Field upgrade module,
225 or 275 kVA
740 x 880 x 1880 mm
600 kg
Altitude (max)
1000 m without derating (max 2000 m)
675, 825 kVA
3710 x 880 x 1880 mm
2520 kg
675, 825 kVA
+ 1 redundant
4450 x 880 x 1880 mm
3120 kg
1100 kVA
4450 x 880 x 1880 mm
3120 kg
Input
Input wiring
3 ph + N + PE
Nominal voltage rating
(configurable)
220/380, 230/400, 240/415 V 50/60 Hz
Options – Eaton 9395 SBM
Input voltage range
+15% / -15%, +10% /-10% for bypass
9395 SBM ratings
Input frequency range
45-65 Hz
Model
2000
2500
3200
4000
5000
Input power factor
0,99
Rating (A)
2000
2500
3200
4000
5000
Input ITHD
< 3-5% on nominal load, depending on the
utility UTHD
Dimensions and weights
Soft start capability
Yes
Internal backfeed protection
Yes, standard
Output
SBM 2000
2200 x 1032 x 1880 mm (wxdxh)
1400 kg
SBM 2500
2200 x 1032 x 1880 mm
1400 kg
SBM 3200
2200 x 1032 x 1880 mm
1550 kg
SBM 4000
2500 x 1032 x 1880 mm
2400 kg
2500 x 1032 x 1880 mm
2500 kg
Output wiring
3 ph + N + PE
SBM 5000
Nominal voltage rating
(configurable)
220/380, 230/400, 240/415 V 50/60 Hz
Accessories
Output UTHD
<3% (100% linear load); <5% (reference non linear
load)
Output power factor
0,9 (e.g. 250 kW at 275 kVA)
Permitted load power factor
0,7 lagging - 0,8 leading
Overload on inverter
10 min 100-110%; 30 sec 110-125%;
10 sec 125-150%; 300 ms >150%
Overload when bypass available
Continuous <115%, 20 ms 1000% Note! Bypass
fuses may limit the overload capability
General characteristics
External battery cabinets with long-life batteries,
NiCd batteries and flywheel on request, X-Slot connectivity (Web/SNMP, ModBus/Jbus, Relay, Hot Sync,
ViewUPS-X remote display), integrated manual bypass
for 225-550 kVA
Communications
X-Slot
4 communication bays
Serial ports
1 available
Relay inputs/outputs
5/1 programmable
Control panel (LCD)
10-inch Color Touchscreen with LED panel
Compliance with standards
Battery startup
Standard
Safety (CB certified)
IEC 62040-1, IEC 60950-1
Frequency conversion
Standard
EMC
IEC 62040-2
Multi-language
Standard
Performance
IEC 62040-3
Building alarm inputs
5 (galvanic isolated)
www.eaton.eu
47
Racks, Enclosures and Airflow Management
Eaton RP Series IT Rack
42U/48U
Main Features
• Unobstructed front, rear, bottom and top cable access,
maximizes cabling flexibility for demanding network
infrastructure
• Four 482mm (19 inch) EIA-310-E vertical mounting rails
with U-markings
• Tool-less adjustable rail positioning reduces set up
and refresh time
• 3 point rail mounting gives superior top to bottom rigidity
• Fast, easily removable doors, left or right hinge
• Split rear doors reduce space requirements on rack back side
• Top panel includes two 150mm wide cable openings allowing
removable covers or brush strip options to accommodate all
cabling requirements.
• Lockable, split side panels for quick and easy removal and
re-installation for stand-alone and end of row racks
• Side dividers with cable pass-through holes for easy cable
management between racks on multiple rack models
• Smart, attractive design with black RAL 9005 colour reflects
high quality construction
• Designed to accommodate all Eaton enclosure PDUs,
rack mounted UPSs
• Highly flexible accessory mounting options
All racks include
• Pre-installed grounding system,
eliminating time and installation cost
• Pull handles with key locks; other handle types
available upon request
• Starter kit including 20 x M6 cage nuts and screws,
20 x M5 accessory mounting screws
• Levelling feet
• Baying kit for multiple rack applications
Airflow Management
• Zero leakage around the front perimeter guides cool air to IT
equipment, significantly increasing cooling efficiency
and reducing energy costs
• High flow 75% open perforation doors maximizes airflow,
increasing cooling effectiveness of the IT equipment
• Vertical air blanking panels with grommet-covered cable
pass-thru on all 800mm wide models
• Extensive airflow management accessories available
Main Options & Accessories
RP Series rack with 2 installed Eaton ePDUs
48
EATON UPS Catalogue
• Side panels – aesthetic side cover includes security lock.
Supplied in two sections for easy installation
• Sided dividers – separate bayed racks for security and airflow
management without adding to rack footprint
• Rack top cable management – flexible distribution of power and
network cables with simple installation
• Full selection of cable management accessories
• Blanking panels in a variety of sizes
• Casters – easily install and move rack
• Shelves
Eaton RP Series IT Rack
42U
600x1200
42U
800x1000
42U
800x1200
48U
600x1000
48U
600x1200
48U
800x1000
48U
800x1200
Equipment Mounting Height
Height
Height (with caster wheels)
Width (with side panels)
Width (without side panels)
Depth (with doors)
Depth (without doors)
Product weight
Weight Capacity (static)
Weight Capacity
Maximum Rail Mounting Depth
Door swing
Rail Mounting Width
42U
42U
2043 mm
2043 mm
2062 mm
2062 mm
638 mm
638 mm
600 mm
600 mm
1057 mm
1257 mm
1000 mm
1200 mm
149kg
164kg
1364 kg
1364 kg
750kg
750kg
860 mm
1060 mm
135°
135°
483 mm (19 inch)
42U
2043 mm
2062 mm
838 mm
800 mm
1057 mm
1000 mm
183kg
1364 kg
750kg
860 mm
135°
42U
2043 mm
2062 mm
838 mm
800 mm
1257 mm
1200 mm
198kg
1364 kg
750kg
1060 mm
135°
48U
2310 mm
2329 mm
638 mm
600 mm
1057 mm
1000 mm
171kg
1364 kg
750kg
860 mm
135°
48U
2310 mm
2329 mm
638 mm
600 mm
1257 mm
1200 mm
188kg
1364 kg
750kg
1060 mm
135°
48U
2310 mm
2329 mm
838 mm
800 mm
1057 mm
1000 mm
210kg
1364 kg
750kg
860 mm
135°
48U
2310 mm
2329 mm
838 mm
800 mm
1257 mm
1200 mm
227kg
1364 kg
750kg
1060 mm
135°
Colour
Black, RAL 9005
2.0 mm
1.5 mm
1.5 mm
1.5 mm
2.0 mm
2.0 mm
1.5 mm
1.5 mm
1.5 mm
2.0 mm
2.0 mm
1.5 mm
1.5 mm
1.5 mm
2.0 mm
2.0 mm
1.5 mm
1.5 mm
1.5 mm
2.0 mm
2.0 mm
1.5 mm
1.5 mm
1.5 mm
2.0 mm
2.0 mm
1.5 mm
1.5 mm
1.5 mm
2.0 mm
TECHNICAL SPECIFICATIONS
42U
600x1000
Physical
Metal Thickness
Frame
Front Door
Rear Door
Roof
EIA Mounting Rail, 9.5mm square holes
2.0 mm
1.5 mm
1.5 mm
1.5 mm
2.0 mm
2.0 mm
1.5 mm
1.5 mm
1.5 mm
2.0 mm
Side Panel
1.0 mm
1.0 mm
1.0 mm
1.0 mm
1.0 mm
1.0 mm
1.0 mm
1.0 mm
Side Divider
1.0 mm
1.0 mm
1.0 mm
1.0 mm
1.0 mm
1.0 mm
1.0 mm
1.0 mm
Airflow
Open Perforation
75%
75%
75%
75%
75%
75%
75%
75%
Front Door Grill Free Area
6882 sqcm
6882 sqcm
10289 sqcm
10289 sqcm
7960 sqcm
7960 sqcm
11897 sqcm
11897 sqcm
Rear Door Grill Free Area
6165 sqcm
6165 sqcm
9563 sqcm
9563 sqcm
7111 sqcm
7111 sqcm
11058 sqcm
11058 sqcm
Shipping Width
Shipping Depth
Shipping Height
780 mm
1200 mm
2250 mm
780 mm
1540 mm
2250 mm
900 mm
1200 mm
2250 mm
900 mm
1540 mm
2250 mm
780 mm
1200 mm
2420 mm
780 mm
1540 mm
2420 mm
900 mm
1200 mm
2420 mm
900 mm
1540 mm
2420 mm
Shipping Weight
170 kg
190 kg
206 kg
224 kg
185 kg
205 kg
221 kg
239 kg
Shipping
Conformance
Regulatory Approvals
Standards
IEC/EN 60950
EIA-310-E
Protection Class
IP20 (when configured with Side Panels and top cover plate options)
Enclosure Power Distribution mounting (ePDU)
Zero U Frame mount, rear
Zero U mount with extention bracket
Qty 4 PDUs, 1700mm high x 55mm wide
Qty 4 PDUs, 1870mm high x 88mm wide
Qty 4 PDUs, 1966mm high x 55mm wide
Qty 4 PDUs, 2136mm high x 88mm wide
Mounting options
Key hole, M5 screw, EIA Mouting Rail (multiple options)
Customer Service and Support
Warranty
Two-year warranty
Part numbers
Stand-alone configuration provided with side panels & caster wheels
Part Number
P1PCP1
P2PCP1
Multiple rack configuration provided with side divider
P3PCP1
P4PCP1
P5PCP1
P6PCP1
P7PCP1
P8PCP1
Part Number
P3MLP1
P4MLP1f
P5MLP1
P6MLP1
P7MLP1
P8MLP1
P1MLP1
P2MLP1
www.eaton.eu
49
Power Distribution
PDUs
Eaton FlexPDU
Eaton HotSwap MBP
FlexPDU range
Power distribution
The no hassle solution for improving availability and adding
flexibility for single phase UPSs.
Eaton FlexPDU
Having the right connectors just where you need them
• FlexPDUs (Power Distribution Units) are flexible mounting
multiway socket blocks for easy connection of multiple loads
either as free-standing or on rack-mounted UPSs
• FlexPDUs have a large number of sockets (8 French or Schuko
sockets, 6 BS sockets or 12 IEC 10A sockets) which fit into a
very compact unit (1U - 19”)
• FlexPDUs are easy to implement into any type of installation:
they can be rack mounted horizontally (1U) or vertically
or directly onto all Eaton RT format (rack/tower) UPSs
HotSwap MBP range
MBP6Ki & MBP11ki
50
EATON UPS Catalogue
Eaton HotSwap MBP
• High availability for all UPSs up to 11 kVA.
• HotSwap MBP provides a maintenance bypass for all UPSs.
UPSs can be hot swapped or upgraded without interrupting the
power supply
• HotSwap MBP has an IEC16A input connector with
retaining clip for compatibility with any UPS now and in the
future from Eaton or any other supplier
• HotSwap MBP are available with multiple power ratings:
3000VA, 6000VA, 11000VA, 11000VA (3ph Input) There is a range
of HotSwap MBP units with different output connectors: French,
Schuko, British and IEC sockets
- terminal blocks on the HW (Hard-Wired) version
• When used with a 9PX or 9SX the HotSwap MBP 6000VA and
above are providing information on the Bypass status through
the UPS LCD screen.
• HotSwap MBP units can be installed as required; at the back,
side, top of the UPSs, or rack-mounted
Eaton FlexPDU
Eaton HotSwap MBP
Flexible system for 19” rack-mounting or on
Eaton RT UPSs
French/Schuko/British/IEC 10A sockets
IEC 16A output for cascading
IEC 16A input socket
Retaining clip
Rotary bypass switch
Colour coded input and output sockets for
connecting the UPS
NB: hard-wired version available
TECHNICAL SPECIFICATIONS
Maximum power
Nominal Voltage
Installation
Format
Installation
Dimensions H x W x D
Connection
Inputs
FR
DIN
BS
Outputs
IEC
Eaton HotSwap MBP
Eaton FlexPDU
Eaton HotSwap MBP 6000
Eaton HotSwap MBP 11000
16 A
3000VA
3000VA
220 - 240V
11000VA
200-240V (350 - 430 V for 3ph version)
1U (except BS) 19” rack-mounting
with multi-position mountings
19” rack, wall mounting or on 9PX/9SX UPS
44 x 483 x 80 mm (BS: 52 x 483 x 120 mm)
3U 19" rack
3U 19" rack
52 x 483 x 120 mm
89 x 483 x 90 mm
1 IEC C20 (16A) connector and 2 cables
Hardwired terminal block
(1 IEC 16A - 16A cable and 1 IEC 10A - 16A cable)
for connection to any UPS
8 French sockets + 1 IEC 16A socket
4 French sockets + 1 IEC 16A socket
8 Schuko sockets + 1 IEC 16A socket
4 Schuko sockets + 1 IEC 16A socket
6 British sockets + 1 IEC 16A socket
3 British sockets + 1 IEC 16A socket
(with 2 circuit breakers)
(with 1 circuit breaker)
12 IEC 10A sockets + 1 IEC 16A socket
"3 IEC 10A sockets + 2 IEC 16A sockets
(with 2 circuit breakers)
(with 3 circuit breakers) + Terminal blocks"
HW
NA
Cascading
Yes, IEC 16A output socket
Retaining clips
Retaining clips on the IEC output sockets
Operating conditions and approvals
Operating temperature
0°C to 40°C continuous
Approvals
CE
Terminal block
Hardwired terminal block
/
/
/
4 IEC 16A sockets
(with 4 circuit breakers)"
/
1: Use cable kits P/N 66 439 (French/Schuko) or 66 440 (British) for connecting a low power UPS <2.2 kVA (with IEC 10A outputs) - see below.
Part Numbers
FR
DIN
BS
IEC
HW (Hard-Wired)
10A French/Schuko cable kit for HotSwap MBP
10A British cable kit for HotSwap MBP
FR
DIN/
BS
Schuko
Eaton FlexPDU
FlexPDU 8 FR: 68 435
FlexPDU 8 DIN: 68 436
FlexPDU 6 BS: 68 437
FlexPDU 12 IEC: 68 438
/
/
/
Eaton HotSwap MBP
HotSwap MBP 4 FR: 68 430
HotSwap MBP 4 DIN: 68 431
HotSwap MBP 3 BS: 68 432
HotSwap MBP 6 IEC: 68 433
HotSwap MBP HW: 68 434
68 439
68 440
IEC C13 IEC C19 IEC C14 IEC C20
10 A
16 A
10 A
16 A
www.eaton.eu
51
Power Distribution
ePDUs
Managed ePDUs
Advanced Monitored
ePDUs
Switched ePDUs
Managed ePDUs offer data centre
managers maximum functionality
and flexibility by providing a
complete understanding of, and
control over, data centre power
distribution.
Advanced Monitored ePDUs give
data centre managers the detailed,
accurate information and understanding needed to run a data
centre efficiently and effectively.
Switched ePDUs give control to the
data centre managers. They provide
the ability to remotely shut off or
restart equipment, ensuring that it
starts up in the correct sequence
with the correct delays, together
with overall monitoring for load
balancing.
Highly accurate individual outlet, userdefined group of outlets, branch circuit
and full ePDU monitoring for kWhrs, V,
W and A (1% accuracy above 2A). Also
temperature and humidity monitoring in
the rack via optional sensors.
Highly accurate monitoring of branch circuit
and the ePDU as a whole for kWhrs, V,
W and A (1% accuracy above 2A). Also
temperature and humidity monitoring in
the rack via optional sensors. Monitor over
Ethernet or via Advanced LCD screen on
the unit.
—
On, off and reboot control of individual
outlets and user-defined group of outlets,
together with cycling and sequencing
of outlets and branch circuits. Power
Scheduling of outlets or outlet groups also
available.
Monitor and measure key properties
and alerts remotely over Ethernet or
via Advanced LCD screen on the unit.
Communication protocols include
HTTP/HTTPS, DHCP, SNMP v1 and v3,
SNTP, SMTP, Telnet, IPv4 and IPv6.
Mass configuration and upgrade available.
Monitor and Control key properties and
alerts remotely over Ethernet. Monitor
via Advanced LCD screen on the unit.
Communication protocols include HTTP/
HTTPS, DHCP, SNMP v1 and v3, SNTP,
SMTP, Telnet, IPv4 and IPv6. Mass configuration and upgrade available.
Includes Eaton’s patented flexible mounting system, which ensures
ePDUs will fit in any standard 42U IT rack.
Eaton Advanced Monitored ePDUs provide reliable, consistent power distribution
at temperatures of up to 50°C.
Cisco EnergyWise compliant.
Includes Eaton’s patented flexible mounting system, which ensures
ePDUs will fit in any standard 42U IT rack.
Eaton switched ePDUs provide reliable,
consistent power distribution at temperatures of up to 50°C.
Cisco EnergyWise compliant.
Monitoring
Highly accurate individual outlet, userdefined group of outlets, branch circuit,
and full ePDU monitoring for kWhrs, V, W
and A (1% accuracy above 2A). Also temperature and humidity monitoring in the
rack via optional sensors.
Switching
IIndividual outlet, sequencing of outlets
with delays or cycling, together with userdefined outlet group or branch circuit,
enables remote reboot of equipment.
Power Scheduling of outlets or outlet
groups also available.
Control
Monitor and control remotely over
Ethernet or via Advanced LCD screen on
the unit. Communication protocols include
HTTP/ HTTPS, DHCP, SNMP v1 and v3,
SNTP, SMTP, Telnet, IPv4 and IPv6.
Mass configuration and upgrade available.
Includes Eaton’s patented flexible mounting system, which ensures ePDUs will
fit in any standard 42U IT rack. Eaton
Managed ePDUs provide reliable, consistent power distribution at temperatures of
up to 50°C.
Cisco EnergyWise compliant.
52
EATON UPS Catalogue
Monitored ePDUs
In-Line Monitored
ePDUs
Basic ePDUs
Monitored ePDUs accurately
monitor the current draw of the
ePDU and branch circuit, to allow for
provisioning and load balancing of
servers, and to ensure current draw is
not approaching breaker limits.
In-line Monitored ePDUs are
designed for new data centres, or for
retrofitting to upgrade an existing
infrastructure which lacks power
monitoring. In-line Monitored ePDUs
provide accurate remote monitoring solutions for both A and B
feeds, with single and dual-feed
capability
Basic ePDUs are designed for reliable
and cost-effective power distribution. They have the reliability, form
factor and outlet choices to meet
your needs.Includes Eaton’s patented
flexible mounting system, which
ensures ePDUs will fit in any
standard 42U IT rack.
A fuseless and breakerless design allows
current monitoring in-line, with no break
to upgrade existing basic infrastructure.
—
—
—
Monitor and measure remotely over
Ethernet or via the LED interface
on the unit.
—
Monitoring
Monitor current on input and each branch
circuit to ensure accurate load balancing.
Switching
—
Control
Monitor and measure remotely over
Ethernet or via the LED interface on
the unit, which can automatically scroll
through branch circuits.
Includes Eaton’s patented flexible mounting system, which ensures ePDUs will fit
in any standard 42U IT rack.
Includes Eaton’s patented flexible mounting system, which ensures
ePDUs will fit in any standard 42U IT rack.
Retro-fit to existing equipment with A and
B feed, while live and without downtime.
Designed for the data centres
All ePDUs are made of rugged
aluminium or steel chassis and incorporate fully shrouded circuit breakers and
switches. Eaton ePDUs are designed for
the Data Centre – to be highly reliable, to
consistently provide power and designed
to last.
www.eaton.eu
53
Power management software & connectivity
Intelligent Power Software
Intelligent Power® Software is a suite of productivity tools for
power management from Eaton. It greatly simplifies the supervision of power conditions and devices in today’s enterprise environment, scaling effortlessly from local area networks with a few
UPSs and ePDUs to the most critical virtualised data centres.
Administrators will value the many automatic functions of
Intelligent Power Software. Installation requires just a few clicks
and a couple of minutes; once the software starts, it will automatically discover manageable equipment.
Intelligent Power Software architecture makes it very flexible.
Completely network-based communications make the server
part very suitable for virtualisation, and the web interface allows
access from any device with a browser, anywhere in the network.
Dynamic web interface presents database contents in text, graphs
and colours, highlighting the essential points.
The software can take automatic action as well. Events can be set
to trigger email sending, notifications and command execution.
This way alarms with exact data reach the right people in seconds,
giving maximum time for action to prevent downtime, reduce
mean time to repair and minimise the impact.
Intelligent Power Software incorporates two important applications
that ensure system uptime and data integrity: Intelligent Power
Manager (IPM) and Intelligent Power Protector (IPP).
Virtualisation
Virtualisation is driving the deployment of many new applications
and data centre demands. It changes the way IT facilities are operated, bringing substantial savings and increasing availability and
flexibility.
Managing the power infrastructure within a virtual platform is
vital for increased uptime and reliability of those applications. To
facilitate the management of power devices, the Intelligent Power
Manager plugs into leading virtual machine management systems,
including VMware® vCenter™ and Citrix XenCenter™, and integrates power management functions to these systems so that all
UPSs and ePDUs in the virtual network can be viewed within the
same application, together with network, physical server and storage information. In case of a local power failure, it can also trigger
vCenter’s vMotion™, SCVMM’s Live Migration and XenCenter’s
XenMove™ to transparently move virtual machines from a server
affected by a power interruption to an available server on the network, ensuring data integrity and enabling zero downtime.
If controlled graceful shutdown of hypervisors and their guests is
sufficient in case of a prolonged power outage, Intelligent Power
Protector is ideal for the task. IPP invokes shutdown or hibernation
of virtual machines, signals the hypervisor to shut down and powers off the physical server. It supports VMware, Hyper-V, Xen and
KVM platforms.
Intelligent Power Software snapshot
Benefits for virtualised environments
• Intelligent Power Manager for monitoring and managing
power equipment in IT environments
• Intelligent Power Protector for graceful shutdown of
operating systems
• Intuitive web-based user interface
• Compatible with Eaton and other manufacturers’ UPSs as
well as Eaton’s ePDU products and environmental sensors
• Generic SNMP driver enables monitoring of practically any
SNMP enabled device
• Reduces total cost of ownership for the whole monitoring
system
• IPM integration with VMware’s vCenter, Citrix XenCenter
and Microsoft’s SCVMM streamlines daily management
work and increases productivity.
• View critical power information on UPS, ePDUs and
environmental sensors from the vCenter dashboard
• Integrate power alarms to vCenter alarm handling and
event logging
• Instantly access critical information such as UPS battery
status, load levels and alarms
• IPM can be configured to trigger vCenter’s vMotion,
XenMove and SCVMM’s Live Migration to transparently
move virtual machines to a back-up facility.
• IPP can perform an automatic orderly shutdown of
VMware, Hyper-V, Xen and KVM hypervisors and their
guest operating systems in case of a prolonged power
failure
• IPM can trigger agentless remote shutdown of
hypervisors and NetApp storage.
54
EATON UPS Catalogue
Intelligent Power Manager
Intelligent Power Manager is a productivity tool for administrators
of several power devices and shutdown applications. It delivers
the big picture and highlights key factors by concentrating information from multiple sources and displaying it in a single view. It also
centralises alarm propagation making sure that important events
are brought to those who need to know.
IPM simplifies many routine maintenance tasks, including its own
updates. It has an automatic update function which will notify the
operator of available upgrades, download and install them. In addition to that, it also checks if there are new versions of shutdown
software. Mass upgrade and configuration of cards and applications saves a lot of valuable operator time and reduces the chance
of human error.
IPM manages up to 10 devices at no charge.
Features:
• Easily monitor hundreds of power and
environmental devices
• User-definable tree structure enables
grouping, access and management of
multiple devices in several locations
• Minimises the effort required in power
management system maintenance
through mass configuration and firmware
management
• Manages all Intelligent Power software
instances in the network
Simply purchase a full license and enter the corresponding license key
to raise this limit and enable management of 100 or more devices.
IPM scales easily from a local area network to a global view, keeping an eye on power conditions and equipment status. In addition
to the default maps, it’s possible to upload more maps, floor plans
and other images. There can be separate views for multiple geographical areas and buildings.
Global view
With IPM list view, the key operational parameters of multiple
devices can be seen at a glance. Users can create their own
views and apply several different filters, such as location, equipment type, function and so forth. Activating an entry provides
more detailed data in the information panes:
Identification of the device, including equipment type, serial
number and user-defined information
Operational status
Readings from optional environmental probe
Synoptic view of power flow
For each node, there is a hyperlink to the web interface of that device
Main list view
List and map views give an excellent real-time snapshot of a large
number of devices, but very often time series data is needed
for analysis, planning and problem mitigation. Intelligent Power
Software has powerful graphing tools which help in visualising
large amounts of data stored in its database. The user can choose
which data is graphed and which timescales are used. Exact values are displayed when the pointer is moved over the graph area.
Graphing tools
www.eaton.eu
55
Power management software & connectivity
Intelligent Power Protector
When the power goes out for longer than your available battery
runtime Intelligent Power Protector software facilitates automatic,
graceful shutdown of computers, servers and network devices
powered by a UPS, saving all work-in-progress and ensuring data
integrity (IPP).
IPP has also monitoring and alarm handling capabilities making it a
complete solution for a single UPS.
Features:
• Graceful shutdown of operating systems in case of
an extended power failure or other condition that threatens
the availability of IT equipment
• Supports Eaton UPS through network,
RS232 serial and USB communication
• Supports redundant power supplies and
parallel UPS configurations
• Silent unattended installation option
• Manageable with Intelligent Power Manager
Intelligent Power Protector has comprehensive choices for shutdown triggers, timings and modes. User can choose whether the
operating system should shut down, hibernate, power off or run a
custom script. The start of shutdown can be based on an instant
event, delay or remaining runtime on the UPS.
Shut down settings
There could be hundreds of UPSs in a network, each powering
multiple servers running shutdown software. Managing that kind
of setup could easily become a nightmare, especially because
new computers are added and old ones moved all the time.
Intelligent Power Manager comes to the rescue by clearly showing which Protectors are connected to a particular UPS.
Powered applications
IPP introduces the concept of Virtual Power Source. That could be
multiple UPS systems in parallel or several power supplies powering a server. It could be also a combination of other virtual power
sources, which allows very complex power schemes to be made
understandable to both IPP and the administrator. It is also possible to set the required level of redundancy.
Support for redundant power
Intelligent Power Software can perform actions when events of
any given type or criticality occur. These actions include notifications on computer screens, command execution and email sending. To limit the amount of emails, it is possible to combine several
events into a single message. This is a particularly valuable feature
in large installations.
56
EATON UPS Catalogue
Connectivity Options
Web/SNMP cards are complete UPS monitoring, control
and shutdown solutions in a networked IT environment.
In case of alert the Web/SNMP card can notify users and administrators through e-mail and SNMP traps. In case of a prolonged
power failure the protected computer systems can be shut down
in a graceful manner with Intelligent Power Protector software.
The unique three-port switching hub on the X-Slot model provides
additional network connections.
ConnectUPS - X
ConnectUPS-X
P/N 116750221-001 for Eaton 9155, 9355, 9395, BladeUPS.
ConnectUPS-E
P/N 116750223-001 is an external model that is connected to a
serial port on a UPS. It supports Eaton 9130, 9155, 9355, and
9395 UPS (requires cable 1023247).
Network Card-MS Web/SNMP adapter
Catalog number: Network-MS
The Eaton Network Card-MS supports SNMP v1 and v3;
IPv4 and v6; http, https and SMTP
Works with: 5130, 5PX, 9130, EX, 5SC, 5P, 9PX, 9SX, 93E and
93PM
Environmental Monitoring Probe (EMP) adds temperature,
humidity and two contact closure monitoring capability to
ConnectUPS Web/SNMP cards. It is well suited for monitoring
rack temperature and door status, as well as battery temperature.
Operating system shutdown can be triggered if user defined
thresholds are exceeded or contact closure status changes.
EMP001 works with Network-MS, Network and Modbus – MS,
ConnectUPS and PXGX cards as well as network enabled ePDUs.
Network Card-MS
Environmental Monitoring Probe
BD relay card (for Eaton 9130 UPS)
Relay/AS400 cards are an easy connection to IBM AS/400 series
computers as well as industrial and building management systems.
P/N 1018460 for Eaton 9155, 9355, 9395, BladeUPS.
P/N 1014018 for Eaton 9130.
C/N RELAY-MS for 5130, 5PX, EX, 5SC, 5P, 9PX, 9SX, 93E and
93PM
X-Slot ModBus card connects the UPS to industrial and building
management systems using ModBus/JBUS RTU protocol.
P/N 103005425-5591 for Eaton 9155, 9355, 9395, BladeUPS.
Relay MS
X-Slot relay card
Network and MODBUS Card-MS (MODBUS-MS) offers
ModBus RTU in addition to Web and SNMP for 5130, 5PX, 9130,
EX, 5SC, 5P, 9PX, 9SX, 93E and 93PM
PXGX UPS card P/N 103007974-5591 offers ModBus TCP as well
as Web and SNMP interfaces for 9155, 9355, 9395 and BladeUPS.
ViewUPS-X remote display is an LCD panel that lets users view
the status of the UPS from as far as 100 m. ViewUPS-X has also
four status LEDs and an alarm sound. The display is bundled with
a dedicated X-Slot card that also powers the display through the
communication cable. In addition to the remote display connection the card has also a SELV isolated relay port for connection to
monitoring systems and AS/400 computers.
P/N 1027020 for 9155, 9355, 9395 and BladeUPS.
X-Slot Modbus card
PXGX UPS
Modbus MS card
ViewUPS-X
www.eaton.eu
57
Green life cycle
Green by design
Eaton is constantly working with
customers to develop solutions that
drive sustainable growth around
the globe. Our UPS solutions strive
for unparalleled energy efficiency,
efficient resource use, maximimum
use of recyclable materials and the
reduction of emissions throughout
the entire life of the product, from
cradle to grave.
58
EATON UPS Catalogue
Our engineers are constantly
developing smarter ways to deliver
ecological and economic benefits.
This includes the development of
energy efficient and environmentally
friendly technologies.
Design
Manufacturing
Taking account of the environment is a part
of the design process at Eaton. Four
characteristics guide the design team
during their work: energy efficiency,
resource efficiency, recycling and
compliance with regulations.
The Life Cycle Assessment (LCA) process
is used to gather information about the
potential environmental impact
of a product.
[email protected]
results for Power Xpert
“ LCA
9395 UPS show that 74%
Eaton is constantly monitoring the use
of hazardous substances and material its
design and manufacturing processes. Our
products do not contain REACH SVHCs
(Substances of Very High Concern) and
Eaton is seeking to comply with the RoHS
Directive in advance of it becoming a legal
requirement to do so.
The Eaton Green Leaf label is our promise
to customers, consumers and our communities, of exceptional and documented
environmental performance. Power Xpert
9395 UPS, Protection Station, BladeUPS
are exceptional Power Quality products
that have been certified as Eaton Green
solutions.
of the impacts stem from
energy losses in the UPS and
25% from cooling energy
“
Eaton is focused on building sustainable
operations and managing Environment,
Safety and Health (EHS) through
standardisation. Our global Managing
Environment, Safety and Health (MESH)
programme is a unified system that
consolidates existing programmes (ISO
14001, OHSAS 18001, OSHA VPP) into a
single integrated management system. All
EMEA manufacturing locations are
ISO14001 certified.
™
Use Phase
Green technologies
Energy Saver System
(ESS)
Enables extremely high energy efficiency and reliability
under normal operating conditions
Easy Capacity Test
(ECT) technology
Enables testing of entire power train under full load stress
Eaton 9355, 93E, 93PM and 9395 UPSs
without the need for an external load
Hot Sync technology
Start from a single module and add power when required
BladeUPS, Eaton 9PX, 9155, 9355,
9390, 93E, 93PM and 9395 UPSs
Advanced Battery Management
(ABM) technology
Increases the life of batteries by employing a three-stage
charging technique
BladeUPS, Eaton 5P, 5PX, 5SC, 9130, 9SX,
9PX, 9155, 9355, 93E, 93PM and 9395 UPS
Hot Swappable batteries
Allows batteries to be replaced or removed one string
at a time while the equipment is still running
BladeUPS, Eaton 5130, 5P, 5PX, EX, 9130, 9SX and
9PX UPSs
EcoControl technology
Automatically disables peripherals
when the master drive is turned off
Eaton Protection Station and
Eaton Ellipse ECO, Eaton Ellipse PRO
Eaton 9390, 93PM and 9395 UPSs
End of Life
Eaton takes into account the environmental
effects of the packaging and the end-of-life processing of our products and to aid more responsible dismantling, end-of-life instructions are
available for recyclers.
We are committed to adhering to the
following legislation when applicable:
WEEE (Directive 2002/96/CE)
Waste Electrical and Electronic Equipment
Batteries (Directive 2006/66/CE)
Batteries and accumulators and
waste batteries and accumulators
Packaging (Directive 2004/12/CE)
Packaging and packaging waste
To find out more about
Green by design, please visit:
www.eaton.eu/green
www.eaton.eu
59
Technology
Hot Sync Technology
Paralleling UPS technology
The number one function of a UPS is to supply continuous conditioned, reliable electricity to a critical load. In case of a single unit,
reliability can be increased by modular design, where redundant
internal modules can take over each others’ tasks, if one of the
modules fails.
To further increase reliability, a true parallel configuration can be
employed, where two or more units share the load. A failed unit is
isolated while the remaining ones continue to support the critical
load. Competitive UPS products on the market utilise centralised
or distributed load-sharing technology with the master-slave principle, which introduces a risk of single point failure. The absolute reliability of a UPS system can be achieved with patented
Powerware Hot Sync® parallel load-sharing technology. (Figure 1)
Hot Sync technology is designed for parallel redundant N+1 systems to satisfy 24/7 applications. It can also be used in parallel
capacity systems to benefit from scalability for customers’ everincreasing load demands modules can share loads without any
communication wiring to the outside world.
Hot Sync
User benefits
20%
Utility
Failure probability / year
• Available for both single- and three -phase
products to meet any mission-critical need up
to 7.7 MVA (400V) systems
• Easy and modular parallel UPS system upgrade
with additional capacity or redundancy
• Erases single point of failure, load sharing is not
endangered by loss of communication
10%
99,99%
No common
logic
Single UPS
Modular UPS
Parallel redundant UPS
Hot Sync
99,999%
99,9999%
Figure 1. Power availability with various power supply configurations.
60
EATON UPS Catalogue
Hot Sync Technology
The internal output impedance of a UPS is inherently mainly inductive, i.e. it looks as a small inductor in series with a stiff alternating
voltage source. So, if there is any difference between the output
voltage phases, it means that there is a power flow from unit to
unit, resulting in unequal load sharing. In the Figure 3, two units
have equal output voltages with phase angle displacement.
90
deg
The voltage Vdiff and current Idiff between units exhibit a 90
degrees phase shift due to the inductive source impedance. The
main voltage (V1 and V2) and the current between units Idiff are in
phase resulting in active power flow.
The greater the phase shift, the heavier the power imbalance.
If we now introduce a controller to adjust the voltage phase by
the output power, the phase difference can be forced to decrease.
To adjust the phase difference to zero and to achieve accurate
load sharing, we may integrate the measured phase thus arriving
at power-controlled frequency. For the purpose of fast frequency
locking and to enable synchronisation to external bypass, a term
containing the power level change rate is added.
V2
Vdiff
Idiff
V1
0 deg
Figure 3. A phase displacement between parallel connected
UPS voltages (V1 and V2) causes current flow between the
units thus imbalances load share.
The flow diagram (Figure 4) shows how the load sharing
proceeds.
Hot Sync technology allows full maintenance to be performed
one-by-one on redundant UPS modules without an external maintenance bypass switch. The critical load does not need to be disconnected from the conditioned power. Scheduled or unscheduled
maintenance can be performed with the load supported continuously by the UPS-grade clean power.
The output power is monitored and the new frequency calculated
at 3000 times per second. The measurements are also used for
fast identification of a failed module. This feature is based on the
computation of instantaneous output power. A negative value,
even for a single instant, is an indication of an internal failure, e.g.
a shorted inverter IGBT. In a response the UPS trips immediately
off-line, causing minimal voltage disturbance. This feature is known
as ‘selective tripping’.
Compute
output power pn
UPS 1
f1
UPS 2
f2
P1
P2 Fn = Fn-1 – K1(Pn) – K2(Pn)
P1
P1+2
P2
Power level difference diminishes
Fn = frequency
Fn-1 = previous frequency
Pn = power to load
Outputs are synchronised
VUPS 1
VUPS 2
Figure 2. Well-balanced load share is achieved by adjusting output
frequencies; thus the phase difference between parallel UPS output
Compute
Dpn - pn-1
Integrate Dpn into
inverter input frequency
fn = fn-1 - K1*pn - K2*pn
Adjust frequency
of inverter to fn
K1 = frequency reduction factor
K2 = power change rate factor
Frequencies are continuously
adjusted based on P1 and P2
Voltages out of phase
Where: Figure 4. With HotSync algorithm,
inverter phase angel is adjusted by
output power and its change rate.
Accurate, equal load share is the number one characteristic to
determine the integral quality and reliability of the parallel UPS
system providing redundancy or increased capacity. With HotSync
technology this is achieved without need for additional communications line between UPSs thus no single point of failure is added
when introducing parallel modules to a system. From operational
and also economical viewpoint, the achieved “close to perfect”
reliability returns clear savings in the long run as every downtime
incident is costly and might lead to unpredictable consequences.
voltages is forced to zero.
www.eaton.eu
61
Technology
ABM Technology
Superior battery management
Battery service life is a major contributor to UPS reliability. Since
batteries are electrochemical devices, their performance gradually
decreases over time. Premature wear-out means higher costs in
terms of replacement labour and shorter service cycle. A worn
battery entails a risk of unexpected load loss. In normal UPS operation, backup power is needed only occasionally and the battery
‘wearing’ rate depends strongly on how the full charge is being
maintained. Excess charging is detrimental under any operating
circumstances.
Significant extension of battery life
ABM technology significantly
increases battery service life.
User benefits
• Predictive and automatic
diagnostics of battery health
• Significant extension
of battery life compared
to traditional charging method
• Optimisation of battery recharging time
with dual mode charging method
• Automatic battery charge voltage
compensation within
0 to +50ºC temperature range
62
EATON UPS Catalogue
Eaton has created ABM® technology to extend the life of valveregulated lead-acid batteries by applying sophisticated logic to
the charging regime. Using the traditional trickle charge method,
batteries become subject to electrode corrosion and electrolyte
dry-out, especially in standby service use due to continuous float
charging. ABM is essentially an addition of intelligence to the
charging routine by preventing unnecessary charging, thus significantly retarding wear-out. ABM provides an additional feature for
monitoring battery condition and advance warning about the end
of battery life upon detection of a weak battery. It also optimises
the recharge time, which is advantageous when there may be
consecutive power outages within a short period. ABM has been
used for over 15 years is now applied in UPSs up to 1100 kVA.
ABM Technology
ABM cycle and operation – how does it work?
The basic idea of ABM is to leave a fully charged battery in rest
mode for most of the time, and then apply charge current only at
certain intervals. Initially, in order to charge up a fully or partly discharged battery, the charger starts at a constant current appropriate for the battery type used. When the battery voltage reaches a
set level, the operation is changed to float mode using a constant
but lower voltage, thus providing an optimum recharge time. The
battery is kept at this voltage for 24 hours until it comes to the
first test point. This takes approximately one minute, and during
this period voltage drop measurements are taken while loading the
battery, giving an indication of battery condition. The float charging
is continued for an additional 24 hours, plus a period equal to 1.5
times the constant current charging time, before the rest mode is
Temperature compensated charger
between ±0°C...+50°C internal/external
initiated. At this point, charging is discontinued for a maximum of
28 days – as if the batteries were disconnected. During the first 10
days the battery voltage is continuously monitored, and if it drops
below 2.1 V/cell, the ABM restarts in charge mode and the user
gets a notification of improper battery operation. If it drops below
this limit after the 10-day period, charging is resumed without an
alarm being raised. In short, the algorithm uses three charging
stages in its operation. Thus, the batteries experience much less
stress than in the case of traditional charging. A typical battery
charging cycle without power interruptions is shown in the graph
below.
For convenience, the user has the facility to disable the ABM and
instead select continuous ‘constant voltage’ charging whereby
measurements.
the charger uses a constant float voltage. ‘ABM enabled’ is the
default setting. The charger voltage levels are (by default setting)
programmed to be dependent on an internal temperature sensor measurement, thus providing further enhancement to battery
health. The external batteries can be also provided with temperature dependent charger voltage. For this purpose a Web/SNMP
card with Environmental Monitoring Probe (EMP) is required.
Optional Web/SNMP card with EMP probe for temperature
measurement of an external battery cabinet or rack.
www.eaton.eu
63
Technology
Energy Saver System
ESS
Energy Advantage Architecture (EAA)
The rising demand for highly available, reliable and efficient power
is a continuous challenge for data centre operators. Higher energy
efficiency helps to address increasing environmental, regulatory
and economic pressures.
Eaton has developed innovative and proprietary technologies that
improve system efficiency without compromising on reliability
under the Energy Advantage Architecture (EAA) umbrella.
Energy Saver System (ESS) is one of these technologies.
Maximised energy efficiency
With 85 percent reduction in UPS energy losses, ESS technology dramatically reduces energy consumption, environmental
impact and power costs without compromising load protection.
With these outstanding energy savings, it is possible to recover
the entire cost of the UPS over a three to five year period.
Applications
UPS EFFICIENCIES
Energy Saver System is available for all
Eaton 9390, 93PM and 9395 UPSs
including:
EATON UPS
LEGACY UPS
UPS EFFICIENCY
• stand-alone single UPSs
• parallel systems
All existing installations
can be upgraded with the ESS capability.
EATON UPS WITH ESS
TYPICAL
OPERATION
UPS LOAD
ESS enables market-leading 99 percent efficiency across the
entire operating range. Compared to conventional ‘eco-mode’
capabilities available with legacy products, ESS offers the best
possible efficiency and the fastest transition times to double conversion when power disturbances occur.
64
EATON UPS Catalogue
Energy Saver System
No compromise on reliability
In ESS mode the UPS safely provides mains current directly to
the load when the input is within the acceptable limits by its voltage and frequency. If input power exceeds the predefined limits
by frequency or voltage, the UPS switches to double conversion.
If input power is outside the tolerances of the system, the UPS
draws power from available battery modules.
Superior detection and control algorithms continuously monitor incoming power quality and allow the UPS to engage power
converters in less than two milliseconds when the utility source
exceeds predefined limits by its voltage or frequency, thus always
providing secured power to the critical load while maximising efficiency. If the UPS detects a fault condition while operating in ESS,
it is able to detect and determine whether the fault is caused by
the load or if it is upstream from the UPS. A fault at the bypass
source results in immediate switchover to the inverter; a fault in
the load keeps the UPS in Energy Saver System (ESS).
Proven Eaton technology ensures reliability and continuous load
availability without compromising the protection of the supported
equipment.
Extensive configurability
Eaton UPS with Energy Saver System features three
configurable modes of operation:
• Standard double conversion mode: the UPS operates as normal, supplying power through the power converters.
• Energy Saver System: the power converters are in ready state and the static bypass switch allows the UPS
to supply mains power directly.
• High Alert mode: the UPS automatically transfers from ESS
to double conversion mode and in case of multiple recurring
utility line disturbances it stays there for a predefined time
(default one hour) until it is safe to return to ESS.
The UPS seamlessly executes transitions through different operating modes as needed. This is only possible with transformer-free
topologies.
Availability
ESS is available for all 9390, 93PM and 9395 UPSs. Parallel UPS systems also support operation in ESS mode. Existing installations can
be upgraded with ESS capability.
Active components engaged during Energy Saver System mode
www.eaton.eu
65
Technology
Variable Module Management System
VMMS
Energy Advantage Architecture (EAA)
The rising demand for highly available, reliable and efficient power
is a continuous challenge for data centre operators. Higher energy
efficiency helps to address increasing environmental, regulatory
and economic pressures.
Eaton has developed innovative and proprietary technologies that
improve system efficiency without compromising on reliability under
the Energy Advantage Architecture (EAA) umbrella.
Typical field operations are usually within low load range, but UPSs
do not operate at optimal efficiency when used for lighter loads.
In some multi-UPS parallel systems used with lighter loads, the
system maximises the load percentage of the UPSs by putting the
UPSs that are not needed to power the load into idle mode. This
results in partial energy savings and is limited to multi-UPS systems, with no efficiency improvements for single-UPS systems.
Variable Module Management System (VMMS) technology
maximises efficiencies at lighter loads without compromising
reliability.
Applications
Typical applications where VMMS is
particularly efficient include:
• UPSs in redundant N+1 and 2N systems
- Lightly loaded: UPSs in these systems
typically operate at low loads,
< 45% load level
• Data centres, especially when the UPS system feeds dual-corded servers
• Any applications where load is not constant
UPS EFFICIENCIES
EATON UPS Efficiency VMMS Enabled
UPS EFFICIENCY
EATON UPS Efficiency VMMS Disabled
TYPICAL
OPERATION
RANGE
UPS LOAD
66
EATON UPS Catalogue
Variable module management technology
maximises efficiencies at lighter loads
Variable Module Management System (VMMS)
Maximised energy efficiency
VMMS optimally employs uninterruptible power modules (UPMs)
in the UPS to achieve higher efficiencies in double conversion
mode in order to maximise the percentage load level of the
remaining active UPMs by switching UPMs that are not needed to
ready state*.
This is calculated according to the UPMs’ VMMS load threshold
– 80% by default – and the system configuration (redundancy
requirements). This results in maximised energy savings.
VMMS is only possible thanks to Eaton 9395 UPS modularity.
VMMS can also be applied in multimodule single-UPS systems.
*In “ready state”, the UPM rectifies the DC-link, generates
logic level PWM (Pulse Width Modulation) signals and filters
EMI and lightning spikes.
No compromise on reliability
When a disturbance or load increase occurs on a critical bus, all
the UPMs in ready state are able to react quickly, immediately
switching back to double conversion mode connecting the existing
PWM signals to the IGBT gates.
In VMMS, all UPMs will switch to double conversion if:
• the output voltage fluctuates by more than 3% for any reason
• any UPM reaches its current limit or discharges its battery
• battery recharge is necessary.
Once the above conditions are resolved, the system switches
back to VMMS, after a customer-preset time delay (1 to 60 hours):
once the load stabilises, Eaton proprietary design and algorithms
allow the system to determine which UPMs to switch back to
ready state to maximise efficiency according to the new operating
conditions.
Extensive configurability
Customers can decide how to configure their system, establishing
the number of redundant UPMs and the max percentage load level
per UPM allowed in VMMS setting other UPM’s in ready state.
VMMS can be used in all multi-module
(multiple-UPM) 9395 systems:
• Single 9395 units from 550kVA to 1100kVA
• All parallel systems 9395 systems
Existing installations can also be upgraded with
VMMS capability:
• VMMS maintains redundancy and achieves higher efficiency
by intelligently controlling the load levels of UPMs
• Number of redundant UPMs can be selected
(N+0, N+1, N+2, N+X)
• UPMs in ready state can be used as redundant units (N+0)
VMMS Parallel Power Xpert 9395 – 825 kVA modular UPS and VMMS
100%
Full system
automatically
optimised
according to the
LOAD
efficiency is
load level
0%
UPS 1
UPS 2
UPS 3
Data centre with dual-corded servers, 825 (3x275) kVA UPS on A and B side – 440 kVA load
UPS configuration
Without VMMS
VMMS on N + 1 redundancy
Efficiency @
440 kVA load
91.2%
92.8%
94.3%
UPS energy
savings
Used as reference for
savings calculation
6 MWh / year
108 MWh / year
3 Industry-leading UPS
3 Additional energy savings from reduced cooling in VMMS
efficiency in double
conversion
3 UPMs in VMMS ready state available for redundancy
UPS energy savings
VMMS on N + 0 redundancy
(typically 30-40% on top of UPS energy savings)
A Feed
220 kVA
A Feed
220 kVA
A Feed
220 kVA
B Feed
220 kVA
B Feed
220 kVA
B Feed
220 kVA
www.eaton.eu
67
Eaton is dedicated to ensuring that reliable, efficient and safe power
is available when it’s needed most. With unparalleled knowledge of
electrical power management across industries, experts at Eaton
deliver customised, integrated solutions to solve our customers’
most critical challenges.
Our focus is on delivering the right solution for the application. But,
decision makers demand more than just innovative products. They
turn to Eaton for an unwavering commitment to personal support
that makes customer success a top priority.
For more information, visit www.eaton.eu/electrical
To contact an Eaton salesperson
or local distributor/agent, please visit
www.eaton.eu/electrical/customersupport
Eaton Industries Manufacturing GmbH
Electrical Sector EMEA
Route de la Longeraie 7
1110 Morges, Switzerland
Eaton.eu
© 2013 EatonAll Rights Reserved
Printed in Europe
Publication No. 00BROC1018124 Rev G
Article: Eaton UPS Catalogue
November 2013
Changes to the products, to the information contained in this
document, and to prices are reserved; so are errors and omissions.
Only order confirmations and technical documentation by Eaton is
binding. Photos and pictures also do not warrant a specific layout or
functionality. Their use in whatever form is subject to prior approval
by Eaton. The same applies to Trademarks (especially Eaton, Moeller,
and Cutler-Hammer). The Terms and Conditions of Eaton apply, as
referenced on Eaton internet pages and Eaton order confirmations.
Eaton is a registered trademark
of Eaton.
All other trademarks are property
of their respective owners.
Follow us on social media to get the
latest product and support information.