Download Sharp R-320CW Technical data

Transcript
Danger that may arise from the unit
DANGER! Danger of electric hazard!
The steam humidifier OEM2 is operated with mains voltage. One may get in touch with live parts when the unit is
open. Touching live parts may cause severe injury or danger to life.
Prevention: Before carrying out any work set the steam humidifier OEM2 out of operation as described in chapter
12.1.3.5 (switch off the unit, disconnect it from the mains and stop the water supply) and secure the unit against
inadvertent power-up.
WARNING! Danger of burning!
The steam humidifier OEM2 produces steam. When producing steam, the steam cylinder inside the humidifier gets
very hot (up to 100 °C). If the unit is opened immediately after having produced steam there is danger of burning
when touching the steam cylinder.
Prevention: Before carrying out any work set the steam humidifier OEM2 out of operation as described in chapter
12.1.3.5, then wait until the steam cylinder has cooled down sufficiently thus preventing danger of burning.
12.1.1.1 Technical data
Steam
Dampfleistung
capacity [kg/h]
[kg/h]
Nominal
Nennleistung
power[kW]
[kW]
Nominal
Nennstrom
current
[A][A]
Maximalstrom
Max. current [A]
[A]
200 ... 230V / 1N~ / 50 ... 60Hz
2,0
1,5
7,5 ... 6,5
9,4 ... 8,2
4,0
3,0
15,0 ... 13,0
18,8 ... 16,3
200 ... 230V / 3~ / 50 ... 60Hz
4,0
3,0
8,7 ... 7,5
10,8 ... 9,4
8,0
6,0
17,3 ... 15,1
21,7 ... 18,8
10,0
7,5
21,7 ... 18,8
27,1 ... 23,5
380 ... 460V / 3~ / 50 ... 60Hz
4,0
3,0
4,6 ... 3,8
5,7 ... 4,7
8,0
6,0
9,1 ... 7,5
11,4 ... 9,4
15,0
11,25
17,1 ... 14,1
21,4 ... 17,6
Operating conditions
Admissible water pressure
Water quality
Admissible water temperature
Admissible ambient temperature
Admissible ambient humidity
Adm. back pressure at steam connection
Type of protection
Conformity
EN04.2011/humidifier/2
1 ... 10 bar
Drinking water with a conductivity of 125 - 1250µS/cm
1 ... 40 °C
1 ... 50 °C (control unit 1 ... 40 °C)
max. 75% rh, non-condensing
- 0,5 kPa ... 1,0 kPa
IP00
produced according VDE regulations 0700 and 0700 part 98