Download VAMP 321 arc flash protection system
Transcript
5.11 Primary, secondary and per unit scaling 5 Measurement functions VAMP 321 Example 5: Secondary to per unit for residual current. Input is I01. CT0 = 50/1 Current injected to the relay's input is 30 mA. Per unit current is IPU = 0.03/1 = 0.03 pu = 3 % Example 6: Per unit to secondary for residual current. Input is I01. CT0 = 50/1 The relay setting is 0.03 pu = 3 %. Secondary current is ISEC = 0.03x1 = 30 mA Example 7: Secondary to per unit for residual current. Input is I0Calc. CT = 750/5 Currents injected to the relay's IL1 input is 0.5 A. IL2 = IL3 = 0. Per unit current is IPU = 0.5/5 = 0.1 pu = 10 % Example 8: Per unit to secondary for residual current. Input is I0Calc. CT = 750/5 The relay setting is 0.1 pu = 10 %. If IL2 = IL3 = 0, then secondary current to IL1 is ISEC = 0.1x5 = 0.5 A 64 VAMP 24h support phone +358 (0)20 753 3264 VM321.EN001_B