Download Product Manual
Transcript
3-3 Operative settings IMPORTANT! Modifications of the unit operating parameters must be carried out using the utmost caution to avoid creating situations of conflict with the other parameter settings. 2. PARAMETERS TABLE The parameters are divided into 4 types depending on their password protection and function. The access to each level can be set to only the parameters of the level in question and lower levels. Factory Parameters: Password protected (issue of the password is at the discretion of BICOLD srl); all unit parameters can be configured from this level. Super User Parameters: Password protected (issue of the password is at the discretion of BICOLD srl); Super User, User and Direct parameters can be configured from this level. User Parameters: Protected by password 22; configuration of typical user settable parameters (User only) and Direct parameters and the related options. Settable parameters and options: PROBES SETTING PARAMETERS (/*) /21 /22 /23 Digital filter Input limitation Unit of measurement 4 8 0 - Digital filter /21: Serves to set the coefficient used in digital filtration of the measured value. High values of this parameter make it possible to eliminate any continuous disturbances on the analog inputs (the measurement response is however reduced). The recommended parameter is 4 (default). - Input limitation /22: Serves to set the maximum detectable variation of the probes in a unit programming cycle; in practice, the maximum permissible variations for the measurement are between 0.1 and 1.5 units (bar, °C or °F depending on the probe and the unit of measurement) approximately per second. Low values of this parameter limit the effect of pulse type disturbances. The recommended value is 8 (default). - Unit of measurement /23: Selects the operating mode with Centigrade or Fahrenheit values. When the parameter is changed µC2SE automatically converts the values read by the temperature probes NTC B1, B2, B3 to the new unit of measurement while all the other programmed parameters (set-point, differential, etc.) remain unchanged. 26