Details of command
„„ When an error has occurred (remote register)
1) Specify the register address number.
2) Check the register address number response.
3) Turn the TRIG from OFF to ON. The selected parameter or operation data is started writing.
4) When the written value is an error, the STATUS is turned from OFF to ON. Check the command code
and DATA.
5) Turn the TRIG from ON to OFF, and reset the error status.
Note
If an error has occurred in data transfer, the STATUS is turned ON.
When specifying data that is outside the setting range (write 1000 to the "STOP input action"
parameter)
[Master to NETC01-M3]
(TM+TS)×2
0001h
Register address number
0 s or more
TRIG
0 s or more
(TM+TS)×2
ON
OFF
0 s or more
1100h
Command code
1000 (03E8h)
DATA
[NETC01-M3 to master]
Register address number
response
0001h
(TM+TS)×2
STATUS
TRIG_R
ON
OFF
ON
OFF
Command code response
DATA response
−44−
1100h
1000 (03E8h)