Download MASTERYS BC - Effekta Power Systems AB
Transcript
6 MASTERYS BC MIMIC PANEL from 15 to 20 kVA 6.1.3.2 “Measurements” menu This menu is used to display all the measurements relating to the UPS input, output and to the battery. For models with single phase input or output, the voltage and current displays are adjusted automatically. ITALIANO ENGLISH MEASUREMENTS menu Type of measurements Value Value Value OUTPUT VOLTAGE ___ V ___ V ___ V OUTPUT LOAD __ % __ % __ % OUT ACTIVE PWR __._ kW OUTPUT FREQNCY __._ Hz AUX VOLTAGE ___ V ___ V ___ V AUX FREQUENCY __._ Hz INPUT VOLTAGE ___ V ___ V ___ V INPUT FREQUENCY __._ Hz BATTERY VOLTAGE B+___ V B-___ V CAPACITY __ % BACKUP TIME T___MIN ENVIRON. TEMP __ °C Note Output voltage Output load percentage Output active power Output frequency Auxiliary mains voltage Auxiliary mains frequency Input mains voltage Input mains frequency Battery voltage Battery capacity percentage during charging Backup time during battery discharge Internal temperature 6.1.3.3 “Commands” menu This used to send immediate commands for start-up/shutdown/reset alarms to the UPS and to select the operating mode. Commands can also be sent for diagnostic purposes by means of the extended commands menu (if enabled in the configurations menu). The command is activated by selecting it with the UP e DOWN keys, press ENTER, confirm YES or NO, then press ENTER. IMMEDIATE COMMANDS menu EXTENDED COMMANDS menu Command START PROCEDURE STOP PROCEDURE HIGH EFF. MODE NORMAL MODE ALARM RESET LED TEST Command BATTERY TEST FORCED ON BY PASS DISABLE CHECK UP Description UPS start-up command UPS shutdown command High efficiency mode: activates the energy saving feature Activates normal double conversion operation Resets all the alarms Performs the test on the mimic panel LEDs Description Activates the battery test to check battery efficiency Activates the switch over to the static bypass. This procedure is necessary when the manual bypass is used. Disable the message of perio dically maintenance 6.1.3.4 “Parameters” menu Provides the display of the parameters set for the UPS. UPS CURRENT DATA menu Message MASTERYS 3/3 12KVA SN. 0000000000 UC FW. REVISION RV 000 CKS: 0000 DSP FW. REVISION RV 000 CKS: 0000 28 Description Displays the size, input and output phases configuration and the serial number of UPS Identifies the software release of microprocessor Identifies the software release of DSP