6
MASTERYS BC
MIMIC PANEL
from 15 to 20 kVA
6.1.3.2 “Measurements” menu
This menu is used to display all the measurements relating to the UPS input, output and to the battery. For
models with single phase input or output, the voltage and current displays are adjusted automatically.
ITALIANO
ENGLISH
MEASUREMENTS menu
Type of measurements Value
Value
Value
OUTPUT VOLTAGE
___ V
___ V
___ V
OUTPUT LOAD __ %
__ %
__ %
OUT ACTIVE PWR
__._ kW
OUTPUT FREQNCY
__._ Hz
AUX VOLTAGE
___ V
___ V
___ V
AUX FREQUENCY
__._ Hz
INPUT VOLTAGE
___ V
___ V
___ V
INPUT FREQUENCY
__._ Hz
BATTERY VOLTAGE
B+___ V
B-___ V
CAPACITY
__ %
BACKUP TIME
T___MIN
ENVIRON. TEMP
__ °C
Note
Output voltage
Output load percentage
Output active power
Output frequency
Auxiliary mains voltage
Auxiliary mains frequency
Input mains voltage
Input mains frequency
Battery voltage
Battery capacity percentage during charging
Backup time during battery discharge
Internal temperature
6.1.3.3 “Commands” menu
This used to send immediate commands for start-up/shutdown/reset alarms to the UPS and to select the operating mode. Commands can also be sent for diagnostic purposes by means of the extended commands menu
(if enabled in the configurations menu). The command is activated by selecting it with the UP
e DOWN
keys, press ENTER, confirm YES or NO, then press ENTER.
IMMEDIATE COMMANDS menu
EXTENDED COMMANDS menu
Command
START PROCEDURE
STOP PROCEDURE HIGH EFF. MODE NORMAL MODE
ALARM RESET LED TEST Command
BATTERY TEST
FORCED ON BY PASS
DISABLE CHECK UP
Description
UPS start-up command
UPS shutdown command
High efficiency mode: activates the energy saving feature
Activates normal double conversion operation
Resets all the alarms
Performs the test on the mimic panel LEDs
Description
Activates the battery test to check battery efficiency
Activates the switch over to the static bypass.
This procedure is necessary when the manual bypass is used.
Disable the message of perio
dically maintenance
6.1.3.4 “Parameters” menu
Provides the display of the parameters set for the UPS.
UPS CURRENT DATA menu
Message
MASTERYS 3/3 12KVA
SN. 0000000000
UC FW. REVISION
RV 000 CKS: 0000
DSP FW. REVISION
RV 000 CKS: 0000
28
Description
Displays the size, input and output phases configuration and the serial number of UPS
Identifies the software release of microprocessor Identifies the software release of DSP