Download LSIS STARVERT iS7 User`s Manual PDF
Transcript
2. Winder/Unwinder Operation Web PID controller does not risk saturating the output, which is effective in significantly reducing the oscillation of the I controller output. The Web PID controller also offers the following functions: Eliminates the transient phenomenon that occurs with the dancer or load cell at start up (related code: APP51). Compensates for the inertia of the winder (related code: APP56-57). Maintains the tension and, if necessary, performs an emergency stop (related code: APP82). Detects potential ruptures in the web material in advance (related code: APP76-80). You must comply with the following settings to ensure that the iS7 properly uses the winder (spooler) or unwinder, or applies them to the closed or open loop system. Group Code number Function Name Setting APP 01 App Mode Application selection 5: Tension Ctrl APP 2-2 02 Tnsn Ctrl Mode Tension control operation mode selection 0 W_Spd Close 1 UW_Spd Close 3 W_Tens Close 4 UW_Tens Close 5 W_Spd Open 6 UW_Spd Open 7 W_Tens Open 8 UW_Tens Open