Issue 12/02 2 Installation Adaptation of fan voltage (only for framesize FX and GX) A transformer is installed to adapt the existing line voltage to the fan voltage. It may be necessary to reconnect the transformer terminals on the primary side to coincide with the existing line power. 0V 1L380V 1L400V 1L440V 1L480V - Connect according input voltage Figure 2-12 Adaptation of fan voltage CAUTION If the terminals are not reconnected to the actually present line voltage, the fan fuses can blow. Replacement for fan fuses Frame size Fuses (2 each) Typ FX (110 kW VT) 1A Cooper-Bussmann FNQ-R-1, 600 V FX (132 kW VT) 2,5 A Ferraz Gould Shawmut ATDR2-1/2, 600 V GX (160-250 kW VT) 4A Ferraz Gould Shawmut ATDR4, 600 V MICROMASTER 430 Operating Instructions 6SE6400-5AE00-0BP0 37