Download User manual - LUCKINSlive
Transcript
Low voltage electrical distribution Compact NS Circuit breakers and switch-disconnectors from 630 to 1600 A User manual 05/2009 Released for Manufacturing Printed on 2014/01/28 Released for Manufacturing Printed on 2014/01/28 User manual for circuit breakers and switch-disconnectors Compact NS630b-1600 A Contents Discovering Compact 2 Manually operated Compact with a toggle 4 Manually operated Compact with a rotary handle 8 Rating plate Components Opening, closing, reset Testing the device Locking the toggle 4 5 6 7 Components Opening, closing, reset Testing the device Locking the rotary handle 8 9 10 11 Remote operated Compact 14 Compact chassis 20 Electrical auxiliaries 30 Start-up 36 Compact operating conditions 38 Components Opening, closing, reset Locking the controls Components Matching a device with its chassis Racking Locking in the "disconnected" position Locking the switchboard door Locking the device when the door is open Locking the safety shutters Electrical diagrams Operation Electrical characteristics of contacts and control auxiliaries Start-up operations What to do when the circuit breaker trips? Environmental conditions Released for Manufacturing 51201640AA - 05/2009 2 Printed on 2014/01/28 14 15 18 20 21 22 24 26 27 28 30 32 33 36 37 38 Rating plate Rated current (x 100 A) DB118617 DB118615 Discovering Compact Performance level Suitability for isolation Type of device: circuit breaker or switch-disconnector Compact Ui - rated insulation level NS630b N push to trip Ui 750 V Uimp 8 kV Ue 220/240 (V) 380/415 Icu 50 (kA) 50 50 40 30 440 500/525 660/690 Ics = 75% Icu Icw 25kA / 0.5s cat B Uimp - impulse withstand voltage Icu - ultimate breaking capacity Ue - rated operational voltage Ics - rated service breaking capacity Icw - rated short-time withstand current Standards IEC 60947-2 AS UNE CEI BS UTE VDE NEMA Released for Manufacturing Printed on 2014/01/28 51201640AA - 05/2009 Released for Manufacturing 51201640AA - 05/2009 Printed on 2014/01/28 Manually operated Compact with a toggle Components DB118619 Control auxiliary terminals OF1 ON/OFF indication contact OF2 ON/OFF indication contact OF3 ON/OFF indication contact SD trip-indication contact MX opening voltage release or MN undervoltage release Control unit SDE fault-trip indication contact Rating plate Spring-charging handle and ON/OFF toggle Device for padlocking the toggle in all positions push to trip "Push to trip" button Device rating Padlocking device for the toggle in the OFF position Released for Manufacturing Printed on 2014/01/28 51201640AA - 05/2009 Opening, closing, reset Manually operated Compact with a toggle E60436A Local opening and closing DB118620 b OFF: breaker open, ON: breaker closed. ON ON push to trip push to trip OFF OFF DB118621 Remote opening Use either: b an MX opening release b an MN undervoltage release b a delayed MN undervoltage release. When connected to the control panel, these releases may be used to remotely open the device. Delay unit E71805A DB118731 MX, MN 1 2 3 4 5 6 S 3 6 30 V 100/1C AC/D 1 2 0.5 1 1.5 3 MN r de R UV dateu Retar delay for Time MN UVR 10 12 3 Resetting the device following a trip DB118622 b The device trips. CLAC ! push to trip DB118623 b Reset the device, then close it again. ON 1 push to trip 1 reset Released for Manufacturing 51201640AA - 05/2009 Printed on 2014/01/28 push to trip 2 Testing the device Manually operated Compact with a toggle DB118624 E60436A b Close the device. ON push to trip 1 DB118625 b Press the "Press to trip" button. CLAC ! push to trip 2 DB118626 b Push the toggle down to reset the device, then back up close it again. ON 3 push to trip push to trip reset 4 Released for Manufacturing Printed on 2014/01/28 51201640AA - 05/2009 Locking the toggle Manually operated Compact with a toggle DB118627 E60425A Locking the toggle in the OFF position using one to three padlocks (shackle diameter 5 to 8 mm) push to trip OFF DB118628 E60423A Locking the toggle in the ON or OFF position using one to three padlocks (shackle diameter 5 to 8 mm) OFF ON push to trip Released for Manufacturing 51201640AA - 05/2009 Printed on 2014/01/28 push to trip Manually operated Compact with a rotary handle Components DB118630 CAF early-make contact CAO early-break contact OF1 ON/OFF indication contact OF2 ON/OFF indication contact OF3 ON/OFF indication contact SD trip-indication contact MX opening voltage release or MN undervoltage release Direct rotary handle Control unit SDE fault-trip indication contact Padlocking device Rating plate pr of alux Keylocks "Push to trip" button Padlocking device Extended rotary handle Door lock Extended rotary handle Released for Manufacturing Printed on 2014/01/28 51201640AA - 05/2009 Opening, closing, reset Manually operated Compact with a rotary handle E71844A Local opening and closing DB118631 b OFF: breaker open, ON: breaker closed. OFF ON DB118632 Remote opening Use either: b an MX opening release b an MN undervoltage release b a delayed MN undervoltage release. When connected to the control panel, these releases may be used to remotely open the device. DB118731 Delay unit E71805A MX, MN 1 2 3 4 5 6 S 3 6 30 100/1C AC/D 1 2 0.5 1 1.5 MN UVR 3 MN r de R UV dateu Retar delay for Time V 10 12 3 Resetting the device following a trip DB118633 b The device trips. CLAC ! 1 ! DB118634 b Reset the device, then close it again. reset 2 Released for Manufacturing 51201640AA - 05/2009 Printed on 2014/01/28 ON 3 Testing the device Manually operated Compact with a rotary handle DB118635 E71844A b Close the device. ON 1 DB118636 b Press the "Press to trip" button. CLAC ! ! 2 DB118637 b Turn the handle to reset the device, then back to close it again. reset 3 Caution: In case of breaker with direct rotary handle installed through door, the opening of the door is only possible when the rotary handle is in ON or OFF position. 10 ON 4 Released for Manufacturing Printed on 2014/01/28 51201640AA - 05/2009 Locking the rotary handle Manually operated Compact with a rotary handle DB118638 Locking the direct or extended rotary handle in all positions using one to three padlocks (shackle diameter 5 to 8 mm) DB118658 b In the standard configuration, the device may be locked in the OFF position. OFF DB118721 b Remove the ring as indicated below to enable locking in both the ON and OFF positions. 3 1 2 DB118639 b Lock the handle. 4 5 DB118640 b The controls are locked. Note: the rotary handle can equipped for locking by both padlocks and keylocks. 51201640AA - 05/2009 ON Released for Manufacturing Printed on 2014/01/28 OFF 11 Locking the rotary handle Manually operated Compact with a rotary handle DB118641 Locking the direct rotary handle in all positions using a keylock DB118643 DB118642 b Lock. prof alux 1 2 DB118644 b The controls are locked. OFF ON DB118645 b Unlock. 2 1 Two types of keylocks are available PROFALUX 12 DB118749 E71810A RONIS Released for Manufacturing Printed on 2014/01/28 51201640AA - 05/2009 Locking the rotary handle Manually operated Compact with a rotary handle Door locking when the device is in the ON position, using the extended rotary handle DB118647 DB118646 b In the standard configuration, the door cannot be opened when the rotary handle is set to the ON position. OFF tripp 2 ed t rese d trippe reset 3 1 ON OK DB118649 DB118648 b It is possible, however, to defeat the door lock. 4 ed tripp ed tripp t rese t rese ON ON 5 OK DB118650 b The door-lock function may be permanently disabled by removing the lock. Released for Manufacturing 51201640AA - 05/2009 Printed on 2014/01/28 13 Remote operated Compact Components Fixed device SD trip-indication contact DB118653 MX opening voltage release or MN undervoltage release OF ON/OFF indication contacts Charging handle for the closing order SDE fault-trip indication contact Control auxiliary terminals Motor mechanism Locking in the OFF position using a padlock Locking in the OFF position using a keylock and a padlock ON button Control unit OFF button Operation counter DB118654 Front Trip indication button used to reset before closing RESE T Rating plate Locking by padlock, lead-seal cover or screws for pushbuttons Indicator for position of the main contacts 14 Closing spring status indicator Released for Manufacturing Printed on 2014/01/28 51201640AA - 05/2009 Opening, closing, reset Remote operated Compact DB118655 Local opening and closing O I Device closed (ON), discharged DB118733 DB118732 Device open (OFF), discharged O h ON Pus Pus OFF I Pus h ON DB118735 DB118734 DB118656 h Pus h ON Device closed (ON), charged Device open (OFF), charged O I P us F h OF Pus F h OF O I h ON Pus FF sh O Pu Released for Manufacturing 51201640AA - 05/2009 Printed on 2014/01/28 15 Opening, closing, reset Remote operated Compact DB118657 Remote opening Use either: b an MX opening release b an MN undervoltage release b a delayed MN undervoltage release b a motor mechanism. When connected to the control panel, these releases may be used to remotely open the device. Delay unit E71805A DB118731 MX, MN 1 2 3 4 5 6 S 3 6 30 V 100/1C AC/D 1 2 0.5 1 1.5 MN UVR 3 MN r de R UV dateu Retar delay for Time 10 12 3 E71805A E71880A E71805A Motor mechanism DB118657 Remotely close 16 E71805A E71805A E71880A Motor mechanism Released for Manufacturing Printed on 2014/01/28 51201640AA - 05/2009 Opening, closing, reset Remote operated Compact DB118656 Manually recharge the device following a trip DB118659 b The device trips. CLAC ! h ON Pus DB118662 O I DB118661 DB119498 b Reset the device, then recharge it. FF sh O Pu or Released for Manufacturing 51201640AA - 05/2009 Printed on 2014/01/28 17 Locking the controls Remote operated Compact Disabling local or remote closing I ON Push Pull out the tab. DB118664 push to trip DB118736 b Lock. Open the device. Install the padlock(s). DB118665 DB118663 Locking the device using one to three padlocks (shackle diameter 5 to 8 mm) Push DB118666 b The controls are locked. Push b Push in the tab. DB118668 DB118667 b Unlock. push to trip Note: Padlocks and keylocks may be used together. 18 Released for Manufacturing Printed on 2014/01/28 51201640AA - 05/2009 Locking the controls Remote operated Compact Disabling local or remote closing I ON Push Remove the key. Turn the key. DB118670 push to trip DB118736 b Keylocking. Open the device. DB118671 DB118669 Locking the device using a keylock and/or one to three padlocks (shackle diameter 5 to 8 mm) Push Padlocks and keylocks may be used together. Locking using padlocks is identical to the system on the previous page. DB118666 b The controls are locked. Push Turn the key. Push in the tab. DB118675 DB118674 DB118673 b Unlock. Insert the key. Two types of keylocks are available PROFALUX DB118749 E71810A RONIS Released for Manufacturing 51201640AA - 05/2009 Printed on 2014/01/28 19 Components Compact chassis DB118677 Carriage switch terminals ON/OFF indication contact terminals Control auxiliary terminals Arc-chute cover Auxiliary terminal shield Terminals for control-unit and fault-trip indication contacts Carriage switch terminals Racking interlock Locking by keylocks Locking by padlocks "Connected", "test" or "disconnected" position indicator Carrying grip Mismatch protection Crank socket Position release button Crank storage Door interlock Crank Disconnecting-contact cluster Withdraw grip Shutter locking blocks Safety shutters push to trip Side plate for withdrawable device Manually operated device with a toggle Manually operated device with a rotary handle Electrically operated device 20 Released for Manufacturing Printed on 2014/01/28 51201640AA - 05/2009 Compact chassis Matching a device with its chassis To set up a mismatch-prevention combination for the device and the chassis, see the mismatch-prevention installation manual. The mismatch protection ensures that a device is installed only in a chassis with compatible characteristics. DB118678 The possible combinations are listed below. A 1 2 4 B 3 5 C D E ABC ABD ABE AB ACD ACE AC ADE AD AE 45 35 34 345 25 24 245 23 235 234 BCD BCE BC BDE BD BE CDE CD CE DE Released for Manufacturing 51201640AA - 05/2009 Printed on 2014/01/28 15 14 145 13 135 134 12 125 124 123 21 Compact chassis Racking For complete information on Compact handling and mounting, see the installation manual(s). Removing the rails Press the release tabs and pull the rails out. 1 DB118680 DB118679 Before mounting Compact NS, make sure it matches the chassis. To put the rails back in, press the release tabs and push the rails in. 2 3 Inserting the device Position the circuit breaker on the rails. Check that it rests on all four supports. DB118681 DB118736 Open the circuit breaker (in any case, it opens automatically during connection). I ON Push Push If you cannot insert the device in the chassis, check that the mismatch protection on the chassis corresponds to that on the device. DB118683 DB118682 Push the device into the chassis, taking care not to push on the control unit. O push I push ON OFF rged discha O OFF O push I push ON OFF rged discha DB118684 O OFF I push O push ON OFF rged discha O OFF 22 Released for Manufacturing Printed on 2014/01/28 51201640AA - 05/2009 Compact chassis Racking Prerequisites To connect and disconnect the device, the crank must be used. The locking systems, padlocks and the racking interlock all inhibit use of the crank. The indicator on the front signals the position of the circuit breaker in the chassis. Racking the circuit breaker from the "disconnected" to "test" position, then to "connected" position E71815A DB110366A The device is in "disconnected" position. The device is in "test" position. The device is in "test" position. Remove the crank or continue to "connected" position. E60413A b "connected" position Test The device is in "connected" position. DB110365 E60414A b "test" position Withdrawing the circuit breaker from the "connected" to "test" position, then to "disconnected" position The circuit breaker is in "connected" position. Test E60415A b "disconnected" position Test The circuit breaker is in "test" position. Note: These operations require that all chassis-locking functions be disabled (see page 24). 51201640AA - 05/2009 The circuit breaker is in "test" position. Remove the crank or continue to "disconnected" position. The circuit breaker is in "disconnected" position. Released for Manufacturing Printed on 2014/01/28 23 Locking in the "disconnected" position Compact chassis Using one to three padlocks Locking Combination of locking systems. It is possible to lock the device on the chassis in the "disconnected" position using: b one to three padlocks b one or two keylocks b a combination of both. Use padlocks with a maximum shackle diameter of 5 to 8 millimetres. 1 Pull out the tab. DB118694 DB118693 Device in "disconnected" position. 2 Test The crank cannot be inserted. DB118696 DB118695 Insert the shackle (max. diameter 5 to 8 mm) of the padlock(s). 3 Unlocking 1 Release the tab. DB118698 DB118697 Remove the padlock(s). 4 2 DB118699 The crank can be inserted. Note: Padlocks and keylocks may be used together. If specified when ordering the chassis, this locking function may be adapted to operate in all positions ("connected", "test" and "disconnected"), instead of in "disconnected" position alone. 24 3 Released for Manufacturing Printed on 2014/01/28 51201640AA - 05/2009 Locking in the "disconnected" position Compact chassis Using one or two keylocks Locking Turn the key(s). DB118701 DB118700 Device in "disconnected" position. 1 22 Test The crank cannot be inserted. DB118703 3 3 Unlocking 1 Turn the key(s). DB118705 DB118704 Insert the key(s). 2 The crank can be inserted. DB118706 DB118702 Remove the key(s). 3 Three types of keylocks are available. PROFALUX Released for Manufacturing 51201640AA - 05/2009 Printed on 2014/01/28 CASTELL E71812A DB118749 E71810A RONIS 25 Locking the switchboard door Compact chassis DB118707 The locking device is installed on the left or right-hand side of the chassis: b when the device is in "connected" or "test" position, the latch is lowered and the door is locked. b when the device is in "disconnected" position, the latch is raised and the door is unlocked. O push OFF O OFF O push I push ON OFF arged disch O OFF Disabling door opening E71831A The door is locked. DB118709 Turn the crank until the device is in "test" or "connected" position. DB118708 Close the door. Enabling door opening The door is unlocked. E71835A DB118710 Turn the crank until the device is in "disconnected" position. OOFF I ON push push discharged O OFF 26 Released for Manufacturing Printed on 2014/01/28 51201640AA - 05/2009 Locking the device when the door is open DB118711 Compact chassis O push I push ON OFF ed harg disc O OFF When the door is closed, the crank can be inserted. DB118713 DB118712 When the door is open, the crank cannot be inserted. OOFF I ON push push discharged O OFF Released for Manufacturing 51201640AA - 05/2009 Printed on 2014/01/28 27 Locking the safety shutters Compact chassis Four locking possibilities inside the chassis using one or two padlocks (maximum shackle diameter 5 to 8 mm) for each shutter Top shutter not locked. Bottom shutter locked. Top shutter locked. Bottom shutter not locked. Top and bottom shutters locked. DB118715 DB118714 Top and bottom shutters not locked. 28 Released for Manufacturing Printed on 2014/01/28 51201640AA - 05/2009 Released for Manufacturing 51201640AA - 05/2009 Printed on 2014/01/28 29 Electrical diagrams Electrical auxiliaries Fixed and withdrawable devices The diagram is shown with circuits de-energised, all devices open, connected and charged and relays in normal position. Remote operation C2 D2 BPF A4 BPO (4) MX MN A3 DB112769 AT A2 Control unit DB118738 Power Control unit Com A P b b b b UC1 UC3 M6C CAF2/CAF1 SDE SD E5 E6 Z5 M1 M2 M3 F2+ Q3 D2 / C12 A4 A2 E3 E4 Z3 Z4 T3 T4 VN Q2 E1 E2 Z1 Z2 T1 T2 F1- Q1 B4 D1 / C11 A1 Control unit Com: E1-E6 communication Remote operation SDE :Fault-trip indication contact (supplied as standard) UC1: SD :Trip-indication contact (supplied as standard) Z1-Z5 zone selective interlocking; Z1 = ZSI = ZSI OUT SOURCE Z2 = ZSI OUT; Z3 = ZSI IN SOURCE Z4 = ZSI IN ST (short time) Z5 = ZSI IN GF (ground fault) M1 = Vigi module input (Micrologic 7) b b b b b UC2 : T1, T2, T3, T4 = external neutral; M2, M3 = Vigi module input (Micrologic 7) b b UC3 : F2+, F1- external 24 V DC power supply VN external voltage connector (must be connected to neutral with circuit breaker 3P) b A1 Remote operation UC2 b b C11 D1 (3) MN :Undervoltage release or MX :Shunt release (standard or communicating) M6C : 6 programmable contacts (must be connected to external relay M6C) ext. 24 V DC power supply required A: Digital ammeter P: A + power meter + programmable protection 30 Released for Manufacturing Printed on 2014/01/28 51201640AA - 05/2009 Electrical diagrams Electrical auxiliaries Fixed and withdrawable devices Indication contacts 914 912 314 312 324 322 334 332 814 812 824 822 CE3 CE2 CE1 311 821 CD1 911 512 DB118742 CT1 511 521 531 541 91 81 11 21 31 Test CAO1 CD2 CAF2 CAF1 Connected 321 CAO2 Disconnected 514 522 CAF1 524 532 Open 534 542 CAF2 544 92 SD Closed 331 SDE 94 82 84 12 OF1 Default 811 OF2 Chassis contacts Default 14 22 34 OF3 Closed 24 Open 32 DB118741 Indication contacts Chassis contacts SDE SD CAO2 CAO1 OF3 OF2 OF1 CD2 CD1 CE3 CE2 CE1 CT1 544 534 84 95 544 514 34 24 14 824 814 334 324 314 914 542 532 82 92 522 512 32 22 12 822 812 332 322 312 912 542 531 81 91 521 511 31 21 11 821 811 331 321 311 911 Indication contacts OF3 / OF2 / OF1: ON/OFF indication contacts Chassis contacts CD2:Disconnected- CE3:Connected- CT1:Test-position CD1 position CE2 position contacts contacts CE1 contacts Key: Withdrawable device only XXX SDE1, OF1, OF2, OF3, OF4 supplied as standard Interconnected connections (only one wire per connection point) Released for Manufacturing 51201640AA - 05/2009 Printed on 2014/01/28 31 Operation The ON/OFF indication contacts signal the status of the device main contacts. Device DB118718 Electrical auxiliaries completely closed closed completely open main contacts open open closed closed open DB118719 The carriage switches indicate the "connected", "test" and "disconnected" positions. OF: ON/OFF (closed/open) indication changeover contacts Chassis completely connected separation of the main circuits test position separation of the auxiliary circuits completely disconnected open CE: connected-position carriage switch contact closed open closed open closed open closed CT: test-position carriage switch contact open closed 32 CD: disconnected-position carriage switch contact Released for Manufacturing Printed on 2014/01/28 51201640AA - 05/2009 Electrical auxiliaries Device indication contacts Designation Type Electrical characteristics of contacts and control auxiliaries Standard, minimum current 100 mA 24 V Low level, minimum current 2 mA 15 V OF ON/OFF contact 3 changeover contacts V AC breaking capacity (AC 12 / DC 12 as per 947-5-1) V DC 240/380 480 690 24/48 125 250 6 A (rms) V AC 6 A (rms) 6 A (rms) 2.5 A V DC 0.5 A 0.3 A 24/48 240 380 24/48 125 250 5 A (rms) 5 A (rms) 5 A (rms) 5 / 2.5 A 0.5 A 0.3 A SD fault indication 1 changeover contact V AC breaking capacity (AC 12 / DC 12 as per 947-5-1) V DC 240/380 480 690 24/48 125 250 6 A (rms) V AC 6 A (rms) 6 A (rms) 2.5 A V DC 0.5 A 0.3 A 24/48 240 380 24/48 125 250 5 A (rms) 5 A (rms) 5 A (rms) 5 / 2.5 A 0.5 A 0.3 A SDE fault-trip indication 1 changeover contact V AC for device with motor breaking capacity mechanism (AC 12 / DC 12 as per 947-5-1) V DC 240/380 480 690 24/48 125 250 6 A (rms) V AC 6 A (rms) 6 A (rms) 2.5 A V DC 0.5 A 0.3 A 24/48 240 380 24/48 125 250 5 A (rms) 5 A (rms) 5 A (rms) 5 / 2.5 A 0.5 A 0.3 A CAO early-break switch 2 changeover contacts V AC for device with rotary breaking capacity handle (AC 12 / DC 12 as per 947-5-1) V DC 240/380 480 690 24/48 125 250 6 A (rms) V AC 6 A (rms) 6 A (rms) 2.5 A V DC 0.5 A 0.3 A 24/48 240 380 24/48 125 250 5 A (rms) 5 A (rms) 5 A (rms) 5 / 2.5 A 0.5 A 0.3 A CAF early-make switch 2 changeover contacts V AC for device with rotary breaking capacity handle (AC 12 / DC 12 as per 947-5-1) V DC 240/380 480 690 24/48 125 250 6 A (rms) V AC 6 A (rms) 6 A (rms) 2.5 A V DC 0.5 A 0.3 A 24/48 240 380 24/48 125 250 5 A (rms) 5 A (rms) 5 A (rms) 5 / 2.5 A 0.5 A 0.3 A Device control auxiliaries Consumption Response time MX opening release Designation V AC: 50/60 Hz: 24/48 - 0.7 to 1.1 Un 100/130 - 200/250 - 277 - 380/480 V DC: 12 - 24/30 - 48/60 - 100/130 - 200/250 Power supply Threshold pick-up: 200 VA or W (80 ms) hold: 4.5 VA or W device at Un: 50 ms ± 10 MN undervoltage release V AC: 50/60 Hz: 24/48 - 100/130 - 200/250 - 380/480 V DC: 24/30 - 48/60 100/130 - 200/250 pick-up: 200 VA or W (80 ms) hold: 4.5 VA or W device at Un: 40 ms ± 10 Delay unit for undervoltage release V AC: 50/60 Hz open: 200 VA V DC not adjustable: 0.35 to 0.7 Un 100/130 - 200/250 close: 0.85 Un V DC adjustable: 48/60 - 100/130 - 200/250 - 380/480 open: 0.35 to 0.7 Un close: 0.85 Un Motor mechanism device at Un: not adjustable: 0.25 s adjustable: 0.5 - 0.9 - 1.5 - 3 s Designation Power supply Threshold Consumption and motor overcurrent Recharge time and operating rate Motor mechanism consumption: 180 VA or W overcurrent: 2 to 3 In for 0.1 s 3 seconds max. 3 cycles per minute V AC: 50/60 Hz: 48/60 - 0.85 to 1.1 Un 100/130 - 200/240 - 277 - 400/440 - 480 V DC: 24/30 - 48/60 100/125 - 200/250 "Connected", "test" and "disconnected" position carriage switches Designation Type Standard, minimum current 100 mA 24 VLow level, minimum current 2 mA 15 V CE, CT, CD 3 changeover contacts V AC breaking capacity (AC 12 / DC 12 as per 947-5-1) V DC 240 380 480 690 24/48 125 250 8 A (rms) V AC 8 A (rms) 8 A (rms) 6 A (rms) 2.5 A V DC 0.8 A 0.3 A Released for Manufacturing 51201640AA - 05/2009 Printed on 2014/01/28 24/48 240 380 5 A (rms) 5 A (rms) 5 A (rms) 24/48 125 250 2.5 A 0.8 A 0.3 A 33 Electrical auxiliaries Electrical characteristics of contacts and control auxiliaries Wiring of control auxiliaries Under pick-up conditions, the level of consumption is approximately 150 to 200 VA. Consequently, for low supply voltages (12, 24, 48 V), cables must not exceed a maximum length determined by the supply voltage and the cross-section of the cables. Indicative values for maximum cable lengths (in meters) 12 V 24 V 48 V 2.5 mm² 1.5 mm² 2.5 mm² 1.5 mm² 2.5 mm² 1.5 mm² MN MX-XF 100 % source voltage 85 % source voltage 100 % source voltage 85 % source voltage — — 58 36 280 165 — — 16 10 75 45 21 12 115 70 550 330 10 6 75 44 350 210 Note : The indicated length is that for each of the two supply wires. 34 Released for Manufacturing Printed on 2014/01/28 51201640AA - 05/2009 Released for Manufacturing 51201640AA - 05/2009 Printed on 2014/01/28 35 Start-up Start-up operations Procedure These operations must be carried out before using a device for the first time. A general check of the device takes only a few minutes and avoids any risk of mistakes due to errors or negligence. A general check must be carried out: b prior to initial use b following an extended period during which the device is not used. A check must be carried out with the entire switchboard de-energised. In switchboards with compartments, only those compartments that may be accessed by the operators must be de-energised. Electrical tests Insulation and dielectric-withstand tests must be carried out immediately after delivery of the switchboard. These tests are precisely defined by international standards and must be directed and carried out by a qualified expert. Prior to running the tests, it is absolutely necessary to: b disconnect all the electrical auxiliaries of the device (MCH, MX, MN) b remove the long-time rating plug on the 7.0 A control units. Removal of the rating plug disconnects the voltage measurement input. Switchboard inspection Check that the devices are installed in a clean environment, free of any installation scrap or items (tools, electrical wires, broken parts or shreds, metal objects, etc.). Conformity with the installation diagram Check that the devices conform with the installation diagram: b breaking capacities indicated on the rating plates b identification of the control unit (type, rating) b presence of any optional functions (motor mechanism) b protection settings (long time, short time, instantaneous, ground fault) b identification of the protected circuit marked on the front of each device. Condition of connections and auxiliaries Check device mounting in the switchboard and the tightness of power connections. Check that all auxiliaries and accessories are correctly installed: b electrical auxiliaries b terminal blocks b connections of auxiliary circuits. Operation Check the mechanical operation of the devices: b opening of contacts b closing of contacts. Check on the control unit Check the control unit of each circuit breaker using the respective user manuals. 36 Released for Manufacturing Printed on 2014/01/28 51201640AA - 05/2009 Start-up What to do when the circuit breaker trips? Note the fault Faults are signalled locally and remotely by the indicators and auxiliary contacts installed on devices (depending on each configuration). See page 32 in this manual and the user manual of the control unit for information on the fault indications available with your circuit breaker. Identify the cause of tripping A circuit must never be reclosed (locally or remotely) before the cause of the fault has been identified and cleared. Depending on the type of fault and the criticality of the loads, a number of precautionary measures must be taken, in particular the insulation and dielectric tests on a part of or the entire installation. These checks and test must be directed and carried out by qualified personnel. Inspect the circuit breaker following a short-circuit b Check the tightness of connections (see the device installation manual) b Check the disconnecting-contact clusters. Reset the circuit breaker The circuit breaker can be reset locally or remotely. See pages 5, 9 and 15 in this manual for information on how the device can be reset. Released for Manufacturing 51201640AA - 05/2009 Printed on 2014/01/28 37 Compact operating conditions Environmental conditions E60416A Ambient temperature Compact devices can operate under the following temperature conditions: b the electrical and mechanical characteristics are stipulated for an ambient temperature of -5 °C to +70 °C b circuit-breaker closing is guaranteed down to -35 °C b Compact (without the control unit) can be stored in an ambient temperature of -40 °C to +85 °C b the control unit can be stored in an ambient temperature of -25 °C to +85 °C. push to trip E60417A Extreme atmospheric conditions Compact devices have successfully passed the tests defined by the following standards for extreme atmospheric conditions: b IEC 68-2-1: dry cold at -55 °C b IEC 68-2-2: dry heat at +85 °C b IEC 68-2-30: damp heat (temperature +55 °C, relative humidity 95%) b IEC 68-2-52 level 2: salt mist. push to trip Compact devices can operate in the industrial environments defined by standard IEC 947 (pollution degree up to 3). It is nonetheless advised to check that the devices are installed in suitably cooled switchboards without excessive dust. E60418A Vibrations Compact devices resist electromagnetic or mechanical vibrations. Tests are carried out in compliance with standard IEC 68-2-6 for the levels required by merchant-marine inspection organisations (Veritas, Lloyd's, etc.): b 2 to 13.2 Hz: amplitude ±1 mm b 13.2 to 100 Hz: constant acceleration 0.7 g. push to trip 38 Excessive vibration may cause tripping, breaks in connections or damage to mechanical parts. Released for Manufacturing Printed on 2014/01/28 51201640AA - 05/2009 Compact operating conditions Environmental conditions E60420A Electromagnetic disturbances Compact devices are protected against: b overvoltages caused by devices that generate electromagnetic disturbances b overvoltages caused by an atmospheric disturbance or by a distribution-system outage (e.g. failure of a lighting system) b devices emitting radio waves (radios, walkie-talkies, radar, etc.) b electrostatic discharges produced by users. push to trip Compact devices have successfully passed the electromagnetic-compatibility tests (EMC) defined by the following international standards: b IEC 947-2, appendix F b IEC 947-2, appendix B (trip units with earth-leakage function). The above tests guarantee that: b no nuisance tripping occurs b tripping times are respected. Cleaning b Non-metallic parts: never use solvent, soap or any other cleaning product. Clean with a dry cloth only b Metal parts: clean with a dry cloth whenever possible. If solvent, soap or any other cleaning product must be used, make sure that it does not come into contact with non-metallic parts. Released for Manufacturing 51201640AA - 05/2009 Printed on 2014/01/28 39 Notes 40 Released for Manufacturing Printed on 2014/01/28 51201640AA - 05/2009 Released for Manufacturing Printed on 2014/01/28 35, rue Joseph Monier CS 30323 F - 92506 Rueil Malmaison Cedex RCS Nanterre 954 503 439 Capital social 896 313 776 € www.schneider-electric.com 51201640AA-04 As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. This document has been printed on ecological paper Design: Schneider Electric Photos: Schneider Electric Printed: Released for Manufacturing Printed on 2014/01/28 © 2009 - Schneider Electric - Tous droits réservés Schneider Electric Industries SAS 05-2009