Download User Manual
Transcript
V5−H High Performance Vector Control Inverter User Manual 2”, the output frequency is in the corresponding FDT setup range and indication signal is output. Output frequency FDT level upper limit FDT level lower limit Y i terminal Time Time Fig.6-29: Frequency level detection signal (FDT) P7.24 Virtual terminal effective selection 000 ~ 111(000) It controls the action of the multifunctional input terminal or output terminal by the host computer. Unit place Tens place Hundreds place Display of operation panel Multifunctional input terminal Xi 0: The real terminal is enabled; 1: The virtual terminal is enabled reserved Y1, Y2 and relay terminals 0: The real terminal is enabled; 1: The virtual terminal is enabled When Xi terminal signal source is input as virtual terminal, whether the corresponding function of this terminal is effective depends on the control of the host computer and has nothing to do with the real status of the current Xi terminal. When Yi, Y2 and relay terminals are output as virtual terminals, the real outputs of these terminals depend on the control of the host computer and have nothing to do with whether the output terminal function set is effective. P7.25 Terminal effective status selection 000 ~ 111(000) It defines the validity of the input and output status of the multifunctional digital terminals. Unit place Tens place Hundreds place Display of operation panel Multifunctional input terminal Xi 0: Current through Xi is valid; 1: No current through Xi is invalid Multifunctional output terminal Yi 0: Current through Yi is valid; 1: No current through Yi is invalid Relay output terminal 0: Enable in magnetizing status; 1: Enable in no magnetizing status Chapter 6 Parameter Description 95