STARTING UP OF THE BOILER To fire up the Boiler Make sure that there is link (or external closed control contacts TA) between terminals 1 and 2. or 10 volts if 0 to 10 volt control. See page 51 and 52 for programming 0 to 10 volt control NOTE When using 0 to 10 Volt control terminals 1 and 2 have no effect on the Boiler operation therefore no link would be required between terminals 1 and 2 when using O to 10 volt control , thus a voltage above 3 volts would be needed on terminals 13 and 14 for the Boiler to start firing. EXTERNAL CONTROL 13 14 0 to 10 volt from others Press the shaded button in each case below Selecting is for a stand alone Boiler using the inbuilt Boiler controls for Heating & Hot Water. Selecting mode is for external control of the Boiler using terminals 1 & 2 (TA ) or 0 to 10volt control when programmed. 0 to 10 volt see page 51 Page 45