Download Feeder Protection and Control REF611 Modbus Point List Manual

Transcript
Relion® 611 series
Feeder Protection and Control
REF611
Modbus Point List Manual
Document ID: 1MRS757463
Issued: 2011-11-18
Revision: A
Product version: 1.0
© Copyright 2011 ABB. All rights reserved
Copyright
This document and parts thereof must not be reproduced or copied without written
permission from ABB, and the contents thereof must not be imparted to a third
party, nor used for any unauthorized purpose.
The software or hardware described in this document is furnished under a license
and may be used, copied, or disclosed only in accordance with the terms of such
license.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or
product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
http://www.abb.com/substationautomation
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept
or product description and are not to be deemed as a statement of guaranteed
properties. All persons responsible for applying the equipment addressed in this
manual must satisfy themselves that each intended application is suitable and
acceptable, including that any applicable safety or other operational requirements
are complied with. In particular, any risks in applications where a system failure and/
or product failure would create a risk for harm to property or persons (including but
not limited to personal injuries or death) shall be the sole responsibility of the
person or entity applying the equipment, and those so responsible are hereby
requested to ensure that all measures are taken to exclude or mitigate such risks.
This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested
to notify the manufacturer. Other than under explicit contractual commitments, in
no event shall ABB be responsible or liable for any loss or damage resulting from
the use of this manual or the application of the equipment.
Conformity
This product complies with the directive of the Council of the European
Communities on the approximation of the laws of the Member States relating to
electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning
electrical equipment for use within specified voltage limits (Low-voltage directive
2006/95/EC). This conformity is the result of tests conducted by ABB in
accordance with the product standards EN 50263 and EN 60255-26 for the EMC
directive, and with the product standards EN 60255-1 and EN 60255-27 for the low
voltage directive. The product is designed in accordance with the international
standards of the IEC 60255 series.
Table of contents
Table of contents
Section 1
Introduction.......................................................................3
This manual........................................................................................3
Intended audience..............................................................................3
Product documentation.......................................................................4
Product documentation set............................................................4
Document revision history.............................................................5
Related documentation..................................................................6
Symbols and conventions...................................................................6
Symbols.........................................................................................6
Document conventions..................................................................6
Functions, codes and symbols......................................................7
Section 2
Modbus data mappings....................................................9
Overview.............................................................................................9
Point list for REF611 Ver. 1.0...........................................................10
Section 3
REF611
Point List Manual
Glossary.........................................................................29
1
2
Section 1
Introduction
1MRS757463 A
Section 1
Introduction
1.1
This manual
The point list manual describes the outlook and properties of the data points
specific to the IED. The manual should be used in conjunction with the
corresponding communication protocol manual.
1.2
Intended audience
This manual addresses the communication system engineer or system integrator
responsible for pre-engineering and engineering for communication setup in a
substation from an IED perspective.
The system engineer or system integrator must have a basic knowledge of
communication in protection and control systems and thorough knowledge of the
specific communication protocol.
REF611
Point List Manual
3
Section 1
Introduction
Decommissioning
deinstalling & disposal
Maintenance
Operation
Product documentation set
Commissioning
1.3.1
Engineering
Product documentation
Planning & purchase
1.3
Installing
1MRS757463 A
Engineering manual
Installation manual
Commissioning manual
Operation manual
Service manual
Application manual
Technical manual
Communication protocol
manual
en07000220.vsd
IEC07000220 V1 EN
Figure 1:
The intended use of manuals in different lifecycles
The engineering manual contains instructions on how to engineer the IEDs using
the different tools in PCM600. The manual provides instructions on how to set up a
PCM600 project and insert IEDs to the project structure. The manual also
recommends a sequence for engineering of protection and control functions, LHMI
functions as well as communication engineering for IEC 61850 and other
supported protocols.
The installation manual contains instructions on how to install the IED. The
manual provides procedures for mechanical and electrical installation. The chapters
are organized in chronological order in which the IED should be installed.
The commissioning manual contains instructions on how to commission the IED.
The manual can also be used by system engineers and maintenance personnel for
assistance during the testing phase. The manual provides procedures for checking
of external circuitry and energizing the IED, parameter setting and configuration as
4
REF611
Point List Manual
Section 1
Introduction
1MRS757463 A
well as verifying settings by secondary injection. The manual describes the process
of testing an IED in a substation which is not in service. The chapters are organized
in chronological order in which the IED should be commissioned.
The operation manual contains instructions on how to operate the IED once it has
been commissioned. The manual provides instructions for monitoring, controlling
and setting the IED. The manual also describes how to identify disturbances and
how to view calculated and measured power grid data to determine the cause of a
fault.
The service manual contains instructions on how to service and maintain the IED.
The manual also provides procedures for de-energizing, de-commissioning and
disposal of the IED.
The application manual contains application descriptions and setting guidelines
sorted per function. The manual can be used to find out when and for what purpose
a typical protection function can be used. The manual can also be used when
calculating settings.
The technical manual contains application and functionality descriptions and lists
function blocks, logic diagrams, input and output signals, setting parameters and
technical data sorted per function. The manual can be used as a technical reference
during the engineering phase, installation and commissioning phase, and during
normal service.
The communication protocol manual describes a communication protocol
supported by the IED. The manual concentrates on vendor-specific implementations.
The point list manual describes the outlook and properties of the data points
specific to the IED. The manual should be used in conjunction with the
corresponding communication protocol manual.
Some of the manuals are not available yet.
1.3.2
Document revision history
Document revision/date
A/2011-11-18
Product series version
1.0
History
First release
Download the latest documents from the ABB Web site
http://www.abb.com/substationautomation.
REF611
Point List Manual
5
Section 1
Introduction
1.3.3
1MRS757463 A
Related documentation
Name of the document
Modbus Communication Protocol Manual
1.4
Symbols and conventions
1.4.1
Symbols
Document ID
1MRS757461
The caution icon indicates important information or warning related
to the concept discussed in the text. It might indicate the presence
of a hazard which could result in corruption of software or damage
to equipment or property.
The information icon alerts the reader of important facts and
conditions.
The tip icon indicates advice on, for example, how to design your
project or how to use a certain function.
Although warning hazards are related to personal injury, it is necessary to
understand that under certain operational conditions, operation of damaged
equipment may result in degraded process performance leading to personal injury
or death. Therefore, comply fully with all warning and caution notices.
1.4.2
Document conventions
A particular convention may not be used in this manual.
•
•
•
•
•
•
6
Abbreviations and acronyms in this manual are spelled out in the glossary. The
glossary also contains definitions of important terms.
Push-button navigation in the LHMI menu structure is presented by using the
push-button icons.
To navigate between the options, use
and
.
HMI menu paths are presented in bold.
Select Main menu/Settings.
LHMI messages are shown in Courier font.
.
To save the changes in non-volatile memory, select Yes and press
Parameter names are shown in italics.
The function can be enabled and disabled with the Operation setting.
Parameter values are indicated with quotation marks.
REF611
Point List Manual
Section 1
Introduction
1MRS757463 A
•
1.4.3
The corresponding parameter values are "On" and "Off".
IED input/output messages and monitored data names are shown in Courier font.
When the function starts, the START output is set to TRUE.
Functions, codes and symbols
Table 1:
REF611 functions, codes and symbols
Function
IEC 61850
IEC 60617
IEC-ANSI
Protection
Three-phase non-directional
overcurrent protection, low stage,
instance 1
PHLPTOC1
3I> (1)
51P-1 (1)
Three-phase non-directional
overcurrent protection, high stage,
instance 1
PHHPTOC1
3I>> (1)
51P-2 (1)
Three-phase non-directional
overcurrent protection, high stage,
instance 2
PHHPTOC2
3I>> (2)
51P-2 (2)
Three-phase non-directional
overcurrent protection, instantaneous
stage, instance 1
PHIPTOC1
3I>>> (1)
50P/51P (1)
Non-directional earth-fault protection,
low stage, instance 1
EFLPTOC1
Io> (1)
51N-1 (1)
Non-directional earth-fault protection,
low stage, instance 2
EFLPTOC2
Io> (2)
51N-1 (2)
Non-directional earth-fault protection,
high stage, instance 1
EFHPTOC1
Io>> (1)
51N-2 (1)
Non-directional earth-fault protection,
instantaneous stage
EFIPTOC1
Io>>>
50N/51N
Directional earth-fault protection, low
stage, instance 1
DEFLPDEF1
Io> -> (1)
67N-1 (1)
Directional earth-fault protection, low
stage, instance 2
DEFLPDEF2
Io> -> (2)
67N-1 (2)
Directional earth-fault protection,
high stage
DEFHPDEF1
Io>> ->
67N-2
Transient / intermittent earth-fault
protection
INTRPTEF1
Io> -> IEF
67NIEF
Non-directional (cross-country) earthfault protection, using calculated Io
EFHPTOC1
Io>> (1)
51N-2 (1)
Negative-sequence overcurrent
protection, instance 1
NSPTOC1
I2> (1)
46 (1)
Negative-sequence overcurrent
protection, instance 2
NSPTOC2
I2> (2)
46 (2)
Phase discontinuity protection
PDNSPTOC1
I2/I1>
46PD
Residual overvoltage protection,
instance 1
ROVPTOV1
Uo> (1)
59G (1)
Residual overvoltage protection,
instance 2
ROVPTOV2
Uo> (2)
59G (2)
Table continues on next page
REF611
Point List Manual
7
Section 1
Introduction
1MRS757463 A
Function
IEC 61850
IEC 60617
IEC-ANSI
Residual overvoltage protection,
instance 3
ROVPTOV3
Uo> (3)
59G (3)
Three-phase thermal protection for
feeders, cables and distribution
transformers
T1PTTR1
3Ith>F
49F
Circuit breaker failure protection
CCBRBRF1
3I>/Io>BF
51BF/51NBF
Three-phase inrush detector
INRPHAR1
3I2f>
68
Master trip, instance 1
TRPPTRC1
Master Trip (1)
94/86 (1)
Master trip, instance 2
TRPPTRC2
Master Trip (2)
94/86 (2)
Input switch group1)
ISWGAPC
ISWGAPC
ISWGAPC
Output switch group2)
OSWGAPC
OSWGAPC
OSWGAPC
Selector switch group3)
SELGAPC
SELGAPC
SELGAPC
TPGAPC
TP
TP
Circuit-breaker control
CBXCBR1
I <-> O CB
I <-> O CB
Auto-reclosing
DARREC1
O -> I
79
Trip circuit supervision, instance 1
TCSSCBR1
TCS (1)
TCM (1)
Trip circuit supervision, instance 2
TCSSCBR2
TCS (2)
TCM (2)
Disturbance recorder
RDRE1
-
-
Three-phase current measurement,
instance 1
CMMXU1
3I
3I
Sequence current measurement
CSMSQI1
I1, I2, I0
I1, I2, I0
Residual current measurement,
instance 1
RESCMMXU1
Io
In
Residual voltage measurement
RESVMMXU1
Uo
Vn
Switch groups
Configurable timer
Minimum pulse timer (2 pcs)4)
Control
Supervision
Measurement
1)
2)
3)
4)
8
10 instances
20 instances
6 instances
10 instances
REF611
Point List Manual
Section 2
Modbus data mappings
1MRS757463 A
Section 2
Modbus data mappings
2.1
Overview
This document describes the Modbus data points and structures available in
REF611 Ver. 1.0. The point lists describe a superset of all data available through
the standard configurations A and B including the optional functionalities. The
names of the standard configurations are FE101 and FE102 respectively.
The majority of the Modbus data points are valid for all standard configurations.
Some data points are standard configuration or optional application dependent and
thus not available in each IED. The unavailable, that means unused, data points
always return value 0 when they are read. The configuration dependent and
optional data do not overlap.
Point list table columns
REF611
Point List Manual
0x addr
Coil (0X) PLC address, base address = 1
Addr.
Signal address
AFL-Common SA name
AFL name of the corresponding data signal
Bit addr
Bit (1X and 0X) PLC address, base address = 1
Ctrl bit
Control bit (0..15) within control structure
Ctrl struct
Control structure number
Description
Signal description
Ds
Object resides as default in some IEC 61850 data set (Y = yes, N = no)
Identification
IED's internal IEC 61850 signal name
IEC 61850 name
IEC 61850 signal description
Mode
Control object mode: unsecured or secured
Reg addr
Modbus register address (3X or 4X). PLC address, base address = 1
Reg.bit
Register PLC address (3X and 4X) and bit within register (0..15)
Scale
Scale factor, default setting
Type
Register type and value interpretation: signed or unsigned
Value range
Value range of the signal
9
Section 2
Modbus data mappings
2.2
10
1MRS757463 A
Point list for REF611 Ver. 1.0
REF611
Point List Manual
REF611
Point List Manual
u16
u16
u16
u16
u16
u16
u16
u16
u16
i16
i16
i16
i16
i16
137
138
139
140
141
142
143
144
145
146
147
148
149
150
0.001
0.001
1
1
1
1000
1000
1000
1000
1000
1000
1000
1000
1
1
LD0.T1PTTR1.TmmsRecEna.stVal
LD0.T1PTTR1.TmmsOp.stVal
LD0.T1PTTR1.TmpUsed.mag
LD0.T1PTTR1.TmpRl.mag
LD0.T1PTTR1.Tmp.mag
LD0.CSMSQI1.SeqA.c3.instCVal.mag
LD0.CSMSQI1.SeqA.c2.instCVal.mag
LD0.CSMSQI1.SeqA.c1.instCVal.mag
LD0.RESVMMXU1.PhV.res.instCVal.mag
LD0.RESCMMXU1.A.res.instCVal.mag
LD0.CMMXU1.A.phsC.instCVal.mag
LD0.CMMXU1.A.phsB.instCVal.mag
LD0.CMMXU1.A.phsA.instCVal.mag
LD0.DARREC1.OpCntRs.stVal
LD0.DARREC1.ShotPntr.stVal
Table continues on next page
151
i16
u16
T1PTTR1.THERMLEV_E ND
T1PTTR1.THERMLEV_S T
T1PTTR1.TEMP_AMB
T1PTTR1.TEMP_RL
T1PTTR1.TEMP
CMSQI1.I3_INST
CMSQI1.I2_INST
CMSQI1.I1_INST
RESCMMXU1.U0_INST
RESCMMXU1.I0_INST
CMMXU1.I_INST_C
CMMXU1.I_INST_B
CMMXU1.I_INST_A
DARREC1.COUNTER
DARREC1.SHOT_PTR
DARREC1.STATUS
(reserved)
Estimated time to deactivate
BLK_CLOSE[.stVal] -
Estimated time to operate[.stVal] -
Ambient temperature used in calculations
[.mag] -
Relative temperature [.mag] -
Protected object temperature [.mag] -
Zero sequence current amplitude
[.c3.instCVal.mag] -
Negative sequence current amplitude
[.c2.instCVal.mag] -
Positive sequence current amplitude
[.c1.instCVal.mag] -
Residual voltage amplitude [.res.instCVal.mag] -
Residual current amplitude [.res.instCVal.mag] -
Phase current C amplitude
[.phsC.instCVal.mag] -
Phase current B amplitude
[.phsB.instCVal.mag] -
Phase current A amplitude
[.phsA.instCVal.mag] -
AR resettable operation counter (all shots)
[.stVal] -
AR shot pointer value[.stVal] -
Autoreclosing status[.stVal] -
(reserved)
134
136
System status register 6
133
135
System status register 5
132
Frequently updated registers
System status register 4
131
Description
System status register 3
Ds
130
System status registers
User definable registers
AFL-Common SA name
System status register 2
LD0.DARREC1.AutoRecSt.stVal
IEC 61850 name
System status register 1
1
Scale
129
Type
Registers
128
127
…
1
Reg
addr
Table 2:
0
0…600000 [ms]
0…600000 [ms]
-99…999.99 [Celsius]
0.00…99.99 [Celcius]
-100.0…9999.9 [Celsius]
0…40.00 [xIn]
0…40.00 [xIn]
0…40.00 [xIn]
0…4.00 [xUn]
0…40.00 [xIn]
0…40.00 [xIn]
0…40.00 [xIn]
0…40.00 [xIn]
0...2147483647
0…6
-2…4 (see documentation)
0
See Modbus CPM
See Modbus CPM
See Modbus CPM
See Modbus CPM
See Modbus CPM
See Modbus CPM
Value range
1MRS757463 A
Section 2
Modbus data mappings
11
12
u16
2003
Update time of phase A max value -reg 3
2018
Table continues on next page
Update time of phase A max value -reg 2
2017
Update time of phase A max value -reg 1
Maximum demand value for phase B[.mag] -
Time structure
Update time of phase A max value -reg 5
2015
2016
Update time of phase A max value -reg 4
Update time of phase A max value -reg 1
Maximum demand value for phase A[.mag] -
Demand value of phase C current[.mag] -
Demand value of phase B current[.mag] -
Demand value of phase A current[.mag] -
2014
CMMXU1.Max demand IL2
CMMXU1.Max demand IL1
Maximum phase current demand values
CMMXU1.I_DMD_C
CMMXU1.I_DMD_B
CMMXU1.I_DMD_A
Update time of phase A max value -reg 3
LD0.CMSTA1.MaxAmpsB.mag
Max. demand value for residual current
2013
1000
N
Phase current demand values (latest values)
RESCMMXU.Max demand Io
N
Update time of phase A max value -reg 2
Time structure
LD0.CMSTA1.MaxAmpsA.mag
LD0.CMSTA1.AvAmpsC.mag
LD0.CMSTA1.AvAmpsB.mag
LD0.CMSTA1.AvAmpsA.mag
LD0.RESCMSTA1.AvAmps.mag
RESCMSTA.I_DMD_RES
Description
2012
u16
1000
1000
1000
1000
1000
LD0.RESCMSTA1.AvAmps.mag
Ds
2011
2010
2009
2008
2007
2006
2005
u16
u16
2002
2004
u16
u16
2001
2000
1999
1998
1997
1996
1995
1994
1993
1992
1991
1000
AFL-Common SA name
Demand value of residual current
1990
...
u16
IEC 61850 name
1989
Scale
Indication bits mirrored and packed in registers
170 onwards
Type
170
Reg
addr
Time structure (see Modbus
CPM)
0…40.00 [xIn]
Time structure (see Modbus
CPM)
0…40.00 [xIn]
Time structure (see Modbus
CPM)
0…40.00 [xIn]
0…40.00 [xIn]
0…40.00 [xIn]
Time structure (see Modbus
CPM)
0.00 …. 40.00 [xIn]
Time structure (see Modbus
CPM)
0.00 …. 40.00 [xIn]
See 'Indications' table
Value range
Section 2
Modbus data mappings
1MRS757463 A
REF611
Point List Manual
REF611
Point List Manual
1
u16
u16
2035
2036
u16
u16
u16
u16
u16
u16
u16
2052
2053
2054
2055
2056
2057
1
1
1
1
1
1
1
1
1
1
1
LD0.LPHD1.NumCmpChg.stVal
LD0.LPHD1.WacTrg.stVal
LD0.LPHD1.WrmStr.stVal
LD0.LPHD1.NumPwrUp.stVal
DR.RDRE1.MemUsed.stVal
DR.RDRE1.FltNum.stVal
LD0.LPHD1.PhyHealth2.stVal
LD0.LPHD1.PhyHealth1.stVal
LD0.DARREC1.FrqOpCnt.stVal
LD0.DARREC1.OpCnt5.stVal
LD0.DARREC1.OpCnt4.stVal
LD0.DARREC1.OpCnt3.stVal
Table continues on next page
2058
u16
2050
2051
2047
...
2037
u16
2034
1
Internal Fault
Warning
Diagnostics
DARREC1.FRQ_OPR_CN T
DARREC1.CNT_SHOT5
DARREC1.CNT_SHOT4
DARREC1.CNT_SHOT3
(reserved)
Number of composition changes
Physical device - Number of watchdog device
resets detected[.stVal] -
Physical device - Number of Warm
starts[.stVal] -
Physical device - Number of Power ups[.stVal] -
Disturbance recorder - Rec. memory
used[.stVal] -
Disturbance recorder - Number of
recordings[.stVal] -
Physical device - Internal Fault[.stVal] -
Physical device - Warning[.stVal] -
(reserved)
(reserved)
Autorecloser frequent operation counter[.stVal] -
Autorecloser operation counter (5th shot)
[.stVal] -
Autorecloser operation counter (4th shot)
[.stVal] -
Autorecloser operation counter (3rd shot)
[.stVal] -
Autorecloser operation counter (2nd shot)
[.stVal] -
u16
DARREC1.CNT_SHOT2
2033
LD0.DARREC1.OpCnt2.stVal
u16
2032
1
Auto recloser operation counter (1st shot)
[.stVal] -
DARREC1.CNT_SHOT1
u16
2031
LD0.DARREC1.OpCnt1.stVal
(reserved)
2030
1
(reserved)
2029
Circuit breaker operation counter[.stVal] (reserved)
CBXCBR1.Operation counter
2028
CTRL.CBCSWI1.OpCntRs.stVal
Update time of phase A max value -reg 5
u16
Update time of phase A max value -reg 4
2026
2027
Update time of phase A max value -reg 3
2025
Counters - Circuit breaker, autorecloser
Update time of phase A max value -reg 2
Update time of phase A max value -reg 1
2024
-
CMMXU1.Max demand IL3
2023
Time structure
LD0.CMSTA1.MaxAmpsC.mag
Description
Maximum demand value for phase C[.mag] -
2022
1000
Ds
Update time of phase A max value -reg 5
u16
AFL-Common SA name
2021
IEC 61850 name
Update time of phase A max value -reg 4
Scale
2020
Type
2019
Reg
addr
0
0…65535
0…65535
0…65535
0…65535
0…100 [%]
0…N
See documentation
See documentation
0
0
0…65535
0…65535
0…65335
0…65535
0…65535
0…65535
0
0
0
0…65535
Time structure (see Modbus
CPM)
0…40.00 [xIn]
Value range
1MRS757463 A
Section 2
Modbus data mappings
13
14
u16
u16
u16
u16
u16
u16
u16
u16
u16
u16
u16
u16
u16
u16
u16
u16
u16
u16
u16
u16
u16
u16
u16
u16
8002
8003
8004
8005
8006
8007
8008
8009
8010
8011
8012
8013
8014
8015
8016
8017
8018
8019
8020
8021
8022
8023
8024
8025
For information on control structure 5 bit
definitions, see Modbus controls table.
For information on control structure 4 bit
definitions, see Modbus controls table.
For information on control structure 3 bit
definitions, see Modbus controls table.
For information on control structure 2 bit
definitions, see Modbus controls table.
For information on control structure 1 bit
definitions, see Modbus controls table.
Table continues on next page
8026
u16
8001
8000
...
Control structure 5
Control structure 4
Control structure 3
Control structure 2
Control structure 1
AFL-Common SA name
Ds
Description
(reserved)
Control Struct 5 - Confirm register
Control Struct 5 - Control register
Control Struct 5 - Password 2
Control Struct 5 - Password 1
Control Struct 5 - Execute register
Control Struct 4 - Confirm register
Control Struct 4 - Control register
Control Struct 4 - Password 2
Control Struct 4 - Password 1
Control Struct 4 - Execute register
Control Struct 3 - Confirm register
Control Struct 3 - Control register
Control Struct 3 - Password 2
Control Struct 3 - Password 1
Control Struct 3 - Execute register
Control Struct 2 - Confirm register
Control Struct 2 - Control register
Control Struct 2 - Password 2
Control Struct 2 - Password 1
Control Struct 2 - Execute register
Control Struct 1 - Confirm register
Control Struct 1 - Control register
Control Struct 1 - Password 2
Control Struct 1 - Password 1
Control Struct 1 - Execute register
(reserved)
(reserved)
IEC 61850 name
(reserved)
Scale
2070
Type
2059
Reg
addr
0
Control structure (see Modbus
CPM)
Control structure (see Modbus
CPM)
Control structure (see Modbus
CPM)
Control structure (see Modbus
CPM)
Control structure (see Modbus
CPM)
0
0
0
Value range
Section 2
Modbus data mappings
1MRS757463 A
REF611
Point List Manual
Ds
REF611
Point List Manual
(reserved)
Description
u16
u16
u16
u16
9205
9206
9207
9208
Device real-time clock in UTC time
Real-time struct - Milliseconds (0..999)
Real-time struct - Seconds (0..59)
Real-time struct - Minute (0..59)
Real-time struct - Hour (0..23)
Real-time struct - Day (1..31)
Real-time struct - Month (1..12)
u16
u16
u16
u16
9215
9216
9217
9218
Timestamp of last device reset
Real-time struct UTC - Milliseconds (0..999)
Real-time struct UTC - Seconds (0..59)
Real-time struct UTC - Minute (0..59)
Real-time struct UTC - Hour (0..23)
Real-time struct UTC - Day (1..31)
Real-time struct UTC - Month (1..12)
u16
u16
u16
u16
u16
u16
u16
9223
9224
9225
9226
9227
9228
Table continues on next page
u16
9221
9222
Reset time struct - Reason
Reset time struct - Milliseconds (0..999)
Reset time struct - Seconds (0..59)
Reset time struct - Minute (0..59)
Reset time struct - Hour (0..23)
Reset time struct - Day (1..31)
Reset time struct - Month (1..12)
Reset time struct - Year (2000..2999)
(reserved)
u16
9214
Real-time struct UTC - Year (2000..2999)
(reserved)
u16
9213
Real-time struct UTC - Control register (0..2)
9220
u16
9219
u16
9211
9212
(reserved)
u16
9204
Real-time struct - Year (2000..2999)
(reserved)
u16
9203
Real-time struct - Control register (0..2)
9210
u16
(reserved)
9209
u16
9201
9202
9128
...
Device real-time clock in local time
Device ID string
AFL-Common SA name
(reserved)
IEC 61850 name
9002
Scale
Max length of device ID string may be 128
registers
Type
9001
9000
...
Reg
addr
1 = Cold reset
0
0
0
0
0
0
Device ID string (see Modbus
CPM)
0
Value range
1MRS757463 A
Section 2
Modbus data mappings
15
16
9231
u16
9261
9262
0
0
0
Event record 7 (11 registers)
Table continues on next page
9318
...
9328
Event record 6 (11 registers)
u16
9260
0
9307
...
9317
u16
9259
0
Event record 5 (11 registers)
u16
9258
0
9296
...
9306
u16
9257
0
Event record 4 (11 registers)
u16
9256
0
9285
...
9295
u16
9255
0
0
Event record 3 (11 registers)
u16
9254
Event record 1 (11 registers)
9274
...
9284
u16
9253
0
0
Event read selection
Event record 2 (11 registers)
u16
9252
0
9263
...
9273
i16
u16
9251
u16
9250
9249
...
9232
u16
Ds
Event record structure
Active parameter setting group
AFL-Common SA name
Description
Event record structure
Event record structure
Event record structure
Event record structure
Event record structure
Event record structure
Event record struct - Data value
Event record struct - Data value
Event record struct - Data object ID 2
Event record struct - Data object ID 1
Event record struct - Event identification
Event record struct - TimeStamp (Milliseconds)
Event record struct - TimeStamp (Min, Sec)
Event record struct - TimeStamp (Day, Hour)
Event record struct - TimeStamp (Year,Month)
Event record struct - Unread records left
Event record struct - Sequence number
Event read operation selection
Number of events records in multiple event
reading
(reserved)
(reserved)
Setting group in use
(reserved)
IEC 61850 name
(reserved)
Scale
9230
Type
9229
Reg
addr
Event record structure (see
Modbus CPM)
Event record structure (see
Modbus CPM)
Event record structure (see
Modbus CPM)
Event record structure (see
Modbus CPM)
Event record structure (see
Modbus CPM)
Event record structure (see
Modbus CPM)
Event record structure (see
Modbus CPM)
-499…3
1…10
0
0
1...6
0
0
2 = Watchdog reset
4 = Warm reset
Value range
Section 2
Modbus data mappings
1MRS757463 A
REF611
Point List Manual
REF611
Point List Manual
LD0.FLTMSTA1.MaxAmpsN.mag
Table continues on next page
1000
Y
Y
Max residual current during fault
Max phase C current during fault
Max phase B current during fault
u16
LD0.FLTMSTA1.MaxAmpsC.mag
Y
9425
1000
LD0.FLTMSTA1.MaxAmpsB.mag
u16
1000
9424
Active setting group
u16
Y
Y
Operate time
Operate time
9423
LD0.FLTMSTA1.MaxAmpsA.mag
LD0.FLTMSTA1.ActSG.stVal
Y
Y
Max phase A current during fault
1000
1
LD0.FLTMSTA1.OpTm.mag
LD0.FLTMSTA1.OpTm.mag
Maximum start duration of all stages during the
fault
u16
u16
9415
1000
1000
Y
9422
u32
9414
LD0.FLTMSTA1.StrDur.mag
Protection function
FLTMSTA fault record number
FLTMSTA fault record number
(reserved)
u32
9413
100
LD0.FLTMSTA1.ProFcn.stVal
Y
Y
9421
u16
9412
1
LD0.FLTMSTA1.OpCnt.stVal
LD0.FLTMSTA1.OpCnt.stVal
(reserved)
i16
9411
1
1
Fault record struct - TimeStamp (Time quality)
9420
u32
Fault record data
Fault record struct - TimeStamp (Milliseconds)
(reserved)
u32
9409
9410
0
Fault record struct - TimeStamp (Min, Sec)
9419
u16
9408
0
Fault record struct - TimeStamp (Day, Hour)
(reserved)
u16
9407
0
Fault record struct - TimeStamp (Year,Month)
9418
u16
9406
0
0
(reserved)
u16
9405
Fault record struct - Unread records left
Fault record struct - Sequence number
Fault record read operation selection
(reserved)
(reserved)
Event record structure
Event record structure
Event record structure
Description
9417
u16
9404
0
Fault record read selection
Ds
(reserved)
u16
9403
0
Fault record structure
AFL-Common SA name
9416
i16
u16
9401
9402
9400
...
0
Event record 10 (11 registers)
9351
...
9361
9362
Event record 9 (11 registers)
IEC 61850 name
9340
...
9350
Scale
Event record 8 (11 registers)
Type
9329
...
9339
Reg
addr
0.00 …. 50.00 [xIn]
0.00 …. 50.00 [xIn]
0.00 …. 50.00 [xIn]
0.00 …. 50.00 [xIn]
0
0
0
0
0
0
1…6
0.000...999999.999 [s]
0.000...999999.999 [s]
0.00 …100.00 [%]
-32768…32767 (see
documentation)
0…999999
0…999999
Header
-99…3
0
0
Event record structure (see
Modbus CPM)
Event record structure (see
Modbus CPM)
Event record structure (see
Modbus CPM)
Value range
1MRS757463 A
Section 2
Modbus data mappings
17
Type
u16
u16
u16
u16
u16
u16
u16
u16
u16
u16
i16
i16
Reg
addr
9426
9427
18
9428
9429
9430
9431
9432
9433
9434
9435
9436
9437
10
10
100
100
1000
1000
1000
1000
1000
1000
1000
1000
Scale
LD0.FLTMSTA1.DifCAngAB.mag
LD0.FLTMSTA1.DifNAngN.mag
LD0.FLTMSTA1.PDNS1MxRat.mag
LD0.FLTMSTA1.MaxTmpRl.mag
LD0.FLTMSTA1.VoltsN.mag
LD0.FLTMSTA1.AmpsNgSeq.mag
LD0.FLTMSTA1.AmpsPsSeq.mag
LD0.FLTMSTA1.AmpsNClc.mag
LD0.FLTMSTA1.AmpsN.mag
LD0.FLTMSTA1.AmpsC.mag
LD0.FLTMSTA1.AmpsB.mag
LD0.FLTMSTA1.AmpsA.mag
IEC 61850 name
AFL-Common SA name
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Ds
Angle phase A to phase B voltage - phase C
current
Angle residual voltage - residual current
PDNSPTOC1 ratio I2/I1
Max relative temperature
Residual voltage at moment of trip
Negative sequence current at moment of trip
Positive sequence current at moment of trip
Residual Clc current at moment of trip
Residual current at moment of trip
Phase C current at moment of trip
Phase B current at moment of trip
Phase A current at moment of trip
Description
-180.00...180.00 [degrees]
-180.00...180.00 [degrees]
0.00...999.99 [%]
0.00 …. 99.99 [ deg Celsius ]
0…4.00 [xUn]
0.00 …. 50.00 [xIn]
0.00 …. 50.00 [xIn]
0.00 …. 50.00 [xIn]
0.00 …. 50.00 [xIn]
0.00 …. 50.00 [xIn]
0.00 …. 50.00 [xIn]
0.00 …. 50.00 [xIn]
Value range
Section 2
Modbus data mappings
1MRS757463 A
REF611
Point List Manual
REF611
Point List Manual
170.00
170.01
170.02
170.03
170.04
170.05
170.06
170.07
170.08
170.09
...
170.15
171.00
171.01
171.02
171.03
171.04
171.05
171.06
171.07
171.08
171.09
171.10
171.11
171.12
171.13
171.14
171.15
172.00
172.01
172.02
172.03
172.04
172.05
2720
2721
2722
2723
2724
2725
2726
2727
2728
2729
...
2735
2736
2737
2738
2739
2740
2741
2742
2743
2744
2745
2746
2747
2748
2749
2750
2751
2752
2753
2754
2755
2756
2757
LD0.CMMXU1.LoWrn.stVal
LD0.CMMXU1.LoWrn.stVal
LD0.CMMXU1.HiWrn.stVal
LD0.CMMXU1.HiWrn.stVal
LD0.CMMXU1.HiAlm.stVal
LD0.CMMXU1.HiAlm.stVal
LD0.TRPPTRC2.Tr.general
LD0.TRPPTRC2.Tr.general
LD0.TRPPTRC2.Op.general
LD0.TRPPTRC2.Op.general
LD0.TRPPTRC1.Tr.general
LD0.TRPPTRC1.Tr.general
LD0.TRPPTRC1.Op.general
LD0.TRPPTRC1.Op.general
LD0.LEDPTRC1.Op.general
LD0.LEDPTRC1.Op.general
LD0.LEDPTRC1.Str.general
LD0.LEDPTRC1.Str.general
LD0.DARREC1.AROn.stVal
DR.RDRE1.RcdMade.stVal
DR.RDRE1.RcdMade.stVal
CTRL.LLN0.Loc.stVal
IEC 61850 name
Indications
Table continues on next page
Reg.bit
Bit addr
Table 3:
Y
Operate(.general) - MCD
Operate (.general) - mom
Start (.general) - MCD
Start (.general)- mom
(reserved)
(reserved)
(reserved)
(reserved)
(reserved)
(reserved)
Autorecloser state
Disturbance recorder file ready - MCD
Disturbance recorder file ready
(reserved)
Local/Remote state - mom
Description
Trip output signal (.general) - MCD
Trip output signal (.general) - mom
Input signal (.general) - MCD
Input signal (.general)- mom
Y
Y
(reserved)
(reserved)
(reserved)
(reserved)
Trip output signal [.general] - MCD
Trip output signal [.general] - mom
Input signal (.general) - MCD
Input signal (.general) - mom
Protection trip conditioning (2)
Y
Y
Protection trip conditioning (1)
Y
Y
Global conditioning
Ds
CMMXU1.LOW_WARN
CMMXU1.HIGH_WARN
Y
Y
Y
Low warning[.stVal] - MCD
Low warning[.stVal] - mom
High warning[.stVal] - MCD
High warning[.stVal] - mom
High alarm[.stVal] - MCD
High alarm[.stVal] - mom
Phase current value limit supervision
CMMXU1.HIGH_ALARM
-
-
-
-
-
-
DARREC1.AR_ON
-
-
AFL-Common SA name
1=Low warning
1=High warning
1=High alarm
0
0
0
0
1=Trip output signal ON
1=Input signal ON
1=Trip output signal ON
1=Input signal ON
1=Operate (LEDPTRC)
1=Start (LEDPTRC)
0
0
0
0
0
0
0=AR Off, 1=AR On
1=DR file captured
0
0 = Remote, 1 = Local (or Off)
Value range
1MRS757463 A
Section 2
Modbus data mappings
19
20
172.11
172.12
172.13
172.14
172.15
173.00
173.01
173.02
173.03
173.04
173.05
173.06
173.07
173.08
173.09
173.10
173.11
173.12
173.13
173.14
173.15
175.04
175.05
175.06
175.07
2763
2764
2765
2766
2767
2768
2769
2770
2771
2772
2773
2774
2775
2776
2777
2778
2779
2780
2781
2782
2783
2804
2805
2806
2807
CTRL.CBCSWI1.Pos.stVal.Fault
CTRL.CBCSWI1.Pos.stVal.Open
CTRL.CBCSWI1.Pos.stVal.Close
LD0.TCSSCBR2.CirAlm.stVal
LD0.TCSSCBR2.CirAlm.stVal
LD0.TCSSCBR1.CirAlm.stVal
LD0.TCSSCBR1.CirAlm.stVal
LD0.LEDGGIO1.SPCSO8.stVal
LD0.LEDGGIO1.SPCSO7.stVal
LD0.LEDGGIO1.SPCSO6.stVal
LD0.LEDGGIO1.SPCSO5.stVal
LD0.LEDGGIO1.SPCSO4.stVal
LD0.LEDGGIO1.SPCSO3.stVal
LD0.LEDGGIO1.SPCSO2.stVal
LD0.LEDGGIO1.SPCSO1.stVal
LD0.RESVMMXU1.HiWrn.stVal
LD0.RESVMMXU1.HiWrn.stVal
LD0.RESVMMXU1.HiAlm.stVal
LD0.RESVMMXU1.HiAlm.stVal
LD0.RESCMMXU1.HiWrn.stVal
LD0.RESCMMXU1.HiWrn.stVal
LD0.RESCMMXU1.HiAlm.stVal
LD0.RESCMMXU1.HiAlm.stVal
LD0.CMMXU1.LoAlm.stVal
LD0.CMMXU1.LoAlm.stVal
IEC 61850 name
Table continues on next page
175.10
172.10
2762
2810
172.09
2761
175.09
172.08
2760
2809
172.07
2759
175.08
172.06
2758
2808
Reg.bit
Bit addr
-
-
CBXCBR1.POSITION
TCSSCBR2.ALARM
TCSSCBR1.ALARM
-
-
-
-
-
-
Low alarm[.stVal] - MCD
Low alarm[.stVal] - mom
Description
Y
Y
High warning[.stVal] - MCD
High warning[.stVal] - mom
High alarm[.stVal] - MCD
High alarm[.stVal] - mom
High warning[.stVal] - MCD
High warning[.stVal] - mom
High alarm[.stVal] - MCD
High alarm[.stVal] - mom
Y
Y
Y
Y
Y
Y
Y
Y
(reserved)
(reserved)
(reserved)
(reserved)
LED 8[.stVal] - mom
LED 7[.stVal] - mom
LED 6[.stVal] - mom
LED 5[.stVal] - mom
LED 4[.stVal] - mom
LED 3[.stVal] - mom
LED 2[.stVal] - mom
LED 1[.stVal] - mom
Indication LED states
Y
Y
Alarm[.stVal] - MCD
Alarm[.stVal] - mom
Alarm[.stVal] - MCD
Alarm[.stVal] - mom
Y
Y
(reserved)
(reserved)
(reserved)
(reserved)
error position
open mom
close mom
Circuit breaker position
Y
Trip circuit supervision (2)
Y
Trip circuit supervision (1)
RESVMMXU1.HIGH_WARN
RESVMMXU1.HIGH_ALARM
-
Y
Residual voltage value limit supervision
RESCMMXU1.HIGH_WARN
RESCMMXU1.HIGH_ALARM
-
Ds
Residual current value limit supervision
CMMXU1.LOW_ALARM
AFL-Common SA name
0
0
0
0
1=Faulty or Intermediate
1=Open
1=Close
1=TCS2 Alarm
1=TCS1 Alarm
0
0
0
0
1=LED ON
1=LED ON
1=LED ON
1=LED ON
1=LED ON
1=LED ON
1=LED ON
1=LED ON
1=High warning
1=High alarm
1=High warning
1= High alarm
1=Low alarm
Value range
Section 2
Modbus data mappings
1MRS757463 A
REF611
Point List Manual
REF611
Point List Manual
175.11
175.12
175.13
175.14
175.15
176.00
176.01
176.02
176.03
176.04
176.05
176.06
176.07
176.08
176.09
176.10
176.11
176.12
176.13
176.14
176.15
177.00
177.01
177.02
177.03
177.04
177.05
177.06
177.07
180.00
180.01
180.02
180.03
180.04
2811
2812
2813
2814
2815
2816
2817
2818
2819
2820
2821
2822
2823
2824
2825
2826
2827
2828
2829
2830
2831
2832
2833
2834
2835
2836
2837
2838
2839
2880
2881
2882
2883
2884
LD0.PHLPTOC1.Str.phsB
LD0.PHLPTOC1.Str.phsA
LD0.PHLPTOC1.Str.phsA
LD0.PHLPTOC1.Str.general
LD0.PHLPTOC1.Str.general
CTRL.CBXCBR1.BlkCls.stVal
CTRL.CBXCBR1.BlkCls.stVal
CTRL.CBXCBR1.BlkOpn.stVal
CTRL.CBXCBR1.BlkOpn.stVal
CTRL.CCBRBRF1.OpIn.general
CTRL.CCBRBRF1.OpIn.general
CTRL.CCBRBRF1.OpEx.general
CTRL.CCBRBRF1.OpEx.general
CTRL.CCBRBRF1.Str.general
CTRL.CCBRBRF1.Str.general
LD0.CBCILO1.ItlByPss.stVal
CTRL.CBCILO1.EnaCls.stVal
CTRL.CBCILO1.EnaOpn.stVal
CTRL.CBCSWI1.Pos.stSeld
CTRL.CBCSWI1.Pos.stSeld
CTRL.CBCSWI1.Pos.stVal
CTRL.CBCSWI1.Pos.stVal
CTRL.CBCSWI1.Pos.stVal
CTRL.CBCSWI1.Pos.stVal
IEC 61850 name
Table continues on next page
Reg.bit
Bit addr
(reserved)
(reserved)
open MCD
open mom
close MCD
close mom
Y
Selected [.stSeld] - MCD
Selected (.stSeld) - mom
Y
Y
Interlocking bypass [.stVal] - mom
Close enabled (.stVal) - mom
Open enabled (.stVal) - mom
Y
Y
Y
Y
Y
Close blocked [.stVal] - MCD
Close blocked [.stVal] - mom
Open blocked [.stVal] - MCD
Open blocked [.stVal] - mom
(reserved)
(reserved)
Operate, internal retrip (.general) - MCD
Operate, internal retrip (.general) - mom
Failure, external trip [.general] - MCD
Failure, external trip [.general] - mom
Start, timer running[.general] - MCD
Start, timer running[.general] - mom
(reserved)
PHLPTOC1.START
Y
Y
Y
Low stage Start[.phsB] - mom
Low stage Start[.phsA] - MCD
Low stage Start[.phsA] - mom
Low stage Start[.general] - MCD
Low stage Start[.general] - mom
Phase overcurrent protection signals (3 stages)
CBXCBR1.BLK_CLOSE
CBXCBR1.BLK_OPEN
CCBRBRF1.TRRET
CCBRBRF1.TRBU
CCBRBRF1.CB_FAULT_AL
Circuit breaker failure detection and -protection
CBXCBR1.ITL_BYPASS
CBXCBR1.ENA_CLOSE
CBXCBR1.ENA_OPEN
-
Y
Y
Circuit breaker control enable signals
CBXCBR1.SELECTED
-
(reserved)
(reserved)
(reserved)
(reserved)
(reserved)
Description
Circuit breaker selected for control operation
CBXCBR1.POSITION
-
Ds
Circuit breaker position + momentary change detect
AFL-Common SA name
1=Low stage phsB start
1=Low stage phsA start
1=Low stage start
1 = Close blocked
1 = Open blocked
0
0
1=Operate, internal re-trip
1=Failure,external trip
1=Start,timer running
0
1=Bypassed
1=Close enabled
1=Open enabled
1=Selected
0
0
1=Open
1=Close
0
0
0
0
0
Value range
1MRS757463 A
Section 2
Modbus data mappings
21
22
180.08
180.09
180.10
180.11
180.12
180.13
180.14
180.15
181.00
181.01
181.02
181.03
181.04
181.05
181.06
181.07
181.08
181.09
181.10
181.11
181.12
181.13
181.14
181.15
182.00
182.01
182.02
182.03
182.04
182.05
182.06
182.07
2888
2889
2890
2891
2892
2893
2894
2895
2896
2897
2898
2899
2900
2901
2902
2903
2904
2905
2906
2907
2908
2909
2910
2911
2912
2913
2914
2915
2916
2917
2918
2919
LD0.DEFLPTOC1.Str.general
LD0.DEFLPTOC1.Str.general
LD0.PHIPTOC1.Op.general
LD0.PHIPTOC1.Op.general
LD0.PHIPTOC1.Str.phsC
LD0.PHIPTOC1.Str.phsC
LD0.PHIPTOC1.Str.phsB
LD0.PHIPTOC1.Str.phsB
LD0.PHIPTOC1.Str.phsA
LD0.PHIPTOC1.Str.phsA
LD0.PHIPTOC1.Str.general
LD0.PHIPTOC1.Str.general
LD0.PHHPTOC2.Op.general
LD0.PHHPTOC2.Op.general
LD0.PHHPTOC2.Str.phsC
LD0.PHHPTOC2.Str.phsC
LD0.PHHPTOC2.Str.phsB
LD0.PHHPTOC2.Str.phsB
LD0.PHHPTOC2.Str.phsA
LD0.PHHPTOC2.Str.phsA
LD0.PHHPTOC2.Str.general
LD0.PHHPTOC2.Str.general
LD0.PHHPTOC1.Op.general
LD0.PHHPTOC1.Op.general
LD0.PHHPTOC1.Str.phsC
LD0.PHHPTOC1.Str.phsC
LD0.PHHPTOC1.Str.phsB
LD0.PHHPTOC1.Str.phsB
LD0.PHHPTOC1.Str.phsA
LD0.PHHPTOC1.Str.phsA
LD0.PHHPTOC1.Str.general
LD0.PHHPTOC1.Str.general
LD0.PHLPTOC1.Op.general
LD0.PHLPTOC1.Op.general
LD0.PHLPTOC1.Str.phsC
LD0.PHLPTOC1.Str.phsC
LD0.PHLPTOC1.Str.phsB
IEC 61850 name
Table continues on next page
182.09
180.07
2887
2921
180.06
2886
182.08
180.05
2885
2920
Reg.bit
Bit addr
PHIPTOC1.START
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
High(2) stage Operate[.general] - MCD
High(2) stage Operate[.general] - mom
High(2) stage Start[.phsC] - MCD
High(2) stage Start[.phsC] - mom
High(2) stage Start[.phsB] - MCD
High(2) stage Start[.phsB] - mom
High(2) stage Start[.phsA] - MCD
High(2) stage Start[.phsA] - mom
High(2) stage Start[.general] - MCD
High(2) stage Start[.general] - mom
High(1) stage Operate[.general] - MCD
High(1) stage Operate[.general] - mom
High(1) stage Start[.phsC] - MCD
High(1) stage Start[.phsC] - mom
High(1) stage Start[.phsB] - MCD
High(1) stage Start[.phsB] - mom
High(1) stage Start[.phsA] - MCD
High(1) stage Start[.phsA] - mom
High(1) stage Start[.general] - MCD
High(1) stage Start[.general] - mom
Low stage Operate[.general] - MCD
Low stage Operate[.general] - mom
Low stage Start[.phsC] - MCD
Low stage Start[.phsC] - mom
Low stage Start[.phsB] - MCD
Description
Y
Y
Y
Y
Y
Instantaneous stage Operate[.general] - MCD
Instantaneous stage Operate[.general] - mom
Instantaneous stage Start[.phsC] - MCD
Instantaneous stage Start[.phsC] - mom
Instantaneous stage Start[.phsB] - MCD
Instantaneous stage Start[.phsB] - mom
Instantaneous stage Start[.phsA] - MCD
Instantaneous stage Start[.phsA] - mom
Instantaneous stage Start[.general] - MCD
Instantaneous stage Start[.general] - mom
DEFLPTOC1.START
Y
Low(1) stage Start[.general] - MCD
Low(1) stage Start[.general] - mom
Directional earth-fault protection signals (3 stages)
PHIPTOC1.OPERATE
-
-
-
Ds
Phase overcurrent protection signals (1 stage)
PHHPTOC2.OPERATE
-
-
-
PHHPTOC2.START
PHHPTOC1.OPERATE
-
-
-
PHHPTOC1.START
PHLPTOC1.OPERATE
-
AFL-Common SA name
1=Low(1) stage start
1=Instantaneous stage operate
1=Inst. stage phsC start
1=Inst. stage phsB start
1=Inst. stage phsA start
1=Instantaneous stage start
1=High(2) stage operate
1=High(2) stage phsC start
1=High(2) stage phsB start
1=High(2) stage phsA start
1=High(2) stage start
1=High(1) stage operate
1=High(1) stage phsC start
1=High(1) stage phsB start
1=High(1) stage phsA start
1=High(1) stage start
1=Low stage operate
1=Low stage phsC start
Value range
Section 2
Modbus data mappings
1MRS757463 A
REF611
Point List Manual
REF611
Point List Manual
182.10
182.11
182.12
182.13
182.14
182.15
183.00
183.01
183.02
183.03
183.04
183.05
183.06
183.07
183.08
183.09
183.10
183.11
183.12
183.13
183.14
183.15
184.00
184.01
184.02
184.03
184.04
184.05
184.06
184.07
184.08
184.09
184.10
184.11
184.12
2922
2923
2924
2925
2926
2927
2928
2929
2930
2931
2932
2933
2934
2935
2936
2937
2938
2939
2940
2941
2942
2943
2944
2945
2946
2947
2948
2949
2950
2951
2952
2953
2954
2955
2956
LD0.NSPTOC1.Str.general
LD0.PDNSPTOC1.Op.general
LD0.PDNSPTOC1.Op.general
LD0.PDNSPTOC1.Str.general
LD0.PDNSPTOC1.Str.general
LD0.INTRPTEF1.Op.general
LD0.INTRPTEF1.Op.general
LD0.INTRPTEF1.Str.general
LD0.INTRPTEF1.Str.general
LD0.EFIPTOC1.Op.general
LD0.EFIPTOC1.Op.general
LD0.EFIPTOC1.Str.general
LD0.EFIPTOC1.Str.general
LD0.EFHPTOC1.Op.general
LD0.EFHPTOC1.Op.general
LD0.EFHPTOC1.Str.general
LD0.EFHPTOC1.Str.general
LD0.EFLPTOC2.Op.general
LD0.EFLPTOC2.Op.general
LD0.EFLPTOC2.Str.general
LD0.EFLPTOC2.Str.general
LD0.EFLPTOC1.Op.general
LD0.EFLPTOC1.Op.general
LD0.EFLPTOC1.Str.general
LD0.EFLPTOC1.Str.general
LD0.DEFHPTOC1.Op.general
LD0.DEFHPTOC1.Op.general
LD0.DEFHPTOC1.Str.general
LD0.DEFHPTOC1.Str.general
LD0.DEFLPTOC2.Op.general
LD0.DEFLPTOC2.Op.general
LD0.DEFLPTOC2.Str.general
LD0.DEFLPTOC2.Str.general
LD0.DEFLPTOC1.Op.general
LD0.DEFLPTOC1.Op.general
IEC 61850 name
Table continues on next page
Reg.bit
Bit addr
Ds
Y
Y
Y
Y
Y
High stage Operate[.general] - MCD
High stage Operate[.general] - mom
High stage Start[.general] - MCD
High stage Start[.general] - mom
Low(2) stage Operate[.general] - MCD
Low(2) stage Operate[.general] - mom
Low(2) stage Start[.general] - MCD
Low(2) stage Start[.general] - mom
Low(1) stage Operate[.general] - MCD
Low(1) stage Operate[.general] - mom
Description
Y
Y
Y
Y
Y
Y
Y
Y
Instantaneous stage Operate[.general] - MCD
Instantaneous stage Operate[.general] - mom
Instantaneous stage Start[.general] - MCD
Instantaneous stage Start[.general] - mom
High stage Operate[.general] - MCD
High stage Operate[.general] - mom
High stage Start[.general] - MCD
High stage Start[.general] - mom
Low(2) stage Operate[.general] - MCD
Low(2) stage Operate[.general] - mom
Low(2) stage Start[.general] - MCD
Low(2) stage Start[.general] - mom
Low(1) stage Operate[.general] - MCD
Low(1) stage Operate[.general] - mom
Low(1) stage Start[.general] - MCD
Low(1) stage Start[.general] - mom
Y
Y
Operate[.general] - MCD
Operate[.general] - mom
Start[.general] - MCD
Start[.general] - mom
Y
Y
Operate[.general] - MCD
Operate[.general] - mom
Start[.general] - MCD
Start[.general] - mom
NSPTOC1.START
Y
Stage1 Start[.general] - mom
Negative sequence overcurrent protection signals (2 stages)
PDNSPTOC1.OPERATE
PDNSPTOC1.START
Phase discontinuity protection signals (1 stage)
INTRPTEF1.OPERATE
INTRPTEF1.START
Transient/intermittent earth-fault protection signals (1 stage)
EFIPTOC1.OPERATE
EFIPTOC1.START
EFHPTOC1.OPERATE
EFHPTOC1.START
EFLPTOC2.OPERATE
EFLPTOC2.START
EFLPTOC1.OPERATE
EFLPTOC1.START
Non-directional earth-fault and sensitive earth-fault protection signals (4 stages)
DEFHPTOC1.OPERATE
DEFHPTOC1.START
DEFLPTOC2.OPERATE
DEFLPTOC2.START
DEFLPTOC1.OPERATE
AFL-Common SA name
1=Stage1 start
1=Stage operate
1=Stage start
1=Stage operate
1=Stage start
1=Instantaneous stage operate
1=Instantaneous stage start
1=High stage operate
1=High stage start
1=Low(2) stage operate
1=Low(2) stage start
1=Low(1) stage operate
1=Low(1) stage start
1=High stage operate
1=High stage start
1=Low(2) stage operate
1=Low(2) stage start
1=Low(1) stage operate
Value range
1MRS757463 A
Section 2
Modbus data mappings
23
24
185.02
185.03
185.04
185.05
185.06
185.07
185.08
185.09
185.10
185.11
185.12
185.13
185.14
185.15
186.00
186.01
190.00
190.01
190.02
190.03
190.04
190.05
190.06
190.07
190.08
190.09
190.10
190.11
2962
2963
2964
2965
2966
2967
2968
2969
2970
2971
2972
2973
2974
2975
2976
2977
3040
3041
3042
3043
3044
3045
3046
3047
3048
3049
3050
3051
Y
Y
Y
Stage2 Operate[.general] - MCD
Stage2 Operate[.general] - mom
Stage2 Start[.general] - MCD
Stage2 Start[.general] - mom
Stage1 Operate[.general] - MCD
Stage1 Operate[.general] - mom
Stage1 Start[.general] - MCD
Description
Y
Y
Y
Y
Start[.phsC] - MCD
Start[.phsC] - mom
Start[.phsB] - MCD
Start[.phsB] - mom
Start[.phsA] - MCD
Start[.phsA] - mom
Start[.general] - MCD
Start[.general] - mom
Three-phase inrush detection signals
Ds
Y
Y
Operate[.general] - MCD
Operate[.general] - mom
Thermal Alarm[.general] - MCD
Thermal Alarm[.general] - mom
Start[.general] - MCD
Start[.general] - mom
Y
Unsuccessful reclose status[.stVal] - mom
DARREC1.UNSUC_RECL
LD0.DARREC1.UnsRec.stVal
Successful reclose status[.stVal] - mom
AR in progress 5th reclose[.stVal] - MCD
AR in progress 5th reclose[.stVal] - mom
AR in progress 4th reclose[.stVal] - MCD
AR in progress 4th reclose[.stVal] - mom
AR in progress 3rd reclose[.stVal] - MCD
AR in progress 3rd reclose[.stVal] - mom
AR in progress 2nd reclose[.stVal] - MCD
AR in progress 2nd reclose[.stVal] - mom
AR in progress 1st reclose[.stVal] - MCD
AR in progress 1st reclose[.stVal] - mom
AR in progress [.stVal] - MCD
AR in progress [.stVal] - mom
Successful reclose status[.stVal] - MCD
Y
Y
Y
Y
Y
Y
Y
Autorecloser detailed signals, optional
DARREC1.SUC_RECL
DARREC1.INPRO_5
DARREC1.INPRO_4
DARREC1.INPRO_3
DARREC1.INPRO_2
DARREC1.INPRO_1
DARREC1.INPRO
T1PTTR1.OPERATE
T1PTTR1.ALARM
Y
Thermal overload protection signals (1 stage)
T1PTTR1.START
-
-
-
INRPHAR1.BLK2H
NSPTOC2.OPERATE
NSPTOC2.START
NSPTOC1.OPERATE
AFL-Common SA name
LD0.DARREC1.SucRec.stVal
LD0.DARREC1.SucRec.stVal
LD0.DARREC1.PrgRec5.stVal
LD0.DARREC1.PrgRec5.stVal
LD0.DARREC1.PrgRec4.stVal
LD0.DARREC1.PrgRec4.stVal
LD0.DARREC1.PrgRec3.stVal
LD0.DARREC1.PrgRec3.stVal
LD0.DARREC1.PrgRec2.stVal
LD0.DARREC1.PrgRec2.stVal
LD0.DARREC1.PrgRec1.stVal
LD0.DARREC1.PrgRec1.stVal
LD0.DARREC1.PrgRec.stVal
LD0.DARREC1.PrgRec.stVal
LD0.T1PTTR1.Op.general
LD0.T1PTTR1.Op.general
LD0.T1PTTR1.AlmThm.general
LD0.T1PTTR1.AlmThm.general
LD0.T1PTTR1.Str.general
LD0.T1PTTR1.Str.general
LD0.INRPHAR1.Str.phsC
LD0.INRPHAR1.Str.phsC
LD0.INRPHAR1.Str.phsB
LD0.INRPHAR1.Str.phsB
LD0.INRPHAR1.Str.phsA
LD0.INRPHAR1.Str.phsA
LD0.INRPHAR1.Str.general
LD0.INRPHAR1.Str.general
LD0.NSPTOC2.Op.general
LD0.NSPTOC2.Op.general
LD0.NSPTOC2.Str.general
LD0.NSPTOC2.Str.general
LD0.NSPTOC1.Op.general
LD0.NSPTOC1.Op.general
LD0.NSPTOC1.Str.general
IEC 61850 name
Table continues on next page
190.14
185.01
2961
3054
185.00
2960
190.13
184.15
2959
190.12
184.14
2958
3053
184.13
2957
3052
Reg.bit
Bit addr
1=Unsuccessful reclose
1=Successful reclose
1=In progress
1=In progress
1=In progress
1=In progress
1=In progress
1=In progress
1=Operate
1=Thermal alarm
1=Start
1=Start phsC
1=Start phsB
1=Start phsA
1=Start general
1=Stage2 operate
1=Stage2 start
1=Stage1 operate
Value range
Section 2
Modbus data mappings
1MRS757463 A
REF611
Point List Manual
REF611
Point List Manual
190.15
191.00
191.01
191.02
191.03
191.04
191.05
191.06
191.07
191.08
191.09
191.10
191.11
191.12
191.13
191.14
191.15
192.00
192.01
192.02
192.03
192.04
192.05
192.06
192.07
192.08
192.09
192.10
192.11
192.12
192.13
192.14
192.15
198.00
198.01
198.02
198.03
198.04
3055
3056
3057
3058
3059
3060
3061
3062
3063
3064
3065
3066
3067
3068
3069
3070
3071
3072
3073
3074
3075
3076
3077
3078
3079
3080
3081
3082
3083
3084
3085
3086
3087
3168
3169
3170
3171
3172
LD0.ROVPTOV2.Str.general
LD0.ROVPTOV1.Op.general
D0.ROVPTOV1.Op.general
LD0.ROVPTOV1.Str.general
LD0.ROVPTOV1.Str.general
LD0.DARREC1.WtMstr.stVal
LD0.DARREC1.WtMstr.stVal
LD0.DARREC1.UnsCBCls.stVal
LD0.DARREC1.UnsCBCls.stVal
LD0.DARREC1.OpOpn.general
LD0.DARREC1.OpOpn.general
LD0.DARREC1.Op.general
LD0.DARREC1.Op.general
LD0.DARREC1.CBManCls.stVal
LD0.DARREC1.CBManCls.stVal
LD0.DARREC1.ProCrd.stVal
LD0.DARREC1.ProCrd.stVal
LD0.DARREC1.RclTmStr.stVal
LD0.DARREC1.RclTmStr.stVal
LD0.DARREC1.FrqOpAlm.stVal
LD0.DARREC1.FrqOpAlm.stVal
LD0.DARREC1.PrgCutOut.stVal
LD0.DARREC1.PrgCutOut.stVal
LD0.DARREC1.PrgDsr.stVal
LD0.DARREC1.PrgDsr.stVal
LD0.DARREC1.ActRec.stVal
LD0.DARREC1.ActRec.stVal
LD0.DARREC1.RdyRec.stVal
LD0.DARREC1.RdyRec.stVal
LD0.DARREC1.LO.stVal
LD0.DARREC1.LO.stVal
LD0.DARREC1.InBlkThm.stVal
LD0.DARREC1.InBlkThm.stVal
LD0.DARREC1.InInhRec.stVal
LD0.DARREC1.InInhRec.stVal
LD0.DARREC1.UnsRec.stVal
IEC 61850 name
Table continues on next page
Reg.bit
Bit addr
Ds
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
(reserved)
(reserved)
Master signal to follower[.stVal] - MCD
Master signal to follower[.stVal] - mom
Unsuccessful CB closing status[.stVal] - MCD
Unsuccessful CB closing status[.stVal] - mom
Operate (open command to XCBR)[.general] - MCD
Operate (open command to XCBR)[.general] - mom
Operate (close command to XCBR)[.general] - MCD
Operate (close command to XCBR)[.general] - mom
CB manually closed[.stVal] - MCD
CB manually closed[.stVal] - mom
Protection coordination[.stVal] - MCD
Protection coordination[.stVal] - mom
Reclaim time started[.stVal] - MCD
Reclaim time started[.stVal] - mom
Frequent operation counter alarm[.stVal] - MCD
Frequent operation counter alarm[.stVal] - mom
Cutout time in progress[.stVal] - MCD
Cutout time in progress[.stVal] - mom
Discrimination time in progress[.stVal] - MCD
Discrimination time in progress[.stVal] - mom
Active reclose status[.stVal] - MCD
Active reclose status[.stVal] - mom
Ready reclose status[.stVal] - MCD
Ready reclose status[.stVal] - mom
Lockout status[.stVal] - MCD
Lockout status[.stVal] - mom
Thermal block (status)[.stVal] - MCD
Thermal block (status)[.stVal] - mom
Inhibit reclose (status)[.stVal] - MCD
Inhibit reclose (status)[.stVal] - mom
Unsuccessful reclose status[.stVal] - MCD
Description
ROVPTOV2.START
ROVPTOV1.OPERATE
ROVPTOV1.START
Y
Y
Y
Stage 2 Start[.general] - mom
Stage 1 Operate[.general] - MCD
Stage 1 Operate[.general] - mom
LD0.ROVPTOV1.Str.general
Stage 1 Start[.general] - mom
Residual overvoltage protection (3 stages)
DARREC1.CMD_WAIT
DARREC1.UNSUC_CB
DARREC1.OPEN_CB
DARREC1.CLOSE_CB
DARREC1.MAN_CB_CL
-
-
DARREC1.FRQ_OP_ALM
DARREC1.CUTOUT_INPRO
DARREC1.DISCR_INPRO
DAAREC1.ACTIVE
DARREC1.READY
DARREC1.LOCKED
-
-
AFL-Common SA name
1=Stage2 start
1=Stage1 operate
1=Stage1 start
0
0
1=Master signal to follower
1=Unsuccessful CB closing
1=Open command to CB
1=Close command to CB
1=CB manually closed
1=Protection coordination
1=Reclaim time started
1=Frequent operation alarm
1=Cutout time in progress
1=Discrimination time in
progress
1=Reclose active
1=Reclose ready
1=Lockout
1=Thermal block
1=Reclose inhibit
Value range
1MRS757463 A
Section 2
Modbus data mappings
25
26
198.10
198.11
199.00
199.01
199.02
199.03
199.04
199.05
199.06
199.07
199.08
199.09
199.10
199.11
199.12
199.13
199.14
199.15
200.00
200.01
200.02
200.03
200.04
200.05
200.06
200.07
200.08
200.09
3178
3179
3184
3185
3186
3187
3188
3189
3190
3191
3192
3193
3194
3195
3196
3197
3198
3199
3200
3201
3202
3203
3204
3205
3206
3207
3208
3209
LD0.XGGIO120.Ind4.stVal
LD0.XGGIO120.Ind4.stVal
LD0.XGGIO120.Ind3.stVal
LD0.XGGIO120.Ind3.stVal
LD0.XGGIO120.Ind2.stVal
LD0.XGGIO120.Ind2.stVal
LD0.XGGIO120.Ind1.stVal
LD0.XGGIO120.Ind1.stVal
199.11 LD0.XGGIO130.Ind6.stVal
LD0.XGGIO130.Ind6.stVal
LD0.XGGIO130.Ind5.stVal
LD0.XGGIO130.Ind5.stVal
LD0.XGGIO130.Ind4.stVal
199.06 LD0.XGGIO130.Ind4.stVal
LD0.XGGIO130.Ind3.stVal
LD0.XGGIO130.Ind3.stVal
LD0.XGGIO130.Ind2.stVal
LD0.XGGIO130.Ind2.stVal
LD0.XGGIO130.Ind1.stVal
199.00 LD0.XGGIO130.Ind1.stVal
LD0.ROVPTOV3.Op.general
LD0.ROVPTOV3.Op.general
LD0.ROVPTOV3.Str.general
LD0.ROVPTOV3.Str.general
LD0.ROVPTOV2.Op.general
LD0.ROVPTOV2.Op.general
LD0.ROVPTOV2.Str.general
IEC 61850 name
Table continues on next page
200.12
198.09
3177
3212
198.08
3176
200.11
198.07
3175
3211
198.06
3174
200.10
198.05
3173
3210
Reg.bit
Bit addr
-
-
-
-
-
-
-
-
-
-
Y
Y
Y
Stage 3 Operate[.general] - MCD
Stage 3 Operate[.general] - mom
Stage 3 Start[.general] - MCD
Stage 3 Start[.general] - mom
Stage 2 Operate[.general] - MCD
Stage 2 Operate[.general] - mom
Stage 2 Start[.general] - MCD
Description
Physical I/O signals
Ds
(reserved)
(reserved)
(reserved)
(reserved)
X130-Input 6[.stVal] - MCD
X130-Input 6[.stVal] - mom
X130-Input 5[.stVal] - MCD
X130-Input 5[.stVal] - mom
X130-Input 4[.stVal] - MCD
X130-Input 4[.stVal] - mom
X130-Input 3[.stVal] - MCD
X130-Input 3[.stVal] - mom
X130-Input 2[.stVal] - MCD
X130-Input 2[.stVal] - mom
X130-Input 1[.stVal] - MCD
X130-Input 1[.stVal] - mom
Y
Y
Y
Y
(reserved)
(reserved)
(reserved)
(reserved)
(reserved)
X120-Input 4[.stVal] - MCD
X120-Input 4[.stVal] - mom
X120-Input 3[.stVal] - MCD
X120-Input 3[.stVal] - mom
X120-Input 2[.stVal] - MCD
X120-Input 2[.stVal] - mom
X120-Input 1[.stVal] - MCD
X120-Input 1[.stVal] - mom
Physical I/O signal states (AIM-card X120)
Y
Y
Y
Y
Y
Y
Physical I/O signal states (BIO-card X130)
ROVPTOV3.OPERATE
ROVPTOV3.START
ROVPTOV2.OPERATE
AFL-Common SA name
0
0
0
0
0
1=ON, 0=OFF
1=ON, 0=OFF
1=ON, 0=OFF
1=ON, 0=OFF
0
0
0
0
1=ON, 0=OFF
1=ON, 0=OFF
1=ON, 0=OFF
1=ON, 0=OFF
1=ON, 0=OFF
1=ON, 0=OFF
1=Stage3 operate
1=Stage3 start
1=Stage2 operate
Value range
Section 2
Modbus data mappings
1MRS757463 A
REF611
Point List Manual
Reg.bit
200.13
200.14
200.15
203.00
203.01
203.02
203.03
203.04
203.05
203.06
203.07
203.08
203.09
203.10
203.11
Bit addr
3213
3214
3215
3248
3249
REF611
Point List Manual
3250
3251
3252
3253
3254
3255
3256
3257
3258
3259
LD0.XGGIO100.SPCSO6.stVal
LD0.XGGIO100.SPCSO6.stVal
LD0.XGGIO100.SPCSO5.stVal
LD0.XGGIO100.SPCSO5.stVal
LD0.XGGIO100.SPCSO4.stVal
LD0.XGGIO100.SPCSO4.stVal
LD0.XGGIO100.SPCSO3.stVal
LD0.XGGIO100.SPCSO3.stVal
LD0.XGGIO100.SPCSO2.stVal
LD0.XGGIO100.SPCSO2.stVal
LD0.XGGIO100.SPCSO1.stVal
LD0.XGGIO100.SPCSO1.stVal
IEC 61850 name
-
-
-
-
-
-
Ds
(reserved)
(reserved)
(reserved)
Description
Y
Y
Y
Y
Y
Y
X100-Output 6[.stVal] - MCD
X100-Output 6[.stVal] - mom
X100-Output 5[.stVal] - MCD
X100-Output 5[.stVal] - mom
X100-Output 4[.stVal] - MCD
X100-Output 4[.stVal] - mom
X100-Output 3[.stVal] - MCD
X100-Output 3[.stVal] - mom
X100-Output 2[.stVal] - MCD
X100-Output 2[.stVal] - mom
X100-Output 1[.stVal] - MCD
X100-Output 1[.stVal] - mom
Physical I/O signal states (PSM-card X100)
AFL-Common SA name
1=ON, 0=OFF
1=ON, 0=OFF
1=ON, 0=OFF
1=ON, 0=OFF
1=ON, 0=OFF
1=ON, 0=OFF
0
0
0
Value range
1MRS757463 A
Section 2
Modbus data mappings
27
28
Uns
LD0.LPHD1.RsDev.ctlVal
Physical device - Reset device - 1=Activate
0
CMMXU1 - CMMXU1 max.demands - 1=Reset
Disturbance recorder - Disturbance records - 1=Activate
(reserved)
3
LD0.CMSTA1.RecRs.ctlVal
Disturbance recorder - Trig recording - 1=Activate
2080
Uns
DR.RDRE1.MemClr.ctlVal
Reset input for CB remaining life and operation counter - 1=Activate
(reserved)
9
Uns
DR.RDRE1.RcdTrg.ctlVal
Reset accumulation energy - 1=Activate
2079
2
2069
8
Uns
LD0.SSCBR1.RsCBWear.ctlVal
Reset reclosing counters - 1=Activate
(reserved)
2
2068
7
Uns
LD0.SSCBR1.RsAccAPwr.ctlVal
Reset reclosing - 1=Activate
2078
2
2067
6
Uns
LD0.DARREC1.RsCnt.ctlVal
General - All data - 1=Activate
(reserved)
2
2066
5
Uns
LD0.DARREC1.RsRec.ctlVal
General - Alarm LEDs - 1=Activate
2077
2
2065
4
Uns
LD0.LLN0.RecRs.ctlVal
General - Indications and LEDs - 1=Activate
(reserved)
2
2064
3
Uns
LD0.LLN0.LEDRs2.ctlVal
LD0.LLN0.LEDRs1.ctlVal
2076
2
2063
2
Uns
Uns
CBXCBR1 - Switch, general - Direct close
CBXCBR1 - Switch, general - Direct open
(reserved)
2
2062
1
0
CTRL.CBCSWI1.Pos.ctlVal
Description
2075
2
Uns
CTRL.CBCSWI1.Pos.ctlVal
Identification
(reserved)
2
2060
2061
5
Uns
Mode
2074
1
2053
4
Ctrl bit
2073
1
Ctrl struct
Controls
2052
0x addr
Table 4:
Section 2
Modbus data mappings
1MRS757463 A
REF611
Point List Manual
Section 3
Glossary
1MRS757463 A
Section 3
Glossary
AFL
Application function block library
AR
Autoreclosing
BIO
Binary input and output
CB
Circuit breaker
CPM
Communication protocol manual
DR
Disturbance recorder
EMC
Electromagnetic compatibility
HMI
Human-machine interface
I/O
Input/output
IEC
International Electrotechnical Commission
IEC 61850 International standard for substation communication and
modeling
REF611
Point List Manual
IED
Intelligent electronic device
LED
Light-emitting diode
LHMI
Local human-machine interface
MCD
Momentary change detect
Modbus
A serial communication protocol developed by the Modicon
company in 1979. Originally used for communication in PLCs
and RTU devices.
PCM600
Protection and Control IED Manager
PLC
Programmable logic controller
PSM
Power supply module
TCS
Trip-circuit supervision
UTC
Coordinated universal time
29
30
31
ABB Oy
Distribution Automation
P.O. Box 699
FI-65101 VAASA, Finland
Phone
+358 10 22 11
Fax
+358 10 22 41094
www.abb.com/substationautomation
1MRS757463 A © Copyright 2011 ABB. All rights reserved.
Contact us