Download Feeder Protection and Control REF611 Modbus Point List Manual
Transcript
Relion® 611 series Feeder Protection and Control REF611 Modbus Point List Manual Document ID: 1MRS757463 Issued: 2011-11-18 Revision: A Product version: 1.0 © Copyright 2011 ABB. All rights reserved Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license. Trademarks ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders. Warranty Please inquire about the terms of warranty from your nearest ABB representative. http://www.abb.com/substationautomation Disclaimer The data, examples and diagrams in this manual are included solely for the concept or product description and are not to be deemed as a statement of guaranteed properties. All persons responsible for applying the equipment addressed in this manual must satisfy themselves that each intended application is suitable and acceptable, including that any applicable safety or other operational requirements are complied with. In particular, any risks in applications where a system failure and/ or product failure would create a risk for harm to property or persons (including but not limited to personal injuries or death) shall be the sole responsibility of the person or entity applying the equipment, and those so responsible are hereby requested to ensure that all measures are taken to exclude or mitigate such risks. This document has been carefully checked by ABB but deviations cannot be completely ruled out. In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment. Conformity This product complies with the directive of the Council of the European Communities on the approximation of the laws of the Member States relating to electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive. The product is designed in accordance with the international standards of the IEC 60255 series. Table of contents Table of contents Section 1 Introduction.......................................................................3 This manual........................................................................................3 Intended audience..............................................................................3 Product documentation.......................................................................4 Product documentation set............................................................4 Document revision history.............................................................5 Related documentation..................................................................6 Symbols and conventions...................................................................6 Symbols.........................................................................................6 Document conventions..................................................................6 Functions, codes and symbols......................................................7 Section 2 Modbus data mappings....................................................9 Overview.............................................................................................9 Point list for REF611 Ver. 1.0...........................................................10 Section 3 REF611 Point List Manual Glossary.........................................................................29 1 2 Section 1 Introduction 1MRS757463 A Section 1 Introduction 1.1 This manual The point list manual describes the outlook and properties of the data points specific to the IED. The manual should be used in conjunction with the corresponding communication protocol manual. 1.2 Intended audience This manual addresses the communication system engineer or system integrator responsible for pre-engineering and engineering for communication setup in a substation from an IED perspective. The system engineer or system integrator must have a basic knowledge of communication in protection and control systems and thorough knowledge of the specific communication protocol. REF611 Point List Manual 3 Section 1 Introduction Decommissioning deinstalling & disposal Maintenance Operation Product documentation set Commissioning 1.3.1 Engineering Product documentation Planning & purchase 1.3 Installing 1MRS757463 A Engineering manual Installation manual Commissioning manual Operation manual Service manual Application manual Technical manual Communication protocol manual en07000220.vsd IEC07000220 V1 EN Figure 1: The intended use of manuals in different lifecycles The engineering manual contains instructions on how to engineer the IEDs using the different tools in PCM600. The manual provides instructions on how to set up a PCM600 project and insert IEDs to the project structure. The manual also recommends a sequence for engineering of protection and control functions, LHMI functions as well as communication engineering for IEC 61850 and other supported protocols. The installation manual contains instructions on how to install the IED. The manual provides procedures for mechanical and electrical installation. The chapters are organized in chronological order in which the IED should be installed. The commissioning manual contains instructions on how to commission the IED. The manual can also be used by system engineers and maintenance personnel for assistance during the testing phase. The manual provides procedures for checking of external circuitry and energizing the IED, parameter setting and configuration as 4 REF611 Point List Manual Section 1 Introduction 1MRS757463 A well as verifying settings by secondary injection. The manual describes the process of testing an IED in a substation which is not in service. The chapters are organized in chronological order in which the IED should be commissioned. The operation manual contains instructions on how to operate the IED once it has been commissioned. The manual provides instructions for monitoring, controlling and setting the IED. The manual also describes how to identify disturbances and how to view calculated and measured power grid data to determine the cause of a fault. The service manual contains instructions on how to service and maintain the IED. The manual also provides procedures for de-energizing, de-commissioning and disposal of the IED. The application manual contains application descriptions and setting guidelines sorted per function. The manual can be used to find out when and for what purpose a typical protection function can be used. The manual can also be used when calculating settings. The technical manual contains application and functionality descriptions and lists function blocks, logic diagrams, input and output signals, setting parameters and technical data sorted per function. The manual can be used as a technical reference during the engineering phase, installation and commissioning phase, and during normal service. The communication protocol manual describes a communication protocol supported by the IED. The manual concentrates on vendor-specific implementations. The point list manual describes the outlook and properties of the data points specific to the IED. The manual should be used in conjunction with the corresponding communication protocol manual. Some of the manuals are not available yet. 1.3.2 Document revision history Document revision/date A/2011-11-18 Product series version 1.0 History First release Download the latest documents from the ABB Web site http://www.abb.com/substationautomation. REF611 Point List Manual 5 Section 1 Introduction 1.3.3 1MRS757463 A Related documentation Name of the document Modbus Communication Protocol Manual 1.4 Symbols and conventions 1.4.1 Symbols Document ID 1MRS757461 The caution icon indicates important information or warning related to the concept discussed in the text. It might indicate the presence of a hazard which could result in corruption of software or damage to equipment or property. The information icon alerts the reader of important facts and conditions. The tip icon indicates advice on, for example, how to design your project or how to use a certain function. Although warning hazards are related to personal injury, it is necessary to understand that under certain operational conditions, operation of damaged equipment may result in degraded process performance leading to personal injury or death. Therefore, comply fully with all warning and caution notices. 1.4.2 Document conventions A particular convention may not be used in this manual. • • • • • • 6 Abbreviations and acronyms in this manual are spelled out in the glossary. The glossary also contains definitions of important terms. Push-button navigation in the LHMI menu structure is presented by using the push-button icons. To navigate between the options, use and . HMI menu paths are presented in bold. Select Main menu/Settings. LHMI messages are shown in Courier font. . To save the changes in non-volatile memory, select Yes and press Parameter names are shown in italics. The function can be enabled and disabled with the Operation setting. Parameter values are indicated with quotation marks. REF611 Point List Manual Section 1 Introduction 1MRS757463 A • 1.4.3 The corresponding parameter values are "On" and "Off". IED input/output messages and monitored data names are shown in Courier font. When the function starts, the START output is set to TRUE. Functions, codes and symbols Table 1: REF611 functions, codes and symbols Function IEC 61850 IEC 60617 IEC-ANSI Protection Three-phase non-directional overcurrent protection, low stage, instance 1 PHLPTOC1 3I> (1) 51P-1 (1) Three-phase non-directional overcurrent protection, high stage, instance 1 PHHPTOC1 3I>> (1) 51P-2 (1) Three-phase non-directional overcurrent protection, high stage, instance 2 PHHPTOC2 3I>> (2) 51P-2 (2) Three-phase non-directional overcurrent protection, instantaneous stage, instance 1 PHIPTOC1 3I>>> (1) 50P/51P (1) Non-directional earth-fault protection, low stage, instance 1 EFLPTOC1 Io> (1) 51N-1 (1) Non-directional earth-fault protection, low stage, instance 2 EFLPTOC2 Io> (2) 51N-1 (2) Non-directional earth-fault protection, high stage, instance 1 EFHPTOC1 Io>> (1) 51N-2 (1) Non-directional earth-fault protection, instantaneous stage EFIPTOC1 Io>>> 50N/51N Directional earth-fault protection, low stage, instance 1 DEFLPDEF1 Io> -> (1) 67N-1 (1) Directional earth-fault protection, low stage, instance 2 DEFLPDEF2 Io> -> (2) 67N-1 (2) Directional earth-fault protection, high stage DEFHPDEF1 Io>> -> 67N-2 Transient / intermittent earth-fault protection INTRPTEF1 Io> -> IEF 67NIEF Non-directional (cross-country) earthfault protection, using calculated Io EFHPTOC1 Io>> (1) 51N-2 (1) Negative-sequence overcurrent protection, instance 1 NSPTOC1 I2> (1) 46 (1) Negative-sequence overcurrent protection, instance 2 NSPTOC2 I2> (2) 46 (2) Phase discontinuity protection PDNSPTOC1 I2/I1> 46PD Residual overvoltage protection, instance 1 ROVPTOV1 Uo> (1) 59G (1) Residual overvoltage protection, instance 2 ROVPTOV2 Uo> (2) 59G (2) Table continues on next page REF611 Point List Manual 7 Section 1 Introduction 1MRS757463 A Function IEC 61850 IEC 60617 IEC-ANSI Residual overvoltage protection, instance 3 ROVPTOV3 Uo> (3) 59G (3) Three-phase thermal protection for feeders, cables and distribution transformers T1PTTR1 3Ith>F 49F Circuit breaker failure protection CCBRBRF1 3I>/Io>BF 51BF/51NBF Three-phase inrush detector INRPHAR1 3I2f> 68 Master trip, instance 1 TRPPTRC1 Master Trip (1) 94/86 (1) Master trip, instance 2 TRPPTRC2 Master Trip (2) 94/86 (2) Input switch group1) ISWGAPC ISWGAPC ISWGAPC Output switch group2) OSWGAPC OSWGAPC OSWGAPC Selector switch group3) SELGAPC SELGAPC SELGAPC TPGAPC TP TP Circuit-breaker control CBXCBR1 I <-> O CB I <-> O CB Auto-reclosing DARREC1 O -> I 79 Trip circuit supervision, instance 1 TCSSCBR1 TCS (1) TCM (1) Trip circuit supervision, instance 2 TCSSCBR2 TCS (2) TCM (2) Disturbance recorder RDRE1 - - Three-phase current measurement, instance 1 CMMXU1 3I 3I Sequence current measurement CSMSQI1 I1, I2, I0 I1, I2, I0 Residual current measurement, instance 1 RESCMMXU1 Io In Residual voltage measurement RESVMMXU1 Uo Vn Switch groups Configurable timer Minimum pulse timer (2 pcs)4) Control Supervision Measurement 1) 2) 3) 4) 8 10 instances 20 instances 6 instances 10 instances REF611 Point List Manual Section 2 Modbus data mappings 1MRS757463 A Section 2 Modbus data mappings 2.1 Overview This document describes the Modbus data points and structures available in REF611 Ver. 1.0. The point lists describe a superset of all data available through the standard configurations A and B including the optional functionalities. The names of the standard configurations are FE101 and FE102 respectively. The majority of the Modbus data points are valid for all standard configurations. Some data points are standard configuration or optional application dependent and thus not available in each IED. The unavailable, that means unused, data points always return value 0 when they are read. The configuration dependent and optional data do not overlap. Point list table columns REF611 Point List Manual 0x addr Coil (0X) PLC address, base address = 1 Addr. Signal address AFL-Common SA name AFL name of the corresponding data signal Bit addr Bit (1X and 0X) PLC address, base address = 1 Ctrl bit Control bit (0..15) within control structure Ctrl struct Control structure number Description Signal description Ds Object resides as default in some IEC 61850 data set (Y = yes, N = no) Identification IED's internal IEC 61850 signal name IEC 61850 name IEC 61850 signal description Mode Control object mode: unsecured or secured Reg addr Modbus register address (3X or 4X). PLC address, base address = 1 Reg.bit Register PLC address (3X and 4X) and bit within register (0..15) Scale Scale factor, default setting Type Register type and value interpretation: signed or unsigned Value range Value range of the signal 9 Section 2 Modbus data mappings 2.2 10 1MRS757463 A Point list for REF611 Ver. 1.0 REF611 Point List Manual REF611 Point List Manual u16 u16 u16 u16 u16 u16 u16 u16 u16 i16 i16 i16 i16 i16 137 138 139 140 141 142 143 144 145 146 147 148 149 150 0.001 0.001 1 1 1 1000 1000 1000 1000 1000 1000 1000 1000 1 1 LD0.T1PTTR1.TmmsRecEna.stVal LD0.T1PTTR1.TmmsOp.stVal LD0.T1PTTR1.TmpUsed.mag LD0.T1PTTR1.TmpRl.mag LD0.T1PTTR1.Tmp.mag LD0.CSMSQI1.SeqA.c3.instCVal.mag LD0.CSMSQI1.SeqA.c2.instCVal.mag LD0.CSMSQI1.SeqA.c1.instCVal.mag LD0.RESVMMXU1.PhV.res.instCVal.mag LD0.RESCMMXU1.A.res.instCVal.mag LD0.CMMXU1.A.phsC.instCVal.mag LD0.CMMXU1.A.phsB.instCVal.mag LD0.CMMXU1.A.phsA.instCVal.mag LD0.DARREC1.OpCntRs.stVal LD0.DARREC1.ShotPntr.stVal Table continues on next page 151 i16 u16 T1PTTR1.THERMLEV_E ND T1PTTR1.THERMLEV_S T T1PTTR1.TEMP_AMB T1PTTR1.TEMP_RL T1PTTR1.TEMP CMSQI1.I3_INST CMSQI1.I2_INST CMSQI1.I1_INST RESCMMXU1.U0_INST RESCMMXU1.I0_INST CMMXU1.I_INST_C CMMXU1.I_INST_B CMMXU1.I_INST_A DARREC1.COUNTER DARREC1.SHOT_PTR DARREC1.STATUS (reserved) Estimated time to deactivate BLK_CLOSE[.stVal] - Estimated time to operate[.stVal] - Ambient temperature used in calculations [.mag] - Relative temperature [.mag] - Protected object temperature [.mag] - Zero sequence current amplitude [.c3.instCVal.mag] - Negative sequence current amplitude [.c2.instCVal.mag] - Positive sequence current amplitude [.c1.instCVal.mag] - Residual voltage amplitude [.res.instCVal.mag] - Residual current amplitude [.res.instCVal.mag] - Phase current C amplitude [.phsC.instCVal.mag] - Phase current B amplitude [.phsB.instCVal.mag] - Phase current A amplitude [.phsA.instCVal.mag] - AR resettable operation counter (all shots) [.stVal] - AR shot pointer value[.stVal] - Autoreclosing status[.stVal] - (reserved) 134 136 System status register 6 133 135 System status register 5 132 Frequently updated registers System status register 4 131 Description System status register 3 Ds 130 System status registers User definable registers AFL-Common SA name System status register 2 LD0.DARREC1.AutoRecSt.stVal IEC 61850 name System status register 1 1 Scale 129 Type Registers 128 127 … 1 Reg addr Table 2: 0 0…600000 [ms] 0…600000 [ms] -99…999.99 [Celsius] 0.00…99.99 [Celcius] -100.0…9999.9 [Celsius] 0…40.00 [xIn] 0…40.00 [xIn] 0…40.00 [xIn] 0…4.00 [xUn] 0…40.00 [xIn] 0…40.00 [xIn] 0…40.00 [xIn] 0…40.00 [xIn] 0...2147483647 0…6 -2…4 (see documentation) 0 See Modbus CPM See Modbus CPM See Modbus CPM See Modbus CPM See Modbus CPM See Modbus CPM Value range 1MRS757463 A Section 2 Modbus data mappings 11 12 u16 2003 Update time of phase A max value -reg 3 2018 Table continues on next page Update time of phase A max value -reg 2 2017 Update time of phase A max value -reg 1 Maximum demand value for phase B[.mag] - Time structure Update time of phase A max value -reg 5 2015 2016 Update time of phase A max value -reg 4 Update time of phase A max value -reg 1 Maximum demand value for phase A[.mag] - Demand value of phase C current[.mag] - Demand value of phase B current[.mag] - Demand value of phase A current[.mag] - 2014 CMMXU1.Max demand IL2 CMMXU1.Max demand IL1 Maximum phase current demand values CMMXU1.I_DMD_C CMMXU1.I_DMD_B CMMXU1.I_DMD_A Update time of phase A max value -reg 3 LD0.CMSTA1.MaxAmpsB.mag Max. demand value for residual current 2013 1000 N Phase current demand values (latest values) RESCMMXU.Max demand Io N Update time of phase A max value -reg 2 Time structure LD0.CMSTA1.MaxAmpsA.mag LD0.CMSTA1.AvAmpsC.mag LD0.CMSTA1.AvAmpsB.mag LD0.CMSTA1.AvAmpsA.mag LD0.RESCMSTA1.AvAmps.mag RESCMSTA.I_DMD_RES Description 2012 u16 1000 1000 1000 1000 1000 LD0.RESCMSTA1.AvAmps.mag Ds 2011 2010 2009 2008 2007 2006 2005 u16 u16 2002 2004 u16 u16 2001 2000 1999 1998 1997 1996 1995 1994 1993 1992 1991 1000 AFL-Common SA name Demand value of residual current 1990 ... u16 IEC 61850 name 1989 Scale Indication bits mirrored and packed in registers 170 onwards Type 170 Reg addr Time structure (see Modbus CPM) 0…40.00 [xIn] Time structure (see Modbus CPM) 0…40.00 [xIn] Time structure (see Modbus CPM) 0…40.00 [xIn] 0…40.00 [xIn] 0…40.00 [xIn] Time structure (see Modbus CPM) 0.00 …. 40.00 [xIn] Time structure (see Modbus CPM) 0.00 …. 40.00 [xIn] See 'Indications' table Value range Section 2 Modbus data mappings 1MRS757463 A REF611 Point List Manual REF611 Point List Manual 1 u16 u16 2035 2036 u16 u16 u16 u16 u16 u16 u16 2052 2053 2054 2055 2056 2057 1 1 1 1 1 1 1 1 1 1 1 LD0.LPHD1.NumCmpChg.stVal LD0.LPHD1.WacTrg.stVal LD0.LPHD1.WrmStr.stVal LD0.LPHD1.NumPwrUp.stVal DR.RDRE1.MemUsed.stVal DR.RDRE1.FltNum.stVal LD0.LPHD1.PhyHealth2.stVal LD0.LPHD1.PhyHealth1.stVal LD0.DARREC1.FrqOpCnt.stVal LD0.DARREC1.OpCnt5.stVal LD0.DARREC1.OpCnt4.stVal LD0.DARREC1.OpCnt3.stVal Table continues on next page 2058 u16 2050 2051 2047 ... 2037 u16 2034 1 Internal Fault Warning Diagnostics DARREC1.FRQ_OPR_CN T DARREC1.CNT_SHOT5 DARREC1.CNT_SHOT4 DARREC1.CNT_SHOT3 (reserved) Number of composition changes Physical device - Number of watchdog device resets detected[.stVal] - Physical device - Number of Warm starts[.stVal] - Physical device - Number of Power ups[.stVal] - Disturbance recorder - Rec. memory used[.stVal] - Disturbance recorder - Number of recordings[.stVal] - Physical device - Internal Fault[.stVal] - Physical device - Warning[.stVal] - (reserved) (reserved) Autorecloser frequent operation counter[.stVal] - Autorecloser operation counter (5th shot) [.stVal] - Autorecloser operation counter (4th shot) [.stVal] - Autorecloser operation counter (3rd shot) [.stVal] - Autorecloser operation counter (2nd shot) [.stVal] - u16 DARREC1.CNT_SHOT2 2033 LD0.DARREC1.OpCnt2.stVal u16 2032 1 Auto recloser operation counter (1st shot) [.stVal] - DARREC1.CNT_SHOT1 u16 2031 LD0.DARREC1.OpCnt1.stVal (reserved) 2030 1 (reserved) 2029 Circuit breaker operation counter[.stVal] (reserved) CBXCBR1.Operation counter 2028 CTRL.CBCSWI1.OpCntRs.stVal Update time of phase A max value -reg 5 u16 Update time of phase A max value -reg 4 2026 2027 Update time of phase A max value -reg 3 2025 Counters - Circuit breaker, autorecloser Update time of phase A max value -reg 2 Update time of phase A max value -reg 1 2024 - CMMXU1.Max demand IL3 2023 Time structure LD0.CMSTA1.MaxAmpsC.mag Description Maximum demand value for phase C[.mag] - 2022 1000 Ds Update time of phase A max value -reg 5 u16 AFL-Common SA name 2021 IEC 61850 name Update time of phase A max value -reg 4 Scale 2020 Type 2019 Reg addr 0 0…65535 0…65535 0…65535 0…65535 0…100 [%] 0…N See documentation See documentation 0 0 0…65535 0…65535 0…65335 0…65535 0…65535 0…65535 0 0 0 0…65535 Time structure (see Modbus CPM) 0…40.00 [xIn] Value range 1MRS757463 A Section 2 Modbus data mappings 13 14 u16 u16 u16 u16 u16 u16 u16 u16 u16 u16 u16 u16 u16 u16 u16 u16 u16 u16 u16 u16 u16 u16 u16 u16 8002 8003 8004 8005 8006 8007 8008 8009 8010 8011 8012 8013 8014 8015 8016 8017 8018 8019 8020 8021 8022 8023 8024 8025 For information on control structure 5 bit definitions, see Modbus controls table. For information on control structure 4 bit definitions, see Modbus controls table. For information on control structure 3 bit definitions, see Modbus controls table. For information on control structure 2 bit definitions, see Modbus controls table. For information on control structure 1 bit definitions, see Modbus controls table. Table continues on next page 8026 u16 8001 8000 ... Control structure 5 Control structure 4 Control structure 3 Control structure 2 Control structure 1 AFL-Common SA name Ds Description (reserved) Control Struct 5 - Confirm register Control Struct 5 - Control register Control Struct 5 - Password 2 Control Struct 5 - Password 1 Control Struct 5 - Execute register Control Struct 4 - Confirm register Control Struct 4 - Control register Control Struct 4 - Password 2 Control Struct 4 - Password 1 Control Struct 4 - Execute register Control Struct 3 - Confirm register Control Struct 3 - Control register Control Struct 3 - Password 2 Control Struct 3 - Password 1 Control Struct 3 - Execute register Control Struct 2 - Confirm register Control Struct 2 - Control register Control Struct 2 - Password 2 Control Struct 2 - Password 1 Control Struct 2 - Execute register Control Struct 1 - Confirm register Control Struct 1 - Control register Control Struct 1 - Password 2 Control Struct 1 - Password 1 Control Struct 1 - Execute register (reserved) (reserved) IEC 61850 name (reserved) Scale 2070 Type 2059 Reg addr 0 Control structure (see Modbus CPM) Control structure (see Modbus CPM) Control structure (see Modbus CPM) Control structure (see Modbus CPM) Control structure (see Modbus CPM) 0 0 0 Value range Section 2 Modbus data mappings 1MRS757463 A REF611 Point List Manual Ds REF611 Point List Manual (reserved) Description u16 u16 u16 u16 9205 9206 9207 9208 Device real-time clock in UTC time Real-time struct - Milliseconds (0..999) Real-time struct - Seconds (0..59) Real-time struct - Minute (0..59) Real-time struct - Hour (0..23) Real-time struct - Day (1..31) Real-time struct - Month (1..12) u16 u16 u16 u16 9215 9216 9217 9218 Timestamp of last device reset Real-time struct UTC - Milliseconds (0..999) Real-time struct UTC - Seconds (0..59) Real-time struct UTC - Minute (0..59) Real-time struct UTC - Hour (0..23) Real-time struct UTC - Day (1..31) Real-time struct UTC - Month (1..12) u16 u16 u16 u16 u16 u16 u16 9223 9224 9225 9226 9227 9228 Table continues on next page u16 9221 9222 Reset time struct - Reason Reset time struct - Milliseconds (0..999) Reset time struct - Seconds (0..59) Reset time struct - Minute (0..59) Reset time struct - Hour (0..23) Reset time struct - Day (1..31) Reset time struct - Month (1..12) Reset time struct - Year (2000..2999) (reserved) u16 9214 Real-time struct UTC - Year (2000..2999) (reserved) u16 9213 Real-time struct UTC - Control register (0..2) 9220 u16 9219 u16 9211 9212 (reserved) u16 9204 Real-time struct - Year (2000..2999) (reserved) u16 9203 Real-time struct - Control register (0..2) 9210 u16 (reserved) 9209 u16 9201 9202 9128 ... Device real-time clock in local time Device ID string AFL-Common SA name (reserved) IEC 61850 name 9002 Scale Max length of device ID string may be 128 registers Type 9001 9000 ... Reg addr 1 = Cold reset 0 0 0 0 0 0 Device ID string (see Modbus CPM) 0 Value range 1MRS757463 A Section 2 Modbus data mappings 15 16 9231 u16 9261 9262 0 0 0 Event record 7 (11 registers) Table continues on next page 9318 ... 9328 Event record 6 (11 registers) u16 9260 0 9307 ... 9317 u16 9259 0 Event record 5 (11 registers) u16 9258 0 9296 ... 9306 u16 9257 0 Event record 4 (11 registers) u16 9256 0 9285 ... 9295 u16 9255 0 0 Event record 3 (11 registers) u16 9254 Event record 1 (11 registers) 9274 ... 9284 u16 9253 0 0 Event read selection Event record 2 (11 registers) u16 9252 0 9263 ... 9273 i16 u16 9251 u16 9250 9249 ... 9232 u16 Ds Event record structure Active parameter setting group AFL-Common SA name Description Event record structure Event record structure Event record structure Event record structure Event record structure Event record structure Event record struct - Data value Event record struct - Data value Event record struct - Data object ID 2 Event record struct - Data object ID 1 Event record struct - Event identification Event record struct - TimeStamp (Milliseconds) Event record struct - TimeStamp (Min, Sec) Event record struct - TimeStamp (Day, Hour) Event record struct - TimeStamp (Year,Month) Event record struct - Unread records left Event record struct - Sequence number Event read operation selection Number of events records in multiple event reading (reserved) (reserved) Setting group in use (reserved) IEC 61850 name (reserved) Scale 9230 Type 9229 Reg addr Event record structure (see Modbus CPM) Event record structure (see Modbus CPM) Event record structure (see Modbus CPM) Event record structure (see Modbus CPM) Event record structure (see Modbus CPM) Event record structure (see Modbus CPM) Event record structure (see Modbus CPM) -499…3 1…10 0 0 1...6 0 0 2 = Watchdog reset 4 = Warm reset Value range Section 2 Modbus data mappings 1MRS757463 A REF611 Point List Manual REF611 Point List Manual LD0.FLTMSTA1.MaxAmpsN.mag Table continues on next page 1000 Y Y Max residual current during fault Max phase C current during fault Max phase B current during fault u16 LD0.FLTMSTA1.MaxAmpsC.mag Y 9425 1000 LD0.FLTMSTA1.MaxAmpsB.mag u16 1000 9424 Active setting group u16 Y Y Operate time Operate time 9423 LD0.FLTMSTA1.MaxAmpsA.mag LD0.FLTMSTA1.ActSG.stVal Y Y Max phase A current during fault 1000 1 LD0.FLTMSTA1.OpTm.mag LD0.FLTMSTA1.OpTm.mag Maximum start duration of all stages during the fault u16 u16 9415 1000 1000 Y 9422 u32 9414 LD0.FLTMSTA1.StrDur.mag Protection function FLTMSTA fault record number FLTMSTA fault record number (reserved) u32 9413 100 LD0.FLTMSTA1.ProFcn.stVal Y Y 9421 u16 9412 1 LD0.FLTMSTA1.OpCnt.stVal LD0.FLTMSTA1.OpCnt.stVal (reserved) i16 9411 1 1 Fault record struct - TimeStamp (Time quality) 9420 u32 Fault record data Fault record struct - TimeStamp (Milliseconds) (reserved) u32 9409 9410 0 Fault record struct - TimeStamp (Min, Sec) 9419 u16 9408 0 Fault record struct - TimeStamp (Day, Hour) (reserved) u16 9407 0 Fault record struct - TimeStamp (Year,Month) 9418 u16 9406 0 0 (reserved) u16 9405 Fault record struct - Unread records left Fault record struct - Sequence number Fault record read operation selection (reserved) (reserved) Event record structure Event record structure Event record structure Description 9417 u16 9404 0 Fault record read selection Ds (reserved) u16 9403 0 Fault record structure AFL-Common SA name 9416 i16 u16 9401 9402 9400 ... 0 Event record 10 (11 registers) 9351 ... 9361 9362 Event record 9 (11 registers) IEC 61850 name 9340 ... 9350 Scale Event record 8 (11 registers) Type 9329 ... 9339 Reg addr 0.00 …. 50.00 [xIn] 0.00 …. 50.00 [xIn] 0.00 …. 50.00 [xIn] 0.00 …. 50.00 [xIn] 0 0 0 0 0 0 1…6 0.000...999999.999 [s] 0.000...999999.999 [s] 0.00 …100.00 [%] -32768…32767 (see documentation) 0…999999 0…999999 Header -99…3 0 0 Event record structure (see Modbus CPM) Event record structure (see Modbus CPM) Event record structure (see Modbus CPM) Value range 1MRS757463 A Section 2 Modbus data mappings 17 Type u16 u16 u16 u16 u16 u16 u16 u16 u16 u16 i16 i16 Reg addr 9426 9427 18 9428 9429 9430 9431 9432 9433 9434 9435 9436 9437 10 10 100 100 1000 1000 1000 1000 1000 1000 1000 1000 Scale LD0.FLTMSTA1.DifCAngAB.mag LD0.FLTMSTA1.DifNAngN.mag LD0.FLTMSTA1.PDNS1MxRat.mag LD0.FLTMSTA1.MaxTmpRl.mag LD0.FLTMSTA1.VoltsN.mag LD0.FLTMSTA1.AmpsNgSeq.mag LD0.FLTMSTA1.AmpsPsSeq.mag LD0.FLTMSTA1.AmpsNClc.mag LD0.FLTMSTA1.AmpsN.mag LD0.FLTMSTA1.AmpsC.mag LD0.FLTMSTA1.AmpsB.mag LD0.FLTMSTA1.AmpsA.mag IEC 61850 name AFL-Common SA name Y Y Y Y Y Y Y Y Y Y Y Y Ds Angle phase A to phase B voltage - phase C current Angle residual voltage - residual current PDNSPTOC1 ratio I2/I1 Max relative temperature Residual voltage at moment of trip Negative sequence current at moment of trip Positive sequence current at moment of trip Residual Clc current at moment of trip Residual current at moment of trip Phase C current at moment of trip Phase B current at moment of trip Phase A current at moment of trip Description -180.00...180.00 [degrees] -180.00...180.00 [degrees] 0.00...999.99 [%] 0.00 …. 99.99 [ deg Celsius ] 0…4.00 [xUn] 0.00 …. 50.00 [xIn] 0.00 …. 50.00 [xIn] 0.00 …. 50.00 [xIn] 0.00 …. 50.00 [xIn] 0.00 …. 50.00 [xIn] 0.00 …. 50.00 [xIn] 0.00 …. 50.00 [xIn] Value range Section 2 Modbus data mappings 1MRS757463 A REF611 Point List Manual REF611 Point List Manual 170.00 170.01 170.02 170.03 170.04 170.05 170.06 170.07 170.08 170.09 ... 170.15 171.00 171.01 171.02 171.03 171.04 171.05 171.06 171.07 171.08 171.09 171.10 171.11 171.12 171.13 171.14 171.15 172.00 172.01 172.02 172.03 172.04 172.05 2720 2721 2722 2723 2724 2725 2726 2727 2728 2729 ... 2735 2736 2737 2738 2739 2740 2741 2742 2743 2744 2745 2746 2747 2748 2749 2750 2751 2752 2753 2754 2755 2756 2757 LD0.CMMXU1.LoWrn.stVal LD0.CMMXU1.LoWrn.stVal LD0.CMMXU1.HiWrn.stVal LD0.CMMXU1.HiWrn.stVal LD0.CMMXU1.HiAlm.stVal LD0.CMMXU1.HiAlm.stVal LD0.TRPPTRC2.Tr.general LD0.TRPPTRC2.Tr.general LD0.TRPPTRC2.Op.general LD0.TRPPTRC2.Op.general LD0.TRPPTRC1.Tr.general LD0.TRPPTRC1.Tr.general LD0.TRPPTRC1.Op.general LD0.TRPPTRC1.Op.general LD0.LEDPTRC1.Op.general LD0.LEDPTRC1.Op.general LD0.LEDPTRC1.Str.general LD0.LEDPTRC1.Str.general LD0.DARREC1.AROn.stVal DR.RDRE1.RcdMade.stVal DR.RDRE1.RcdMade.stVal CTRL.LLN0.Loc.stVal IEC 61850 name Indications Table continues on next page Reg.bit Bit addr Table 3: Y Operate(.general) - MCD Operate (.general) - mom Start (.general) - MCD Start (.general)- mom (reserved) (reserved) (reserved) (reserved) (reserved) (reserved) Autorecloser state Disturbance recorder file ready - MCD Disturbance recorder file ready (reserved) Local/Remote state - mom Description Trip output signal (.general) - MCD Trip output signal (.general) - mom Input signal (.general) - MCD Input signal (.general)- mom Y Y (reserved) (reserved) (reserved) (reserved) Trip output signal [.general] - MCD Trip output signal [.general] - mom Input signal (.general) - MCD Input signal (.general) - mom Protection trip conditioning (2) Y Y Protection trip conditioning (1) Y Y Global conditioning Ds CMMXU1.LOW_WARN CMMXU1.HIGH_WARN Y Y Y Low warning[.stVal] - MCD Low warning[.stVal] - mom High warning[.stVal] - MCD High warning[.stVal] - mom High alarm[.stVal] - MCD High alarm[.stVal] - mom Phase current value limit supervision CMMXU1.HIGH_ALARM - - - - - - DARREC1.AR_ON - - AFL-Common SA name 1=Low warning 1=High warning 1=High alarm 0 0 0 0 1=Trip output signal ON 1=Input signal ON 1=Trip output signal ON 1=Input signal ON 1=Operate (LEDPTRC) 1=Start (LEDPTRC) 0 0 0 0 0 0 0=AR Off, 1=AR On 1=DR file captured 0 0 = Remote, 1 = Local (or Off) Value range 1MRS757463 A Section 2 Modbus data mappings 19 20 172.11 172.12 172.13 172.14 172.15 173.00 173.01 173.02 173.03 173.04 173.05 173.06 173.07 173.08 173.09 173.10 173.11 173.12 173.13 173.14 173.15 175.04 175.05 175.06 175.07 2763 2764 2765 2766 2767 2768 2769 2770 2771 2772 2773 2774 2775 2776 2777 2778 2779 2780 2781 2782 2783 2804 2805 2806 2807 CTRL.CBCSWI1.Pos.stVal.Fault CTRL.CBCSWI1.Pos.stVal.Open CTRL.CBCSWI1.Pos.stVal.Close LD0.TCSSCBR2.CirAlm.stVal LD0.TCSSCBR2.CirAlm.stVal LD0.TCSSCBR1.CirAlm.stVal LD0.TCSSCBR1.CirAlm.stVal LD0.LEDGGIO1.SPCSO8.stVal LD0.LEDGGIO1.SPCSO7.stVal LD0.LEDGGIO1.SPCSO6.stVal LD0.LEDGGIO1.SPCSO5.stVal LD0.LEDGGIO1.SPCSO4.stVal LD0.LEDGGIO1.SPCSO3.stVal LD0.LEDGGIO1.SPCSO2.stVal LD0.LEDGGIO1.SPCSO1.stVal LD0.RESVMMXU1.HiWrn.stVal LD0.RESVMMXU1.HiWrn.stVal LD0.RESVMMXU1.HiAlm.stVal LD0.RESVMMXU1.HiAlm.stVal LD0.RESCMMXU1.HiWrn.stVal LD0.RESCMMXU1.HiWrn.stVal LD0.RESCMMXU1.HiAlm.stVal LD0.RESCMMXU1.HiAlm.stVal LD0.CMMXU1.LoAlm.stVal LD0.CMMXU1.LoAlm.stVal IEC 61850 name Table continues on next page 175.10 172.10 2762 2810 172.09 2761 175.09 172.08 2760 2809 172.07 2759 175.08 172.06 2758 2808 Reg.bit Bit addr - - CBXCBR1.POSITION TCSSCBR2.ALARM TCSSCBR1.ALARM - - - - - - Low alarm[.stVal] - MCD Low alarm[.stVal] - mom Description Y Y High warning[.stVal] - MCD High warning[.stVal] - mom High alarm[.stVal] - MCD High alarm[.stVal] - mom High warning[.stVal] - MCD High warning[.stVal] - mom High alarm[.stVal] - MCD High alarm[.stVal] - mom Y Y Y Y Y Y Y Y (reserved) (reserved) (reserved) (reserved) LED 8[.stVal] - mom LED 7[.stVal] - mom LED 6[.stVal] - mom LED 5[.stVal] - mom LED 4[.stVal] - mom LED 3[.stVal] - mom LED 2[.stVal] - mom LED 1[.stVal] - mom Indication LED states Y Y Alarm[.stVal] - MCD Alarm[.stVal] - mom Alarm[.stVal] - MCD Alarm[.stVal] - mom Y Y (reserved) (reserved) (reserved) (reserved) error position open mom close mom Circuit breaker position Y Trip circuit supervision (2) Y Trip circuit supervision (1) RESVMMXU1.HIGH_WARN RESVMMXU1.HIGH_ALARM - Y Residual voltage value limit supervision RESCMMXU1.HIGH_WARN RESCMMXU1.HIGH_ALARM - Ds Residual current value limit supervision CMMXU1.LOW_ALARM AFL-Common SA name 0 0 0 0 1=Faulty or Intermediate 1=Open 1=Close 1=TCS2 Alarm 1=TCS1 Alarm 0 0 0 0 1=LED ON 1=LED ON 1=LED ON 1=LED ON 1=LED ON 1=LED ON 1=LED ON 1=LED ON 1=High warning 1=High alarm 1=High warning 1= High alarm 1=Low alarm Value range Section 2 Modbus data mappings 1MRS757463 A REF611 Point List Manual REF611 Point List Manual 175.11 175.12 175.13 175.14 175.15 176.00 176.01 176.02 176.03 176.04 176.05 176.06 176.07 176.08 176.09 176.10 176.11 176.12 176.13 176.14 176.15 177.00 177.01 177.02 177.03 177.04 177.05 177.06 177.07 180.00 180.01 180.02 180.03 180.04 2811 2812 2813 2814 2815 2816 2817 2818 2819 2820 2821 2822 2823 2824 2825 2826 2827 2828 2829 2830 2831 2832 2833 2834 2835 2836 2837 2838 2839 2880 2881 2882 2883 2884 LD0.PHLPTOC1.Str.phsB LD0.PHLPTOC1.Str.phsA LD0.PHLPTOC1.Str.phsA LD0.PHLPTOC1.Str.general LD0.PHLPTOC1.Str.general CTRL.CBXCBR1.BlkCls.stVal CTRL.CBXCBR1.BlkCls.stVal CTRL.CBXCBR1.BlkOpn.stVal CTRL.CBXCBR1.BlkOpn.stVal CTRL.CCBRBRF1.OpIn.general CTRL.CCBRBRF1.OpIn.general CTRL.CCBRBRF1.OpEx.general CTRL.CCBRBRF1.OpEx.general CTRL.CCBRBRF1.Str.general CTRL.CCBRBRF1.Str.general LD0.CBCILO1.ItlByPss.stVal CTRL.CBCILO1.EnaCls.stVal CTRL.CBCILO1.EnaOpn.stVal CTRL.CBCSWI1.Pos.stSeld CTRL.CBCSWI1.Pos.stSeld CTRL.CBCSWI1.Pos.stVal CTRL.CBCSWI1.Pos.stVal CTRL.CBCSWI1.Pos.stVal CTRL.CBCSWI1.Pos.stVal IEC 61850 name Table continues on next page Reg.bit Bit addr (reserved) (reserved) open MCD open mom close MCD close mom Y Selected [.stSeld] - MCD Selected (.stSeld) - mom Y Y Interlocking bypass [.stVal] - mom Close enabled (.stVal) - mom Open enabled (.stVal) - mom Y Y Y Y Y Close blocked [.stVal] - MCD Close blocked [.stVal] - mom Open blocked [.stVal] - MCD Open blocked [.stVal] - mom (reserved) (reserved) Operate, internal retrip (.general) - MCD Operate, internal retrip (.general) - mom Failure, external trip [.general] - MCD Failure, external trip [.general] - mom Start, timer running[.general] - MCD Start, timer running[.general] - mom (reserved) PHLPTOC1.START Y Y Y Low stage Start[.phsB] - mom Low stage Start[.phsA] - MCD Low stage Start[.phsA] - mom Low stage Start[.general] - MCD Low stage Start[.general] - mom Phase overcurrent protection signals (3 stages) CBXCBR1.BLK_CLOSE CBXCBR1.BLK_OPEN CCBRBRF1.TRRET CCBRBRF1.TRBU CCBRBRF1.CB_FAULT_AL Circuit breaker failure detection and -protection CBXCBR1.ITL_BYPASS CBXCBR1.ENA_CLOSE CBXCBR1.ENA_OPEN - Y Y Circuit breaker control enable signals CBXCBR1.SELECTED - (reserved) (reserved) (reserved) (reserved) (reserved) Description Circuit breaker selected for control operation CBXCBR1.POSITION - Ds Circuit breaker position + momentary change detect AFL-Common SA name 1=Low stage phsB start 1=Low stage phsA start 1=Low stage start 1 = Close blocked 1 = Open blocked 0 0 1=Operate, internal re-trip 1=Failure,external trip 1=Start,timer running 0 1=Bypassed 1=Close enabled 1=Open enabled 1=Selected 0 0 1=Open 1=Close 0 0 0 0 0 Value range 1MRS757463 A Section 2 Modbus data mappings 21 22 180.08 180.09 180.10 180.11 180.12 180.13 180.14 180.15 181.00 181.01 181.02 181.03 181.04 181.05 181.06 181.07 181.08 181.09 181.10 181.11 181.12 181.13 181.14 181.15 182.00 182.01 182.02 182.03 182.04 182.05 182.06 182.07 2888 2889 2890 2891 2892 2893 2894 2895 2896 2897 2898 2899 2900 2901 2902 2903 2904 2905 2906 2907 2908 2909 2910 2911 2912 2913 2914 2915 2916 2917 2918 2919 LD0.DEFLPTOC1.Str.general LD0.DEFLPTOC1.Str.general LD0.PHIPTOC1.Op.general LD0.PHIPTOC1.Op.general LD0.PHIPTOC1.Str.phsC LD0.PHIPTOC1.Str.phsC LD0.PHIPTOC1.Str.phsB LD0.PHIPTOC1.Str.phsB LD0.PHIPTOC1.Str.phsA LD0.PHIPTOC1.Str.phsA LD0.PHIPTOC1.Str.general LD0.PHIPTOC1.Str.general LD0.PHHPTOC2.Op.general LD0.PHHPTOC2.Op.general LD0.PHHPTOC2.Str.phsC LD0.PHHPTOC2.Str.phsC LD0.PHHPTOC2.Str.phsB LD0.PHHPTOC2.Str.phsB LD0.PHHPTOC2.Str.phsA LD0.PHHPTOC2.Str.phsA LD0.PHHPTOC2.Str.general LD0.PHHPTOC2.Str.general LD0.PHHPTOC1.Op.general LD0.PHHPTOC1.Op.general LD0.PHHPTOC1.Str.phsC LD0.PHHPTOC1.Str.phsC LD0.PHHPTOC1.Str.phsB LD0.PHHPTOC1.Str.phsB LD0.PHHPTOC1.Str.phsA LD0.PHHPTOC1.Str.phsA LD0.PHHPTOC1.Str.general LD0.PHHPTOC1.Str.general LD0.PHLPTOC1.Op.general LD0.PHLPTOC1.Op.general LD0.PHLPTOC1.Str.phsC LD0.PHLPTOC1.Str.phsC LD0.PHLPTOC1.Str.phsB IEC 61850 name Table continues on next page 182.09 180.07 2887 2921 180.06 2886 182.08 180.05 2885 2920 Reg.bit Bit addr PHIPTOC1.START Y Y Y Y Y Y Y Y Y Y Y Y High(2) stage Operate[.general] - MCD High(2) stage Operate[.general] - mom High(2) stage Start[.phsC] - MCD High(2) stage Start[.phsC] - mom High(2) stage Start[.phsB] - MCD High(2) stage Start[.phsB] - mom High(2) stage Start[.phsA] - MCD High(2) stage Start[.phsA] - mom High(2) stage Start[.general] - MCD High(2) stage Start[.general] - mom High(1) stage Operate[.general] - MCD High(1) stage Operate[.general] - mom High(1) stage Start[.phsC] - MCD High(1) stage Start[.phsC] - mom High(1) stage Start[.phsB] - MCD High(1) stage Start[.phsB] - mom High(1) stage Start[.phsA] - MCD High(1) stage Start[.phsA] - mom High(1) stage Start[.general] - MCD High(1) stage Start[.general] - mom Low stage Operate[.general] - MCD Low stage Operate[.general] - mom Low stage Start[.phsC] - MCD Low stage Start[.phsC] - mom Low stage Start[.phsB] - MCD Description Y Y Y Y Y Instantaneous stage Operate[.general] - MCD Instantaneous stage Operate[.general] - mom Instantaneous stage Start[.phsC] - MCD Instantaneous stage Start[.phsC] - mom Instantaneous stage Start[.phsB] - MCD Instantaneous stage Start[.phsB] - mom Instantaneous stage Start[.phsA] - MCD Instantaneous stage Start[.phsA] - mom Instantaneous stage Start[.general] - MCD Instantaneous stage Start[.general] - mom DEFLPTOC1.START Y Low(1) stage Start[.general] - MCD Low(1) stage Start[.general] - mom Directional earth-fault protection signals (3 stages) PHIPTOC1.OPERATE - - - Ds Phase overcurrent protection signals (1 stage) PHHPTOC2.OPERATE - - - PHHPTOC2.START PHHPTOC1.OPERATE - - - PHHPTOC1.START PHLPTOC1.OPERATE - AFL-Common SA name 1=Low(1) stage start 1=Instantaneous stage operate 1=Inst. stage phsC start 1=Inst. stage phsB start 1=Inst. stage phsA start 1=Instantaneous stage start 1=High(2) stage operate 1=High(2) stage phsC start 1=High(2) stage phsB start 1=High(2) stage phsA start 1=High(2) stage start 1=High(1) stage operate 1=High(1) stage phsC start 1=High(1) stage phsB start 1=High(1) stage phsA start 1=High(1) stage start 1=Low stage operate 1=Low stage phsC start Value range Section 2 Modbus data mappings 1MRS757463 A REF611 Point List Manual REF611 Point List Manual 182.10 182.11 182.12 182.13 182.14 182.15 183.00 183.01 183.02 183.03 183.04 183.05 183.06 183.07 183.08 183.09 183.10 183.11 183.12 183.13 183.14 183.15 184.00 184.01 184.02 184.03 184.04 184.05 184.06 184.07 184.08 184.09 184.10 184.11 184.12 2922 2923 2924 2925 2926 2927 2928 2929 2930 2931 2932 2933 2934 2935 2936 2937 2938 2939 2940 2941 2942 2943 2944 2945 2946 2947 2948 2949 2950 2951 2952 2953 2954 2955 2956 LD0.NSPTOC1.Str.general LD0.PDNSPTOC1.Op.general LD0.PDNSPTOC1.Op.general LD0.PDNSPTOC1.Str.general LD0.PDNSPTOC1.Str.general LD0.INTRPTEF1.Op.general LD0.INTRPTEF1.Op.general LD0.INTRPTEF1.Str.general LD0.INTRPTEF1.Str.general LD0.EFIPTOC1.Op.general LD0.EFIPTOC1.Op.general LD0.EFIPTOC1.Str.general LD0.EFIPTOC1.Str.general LD0.EFHPTOC1.Op.general LD0.EFHPTOC1.Op.general LD0.EFHPTOC1.Str.general LD0.EFHPTOC1.Str.general LD0.EFLPTOC2.Op.general LD0.EFLPTOC2.Op.general LD0.EFLPTOC2.Str.general LD0.EFLPTOC2.Str.general LD0.EFLPTOC1.Op.general LD0.EFLPTOC1.Op.general LD0.EFLPTOC1.Str.general LD0.EFLPTOC1.Str.general LD0.DEFHPTOC1.Op.general LD0.DEFHPTOC1.Op.general LD0.DEFHPTOC1.Str.general LD0.DEFHPTOC1.Str.general LD0.DEFLPTOC2.Op.general LD0.DEFLPTOC2.Op.general LD0.DEFLPTOC2.Str.general LD0.DEFLPTOC2.Str.general LD0.DEFLPTOC1.Op.general LD0.DEFLPTOC1.Op.general IEC 61850 name Table continues on next page Reg.bit Bit addr Ds Y Y Y Y Y High stage Operate[.general] - MCD High stage Operate[.general] - mom High stage Start[.general] - MCD High stage Start[.general] - mom Low(2) stage Operate[.general] - MCD Low(2) stage Operate[.general] - mom Low(2) stage Start[.general] - MCD Low(2) stage Start[.general] - mom Low(1) stage Operate[.general] - MCD Low(1) stage Operate[.general] - mom Description Y Y Y Y Y Y Y Y Instantaneous stage Operate[.general] - MCD Instantaneous stage Operate[.general] - mom Instantaneous stage Start[.general] - MCD Instantaneous stage Start[.general] - mom High stage Operate[.general] - MCD High stage Operate[.general] - mom High stage Start[.general] - MCD High stage Start[.general] - mom Low(2) stage Operate[.general] - MCD Low(2) stage Operate[.general] - mom Low(2) stage Start[.general] - MCD Low(2) stage Start[.general] - mom Low(1) stage Operate[.general] - MCD Low(1) stage Operate[.general] - mom Low(1) stage Start[.general] - MCD Low(1) stage Start[.general] - mom Y Y Operate[.general] - MCD Operate[.general] - mom Start[.general] - MCD Start[.general] - mom Y Y Operate[.general] - MCD Operate[.general] - mom Start[.general] - MCD Start[.general] - mom NSPTOC1.START Y Stage1 Start[.general] - mom Negative sequence overcurrent protection signals (2 stages) PDNSPTOC1.OPERATE PDNSPTOC1.START Phase discontinuity protection signals (1 stage) INTRPTEF1.OPERATE INTRPTEF1.START Transient/intermittent earth-fault protection signals (1 stage) EFIPTOC1.OPERATE EFIPTOC1.START EFHPTOC1.OPERATE EFHPTOC1.START EFLPTOC2.OPERATE EFLPTOC2.START EFLPTOC1.OPERATE EFLPTOC1.START Non-directional earth-fault and sensitive earth-fault protection signals (4 stages) DEFHPTOC1.OPERATE DEFHPTOC1.START DEFLPTOC2.OPERATE DEFLPTOC2.START DEFLPTOC1.OPERATE AFL-Common SA name 1=Stage1 start 1=Stage operate 1=Stage start 1=Stage operate 1=Stage start 1=Instantaneous stage operate 1=Instantaneous stage start 1=High stage operate 1=High stage start 1=Low(2) stage operate 1=Low(2) stage start 1=Low(1) stage operate 1=Low(1) stage start 1=High stage operate 1=High stage start 1=Low(2) stage operate 1=Low(2) stage start 1=Low(1) stage operate Value range 1MRS757463 A Section 2 Modbus data mappings 23 24 185.02 185.03 185.04 185.05 185.06 185.07 185.08 185.09 185.10 185.11 185.12 185.13 185.14 185.15 186.00 186.01 190.00 190.01 190.02 190.03 190.04 190.05 190.06 190.07 190.08 190.09 190.10 190.11 2962 2963 2964 2965 2966 2967 2968 2969 2970 2971 2972 2973 2974 2975 2976 2977 3040 3041 3042 3043 3044 3045 3046 3047 3048 3049 3050 3051 Y Y Y Stage2 Operate[.general] - MCD Stage2 Operate[.general] - mom Stage2 Start[.general] - MCD Stage2 Start[.general] - mom Stage1 Operate[.general] - MCD Stage1 Operate[.general] - mom Stage1 Start[.general] - MCD Description Y Y Y Y Start[.phsC] - MCD Start[.phsC] - mom Start[.phsB] - MCD Start[.phsB] - mom Start[.phsA] - MCD Start[.phsA] - mom Start[.general] - MCD Start[.general] - mom Three-phase inrush detection signals Ds Y Y Operate[.general] - MCD Operate[.general] - mom Thermal Alarm[.general] - MCD Thermal Alarm[.general] - mom Start[.general] - MCD Start[.general] - mom Y Unsuccessful reclose status[.stVal] - mom DARREC1.UNSUC_RECL LD0.DARREC1.UnsRec.stVal Successful reclose status[.stVal] - mom AR in progress 5th reclose[.stVal] - MCD AR in progress 5th reclose[.stVal] - mom AR in progress 4th reclose[.stVal] - MCD AR in progress 4th reclose[.stVal] - mom AR in progress 3rd reclose[.stVal] - MCD AR in progress 3rd reclose[.stVal] - mom AR in progress 2nd reclose[.stVal] - MCD AR in progress 2nd reclose[.stVal] - mom AR in progress 1st reclose[.stVal] - MCD AR in progress 1st reclose[.stVal] - mom AR in progress [.stVal] - MCD AR in progress [.stVal] - mom Successful reclose status[.stVal] - MCD Y Y Y Y Y Y Y Autorecloser detailed signals, optional DARREC1.SUC_RECL DARREC1.INPRO_5 DARREC1.INPRO_4 DARREC1.INPRO_3 DARREC1.INPRO_2 DARREC1.INPRO_1 DARREC1.INPRO T1PTTR1.OPERATE T1PTTR1.ALARM Y Thermal overload protection signals (1 stage) T1PTTR1.START - - - INRPHAR1.BLK2H NSPTOC2.OPERATE NSPTOC2.START NSPTOC1.OPERATE AFL-Common SA name LD0.DARREC1.SucRec.stVal LD0.DARREC1.SucRec.stVal LD0.DARREC1.PrgRec5.stVal LD0.DARREC1.PrgRec5.stVal LD0.DARREC1.PrgRec4.stVal LD0.DARREC1.PrgRec4.stVal LD0.DARREC1.PrgRec3.stVal LD0.DARREC1.PrgRec3.stVal LD0.DARREC1.PrgRec2.stVal LD0.DARREC1.PrgRec2.stVal LD0.DARREC1.PrgRec1.stVal LD0.DARREC1.PrgRec1.stVal LD0.DARREC1.PrgRec.stVal LD0.DARREC1.PrgRec.stVal LD0.T1PTTR1.Op.general LD0.T1PTTR1.Op.general LD0.T1PTTR1.AlmThm.general LD0.T1PTTR1.AlmThm.general LD0.T1PTTR1.Str.general LD0.T1PTTR1.Str.general LD0.INRPHAR1.Str.phsC LD0.INRPHAR1.Str.phsC LD0.INRPHAR1.Str.phsB LD0.INRPHAR1.Str.phsB LD0.INRPHAR1.Str.phsA LD0.INRPHAR1.Str.phsA LD0.INRPHAR1.Str.general LD0.INRPHAR1.Str.general LD0.NSPTOC2.Op.general LD0.NSPTOC2.Op.general LD0.NSPTOC2.Str.general LD0.NSPTOC2.Str.general LD0.NSPTOC1.Op.general LD0.NSPTOC1.Op.general LD0.NSPTOC1.Str.general IEC 61850 name Table continues on next page 190.14 185.01 2961 3054 185.00 2960 190.13 184.15 2959 190.12 184.14 2958 3053 184.13 2957 3052 Reg.bit Bit addr 1=Unsuccessful reclose 1=Successful reclose 1=In progress 1=In progress 1=In progress 1=In progress 1=In progress 1=In progress 1=Operate 1=Thermal alarm 1=Start 1=Start phsC 1=Start phsB 1=Start phsA 1=Start general 1=Stage2 operate 1=Stage2 start 1=Stage1 operate Value range Section 2 Modbus data mappings 1MRS757463 A REF611 Point List Manual REF611 Point List Manual 190.15 191.00 191.01 191.02 191.03 191.04 191.05 191.06 191.07 191.08 191.09 191.10 191.11 191.12 191.13 191.14 191.15 192.00 192.01 192.02 192.03 192.04 192.05 192.06 192.07 192.08 192.09 192.10 192.11 192.12 192.13 192.14 192.15 198.00 198.01 198.02 198.03 198.04 3055 3056 3057 3058 3059 3060 3061 3062 3063 3064 3065 3066 3067 3068 3069 3070 3071 3072 3073 3074 3075 3076 3077 3078 3079 3080 3081 3082 3083 3084 3085 3086 3087 3168 3169 3170 3171 3172 LD0.ROVPTOV2.Str.general LD0.ROVPTOV1.Op.general D0.ROVPTOV1.Op.general LD0.ROVPTOV1.Str.general LD0.ROVPTOV1.Str.general LD0.DARREC1.WtMstr.stVal LD0.DARREC1.WtMstr.stVal LD0.DARREC1.UnsCBCls.stVal LD0.DARREC1.UnsCBCls.stVal LD0.DARREC1.OpOpn.general LD0.DARREC1.OpOpn.general LD0.DARREC1.Op.general LD0.DARREC1.Op.general LD0.DARREC1.CBManCls.stVal LD0.DARREC1.CBManCls.stVal LD0.DARREC1.ProCrd.stVal LD0.DARREC1.ProCrd.stVal LD0.DARREC1.RclTmStr.stVal LD0.DARREC1.RclTmStr.stVal LD0.DARREC1.FrqOpAlm.stVal LD0.DARREC1.FrqOpAlm.stVal LD0.DARREC1.PrgCutOut.stVal LD0.DARREC1.PrgCutOut.stVal LD0.DARREC1.PrgDsr.stVal LD0.DARREC1.PrgDsr.stVal LD0.DARREC1.ActRec.stVal LD0.DARREC1.ActRec.stVal LD0.DARREC1.RdyRec.stVal LD0.DARREC1.RdyRec.stVal LD0.DARREC1.LO.stVal LD0.DARREC1.LO.stVal LD0.DARREC1.InBlkThm.stVal LD0.DARREC1.InBlkThm.stVal LD0.DARREC1.InInhRec.stVal LD0.DARREC1.InInhRec.stVal LD0.DARREC1.UnsRec.stVal IEC 61850 name Table continues on next page Reg.bit Bit addr Ds Y Y Y Y Y Y Y Y Y Y Y Y Y Y Y (reserved) (reserved) Master signal to follower[.stVal] - MCD Master signal to follower[.stVal] - mom Unsuccessful CB closing status[.stVal] - MCD Unsuccessful CB closing status[.stVal] - mom Operate (open command to XCBR)[.general] - MCD Operate (open command to XCBR)[.general] - mom Operate (close command to XCBR)[.general] - MCD Operate (close command to XCBR)[.general] - mom CB manually closed[.stVal] - MCD CB manually closed[.stVal] - mom Protection coordination[.stVal] - MCD Protection coordination[.stVal] - mom Reclaim time started[.stVal] - MCD Reclaim time started[.stVal] - mom Frequent operation counter alarm[.stVal] - MCD Frequent operation counter alarm[.stVal] - mom Cutout time in progress[.stVal] - MCD Cutout time in progress[.stVal] - mom Discrimination time in progress[.stVal] - MCD Discrimination time in progress[.stVal] - mom Active reclose status[.stVal] - MCD Active reclose status[.stVal] - mom Ready reclose status[.stVal] - MCD Ready reclose status[.stVal] - mom Lockout status[.stVal] - MCD Lockout status[.stVal] - mom Thermal block (status)[.stVal] - MCD Thermal block (status)[.stVal] - mom Inhibit reclose (status)[.stVal] - MCD Inhibit reclose (status)[.stVal] - mom Unsuccessful reclose status[.stVal] - MCD Description ROVPTOV2.START ROVPTOV1.OPERATE ROVPTOV1.START Y Y Y Stage 2 Start[.general] - mom Stage 1 Operate[.general] - MCD Stage 1 Operate[.general] - mom LD0.ROVPTOV1.Str.general Stage 1 Start[.general] - mom Residual overvoltage protection (3 stages) DARREC1.CMD_WAIT DARREC1.UNSUC_CB DARREC1.OPEN_CB DARREC1.CLOSE_CB DARREC1.MAN_CB_CL - - DARREC1.FRQ_OP_ALM DARREC1.CUTOUT_INPRO DARREC1.DISCR_INPRO DAAREC1.ACTIVE DARREC1.READY DARREC1.LOCKED - - AFL-Common SA name 1=Stage2 start 1=Stage1 operate 1=Stage1 start 0 0 1=Master signal to follower 1=Unsuccessful CB closing 1=Open command to CB 1=Close command to CB 1=CB manually closed 1=Protection coordination 1=Reclaim time started 1=Frequent operation alarm 1=Cutout time in progress 1=Discrimination time in progress 1=Reclose active 1=Reclose ready 1=Lockout 1=Thermal block 1=Reclose inhibit Value range 1MRS757463 A Section 2 Modbus data mappings 25 26 198.10 198.11 199.00 199.01 199.02 199.03 199.04 199.05 199.06 199.07 199.08 199.09 199.10 199.11 199.12 199.13 199.14 199.15 200.00 200.01 200.02 200.03 200.04 200.05 200.06 200.07 200.08 200.09 3178 3179 3184 3185 3186 3187 3188 3189 3190 3191 3192 3193 3194 3195 3196 3197 3198 3199 3200 3201 3202 3203 3204 3205 3206 3207 3208 3209 LD0.XGGIO120.Ind4.stVal LD0.XGGIO120.Ind4.stVal LD0.XGGIO120.Ind3.stVal LD0.XGGIO120.Ind3.stVal LD0.XGGIO120.Ind2.stVal LD0.XGGIO120.Ind2.stVal LD0.XGGIO120.Ind1.stVal LD0.XGGIO120.Ind1.stVal 199.11 LD0.XGGIO130.Ind6.stVal LD0.XGGIO130.Ind6.stVal LD0.XGGIO130.Ind5.stVal LD0.XGGIO130.Ind5.stVal LD0.XGGIO130.Ind4.stVal 199.06 LD0.XGGIO130.Ind4.stVal LD0.XGGIO130.Ind3.stVal LD0.XGGIO130.Ind3.stVal LD0.XGGIO130.Ind2.stVal LD0.XGGIO130.Ind2.stVal LD0.XGGIO130.Ind1.stVal 199.00 LD0.XGGIO130.Ind1.stVal LD0.ROVPTOV3.Op.general LD0.ROVPTOV3.Op.general LD0.ROVPTOV3.Str.general LD0.ROVPTOV3.Str.general LD0.ROVPTOV2.Op.general LD0.ROVPTOV2.Op.general LD0.ROVPTOV2.Str.general IEC 61850 name Table continues on next page 200.12 198.09 3177 3212 198.08 3176 200.11 198.07 3175 3211 198.06 3174 200.10 198.05 3173 3210 Reg.bit Bit addr - - - - - - - - - - Y Y Y Stage 3 Operate[.general] - MCD Stage 3 Operate[.general] - mom Stage 3 Start[.general] - MCD Stage 3 Start[.general] - mom Stage 2 Operate[.general] - MCD Stage 2 Operate[.general] - mom Stage 2 Start[.general] - MCD Description Physical I/O signals Ds (reserved) (reserved) (reserved) (reserved) X130-Input 6[.stVal] - MCD X130-Input 6[.stVal] - mom X130-Input 5[.stVal] - MCD X130-Input 5[.stVal] - mom X130-Input 4[.stVal] - MCD X130-Input 4[.stVal] - mom X130-Input 3[.stVal] - MCD X130-Input 3[.stVal] - mom X130-Input 2[.stVal] - MCD X130-Input 2[.stVal] - mom X130-Input 1[.stVal] - MCD X130-Input 1[.stVal] - mom Y Y Y Y (reserved) (reserved) (reserved) (reserved) (reserved) X120-Input 4[.stVal] - MCD X120-Input 4[.stVal] - mom X120-Input 3[.stVal] - MCD X120-Input 3[.stVal] - mom X120-Input 2[.stVal] - MCD X120-Input 2[.stVal] - mom X120-Input 1[.stVal] - MCD X120-Input 1[.stVal] - mom Physical I/O signal states (AIM-card X120) Y Y Y Y Y Y Physical I/O signal states (BIO-card X130) ROVPTOV3.OPERATE ROVPTOV3.START ROVPTOV2.OPERATE AFL-Common SA name 0 0 0 0 0 1=ON, 0=OFF 1=ON, 0=OFF 1=ON, 0=OFF 1=ON, 0=OFF 0 0 0 0 1=ON, 0=OFF 1=ON, 0=OFF 1=ON, 0=OFF 1=ON, 0=OFF 1=ON, 0=OFF 1=ON, 0=OFF 1=Stage3 operate 1=Stage3 start 1=Stage2 operate Value range Section 2 Modbus data mappings 1MRS757463 A REF611 Point List Manual Reg.bit 200.13 200.14 200.15 203.00 203.01 203.02 203.03 203.04 203.05 203.06 203.07 203.08 203.09 203.10 203.11 Bit addr 3213 3214 3215 3248 3249 REF611 Point List Manual 3250 3251 3252 3253 3254 3255 3256 3257 3258 3259 LD0.XGGIO100.SPCSO6.stVal LD0.XGGIO100.SPCSO6.stVal LD0.XGGIO100.SPCSO5.stVal LD0.XGGIO100.SPCSO5.stVal LD0.XGGIO100.SPCSO4.stVal LD0.XGGIO100.SPCSO4.stVal LD0.XGGIO100.SPCSO3.stVal LD0.XGGIO100.SPCSO3.stVal LD0.XGGIO100.SPCSO2.stVal LD0.XGGIO100.SPCSO2.stVal LD0.XGGIO100.SPCSO1.stVal LD0.XGGIO100.SPCSO1.stVal IEC 61850 name - - - - - - Ds (reserved) (reserved) (reserved) Description Y Y Y Y Y Y X100-Output 6[.stVal] - MCD X100-Output 6[.stVal] - mom X100-Output 5[.stVal] - MCD X100-Output 5[.stVal] - mom X100-Output 4[.stVal] - MCD X100-Output 4[.stVal] - mom X100-Output 3[.stVal] - MCD X100-Output 3[.stVal] - mom X100-Output 2[.stVal] - MCD X100-Output 2[.stVal] - mom X100-Output 1[.stVal] - MCD X100-Output 1[.stVal] - mom Physical I/O signal states (PSM-card X100) AFL-Common SA name 1=ON, 0=OFF 1=ON, 0=OFF 1=ON, 0=OFF 1=ON, 0=OFF 1=ON, 0=OFF 1=ON, 0=OFF 0 0 0 Value range 1MRS757463 A Section 2 Modbus data mappings 27 28 Uns LD0.LPHD1.RsDev.ctlVal Physical device - Reset device - 1=Activate 0 CMMXU1 - CMMXU1 max.demands - 1=Reset Disturbance recorder - Disturbance records - 1=Activate (reserved) 3 LD0.CMSTA1.RecRs.ctlVal Disturbance recorder - Trig recording - 1=Activate 2080 Uns DR.RDRE1.MemClr.ctlVal Reset input for CB remaining life and operation counter - 1=Activate (reserved) 9 Uns DR.RDRE1.RcdTrg.ctlVal Reset accumulation energy - 1=Activate 2079 2 2069 8 Uns LD0.SSCBR1.RsCBWear.ctlVal Reset reclosing counters - 1=Activate (reserved) 2 2068 7 Uns LD0.SSCBR1.RsAccAPwr.ctlVal Reset reclosing - 1=Activate 2078 2 2067 6 Uns LD0.DARREC1.RsCnt.ctlVal General - All data - 1=Activate (reserved) 2 2066 5 Uns LD0.DARREC1.RsRec.ctlVal General - Alarm LEDs - 1=Activate 2077 2 2065 4 Uns LD0.LLN0.RecRs.ctlVal General - Indications and LEDs - 1=Activate (reserved) 2 2064 3 Uns LD0.LLN0.LEDRs2.ctlVal LD0.LLN0.LEDRs1.ctlVal 2076 2 2063 2 Uns Uns CBXCBR1 - Switch, general - Direct close CBXCBR1 - Switch, general - Direct open (reserved) 2 2062 1 0 CTRL.CBCSWI1.Pos.ctlVal Description 2075 2 Uns CTRL.CBCSWI1.Pos.ctlVal Identification (reserved) 2 2060 2061 5 Uns Mode 2074 1 2053 4 Ctrl bit 2073 1 Ctrl struct Controls 2052 0x addr Table 4: Section 2 Modbus data mappings 1MRS757463 A REF611 Point List Manual Section 3 Glossary 1MRS757463 A Section 3 Glossary AFL Application function block library AR Autoreclosing BIO Binary input and output CB Circuit breaker CPM Communication protocol manual DR Disturbance recorder EMC Electromagnetic compatibility HMI Human-machine interface I/O Input/output IEC International Electrotechnical Commission IEC 61850 International standard for substation communication and modeling REF611 Point List Manual IED Intelligent electronic device LED Light-emitting diode LHMI Local human-machine interface MCD Momentary change detect Modbus A serial communication protocol developed by the Modicon company in 1979. Originally used for communication in PLCs and RTU devices. PCM600 Protection and Control IED Manager PLC Programmable logic controller PSM Power supply module TCS Trip-circuit supervision UTC Coordinated universal time 29 30 31 ABB Oy Distribution Automation P.O. Box 699 FI-65101 VAASA, Finland Phone +358 10 22 11 Fax +358 10 22 41094 www.abb.com/substationautomation 1MRS757463 A © Copyright 2011 ABB. All rights reserved. Contact us