Download BACCHUS GENIUS SERVICE MANUAL
Transcript
BACCHUS GENIUS SERVICE MANUAL S.40724 Rev 00 DISPLAY WHEN THE MACHINE IS OFF When the machine is off, the thermostat display shows the following message: STAND BY Push> DISPLAY WHEN THE MACHINE IS ON When the machine is on, three main display frames are possible if the RTC board is present; if not, the main display frames are only two. The display depends on the operating mode (single- or double zone operation). The main display frame can be selected by pressing the ok key; the selected frame remains displayed permanently. Single-zone display -05,5°C_ Press “OK” key Set: -05°C_ 10:26 08/04/05 Cell real temperature: (Sensor_A+Sensor_B)/2 Adjusting Set Point for single-zone (SP0) System Time/Date Frame present only if RTC board is present Single-zone display with Humidity sensor enabled -05,5°C_ Press “OK” key 65%Rh Set: -05°C_70%Rh 10:26 08/04/05 Cell real temperature: (Sensor_A+Sensor_B)/2 And reading of the humidity sensor Adjusting Set Point for single-zone (SP0) and Humidity set (RH%) System Time/Date Frame present only if RTC board is present Double-zone display ↓ +03°C_ ↑ +12°C Press “OK” key Set: +02°C –03°C 10:26 08/04/05 Cell real temperature: Sensor_A (zone 1) and Sensor_B (zone 2) Adjusting Set Point zone 1 (SP1) and zone 2 (SP2) System Time/Date Frame present only if RTC board is present Note In the case the Humidity sensor is enabled for double-zone operation, the sensor reading value and the adjusting set are not displayed. S.40724 Rev 00 SCREENSAVER During the display of the normal operating frame (failures not enabled and menus not enabled) every MES seconds a snipe is launched with "BACCHUS LINE". Such snipe is repeated four consecutive times, alternatively from the left to the right and from the right to the left. Set up MES to zero to disable the snipe. To enable the snipe, MES values suggested are lower than 10 seconds (in this case, the snipe would be continuous). DISPLAY DISPLAY OF FAILURES In the case of failure, a message is displayed, the display backlight flashes and the buzzer goes on. Press any key during the failure to switch it off; in this condition, the buzzer goes off and the failure display frame comes alternated to the main display frame. In the case of several contemporary failures, only the one with higher priority is displayed. Failures and priority levels Priority Type of failure 1 2 3 4 5 6 7 8 Failure of sensor S1 (adjusting sensor A) Failure of sensor S2 (evaporator sensor) Failure of sensor S3 (adjusting sensor B) Failure of sensor S4 (composite digital input) Failure of sensor S5 (Humidity sensor) Time reference missing (only for versions with RTC board) Compressor time failure Defrosting time failure 9 Water level sensor triggered Failure display frame PROBE S1 COMPRES.WORK DEFROST TIME WATER LEVEL DISPLAY OF ADJUSTMENT STATE If bit#6 of VOP (weight 64) is set, the adjustment state display is enabled. In this situation, a symbol on the side of the sensor reading indicates the adjustment action carried out on that specific sensor. The symbols displayed are the following: “▼” “▲” “÷” “▼” “▲” “÷” “▼” “▲” “§” (triangle downwards) on the side of the A sensor reading Cooling down action Z1 (compressor) (triangle upwards) on the side of the A sensor reading Heating action Z1 (line between two points) on the side of the A sensor reading Neutral Zone Z1 (triangle downwards) on the side of the B sensor reading Cooling down action Z1 (triangle upwards) on the side of the B sensor reading Heating action Z2 (line between two points) on the side of the B sensor reading (triangle downwards) on the side of the Humidity reading Neutral Zone Z2 De-humidification action (triangle upwards) on the side of the Humidity reading Humidification action (styled S) Defrosting enabled The blinking symbol indicates that the action indicated is going to be enabled soon (the action is temporarily locked, due to the anti-oscillation timer). S.40724 Rev 00 Examples of adjustment state display: ▲-03,0°C ▼-03,0°C ÷65%Rh Single-zone Mode: Heating action enabled Single-zone Mode with Humidity sensor enabled: Cooling down action enabled, humidity in neutral zone ↓▼+03°C_ ↑▲+12°C Double-one Mode Cooling down action enabled Z1, Heating action enabled Z2 ↓§+03°C_ ↑§+12°C Double-one Mode Defrosting enabled TEMPERATURE TEMPERATURE ALARMS AND ALARM DISPLAY The system detects the cell temperature continuously. If the temperature exceeds the pre-set limits for a time longer than the pre-set alarm delay, the visual and acoustic warning go on. Temperature alarm in case of Single-zone Adjusting temperature = [ Sensor_A (+OFA) + Sensor_B (+OFB) ] /2 Conditions for activation of the high temperature alarm: Adjusting temperature >= Limit of high temperature = SP0 + ALH Conditions for activation of the low temperature alarm: Adjusting temperature <= Limit of low temperature = SP0 - ALL Temperature alarm in case of Double-zone In case of double-zone mode, the temperature alarm is managed in parallel on the two zones. Zone 1: Adjusting temperature = Sensor_A (+OFA) Conditions for activation of the high temperature alarm: Adjusting temperature >= Limit of high temperature = SP1 + ALH Conditions for activation of the low temperature alarm: Adjusting temperature <= Limit of low temperature = SP1 - ALL Zone 2: Adjusting temperature = Sensor_B (+OFB) Conditions for activation of the high temperature alarm: Adjusting temperature >= Limit of high temperature = SP2 + ALH Conditions for activation of the low temperature alarm: Adjusting temperature <= Limit of low temperature = SP2 - ALL Temperature alarm delay The alarm for high and low temperature goes on if the conditions above remain stable for a time longer than the alarm delay. In general, the alarm delay used is given by the parameter ALD (expressed in minutes). In case the conditions for alarm activation occur after the machine start-up or after the defrosting activation, the alarm delay used is given by the parameter ADD (expressed in minutes). Temperature alarm signalling In case of temperature alarm, a message is displayed, the display backlight flashes and the buzzer goes on. • In case of high temperature alarm, “«HT»” is displayed, alternated to the temperature sensor reading to which the alarm refers to. • In case of high temperature alarm, “«LT»” is displayed, alternated to the temperature sensor reading to which the alarm refers to. S.40724 Rev 00 Examples of temperature alarm display +00,0°C Frame alternated every 2 seconds Single-zone Mode: High temperature alarm on «HT» ↓ +00°C_ ↑ +00°C Frame alternated every 2 seconds ↓ Double-zone Mode: Z1 High temperature alarm on «HT»_ ↑ +00°C ↓ +00°C_ ↑ -05C Frame alternated every 2 seconds ↓ «HT»_ ↑ «LT»_ Double-zone Mode: Z1 High temperature alarm on and Z2 Low temperature alarm on Temperature pre-alarm signalling If bit#5 of VOP (weight 32)is set, the temperature pre-alarm state display is enabled. In this case, the information on the temperature anomaly is displayed even if the alarm delay has not elapsed yet. “<HT>” High temperature detected, but alarm delay has not elapsed, alarm delay set to ALD. “-HT-” High temperature detected, but alarm delay has not elapsed, alarm delay set to ADD. “<LT>” Low temperature detected, but alarm delay has not elapsed, alarm delay set to ALD. “-LT-” Low temperature detected, but alarm delay has not elapsed, alarm delay set to ADD. MAIN MENU MENU The main menu is enabled by pressing the "MENU" key during the normal operation of the machine (during the display of the main frame). From whichever menu, press the "MENU" key to escape. Main Menu Interface ↓ +10°C_ +18°C ↑ Main Frame MODE TEMPERATURE DEFROST Press “DW” or “UP” keys Menu present only if MOD =2 or 3 m1 SERVICE TURN OFF UMIDITY m2 Menu enabled only if manual defrosting is enabled m3 m4 m5 m6 Menu present only if Humidity control is enabled S.40724 Rev 00 Main Menu Interface if RTC board is present Main Frame ↓ +10°C_ +18°C ↑ USAGE Menu present only if MOD =2 or 3 m1 TEMPERATURE m2 DEFROST SERVICE Press “DW” or “UP” keys Menu enabled only if manual defrosting is enabled m3 m4 TURN OFF m5 UMIDITY m6 CLOCK SET Menu present only if Humidity control is enabled m7 PRINT MENU m8 Menu enabled only if PRT <>0 (m1) MENU MENU FOR SELECTING THE MACHINE OPERATION The menu m1 for selecting the operation (single-zone and double-zone) is displayed when the parameter MOD has value 2 or 3; otherwise, the menu is not displayed and therefore the user is not able to modify the machine operation (unless he access directly the parameter MOD in the SERVICE/PARAMETERS menu). If the menu is not displayed, the main menu display starts directly from the menu m2. MODE Press “OK” key m1 SINGLE COLD ROOM Press “DW” or “UP” keys DOUBLE COLD ROOM Press “OK” key Press “UP” or “DW” to exit without confirmation <-Esc Confirm-> Press “OK” to confirm >> CONFIRMED << S.40724 Rev 00 (m2) MENU FOR PROGRAMMING PROGRAMMING THE TEMPERATURE SET POINT POINT Single-zone TEMPERATURE Press “OK” key m2 ACTUAL Change with “UP” and “DW”. Confirm with “OK” +12°C Press “OK” key Press “UP” or “DW” to exit without confirmation <-Esc Press “OK” to confirm Confirm-> >> CONFIRMED << Double-zone TEMPERATURE Press “OK” key m2 LOW HIGH Select the zone for which the set point shall be changed with “UP” and “DW” +04°C ↓ ↑ +18°C Press “OK” key ACTUAL +12°C Change with “UP” and “DW”. Confirm with “OK” Press “OK” key Press “UP” or “DW” to exit without confirmation <-Esc Confirm-> Press “OK” to confirm >> CONFIRMED << (m3) MENU FOR DEFROSTING ENABLING DEFROST Press “OK” with manual defrosting disabled m3 Press “OK” with manual defrosting enabled Press “UP” or “DW” to exit without confirmation ACCESS DENIED <-Esc Confirm-> Press “OK” to confirm defrosting S.40724 Rev 00 (m4) SERVICE MENU SERVICE Press “OK” when password is present M4 PASSWORD Press “OK” when password is not present INFO ->007 Enter password to access the service menu (255 in case of old machines) s1 DEFROST LIST s2 FAILURE LIST s3 PARAMETERS s4 INFOTEST DATA s5 Press “DW” OR “UP” TEST START s6 LANGUAGE s7 MEMORY RESET s8 PARAM.RESTORE s9 PASSWORD s10 INPUT/OUTPUT s11 WIZARD KEY s12 Menu displayed only if programming key is present (m5) MENU FOR SWITCHING OFF OFF TURN OFF m5 Press “UP” or “DW” to exit without confirmation Press “OK” key <-Esc Confirm-> Press “OK” to confirm Switching off BYE Bye bye snipe Display of switched off state BYE BYE STAND BY Push> S.40724 Rev 00 (m6) MENU FOR PROGRAMMING THE HUMIDITY SET POINT In case the Humidity control is disabled, this menu is not displayed, or, if the RTC board is present, the menu is displayed but forbidden. UMIDITY Press “OK” when Humidity control is disabled m6 Press “OK” when Humidity control is enabled ACCESS DENIED SET Rh% Change with “UP” and “DW”. Confirm with “OK” 60% Press “OK” key Press “UP” or “DW” to exit without confirmation <-Esc Confirm-> Press “OK” to confirm >> CONFIRMED << Note: Humidity control, as well as the change menu of the set thereof, is enabled if: Humidity sensor is enabled (HRH <>0 or HRL <>0) and/or Humidity control from evaporator fan is enabled (FOP, bit#3 =1 weight 8) (m7) MENU FOR CLOCK PROGRAMMING CLOCK SET Press “OK” key m7 16:27 08/03/05 Clock programming in 5 steps. Programming sequence: mm, hh, gg, mm, aa. The data under current programming is blinking. The data under current programming is changed with “UP” and “DW” keys Confirm the data programmed with “OK” (m7) MENU FOR PRINTER SETTING This menu is displayed if the RTC board is present and the printer is enabled (PRT <>0) PRINT MENU m8 Press “OK” key PRINTER ON p1 PRINT OPTIONS p2 Press “DW” and “UP” PARAM. REPORT p3 HYSTORY TEMP..p5 S.40724 Rev 00 (s1) SERVICE MENU FOR DISPLAY OF STATE DATA INFO s1 Press “OK” key KEYPAD ON 65355 POWER ON 65355 3 HTWL 4 65535d:23h 65535d:23h COMP% COMP% COMP ON 1h= 40% 24h= 40% 255’59” COMP OFF 255’59” Fw 5102.77 S/n 2 RESET 65535d:23h COMP Press “DW” and “UP” 1 B.01 255.255.255 5 6 7 8 9 10 11 (s2) SERVICE MENU FOR DISPLAY OF DEFROSTING DATA DEFROST LIST Press “OK” key S2 Press “OK” key DEF22 M01 d=010’ Press “DW” and “UP” DEF21 M05 d=009’ S 14/04/04 13:01 S 00023d:05h DEF20 M10 d=012’ DEF19 M09 d=015’ S.40724 Rev 00 (s3) SERVICE MENU FOR DISPLAY OF FAILURE DATA FAILURE LIST Press “OK” key S3 Press “OK” key F14 PROBE S1 Press “DW” and “UP” F13 PROBE F12 PROBE F11 PROBE S2 S 15/04/04 08:08 S 00024d:23h S3 S4 (s4) SERVICE MENU FOR PARAMETER PROGRAMMING PROGRAMMING PARAMETERS Press “OK” key S4 Press “OK” key P01 P02 Press “DW” and “UP” P70 ADR= 01 flg MOD= 03 flg P03 ISP= 00 flg P04 OSP= 00 flg P01 ADR= 01 flg The value of the parameter selected is blinking. Change this value with “UP” and “DW” then confirm with “OK”. Press “MENU” to exit the set point menu or wait for the time out (30 sec.) PV6= 00 flg EDIT PROG TITLE Menu for editing the title of the recipe present only if the programming key is present S.40724 Rev 00 (s5) SERVICE MENU FOR DISPLAY OF INFOTEST DATA Press “OK” (infotest data not present) INFOTEST DATA S5 Press “OK” key NO EVENT NOTICED Ph1 ON 00’07” Ph1 OFF Press “UP” or “DW” 00’15” Ph2 DEF 00’01” Ph3 REC 01’15” Ph4 UP 00002s/°C Ph5 DW 00029s/°C Ph7 COL2 Ph7 HEA2 02’30” 00’35” Step 7 complete, only if infotest carried out in double-zone mode (s6) SERVICE MENU FOR INFOTEST ENABLING TEST START s6 Press “OK” key Press “UP” or “DW” to exit without confirmation <-Esc Confirm-> Press “OK” to confirm Infotest enabling S.40724 Rev 00 (s7) SERVICE MENU FOR CHANGING THE INTERFACE INTERFACE LANGUAGE LANGUGE s7 Press “OK” key LINGUA ITALIANA LANGUE FRANCAISE Press “UP” or “DW” IDIOMA ESPANOL DEUTSCHESPRACHE ENGLISH LANGUAGE Press “OK” to confirm (s8) SERVICE SERVICE MENU FOR DELETING MEMORIES MEMORIES MEMORY RESET Press “UP” or “DW” to exit without confirmation s8 <-Esc Press “OK” key Confirm-> Press “OK” to confirm the deletion of memories (s9) SERVICE MENU FOR PARAMETE PARAMETER RESTORING Press “OK” key PARAM.RESTORE s9 Press “UP” or “DW” to exit without confirmation <-Esc Confirm-> Press “OK” to confirm the default parameter restoring (s10) SERVICE MENU FOR SETTING THE SERVICE ACCESS PASSWORD PASSWORD s10 PASSWORD Press “OK” key >>255 Change with “UP” and “DW”. Confirm with “OK” S.40724 Rev 00 (s11) SERVICE MENU FOR DISPLAY THE SENSORS AND OUTPUT STATE INPUT/OUTPUT s11 Press “UP” or “DW” Press “OK” key Probe A +02,5°C Probe B +02,0°C Probe AB +02,0°C Frame present only in single-zone mode Frame present only if evaporator sensor is enabled (DTE <>50) Evaporat -05,5°C U123456 = 011000 (s12) SERVICE MENU FOR USING THE PROGRAMMING KEY (WIZARD) This menu is displayed only if the programming key is present. WIZARD KEY s12 Press “OK” key Press “OK” key LOADING Press “UP” or “DW” k1 SAVING k2 UPGRADE Load the parameters of the programming key LOAD FROM >32 k3 Press “OK” key Change with “UP” and “DW”. Confirm with “OK” Press “OK” key Save current parameters to the programming key Firmware upgrade ERASING FIRM... WRITING FW > 55% SAVE IN >32 Change with “UP” and “DW”. Confirm with “OK” >> UPGRADE OK << S.40724 Rev 00 SWITCHING ON SEQUEN SEQUENC EQUENCE – MENU OF INIT INITIAL SETTINGS STAND BY Press any key during the switching off state Push> Frame displayed until the key is released TURNING ON... (((((((()))))))) Welcome animation ((((CCHUS LI)))) Welcome animation BACCHUS LINE Welcome animation Press “DW” LANGUAGE “UP” or LINGUA ITALIANA ?OK/↓↑ LANGUE FRANCAISE IDIOMA ESPANOL Press “UP” or “DW” DEUTSCHESPRACHE ENGLISH LANGUAGE Press “OK” key Request present only if the menu is enabled (MOD=2 or MOD=3) otherwise, skip to menu Temperature MODE “UP” or Press “DW” ?OK/↓↑ SINGLE COLD ROOM Press “OK” key Press “UP” or “DW” DOUBLE COLD ROOM TEMPERATURE ?OK Press “DW” “UP” or LOW Press “OK” key ↓ Press “OK” key HIGH >> CONFIRMED +04°C Press “OK” key << HELLO WORLD ↑ +18°C ‘Hello’ snipe Machine start-up ACTUAL Increase and reduction of SET with “UP” or “DW” Increase and reduction of SET with “UP” or “DW” +12°C Single-zone is set only if set is SP0 S.40724 Rev 00 SEQUENC SEQUENCE OF SPECIAL KEYS UPON STARTSTART-UP After the ‘Hello’ snipe, some specific operations are possible by means of special sequences of keys. Procedure of output Switch Press (OK, MENU)keys during the ‘Hello’ snipe to start the relays test procedure. Press “UP” , “DW” , “OK” , “MENU” at the same time BACCHUS LINE U123456 = 000000 Change the relay on with “UP” and “DW” Procedure of access to service menu (by-passing the password request) Press UP, DW) keys during the ‘Hello’ snipe to access immediately the service menu without entering the password. Press “UP” , “DW” at the same time BACCHUS LINE Sequence of any key Any sequence other than those described above skip the initial setting (displayed in case of start-up from key). INFO STAND BY s1 Press any key during the switching off state Push> Frame displayed until the key is released TURNING ON... (((((((()))))))) Welcome animation ((((CCHUS LI)))) Welcome animation BACCHUS LINE Welcome animation No key pressed Bypass the menu of initial setting; Immediate machine start-up Menu of initial setting LANGUAGE Press any key (e.g. “OK” key) ?OK/↓↑ ↓ +03°C_ ↑ +12°C S.40724 Rev 00 PRINCIPLE PRINCIPLE DIAGRAM – SINGLESINGLE-ZONE VERSION SP0 set point H0S,H0C hysteresis action hot/cold SL0,SH0 set point limits Sensor B ntc –50°C / +50°C Connected to input S3 OFB: Offset sensor B (Sensor A + Sensor B) SP0+H0S SP0 SP0-H0C COLD t HOT t Sensor A ntc –50°C / +50°C Connected to input S1 OFA: Offset sensor A PRINCIPLE PRINCIPLE DIAGRAM – DOUBLEDOUBLE-ZONE MULTIMULTI-TEMPERATURE TEMPERATURE VERSION Z2: High Zone (hot) SP2 set point zone 2 H2S,H2C hysteresis action hot/cold SL2,SH2 set point limits zone 2 Sensor B SP2+H2S Sensor B ntc –50°C / +50°C (sensor in hot zone) Connected to input S3 OFB: Offset sensor B SP2 SP2-H2C COLD_2 t Z1: Low Zone (Cold) SP1 set point zone 1 H1S,H1C hysteresis action hot/cold SL1,SL1 set point limits zone 2 HOT_2 t Sensor A SP1+H1S SP1 Sensor A ntc –50°C / +50°C (sensor in cold zone) Connected to input S1 OFA: Offset sensor A SP1-H1C COLD t HOT t S.40724 Rev 00 IMPORTANT NOTES (in case of double-zone) • The two adjustments are completely independent and parallel. • The calculation of the average times of Cold Action (compressor) is carried out only for zone 1. • The calculation of the percentage of compressor use is carried out only for zone 1. • The CPH failure (compressor time failure) is managed only for zone 1. • The counting of compressor hours is carried out only for zone 1. • The adjustment management in case of sensor failure is carried out only for zone 1. • In case of sensor failure for zone 2, the adjustment is disabled. • HACCP alarm management is carried out only for sensor of zone 1. SINGLE-TEMPERATURE OPERATION In case of single-zone, the adjusting temperature is calculated as the arithmetical average of readings from sensors A and B (including any possible offset) Adjusting temperature = [ Sensor_A (+OFA) + Sensor_B (+OFB) ] /2 The adjusting parameters for single-zone operation are: SetPoint = SP0; Hysteresis = H0S, H0C Anti-oscillation time = ADL; Adjusting delay = CCD Therefore: COLD ACTION enabled for Adjusting temperature >= SP0 + H0S COLD ACTION disabled for Adjusting temperature <= SP0 If H0S =0 COLD ACTION is always disabled HOT ACTION enabled for Adjusting temperature <= SP0 – H0C HOT ACTION disabled for Adjusting temperature >= SP0 If H0C =0 HOT ACTION is always disabled The setpoint programming limits are SL0 (Set point limit Low) and SH0 (Set point limit High) Exit Matrix: In case of single-zone, the exit matrix defined by parameters PU1, PU2, PU3, PU4, PU5, PU6 is used. The anti-oscillation timer is loaded to the value of parameter ADL upon enabling of the cold action, upon enabling of the hot action, upon disabling of the cold action and upon disabling of the hot action (upon enabling and upon disabling of all the actions). The anti-oscillation timer is only used upon enabling of the two cold and hot actions: the real enabling of the hot and cold actions only takes place when the anti-oscillation timer is elapsed. MULTI-TEMPERATURE OPERATION Zone 1 (low): Adjusting temperature = Sensor_A (+OFA) Adjusting parameters Zone 1: Set Point = SP1; Hysteresis = H1S, H1C; Anti-oscillation time= ADL Adjusting delay = CCD Therefore: COLD ACTION (zone 1) enabled for Adjusting temperature >= SP1 + H1S COLD ACTION (zone 1) disabled for Adjusting temperature <= SP1 If H1S =0 COLD ACTION (zone 1) is always disabled HOT ACTION (zone 1) enabled for Adjusting temperature <= SP1 – H1C HOT ACTION (zone 1) disabled for Adjusting temperature >= SP1 If H1C =0 HOT ACTION (zone 1) is always disabled The setpoint programming limits are SL1 (Set point limit Low) and SH1 (Set point limit High) Zone 2 (high): ): Adjusting temperature = Sensor_B (+OFB) Adjusting parameters Zone 2: Set Point = SP2; Hysteresis = H2S, H2C; Anti-oscillation time = ADL Adjusting delay = CCD Therefore: COLD ACTION (zone 2) enabled for Adjusting temperature >= SP2 + H2S COLD ACTION (zone 2) disabled for Adjusting temperature <= SP2 If H2S =0 COLD ACTION (zone 2) is always disabled S.40724 Rev 00 HOT ACTION (zone 2) enabled for Adjusting temperature <= SP2 – H1C HOT ACTION (zone 2) disabled for Adjusting temperature >= SP2 If H2C =0 HOT ACTION (zone 2) is always disabled The setpoint programming limits are SL2 (Set point limit Low) and SH2 (Set point limit High) Output Matrix: In case of double-zone, the output matrix defined by parameters PV1, PV2, PV3, PV4, PV5, PV6 is used. The anti-oscillation is managed as in single-zone; two different timers are used for each single adjustment (adjustment of zone 1 and adjustment of zone 2) Operation selection The parameter MOD selects the single- or double-zone operation. The same parameter enables or disables the menu for selecting the operating mode MOD =0 MOD =1 MOD =2 MOD =3 Single zone operation, menu for selecting the operating mode disabled Double zone operation, menu for selecting the operating mode disabled Single zone operation, menu for selecting the operating mode enabled Double zone operation, menu for selecting the operating mode enabled If the menu for selecting the operating mode is disabled, the machine operation can not be changed (unless by means of the parameter MOD in the service/parameter menu). If the menu for selecting the operating mode is enabled, the MOD value can be changed directly from the menu “Use”, in this case, MOD can be 2 or 3, according to the user’s selection. DEFROSTING MANAGEMENT During the defrosting activity, the adjusting actions on zone 1 and zone 2 are inhibited. All the adjusting actions on zone 1 and zone 2 remain inhibited until DRP seconds after completion of the defrosting (droptime). In the case of defrosting with reversal (DCM <>0) the output referred to the cooling action (on zone 1 if double-zone operation) remains forced active. The activation of the hot action on zone 1 or of the hot action on zone 2 resets the ITD hour counting. CONDENSE CONDENSER FAN MANAGEMENT The condenser fans start up upon enabling the Cold Action (of zone 1 in the case of double zone operation). The condenser fans stop 30 seconds after the end of the Cold Action (of zone 1 in the case of double zone operation). The heating action (Hot Action) start and the adjustment of the second zone (Cold Action zone 2 and Hot Action zone 2) do not interact with the management of the condenser fan. The management of the condenser fans during the defrosting activity follows the trend set up from parameter FOP. EVAPORATOR FAN MANAGEMENT The evaporator fans are managed according to the state of the Cold Action (of zone 1 in the case of double zone operation). The heating action (Hot Action) start and the adjustment of the second zone (Cold Action zone 2 and Hot Action zone 2) do not interact with the management of the evaporator fan. The management of the evaporator fans during the defrosting activity follows the trend set up from parameter FOP Evaporator fans in relation with the evaporator sensor temperature Regardless to the state of the parameter FOP, the output to the evaporator fans is forced off if the evaporator sensor temperature is higher than FAS +5°C. Evaporator fan output forced off if evaporator temperature >= FAS +5°C Evaporator fan output can be switched on if evaporator temperature <= FAS Evaporator fans inde independent from compressor Set FOP =1 to enable the output to the evaporator fans independent from the compressor state (cooling action zone 1). This way, the output is always enabled (stated that evaporator temperature is lower than FAS). Evaporator fans parallel to compressor Set FOP =5 to enable the output to the evaporator fans dependent from the compressor state (cooling action zone 1). This way, the output is always enabled if the cooling action zone 1 is enabled, contrary, it is disabled if the cooling action zone 1 is disabled. S.40724 Rev 00 OUTPUT MATRIX MATRIX num 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 description No action (connected output always off) Cold action zone 1 (Compressor) Cold action zone 1 denied (Compressor) Neutral zone 1 Hot action zone 1 Hot action zone 1 denied Cold action zone 2 Cold action zone 2 denied Neutral zone Z2 Hot action zone 2 Hot action zone 2 denied Defrosting Defrosting denied Evaporator fans Condenser fans Humidification De-humidification Auxiliary output Cell Light Output (from micro-door input or key) Alarm Alarm denied Printer supply output Switching on state Switching off state Cold action zone 1 or De-humidification Hot action zone 1 or humidification Cold action zone 1 or Cold action zone 2 Hot action zone 1 or Hot action zone 2 Water level microswitch triggered Hot action zone 1 or Defrosting Hot action zone 1 or Evaporator fans The output parameterisation is defined PU1,PU2,PU3,PU4,PU5,PU6 in case of PV1,PV2,PV3,PV4,PV5,PV6 in case of double-zone. • • • • • • by parameters single-zone, or PU1 and PV1 define the use of RL6 (relays 30A) PU2 and PV2 define the use of RL5 (relays 8A) referred to contacts U2B (na) and U2A (nc) PU3 and PV3 define the use of RL3 (relays 5A) referred to contact U3 PU4 and PV4 define the use of RL2 (relays 5A) referred to contact U4 PU5 and PV5 define the use of RL1 (relays 5A) referred to contact U5 PU6 and PV6 define the use of RL4 (relays 5A) referred to contact U6 The value of the parameter PUx and PVx and meaning thereof are listed in the following table: S.40724 Rev 00 PARAMETRI HTWL BACCHUS LINE Code. 11.88.074 - 11.88.113 -- 5147.08 P DESCRIZIONE 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 Indirizzo network seriale SuperParametro di impostazione della modalita' di funzionamento Parametro di configurazione ingressi (Input SetuP) Parametro di configurazione uscite (Output SetuP) Opzioni di visualizzazione Intervallo stringa titolo Opzioni di microporta Minuti di apertura porta critici Offset Sonda_A (PT_0 detta S1) Monotemperatura Offset Sonda_B (PT_2 detta S3) Monotemperatura Massima differenza di temperatura ammessa [Sb-Sa] Tempo di ritardo allarme ri ricircolo [Sb-Sa] Set Point (nel caso di funzionamento monozona) Isteresi azione raffreddante (nel caso di funzionamento monozona) Isteresi azione riscaldante (nel caso di funzionamento monozona) Limite minimo di impostazione di SET_0 Limite massimo di impostazione di SET_0 Offset Sonda_A (PT_0 detta S1) Multitemperatura Offset Sonda_B (PT_2 detta S3) Multitemperatura Set Point Zona 1 (zona fredda) Isteresi azione raffreddante Zona 1 (zona fredda) Isteresi azione riscaldante Zona 1 (zona fredda) Limite minimo di impostazione di SET_1 Limite massimo di impostazione di SET_1 Set Point Zona 2 (zona calda) Isteresi azione raffreddante Zona 2 (zona calda) Isteresi azione riscaldante Zona 2 (zona calda) Limite minimo di impostazione di SET_2 Limite massimo di impostazione di SET_2 Calibrazione sonda Umidita' Modalità di regolazione di umidificazione/deumidificazione Set di Umidità Isteresi di attivazione uscita di deumidificazione Isteresi di attivazione uscita di umidificazione Tempo di ritardo azione ventole condensatore in termostatazione Tempo minimo tra accensioni del compressore (antipendolamento) Tempo di ritardo regolazione dopo l'accensione Ritardo di regolazione Tempo compressore acceso durante guasto compressore Tempo compressore spento durante guasto compressore Percentuale Limite di utilizzo compressore (attivazione tempi CON-COF) Tempo di sgocciolamento dopo lo sbrinamento Funzionamento del compressore durante lo sbrinamento Opzioni di attivazione sbrinamento Intervallo di attivazione sbrinamenti Defrost time Out Temperatura di fine sbrinamento (riferito alla sonda evaporatore) Intervallo di tempo degli sbrinamenti suplementari Opzione di attivazione ventole evaporatore/condensatore Set point ventola evaporatore Ritardo attivazione ventola evaporatore dopo lo sbrinamento Set point ventola evaporatore durante lo sbrinamento Isteresi di attivazione/disattivazione fan evap in Warm-Air-Lock Differenziale di allarme di bassa temperatura Differenziale di allarme di alta temperatura Ritardo intervento allarme Ritardo di allarme dopo accensione, dopo sbrinamento, durante carico cella Opzioni di termoregistrazione Intervallo di campionamento termoregistrazione Numero di cicli da eseguire nella fase_1 e nella fase_7 di INFOTEST Numero di cicli di stabilizzazione fase_0 e nella fase_6 di INFOTEST Temperatura di Pull-up fase_4 in Infotest Modalita' di stampa Configurazione Uscita U1 (rele' 30A) - Funzionamento Monozona Configurazione uscita U2 (rele' 8A) - Funzionamento Monozona Configurazione uscita U3 (rele' 5A) - Funzionamento Monozona Configurazione uscita U4 (rele' 5A) - Funzionamento Monozona Configurazione uscita U5 (rele' 5A) - Funzionamento Monozona Configurazione uscita U6 (rele' 5A) - Funzionamento Monozona Configurazione Uscita U1 (rele' 30A) - Funzionamento Bizona Configurazione uscita U2 (rele' 8A) - Funzionamento Bizona Configurazione uscita U3 (rele' 5A) - Funzionamento Bizona Configurazione uscita U4 (rele' 5A) - Funzionamento Bizona Configurazione uscita U5 (rele' 5A) - Funzionamento Bizona Configurazione uscita U6 (rele' 5A) - Funzionamento Bizona PASSWORD S.39582 m M U BACCHUS 32/40/60 0 0 0 0 0 0 0 2 -15.0 -15.0 1.0 1.0 -30 0.0 0.0 -30 -30 -15.0 -15.0 -30 0.0 0.0 -30 -30 -30 0.0 0.0 -30 -30 -30 0 20 0 0 0 15 15 1 2 2 20 0 0 0 1 2 -50 0 0 -50 0 -50 0.5 -30 2 2 2 0 1 1 1 -30 0 0 0 0 0 0 0 0 0 0 0 0 0 0 99 3 255 255 255 255 2 60 15.0 15.0 20.0 250.0 30 15.0 15.0 30 30 15.0 15.0 30 15.0 15.0 30 30 30 15.0 15.0 30 30 30 15 90 20 20 240 240 240 120 255 255 99 255 60 255 255 255 50 60 255 50 255 50 5.0 -2 60 255 255 9 120 5 5 30 3 255 255 255 255 255 255 255 255 255 255 255 255 255 flg flg flg flg flg sec flg min °C/°F °C/°F °C/°F min °C/°F °C/°F °C/°F °C/°F °C/°F °C/°F °C/°F °C/°F °C/°F °C/°F °C/°F °C/°F °C/°F °C/°F °C/°F °C/°F °C/°F % flg % % % min sec sec sec min min % sec min flg hrs min °C/°F min flg °C/°F sec °C/°F °C/°F °C/°F °C/°F min min flg min flg flg °C/°F flg flg flg flg flg flg flg flg flg flg flg flg flg flg 1 3 0 1 138 255 2 4 0 0 7 250 12 1 1.5 2 20 0 0 3 1 4 2 8 18 3 1 12 20 0 0 60 0 0 15 240 60 30 6 5 98 180 0 5 6 90 6 0 3 45 15 1 1.5 -5 5 90 120 0 1 3 3 15 0 1 4 13 18 29 0 1 9 32 18 29 0 7 Redatto: F.Viarino Rev.09- 31-01-08 Controllato: Fossati Firmware 5147-08 ADR MOD ISP OSP VOP MES DIN DOO OMA OMB DTX DTD SP0 H0S H0C SL0 SH0 ODA ODB SP1 H1S H1C SL1 SH1 SP2 H2S H2C SL2 SH2 HPO URM RH% HRH HRL CND ADL ADS CCD CON COF CPH DRP DCM DOP ITD DTO DTE DEO FOP FAS FAD FSD HYW ALL ALH ALD ADD LOG SPT CYC STA ETT PRT PU1 PU2 PU3 PU4 PU5 PU6 PV1 PV2 PV3 PV4 PV5 PV6 Modificato: CND (era 30);CCD (era 4); CON (era 4); COF (era 4); ADL (era 180)