Download Trane XV18 Install Manual
Transcript
Installer’s Guide Variable Speed ComfortLink™ ™ II Heat Pumps and Air Conditioners 4TWV8024A1000A 4TWV8036A1000A 4TWV8037A1000A 4TWV8048A1000A 4TWV8049A1000A 4TWV8060A1000A 4TTV8024A1000A 4TTV8036A1000A 4TTV8037A1000A 4TTV8048A1000A 4TTV8060A1000A N o t e : “Graphics in this document are for representation only. Actual model may differ in appearance.” Scan to see help videos on this product S A F E T Y WA R N I N G Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment. October 2014 18-BC92D1-1D-EN SAFETY SECTION — OUTDOOR I m p o rt a n t — This document contains a wiring diagram and service information. This is customer property and is to remain with this unit. Please return to service information pack upon completion of work. WA R N I N G H A Z A R D O U S VO LTA G E ! F a i l u r e t o f o l l o w t h i s Wa r n i n g c o u l d r e s u l t i n p r o p e rt y d a m a g e , s e v e r e p e r s o n a l i n j u r y, o r d e a t h . D i s c o n n e c t a l l e l e c t r i c p o w e r, i n c l u d i n g r e m o t e di sc o nne c ts be for e s erv i c in g. Fo ll ow p rop er l o ck o u t / t a g o u t p r o c e d u r e s t o e n s u r e t h e p o w e r c a n n o t b e i n a d v e rt e n t l y e n e r g i z e d . WA R N I N G R E F R I G E R A NT O I L ! A n y a tt e m p t t o r e p a i r a c e n t r a l a i r c o n d i t i o n i n g p r o d u c t m a y r e s u l t i n p r o p e rt y d a m a g e , s e v e r e p e r s o n a l i n j u r y, o r d e a t h . T h e s e u n i t s u s e R - 4 10 A r e f r i g e r a n t w h i ch o p e r a t e s at 50 to 70% higher pressures than R-22. Use only R - 4 10 A a p p r o v e d s e r v i c e e q u i p m e n t . R e f r i g e r a n t c y l i n d e r s a r e p a i n t e d a “ R o s e” c o l o r t o i n d i c a t e the type of refrigerant and may contain a “dip” t u b e t o a l l o w f o r ch a r g i n g o f l i q u i d r e f r i g e r a n t i n t o t h e s y s t e m . A l l R - 4 10 A s y s t e m s w i t h v a r i a b l e speed compressor s use a PVE oil that readily a b s o r b s m o i s t u r e f r o m t h e a t m o s p h e r e . To l i m i t thi s “ hyg roscop ic” a cti on , th e syste m sh oul d remain sealed whenever possible. If a system has been open to the atmosphere for more than 4 hour s, the compressor oil must be replaced. Never b r e a k a v a c u u m w i t h a i r a n d a l w a y s ch a n g e t h e driers when opening the system for component replacement. C AU T I O N H OT S U R F A C E ! M ay ca us e m i no r t o s e v ere bur ni ng. Fai l ure t o f o l l o w t h i s C a u t i o n c o u l d r e s u l t i n p r o p e rt y d a m a g e o r p e r s o n a l i n j u r y. D o n o t t o u ch t o p o f c o m p r e s s o r. CAUTION C O NTA I N S R E F R I G E R A NT ! Fa il u re to f ol lo w pro pe r p roc e du res c an re s ul t in per sonal illness or injury or severe equipment damage. Syst em cont ains oil and refrigerant u nder high p ressur e. Re cov e r re fr ig era nt to r el i ev e pr essur e before opening system. CAUTION GR OUNDI NG R E QUIR E D! Fa il u re to i ns pe c t or us e p rop er se rv i c e too ls m ay r e s u l t i n e q u i p m e n t d a m a g e o r p e r s o n a l i n j u r y. R e c o n n e c t a l l g r o u n d i n g d e v i c e s . A l l p a rt s o f t h i s product that are capable of conducting electrical c u rr e n t a r e g r o u n d e d . I f g r o u n d i n g w i r e s , s c r e w s , s tr ap s, cl i ps , n uts , o r wa s he r s us e d to c ompl e te a p at h t o gro und a re r emov ed f or se rv ice , th ey must be returned to their original position and properly fastened. WA R N I N G S E RV I C E VA LV E S ! Fa il u re to f ol lo w thi s wa rn in g w i ll res u lt i n ab rup t r e l e a s e o f s y s t e m ch a r g e a n d m a y r e s u l t i n p e r s o n a l i n j u r y a n d / o r p r o p e rt y d a m a g e . Extreme caution should be exercised when o p e n i n g t h e L i q u i d L i n e S e r v i c e Va l v e . Tu r n v a l v e s t e m c o u n t e r c l o ck w i s e o n l y u n t i l t h e s t e m contacts the rolled edge. No torque is required. WA R N I N G B RA ZI NG RE QUI RE D! Fa il u re to i ns pe c t li n es or us e pr ope r s e rv ic e t oo ls may result in equipment damage or per sonal i n j u r y. i f u s i n g e x i s t i n g r e f r i g e r a n t l i n e s m a k e c e rt a i n t h a t a ll jo in t s ar e b r a ze d , n o t s o l d e r e d . WA R N I N G H I G H L E A K A G E C U R R E NT ! F a i l u r e t o f o l l o w t h i s Wa r n i n g c o u l d r e s u l t i n p r o p e rt y d a m a g e , s e v e r e p e r s o n a l i n j u r y, o r d e a t h . E a rt h c o n n e c t i o n e s s e n t i a l b e f o r e c o n n e c t i n g e l e c t r i c a l s u p p l y. ©2014 Trane 18-BC92D1-1D-EN SA F E T Y S E C T I ON — O UT DO O R WARNING 400 VOLTS CAUTION - HO T S URFACE ELECTRICAL HAZARD Fa ilu re to fo llo w th is wa rn in g coul d re s u lt in p e rs o n a l in ju ry o r d e a th . WAIT TWO (2) MINUTES a fte r d is co n n e ctin g p o w e r p rio r to to u ch in g e le ctrica l components as they may hol d a d a n g e ro u s ch a rg e o f 400VDC, th e n ve rify DC Vo lta g e is le s s th a n 42 VDC a t inve rte r te s t p o in ts la b e le d +VDC and -VDC befor e ser vicin g b o a rd . +VDC -VDC + VDC and - VDC Approved Combinations for Variable Speed Units • • • • • TZONE 850 Comfort Control, or TZONE 950 with Software Version 3.0 or Higher TAM8C or later models XC80 Furnace XC95m Furnace Approved System Accessories Note: See AHRI directory for approved indoor and outdoor model combinations. Only Trane coils and air handlers are approved for use with variable speed outdoor units. Table 1. Scan to see an overview video about the IVSC Board Operating Range Cooling 55° F to 120° F Heating -10° F to 66° F 18-BC92D1-1D-EN 3 Table of Contents Unit Location Considerations . . . . . . . . . . . . . . . 5 Electrical — High Voltage . . . . . . . . . . . . . . . . . . 18 ......................................... 6 Coastal Considerations . . . . . . . . . . . . . . . . 7 Integrated Variable Speed Control Board LED Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Unit Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Setting Up the Unit . . . . . . . . . . . . . . . . . . . . . . . 8 Refrigerant Line Considerations . . . . . . . . . . . . 9 Refrigerant Line Brazing . . . . . . . . . . . . . . . . . . . 12 Refrigerant Line Leak Check . . . . . . . . . . . . . . . 14 Refrigerant Line and Indoor Coil Evacuation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Charging: Weigh-In Method . . . . . . . . . . . . . . . 15 Service Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Start Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 System Charge Adjustment . . . . . . . . . . . . . . . 21 Subcool Charging Correction Charts. . . . . . . 22 Refrigerant Charging Chart . . . . . . . . . . . . . . . 22 Charging the Unit. . . . . . . . . . . . . . . . . . . . . . . . . . 23 Communicating Display Assembly (CDA) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Defrost Control (Heat Pump only). . . . . . . . . . 26 Checkout Procedures . . . . . . . . . . . . . . . . . . . . . . 27 Electrical — Low Voltage . . . . . . . . . . . . . . . . . . 17 4 18-BC92D1-1D-EN Unit Location Considerations Table 2. Unit Dimensions and Weight Models H x D x W (in) Weight * (lb) 4TWV8024A 41 x 30 x 33 195 4TWV8036A 41 x 30 x 33 208 4TWV8037A 41 x 34 x 37 229 4TWV8048A 41 x 34 x 37 234 4TWV8049A 41 x 34 x 37 241 4TWV8060A 45 x 34 x 37 250 4TTV8024A 41 x 30 x 33 196 4TTV8036A 41 x 30 x 33 207 4TTV8037A 41 x 34 x 37 225 4TTV8048A 41 x 34 x 37 245 4TTV8060A 45 x 34 x 37 250 W H * Weight values are estimated (uncrated). • • When mounting the outdoor unit on a roof, be sure the roof will support the unit’s weight. Properly selected isolation is recommended to alleviate sound or vibration transmission to the building structure. D Table 3. Refrigerant Line and Service Valve Connection Sizes Rated Line Sizes Model Service Valve Connection Sizes Vapor Line Liquid Line Vapor Line Connection Liquid Line Connection 4TWV8024A 5/8 (a) 3/8 5/8 3/8 4TWV8036A 3/4 (a) 3/8 3/4 3/8 4TWV8037A 3/4 (a) 3/8 3/4 3/8 4TWV8048A 7/8 (a) 3/8 7/8 3/8 4TWV8049A 7/8 (a) 3/8 7/8 3/8 4TWV8060A 1—1/8 (b) 3/8 7/8 3/8 4TTV8024A 5/8 (a) 3/8 5/8 3/8 4TTV8036A 3/4 (a) 3/8 3/4 3/8 4TTV8037A 3/4 (a) 3/8 3/4 3/8 4TTV8048A 7/8 (a) 3/8 7/8 3/8 4TTV8060A 1—1/8 (c) 3/8 7/8 3/8 Sta n d a rd Lin e Se t 150’ Ma x Lin e Le n g th 100’ Ma x Lin e Le n g th 50’ Ma x Lin e Lift Re fe r to (a ), (b ), a n d (c) fo o tn o te s fo r s p e cific m o d e l d e ta ils 50 Ma x Lin e Lift (a) (b) (c) 100’ Ma x Lin e Le n g th The max length of refrigerant lines from outdoor to indoor unit MUST NOT exceed 150 feet. The max vertical change MUST NOT exceed 50 feet. The max length of refrigerant lines from the outdoor to indoor unit MUST NOT exceed 80 feet. The max vertical change MUST NOT exceed 10 feet. The max length of refrigerant lines from outdoor to indoor unit MUST NOT exceed 80 feet. The max vertical change MUST NOT exceed 25 feet. 18-BC92D1-1D-EN 5 Unit Location Considerations Table 4. Alternate Refrigerant Line and Service Valve Connection Sizes Service Valve Connection Sizes Alternate Line Sizes Model Vapor Line Liquid Line Vapor Line Connection Liquid Line Connection 3/4" (a) 5/16" 5/8" 3/8" 5/8" (a) 5/16" 3/4" 3/8" 7/8" (b) 5/16" 3/4" 3/8" 5/8" (a) 5/16" 3/4" 3/8" 7/8" (b) 5/16" 3/4" 3/8" 4TWV8048A 3/4" (a) 3/8" 7/8" 3/8" 4TWV8049A 3/4" (a) 3/8" 7/8" 3/8" 3/4" (a) 3/8" 7/8" 3/8" 7/8" (a) 3/8" 7/8" 3/8" 4TWV8024A 4TWV8036A 4TWV8037A 4TWV8060A Service Valve Connection Sizes Alternate Line Sizes Model 4TTV8024A 4TTV8036A 4TTV8048A 4TTV8060A (a) (b) 6 Vapor Line Liquid Line Vapor Line Connection Liquid Line Connection 3/4" (a) 5/16" 5/8" 3/8" 5/8" (a) 5/16" 3/4" 3/8" 7/8" (b) 5/16" 3/4" 3/8" 3/4" (a) 3/8" 7/8" 3/8" 3/4" (a) 3/8" 7/8" 3/8" 7/8" (a) 3/8" 7/8" 3/8" The max length of refrigerant lines from outdoor to indoor unit MUST NOT exceed 150 feet. The max vertical change MUST NOT exceed 50 feet. The max length of refrigerant lines from outdoor to indoor unit MUST NOT exceed 80 feet. The max vertical change MUST NOT exceed 25 feet. 18-BC92D1-1D-EN Unit Location Considerations Table 5. Suggested Locations for Best Reliability • • • • • • • • Ensure the top discharge area is unrestricted for at least 5 feet above the unit. Provide at least 3 feet clearance in front of the control box (access panels) and any other side requiring service. Do not locate close to bedrooms as operational sounds may be objectionable. Avoid locations near windows and similar areas where condensation and freezing defrost vapor can annoy a customer. Position the outdoor unit a minimum of 12” from any wall or surrounding shrubbery to ensure adequate airflow. Outdoor unit location must be far enough away from any structure to prevent excess roof runoff water or icicles from falling directly on the unit. Avoid Install Near Bedrooms Min 5’ Unrestricted Min. 12” to Shrubbery Min 3’ Unrestricted Acce ss Panel Position the outdoor unit a minimum of 12” from any wall or surrounding shrubbery to ensure adequate airflow. Outdoor unit location must be far enough away from any structure to prevent excess roof runoff water or icicles from falling directly on the unit. Min. 12” to Shrubbery Min. 12” to Wa ll Table 6. Cold Climate Considerations (Heat Pump Only) Note: It is recommended that these precautions be taken for units being installed in areas where snow accumulation and prolonged below-freezing temperatures occur. • • Units should be elevated 3–12 inches above the pad or rooftop, depending on local weather. This additional height will allow drainage of snow and ice melted during defrost cycle prior to its refreezing. Ensure that drain holes in unit base pan are not obstructed, preventing drainage of defrost water. If possible, avoid locations that are likely to accumulate snow drifts. If not possible, a snow drift barrier should be installed around the unit to prevent a build-up of snow on the sides of the unit. Min . 12” Snow Ba rrie r Snow L egs 3-12” Elevation Pa d Coastal Considerations If installed within one mile of salt water, including seacoasts and inland waterways, models without factory supplied Seacoast Salt Shields require the addition of BAYSEAC001 (Seacoast Kit) at installation time. 18-BC92D1-1D-EN 7 Unit Preparation 1. Check for damage and report promptly to the carrier any damage found to the unit. 2. To remove the unit from the pallet, remove tabs by cutting with a sharp tool. Setting Up the Unit Table 7. Pad Installation When installing the unit on a support pad, such as a concrete slab, consider the following: 8 • The pad should be at least 1” larger than the unit on all sides. • The pad must be separate from any structure. • The pad must be level. • The pad should be high enough above grade to allow for drainage. • The pad location must comply with National, State, and Local codes. 18-BC92D1-1D-EN Refrigerant Line Considerations Table 8. Required Refrigerant Line Length Determine required line length and lift. You will need this to determine the subcooling charging corrections later in the installation process. Total Line Length = ___________________________Ft. Total Vertical Change (lift) = ____________________Ft. Line Le ngth Table 9. Refrigerant Line Insulation Important: The Vapor Line must always be insulated. DO NOT allow the Liquid Line and Vapor Line to come in direct (metal to metal) contact. Liquid Li n e Va p o r Lin e Insulati o n Note: The gas line must always be insulated. Insulating the liquid line through attic spaces may benefit system performance by minimizing heat gain in the liquid line. 18-BC92D1-1D-EN 9 Ref ri g er an t Li n e C o n s i d er at i o n s Table 10. Reuse Existing Refrigerant Lines C AU T I O N R E F R I G E R A NT ! Fai l ure t o in sp ec t o r u se pro pe r s er vi c e to ol s m a y r e s u l t i n e q u i p m e n t d a m a g e o r p e r s o n a l i n j u r y. I f u s i n g e x i s t i n g r e f r i g e r a n t l i n e s m a k e c e rt a i n t h a t all joints are brazed, not soldered. For retrofit applications, where the existing indoor evaporator coil and/or refrigerant lines will be used, the following precautions should be taken. • Ensure that the indoor evaporator coil and refrigerant lines are the correct size. • Ensure that the refrigerant lines are free of leaks, acid, and oil. Important: For more information, see publication number SSAPG006–EN Table 11. Refrigerant Line Routing Precautions Important: Comply with National, State, and Local Codes when isolating line sets from joists, rafters, walls, or other structural elements. Important: Take precautions to prevent noise within the building structure due to vibration transmission from the refrigerant lines. For Example: • When the refrigerant lines must be fastened to floor joists or other framing in a structure, use isolation type hangers. • Isolation hangers should also be used when refrigerant lines are run in stud spaces or enclosed ceilings. • Where the refrigerant lines run through a wall or sill, they should be insulated and isolated. • Isolate the lines from all duct work. • Minimize the number of 90° turns. Table 12. Isolation From Joist/Rafter 8 Fe e t Ma xim u m J o is t/Ra fte r Is o la to r Lin e Se t S id e Vie w 8 Fe e t Ma xim u m Secure Vapor Line from joists using isolators every 8 ft. Secure Liquid Line directly to insulated Vapor Line using tape, wire, or other appropriate method every 8 ft. 10 18-BC92D1-1D-EN Re fr i g e ra n t L i n e C o n s i d e ra ti o n s Table 13. Isolation In Wall Spaces 8 Fe e t Ma xim u m Wa ll Is o la to r Lin e Se t 8 Fe e t Ma xim u m S id e Vie w Secure Vapor Line from joists using isolators every 8 ft. Secure Liquid Line directly to insulated Vapor Line using tape, wire, or other appropriate method every 8 ft. Table 14. Isolation Through Wall Wa ll Du ct Wo rk Se a la n t In s u la tio n Va p o r Lin e Is o la to r Lin e Se t DO NOT h a n g lin e s e ts fro m d u ct w o rk 18-BC92D1-1D-EN 11 Refrigerant Line Brazing Table 15. Braze the Refrigerant Lines 1. Remove caps or plugs. Use a deburring tool to debur the pipe ends. Clean both internal and external surfaces of the tubing using an emery cloth. 2. Remove the pressure tap cap and valve core from each service valves. 3. Purge the refrigerant lines and indoor coil with dry nitrogen. 12 18-BC92D1-1D-EN Re fr ig er a n t L in e B ra z i n g Table 15. Braze the Refrigerant Lines (continued) 4. Wrap a wet rag around the valve body to avoid heat damage and continue the dry nitrogen purge. 5. Braze the refrigerant lines to the service valves. a. 6. For Units shipped with a field-installed external drier, check liquid line filter drier’s directional flow arrow to confirm correct direction of refrigeration flow (away from outdoor unit and toward evaporator coil) as illustrated. Braze the filter drier to the Liquid Line. Continue the dry nitrogen purge. Do not remove the wet rag until all brazing is completed. Important: Remove the wet rag before stopping the dry nitrogen purge. 3-4” fro m va lve Note: Precautions should be taken to avoid heat damage to base pan during brazing. It is recommended to keep the flame directly off of the base pan. 7. Replace the pressure tap valve cores after the service valves have cooled. 18-BC92D1-1D-EN 13 Refrigerant Line Leak Check Table 16. Check for Leaks 1. Pressurize the refrigerant lines and evaporator coil to 150 PSIG using dry nitrogen. 2. Check for leaks by using a soapy solution at each brazed location. 150 PSIG Note: Remove nitrogen pressure and repair any leaks before continuing. Refrigerant Line and Indoor Coil Evacuation I m p o rt a n t : Do not open the service valves until the refrigerant lines and indoor coil leak check and evacuation are complete. 1. Evacuate until the micron gauge reads no higher than 350 microns, then close off the valve to the vacuum pump. 0350 Microns ON OFF 2. Observe the micron gauge. Evacuation is complete if the micron gauge does not rise above 500 microns in one (1) minute. 3. When evacuation is complete, blank off the vacuum pump and micron gauge, and close the valves on the manifold gauge set. 14 1 MIN. 18-BC92D1-1D-EN Charging: Weigh-In Method Weigh-In Method can be used for the initial installation, or anytime a system charge is being replaced. Weigh-In Method can also be used when power is not available to the equipment site or operating conditions (indoor/outdoor temperatures) are not in range to verify with the subcooling charging method. Table 17. Heat Pumps A Model 024 036 B C Factory Charge 7 lb. 8 lb. Table 18. Air Conditioners 6 oz. 3 oz. D A B C D Charge adder for Indoor Coil Charge multiplier for interconnecting refrigerant tube length 0.6 oz/ft Charge adder for Indoor Coil Charge multiplier for interconnecting refrigerant tube length Model 6 oz. 0.6 oz/ft 024 7 lb. 6 oz. 6 oz. 0.6 oz/ft 036 7 lb. 14 oz. 7 oz. 0.6 oz/ft 9 lb. 6 oz. 12 oz. 0.6 oz/ft 8 oz. Factory Charge 037 9 lb. 8 oz. 12 oz. 0.6 oz/ft 037 048 9 lb. 13 oz. 13 oz. 0.6 oz/ft 048 11 lb. 1 oz. 1 lb., 0 oz. 0.6 oz/ft 049 10 lb. 12 oz. 15 oz. 0.6 oz/ft 060 11 lb. 14 oz. 1 lb., 2 oz. 0.6 oz/ft 060 11 lb. 14 oz. 1 lb., 2 oz. 0.6 oz/ft Table 19. New Installations — Calculating Charge using the Weigh-In method 1. Measure in feet the distance between the outdoor unit and the indoor unit and record on Line 1. Include the entire length of the line from the service valve to the IDU. New Installation Weigh-In Method Worksheet 2. Enter the charge multiplier from Column D. 2. Value from Column D x ________________________ 3. Multiply the total length of refrigerant tubing (Line 1) times the value on Step 2. Record the result on Line 3 of the Worksheet. 3. Step 1 x Step 2 = ________________________ 1. Line Length (ft) ________________________ 4. Charge Adder (column C) + ________________________ 4. Locate the outdoor equipment size in Column A. Record the value shown in Column C of Table 16 for Heat Pumps or Table 17 for Air Conditioners. 5. Refrigerant (Steps 3+4) = ________________________ 5. Add the values from Step 3 and Step 4 and record the resulting value. This is the amount of refrigerant to weigh-in prior to opening the service valves. Table 20. Sealed-System Repairs — Calculating Charge using the Weigh-In method. 1. Measure in feet the distance between the outdoor unit and the indoor unit and record on Line 1. Include the entire length of the line from the service valve to the IDU. New Installation Weigh-In Method Worksheet 1. Line Length (ft) 2. Enter the charge multiplier from Column D. 2. Value from Column D x ________________________ 3. Multiply the total length of refrigerant tubing (Line 1) times the value on Line 2. Record the result on Line 3 of the Worksheet. 3. Step 1 x Step 2 = ________________________ 4. Charge Adder (column C) + ________________________ ________________________ 4. Locate the outdoor equipment size in Column A. Record the value shown in Column C of Table 16 for Heat Pumps or Table 17 for Air Conditioners. 5. Factory Charge (column B) + ________________________ 5. Record the value in Column B to Line 5 of the Worksheet. 6. Refrigerant (Steps 3+4+5) = ________________________ 6. Add the values from Step 3, Step 4, and Step 5 and record the resulting value on Line 6. This is the amount of refrigerant to weigh-in. Note: The only mode approved for setting or validating system charge is using Charging Mode-Cooling. Charging Mode-Cooling is a variable speed test mode found in the 850/950 comfort control Technician Menu. Outdoor Temperature must be between 55°F and 120°F with Indoor Temperature kept between 70°F and 80°F. 18-BC92D1-1D-EN 15 Service Valves Table 21. Open the Gas Service Valve Important: Leak check and evacuation must be completed before opening the service valves. Cap Note: Do not vent refrigerant gases into the atmosphere. 1. Remove valve stem cap. 2. Using a wrench, turn valve stem 1/4 turn counterclockwise to the fully open position. 3. Replace the valve stem cap to prevent leaks. Tighten finger tight plus an additional 1/6 turn. 1/4 Turn Only Counterclockwise for Full Open Position Valve Stem Unit Side of Valve Pressure Tap Port Gas Line Connection Table 22. Open the Liquid Service Valve Cap WA R N I N G S E RV I C E VA LV E S ! Fai l ure t o fol l ow th is war ni ng wi l l re s ul t in a bru pt r e l e a s e o f s y s t e m ch a r g e a n d m a y r e s u l t i n p e r s o n a l i n j u r y a n d / o r p r o p e rt y d a m a g e . Extreme caution should be exercised when o p e n i n g t h e L i q u i d L i n e Se r v i c e Va l v e . Tu r n v a l v e s t e m c o u n t e r c l o ck w i s e o n l y u n t i l t h e s t e m contacts the rolled edge. No torque is required. Un it S id e of Se rvice Va lve 3/16” He x Wre n ch Ro lle d Ed g e to Ca p tiva te S te m Important: Leak check and evacuation must be completed before opening the service valves. 4. Remove service valve cap. 5. Fully insert 3/16” hex wrench into the stem and back out counterclockwise until valve stem just touches the rolled edge (approximately five (5) turns). 6. Replace the valve cap to prevent leaks. Tighten finger tight plus an additional 1/6 turn. He x He a d e d Va lve Sys te m Se rvice Po rt 16 18-BC92D1-1D-EN Electrical — Low Voltage Table 23, p. 17defines the size and combined total maximum length of low voltage wiring from the outdoor unit, to the indoor unit, and to the thermostat. Note: The use of color coded low voltage wire is recommended to simplify connections between the outdoor unit, the control, and the indoor unit. Note: The maximum total cable length for the entire comfort control communicating system is 500 ft. 18 AWG. Table 23. Low Voltage Maximum Wire Length CONTROL WIRING WIRE SIZE MAX. WIRE LENGTH 18 AWG 500 Ft. Combined Table 24. Low Voltage Hook-up Diagrams Figure 1. Fully Communicating System Co m m u n ica tin g Ou td o o r Un it Neatl y b u n d le a ll lo w vo lta g e w ire s a s s h o w n . Com m u n ica tin g Com for t Cont rol No te 4 D R B Bro w n Re d Blu e Com m u n ica tin g Indoo r Unit R BK D Y1 Y2 G W1 W2 W3 B O Bro w n D - No te 3 No te 1 & No te 2 Blu e Re d No te 5 On ly u s e d fo r Lo a d S h e d (Ca p o ff if not u s e d ) B - Blue Fiel d w irin g 1. 2. 3. 4. 5. In communicating mode, unused terminals are non-functional. Do not use. Terminals present will vary by indoor model. “D” is the data line. Installer to select a wire color. If a 3rd party condensate overflow switch is installed, it should be wired in series with R to the thermostat or connected to the External Switch terminals on the AFC. See External Switch wiring section in the air handler Installer’s Guide. Wire present only on Variable Speed Outdoor Units. Note: Anti-oxidizing grease is supplied in the documentation package for use when making low voltage field wiring connections at the outdoor unit. Apply grease to field wiring before installing wire caps to protect these connections from corrosion. 18-BC92D1-1D-EN 17 Electrical — High Voltage Table 25. High Voltage Power Supply WA R N I N G L I V E E L E C T R I C A L C O M P O N E NT S ! F a i l u r e t o f o l l o w t h i s Wa r n i n g c o u l d r e s u l t i n p r o p e rt y d a m a g e , s e v e r e p e r s o n a l i n j u r y, o r d e a t h . Fol lo w a ll el e ct ri ca l s a fe ty p re ca ut io ns whe n exposed to li ve electrical components. It may be necessary to work with li ve electrical components during installation, testing, servicing, and troubleshooting of this product. The high voltage power supply must agree with the equipment nameplate. Power wiring must comply with national, state, and local codes. Follow instructions on unit wiring diagram located on the inside of the control box cover and in the Service Facts document included with the unit. Table 26. High Voltage Disconnect Switch WA R N I N G H I G H L E A K A G E C U R R E NT ! F a i l u r e t o f o l l o w t h i s Wa r n i n g c o u l d r e s u l t i n p r o p e rt y d a m a g e , s e v e r e p e r s o n a l i n j u r y, o r d e a t h . E a rt h c o n n e c t i o n e s s e n t i a l b e f o r e c o n n e c t i n g e l e c t r i c a l s u p p l y. Install a separate disconnect switch at the outdoor unit. For high voltage connections, flexible electrical conduit is recommended whenever vibration transmission may create a noise problem within the structure. Table 27. High Voltage Disconnect Switch Ground the outdoor unit per national, state, and local code requirements. 18 18-BC92D1-1D-EN Integrated Variable Speed Control Board LED Indicators EXT.ODT CDA EEV LSOV J3 T4 PERSONALITY MODULE J2 PWM J 10 J5 J9 PSC (not used) J8 J 20 FAN High Voltage to Condensor T3 COMM COMM STATUS STATUS LOAD SHED T1 T2 9 1 J1 10 18 HPCO CHARGE SOLENOID (N/A P hase I) DATA J6 MONITOR TOOL Th e S t a tu s (Gre e n ) a n d COMM (Am b e r) LEDs a re lo ca te d in t h e u p p e r rig h t re g io n o f t h e Co n t ro l Bo a rd . Fa u lt m e s s a ge s a re d is p laye d o n t h e CDA D R B J4 ALUMINUM COVER PLATE LED’S LED RATE DESCRIPTION INDICATION 1 TIME PER SECOND STANDBY/ IDLE LED MEDIUM 2 TIMES PER SECOND CALL FOR CAPACITY COMM (AMBER) FAST 5 TIMES PER SECOND POWER UP DELAY SLOW STATUS (GREEN) SOLID ON INTERMITTENT 18-BC92D1-1D-EN RATE DESCRIPTION INDICATION SLOW 1 TIME PER DEVICE DEVICE COUNT FAST 5 TIME PER SECOND LOSS OF COMMUNICATION TEST MODE 1 FLASH EVERY 4 SECONDS HARD LOCKOUT 19 Start Up 1. Ensure you have completed the following sections. ”Refrigerant Line Brazing,” p. 12 through ”Electrical — High Voltage,” p. 18 2. Set System Thermostat to OFF. 3. Turn on disconnect(s) to apply power to the indoor and outdoor units. ON OFF 4. Wait 3 hours before starting the unit if the outdoor ambient temperature is below 85° F. 3 HRS . 5. Run the system using the “Charging Mode-Cooling” test mode found in the 850/950 comfort control. This is the only approved method for setting the system charge level by subcooling. Follow the on-screen prompts. 20 18-BC92D1-1D-EN System Charge Adjustment Table 28. Temperature Measurements Check the outdoor temperatures. 120° F Subcooling using “Charging Mode-Cooling” is the only recommended method of charging between 55 ° F and 120° F ambient outdoor temperature. 55° F For best results the indoor temperature should be kept between 70° F to 80° F. 80° F 70° F Table 29. Subcooling Charging Corrections Subcooling Charging Correction Worksheet Determine the final subcooling value using total Line Length and Lift measured in Table 8, p. 9— (Required Refrigerant Line Length) and the Subcooling Charging Corrections Charts. Total Line Length (ft) ________________________ Total Vertical Charge (lift) ________________________ (Values from — Required Refrigerant Line Length) Design Subcooling Value ________________________ (from nameplate or Service Facts) Final Subcooling Value ________________________ 18-BC92D1-1D-EN 21 Subcool Charging Correction Charts Figure 2. Subcool Charging Corrections — 2.0 Ton Figure 4. Subcool Charging Corrections — 4.0 Ton 2.0 TON SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE) 4.0 TON SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE) REFRIGERANT LINELIFT (FEET) 40 Add 2° 50 Add 1° 40 REFRIGERANT LINELIFT (FEET) Add 1° 50 30 Use Design Subcoo 25 lin g 15 10 0 20 30 40 50 60 70 80 90 Add 1° Add 2° Add 1° 1° 30 Use Design Subcoo 25 1° lin g 1° 15 10 0 100 110 120 130 140 150 20 30 40 50 60 70 80 90 100 110 120 130 140 150 TOTAL REFRIGERANT LINE LENGTH (FEET) TOTAL REFRIGERANT LINE LENGTH (FEET) Figure 3. Subcool Charging Corrections — 3.0 Ton Figure 5. Subcool Charging Corrections — 5.0 Ton 3.0 TON SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE) 5.0 TON SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE) REFRIGERANT LINELIFT (FEET) Add 2° REFRIGERANT LINE LIFT (FEET) Add 1° 50 Add 1° 40 30 Use Design Subcoo 25 lin g 15 10 0 20 30 40 50 60 70 80 90 100 110 120 130 140 150 1° 50 Ad d 1° 25 15 AC: 1-1/8” Va p o r Lin e Lim it Ad d 1° 10 0 Add 2° Use De sig n S u b co o lin g 30 HP: 1-1/8” Va p o r Lin e Lim it 20 TOTAL REFRIGERANT LINE LENGTH (FEET) Ad d 4° Ad d 1° 40 30 40 50 60 70 1° 80 90 100 110 120 130 140 150 TOTAL REFRIGERANT LINE LENGTH (FEET) NOTE: 150 ft. le ngth is a pprove d ONLY with 7/8” va por line s. Refrigerant Charging Chart R-410A REFRIGERANT CHARGING CHART DESIGN SUBCOOLING (°F) LIQUID TEMP (°F) 8 9 10 11 12 13 14 LIQUID GAGE PRESSURE (PSI) 55 179 182 185 188 191 195 198 60 195 198 201 204 208 211 215 65 211 215 218 222 225 229 232 70 229 232 236 240 243 247 251 75 247 251 255 259 263 267 271 80 267 271 275 279 283 287 291 85 287 291 296 300 304 309 313 90 309 313 318 322 327 331 336 95 331 336 341 346 351 355 360 100 355 360 365 370 376 381 386 105 381 386 391 396 402 407 413 110 407 413 418 424 429 435 441 115 435 441 446 452 458 464 470 120 464 470 476 482 488 495 501 125 495 501 507 514 520 527 533 Refer to Service Facts or Installer’s Guide for charging method 22 18-BC92D1-1D-EN Charging the Unit Table 30. Proper Gage Pressure Using the ”Refrigerant Charging Chart”, p. 22adjust refrigerant level to attain proper gage pressure. Add refrigerant if the Liquid Gage Pressure is lower than the chart value. 1. Connect gauges to refrigerant bottle and unit as illustrated. 2. Purge all hoses. 3. Open bottle. 4. Stop adding refrigerant when liquid line temperature and Liquid Gage Pressure match the charging chart. Note: Recover refrigerant if the Liquid Gage Pressure is higher than the chart value. Table 31. Stabilize the system 5. Wait 20 minutes for the system condition to stabilize between adjustments. Note: When the Liquid Line Temperature and Gage Pressure approximately match the chart, the system is properly charged. 6. Remove gauges. 7. Replace service port caps to prevent leaks. Tighten finger tight plus an additional 1/6 turn. 20 MIN. Table 32. Verify Performance PRESSURE CURVE S AMPLE 8. Refer to System Pressure Curves in the Service Facts document to verify typical performance. Cooling @1450 SCFM 550 INDOORENTERING WET BULB CURVES TOPTO BOTTO M 71, 67, 63 AND 59 DEG F. 500 DISCHARGE PRESSURE (PSIG) Heating @1350 SCFM 500 INDOORENTERING DRY BULB CURVES TOP TO BOTTOM 80, 70, AND 60 DEG F. (2) 450 450 400 400 350 350 (4) (3) 300 300 250 250 (1) 200 40 60 80 200 100 -5 120 5 15 25 35 45 55 65 25 35 45 55 65 OUTDOORTEMPERATURE (Degree F) 170 165 160 140 INDOORENTERING WET BULB CURVES TOPTO BOTTO M 71, 67, 63 AND 59 DEG F. (2) SUCTION PRESSURE (PSIG) 155 150 120 110 100 145 (5) 140 (3) 90 135 80 130 70 125 60 50 120 115 40 (1) 110 40 18-BC92D1-1D-EN INDOORENTERING DRY BULB CURVES TOP TO BOTTOM 80, 70, AND 60 DEG F. 130 60 80 30 100 120 -5 5 15 23 Charging the Unit Table 33. System Information 9. Record system pressures and temperatures after charging is complete. Outdoor model number = ________________________ Measured Outdoor Ambient = ________________________°F Measured Indoor Ambient = ________________________°F Measured Liquid Line Temp = ________________________°F Indoor Wet Bulb = ________________________°F Liquid Gage Pressure = ________________________ PSIG Suction Gage Pressure = ________________________ PSIG Measured Suction Line Temp = ________________________°F 24 18-BC92D1-1D-EN Communicating Display Assembly (CDA) NAVIGATION • To e n te r a n d e xit Te ch n icia n Me n u s , p re s s th e Up /Do w n b u tto n s s im u lta n e o u s ly fo r 5 s e co n d s . • To re tu rn to th e Ho m e Scre e n , p re s s th e Up /Do w n b u tto n s s im u lta n e o u s ly fo r 5 s e co n d s . • To re tu rn to th e to p le ve l o f a ny m e n u , p re s s th e Le ft/Rig h t b u tto n s s im u lta n e o u s ly fo r 5 s e co n d s . • Afte r five m in u te s o f in a ctivity in th e Te ch n icia n Me n u s e ctio n , th e Ho m e Scre e n w ill b e d is p la ye d . Pre s s in g th e En te r b u tto n fo r 5 s e co n d s w ill in cre a s e th is tim e to 20 m in u te s . SYSTEM STATUS XXXXXXXXXXXXXXXX TECHNICIAN MENUS MONITOR MENU Th e Mo n ito r Me n u d is p la ys in fo rm a tio n o n Sys te m s ta tu s , Drive s ta ts a n d th e Sys te m Ta ch o m e te r. ALERT MENU ALERT HISTORY MENU Th e Ale rt Me n u Th e Ale rt His to ry d is p la ys a ctive a le rts . m e n u d is p la ys a le rts sto re d ove r tim e . No te th a t cle a rin g Ale rt His to ry w ill a ls o cle a r Acti ve Ale rts . Scan to see an overview video about the CDA CONFIG MENU CONTROL MENU Th e Co n fig u ra tio n Me n u is w h e re Sys te m p a ra m e te rs a n d o p tio n s a re s e t a n d re p o rte d . Th e Co n tro l Me n u co n ta in s a s e le ctio n o f u n it fu n ctio n te s ts th a t a re u s e d to ve rify o p e ra tio n . 1. Exte rn a l s h u t d o w n (Lo a d S h e d ) 2. Min . Airflo w 3. Blo w e r o n /o ff d e la ys 4. Cu s to m Airflo w 5. PFC (Po w e r Fa cto r Co rre ctio n ) 1. FRC DFT (Fo rce d De fro s t) 2. EEV Te s t 3. Eva cu a tio n 4. Drive Dia g n o s tic Te s t 5. OD Fa n Te s t N o t e : See the Service Facts found in the control box of the outdoor unit for more information. 18-BC92D1-1D-EN 25 Defrost Control (Heat Pump only) Demand Defrost C DA N a v i ga t i o n t o Fo r c e d D e f r o s t The demand defrost control measures heat pump outdoor ambient temperature with a sensor located outside the outdoor coil. A second sensor located on the outdoor coil is used to measure the coil temperature. The difference between the ambient and the colder coil temperature is the difference or delta-T measurement. This delta-T measurement is representative of the operating state and relative capacity of the heat pump system. By measuring the change in delta-T, we can determine the need for defrost. The coil sensor also serves to sense outdoor coil temperature for termination of the defrost cycle. Figure 6. CDA Mini Menu CONFIG MENU CONTROL MENU FRC DFT PRESS ENTER MONITOR MENU TEST INPROGRESS CTS <value> Fau lt I de nt if ic a ti on TEST C OMPLETE A fault condition is indicated by the CDA connected to the control board inside the heat pump control box. Defrost Enabled N OT E S : F o r c e d D e f r o s t Demand Defrost is enabled with the following inputs to the Integrated Variable Speed Control (IVSC): • Outdoor ambient temperature sensor (ODS-B) reporting an outdoor temperature at or below 52° F. • Coil temperature sensor (CBS) reporting a coil temperature at or below 35° F. • Heat/Cool Demand (HCD) from the communicating comfort control for at least two minutes or more. 2. FRC DFT TEST can be initiated in heat mode only. 3. Press ENTER to begin forced defrost. 4. Execute Forced Defrost following Forced Defrost (Defrost terminates on Coil Temperature or maximum time override of 15 minutes). 5. When test begins, TEST IN PROGRESS displays on line 1 and Coil Temperature value on line 2. Defrost Initiation The calculated temperature difference between the outdoor temperature sensor and the coil temperature sensor is called Delta T. Defrost can occur once the current Delta T exceeds the Delta T initiate value. The Defrost initiate value is calculated using a clean-coil Delta T x 2.0, plus a temperature bin correction factor. Initiation Delta T will automatically adjust based on the outdoor temperature. This adaptive logic assures a complete defrost for a range of outdoor temperatures. DEFROST TERMINATION PROFILES N o t e : Home Screen, under System Status will display DEFROST. 6. When test is complete, TEST COMPLETE displays for 10 seconds. 7. If there is a defrost fault condition, test terminates and sends alert to the alert menu. 8. For more information, refer to the Alert Code Tables in Service Facts and Technical Service Manual (Pub. No. 34–4301–01) documents. N o t e : Screens will update as the test proceeds. 65ºF HIGH TERMINATION TEMP 60ºF TERMINATION TEMPERATURE 1. System must be running with demand from the thermostat. MEDIUM TERMINATION TEMP 55ºF 50ºF FACTORY TERMINATION TEMP 45ºF 40ºF 35ºF 30ºF -40ºF -20ºF 0ºF 20ºF 40ºF 60ºF AMBIENT TEMPERATURE 26 18-BC92D1-1D-EN Checkout Procedures The final phase of the installation is the system Checkout Procedures. The following list represents the most common items covered in a Checkout Procedure. Confirm all requirements in this document have been met. All wiring connections are tight and properly secured. Supply registers and return grilles are open, unobstructed, and air filter is installed. Voltage and running current are within limits. All refrigerant lines (internal and external to equipment) are isolated, secure, and not in direct contact with each other or structure. All braze connections have been checked for leaks. A vacuum of 350 microns provides confirmation that the refrigeration system is leak free and dry. Final unit inspection to confirm factory tubing has not shifted during shipment. Adjust tubing if necessary so tubes do not rub against each other or any component when unit runs. Ductwork is sealed and insulated. All drain lines are clear with joints properly sealed. Pour water into drain pan to confirm proper drainage. 18-BC92D1-1D-EN Indoor blower and outdoor fan are operating smoothly and without obstruction. Indoor blower motor set on correct speed setting to deliver required CFM. Cover panels are in place and properly tightened. For gas heating systems, manifold pressure has been checked and all gas line connections are tight and leak free. For gas heating systems, flue gas is properly vented. System functions safely and properly in all modes. Owner has been instructed on use of system and given manual. 27 Notes Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com. Trane has a policy of continuous product and product data improvements and reserves the right to change design and specifications without notice. ©2014 Trane 18-BC92D1-1D-EN 13 Oct 2014 Supersedes 18-BC92D1-1C-EN (January 2014)