Internal Use Only http://biz.lgservice.com System Indoor Unit R410A SERVICE MANUAL R410A MODEL : ARNU Series URNU Series CAUTION Before Servicing the unit, read the safety precautions in General SVC manual. Only for authorized service personnel. Air Conditioner Service Manual TABLE OF CONTENTS Part 1 General Information .......................................................................................................3 Model Names ...............................................................................................................................4 External Appearance ...................................................................................................................5 Nomenclature ...............................................................................................................................6 Part 2 Indoor Units ......................................................................................................................7 Ceiling Mounted Cassette Type (1 way) ........................................................................................8 Ceiling Mounted Cassette Type (2 way) ......................................................................................16 Ceiling Mounted Cassette Type (4 way)(1)..................................................................................21 Ceiling Mounted Cassette Type (4 way)(2)..................................................................................27 Art Cool Type(Mirror) ...................................................................................................................34 Art Cool Type(Gallery) .................................................................................................................45 Ceiling Concealed Duct Type (Low static) ...................................................................................55 Ceiling Concealed Duct Type (Built in) ........................................................................................61 Ceiling Concealed Duct Type (High static) ..................................................................................67 Wall Mounted Type ......................................................................................................................76 Ceiling & Floor Ceiling Suspended ..............................................................................................87 Floor Standing Type.....................................................................................................................94 Vertical Air Handling Unit ...........................................................................................................101 Part 3 Trouble shooting guide...............................................................................109 Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes -2- LGE Internal Use Only Part 1 General Information 1. Model Names .............................................4 2. External Appearance .................................5 3. Nomenclature .............................................6 Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes -3- LGE Internal Use Only Model Names 1. Model Names Category Wall Mounted (General) ART COOL Chassis Name SE S5 SE Mirror S8 1 Way TJ 2 Way TL TR Ceiling Cassette TQ 4 Way 7.5 9.6 12.3 15.4 19.1 (2.2) (2.8) (3.6) (4.5) (5.6) ARNU07 ARNU09 ARNU12 ARNU15 3SE*2 3SE*2 3SE*2 3SE*2 ARNU18 3S5*2 ARNU07 ARNU09 ARNU12 ARNU15 3SE*2 3SE*2 3SE*2 3SE*2 ARNU18 3S8*2 ARNU07 ARNU09 ARNU12 3TJ*2 3TJ*2 3TJ*2 ARNU18 3TL*2 ARNU07 ARNU09 ARNU12 3TR*2 3TR*2 3TR*2 ARNU15 ARNU18 3TQ*2 3TQ*2 Capacity(Btu/h(kW)) 24.2 28.0 30.0 36.2 42.0 (7.1) (8.2) (8.8) (10.6) (12.3) 54.0 (15.8) ARNU24 3S5*2 ARNU24 3S8*2 ARNU24 3TL*2 ARNU36 3TN*2 TN ARNU42 ARNU48 3TM*2 3TM*2 TM ARNU07 ARNU09 ARNU12 ARNU15 ARNU18 ARNU24 3BHA2 3BHA2 3BHA2 3BHA2 3BHA2 3BHA2 ARNU28 3BGA2 BG High Static ARNU36 ARNU42 3BGA2 3BGA2 ARNU483 BRA2 BR URNU76 URNU96 3B8A2 3B8A2 B8 Ceiling Concealed Duct B1 Low Static ARNU07 ARNU09 ARNU12 ARNU15 3B1G2 3B1G2 3B1G2 3B1G2 ARNU18 ARNU24 3B2G2 3B2G2 B2 B3 Built In ARNU07 ARNU09 ARNU12 ARNU15 3B3G2 3B3G2 3B3G2 3B3G2 ARNU18 ARNU24 3B4G2 3B4G2 B4 Ceiling & Floor VE Ceiling Suspended VJ CE With Case ARNU09 ARNU12 3VEA2 3VEA2 ARNU18 3VJA2 ARNU07 ARNU09 ARNU12 ARNU15 3CEA2 3CEA2 3CEA2 3CEA2 ARNU18 ARNU24 3CFA2 3CFA2 CF Floor Standing Without Case CE 76.4 95.5 (22.4) (28.0) ARNU24 ARNU28 3TP*2 3TP*2 TP BH 48.1 (14.1) ARNU07 ARNU09 ARNU12 ARNU15 3CEU2 3CEU2 3CEU2 3CEU2 CF NJ Vertical AHU ARNU18 3CFU2 ARNU18 3NJA2 ARNU24 3CFU2 ARNU24 3NJA2 ARNU30 ARNU36 3NJA2 3NJA2 ARNU42 ARNU48 ARNU54 3NKA2 3NKA2 3NKA2 NK h *ART COOL- SE/S8( * R:Mirror, V:Silver, B : Blue), SF(* E:Red, V:Silver, G:Gold , 1: Kiss (Photo changeable)) *Wall Mounted- A: Basic, L:Plasma, *Ceiling Cassette- A: Basic, C:Plasma Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes -4- LGE Internal Use Only External Appearance 2. External Appearance Ceiling Cassette- 1Way Ceiling Concealed Duct - High Static ARNU073TJ*2 ARNU093TJ*2 ARNU123TJ*2 ARNU073BHA2 ARNU093BHA2 ARNU123BHA2 ARNU153BHA2 ARNU183BHA2 ARNU243BHA2 ARNU283BGA2 * A:Basic, C:Plasma Ceiling Cassette- 4Way ARNU073TR*2 ARNU093TR*2 ARNU123TR*2 ARNU153TQ*2 ARNU183TQ*2 ARNU243TP*2 ARNU283TP*2 ARNU363TN*2 ARNU423TM*2 ARNU483TM*2 ARNU363BGA2 ARNU423BGA2 ARNU483BRA2 URNU763B8A2 URNU963B8A2 Wall Mounted ARNU073SE*2 ARNU093SE*2 ARNU123SE*2 ARNU153SE*2 ARNU183S5*2 ARNU243S5*2 * A:Basic, L:Plasma * A:Basic, C:Plasma Ceiling Concealed Duct - Low Static ART COOL Mirror ARNU073B1G2 ARNU093B1G2 ARNU123B1G2 ARNU073SE*2 ARNU093SE*2 ARNU123SE*2 ARNU153SE*2 ARNU183S8*2 ARNU243S8*2 ARNU153B1G2 ARNU183B2G2 ARNU243B2G2 Ceiling Concealed Duct – Built-in ARNU073B3G2 ARNU093B3G2 ARNU123B3G2 * R:Mirror V:Silver B : Blue Floor Standing With case ARNU153B3G2 ARNU183B4G2 ARNU243B4G2 ARNU073CEA2 ARNU093CEA2 ARNU123CEA2 ARNU153CEA2 ARNU183CFA2 ARNU243CFA2 Ceiling & Floor Without case ARNU093VEA2 ARNU123VEA2 ARNU183VJA2 ARNU243VJA2 ARNU073CEU2 ARNU093CEU2 ARNU123CEU2 ARNU153CEU2 ARNU183CFU2 ARNU243CFU2 Ceiling Cassette -2Way Vertical AHU ARNU183TL*2 ARNU243TL*2 ARNU183NJA2 ARNU243NJA2 ARNU303NJA2 ARNU363NJA2 ARNU423NKA2 ARNU483NKA2 ARNU543NKA2 Ceiling Suspended * A:Basic, C:Plasma Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes -5- LGE Internal Use Only Nomenclature 3. Nomenclature ARN U 07 3 TJ A 2 Generation Combinations of functions A: Basic function L: Neo Plasma(Wall Mounted) C:Plasma(Ceiling Cassette) G: Low Static U: Floor Standing without Case ART COOL Type Panel Color B:Blue R:Mirror V: Silver Chassis Name Electrical Ratings 1:1Ø, 115V, 60Hz 6:1Ø, 220 - 240V, 50Hz 3:1Ø, 208/230V, 60Hz 2: 1Ø, 220V, 60Hz 7: 1Ø, 100V, 50/60Hz Total Cooling Capacity in Btu/h Class EX) 18,000 Btu/h Class → '18' Combination of Inverter Type and Cooling Only or Heat Pump N: AC Inverter and H/P V: AC Inverter and C/O U: DC Inverter and H/P and C/O System with Indoor Unit using R410A ❈ LGETA:U Ex) URN Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes -6- LGE Internal Use Only Part 2 Indoor Units Ceiling Cassette 1 Way .................................................................................8 2 Way...............................................................................13 4 Way(1)...........................................................................20 4 Way(2)...........................................................................23 Art Cool Series ART COOL Miror..............................................................34 ART COOL Gallery ..........................................................45 Ceiling Concealed Duct Low Static ........................................................................55 Built In ..............................................................................62 High Static........................................................................67 Wall Mounted(General) Wall Mounted ...................................................................76 Ceiling & Floor Ceiling & Floor Ceiling Suspended...........................................................87 Floor Standing Floor Standing..................................................................94 Vertical Air Handling Unit................................................117 Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes -7- LGE Internal Use Only Ceiling Mounted Cassette Type (1Way) 1. Functions ......................................................................................9 2. Operation Details........................................................................10 3. Dimensions .................................................................................12 Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes -8- LGE Internal Use Only Functions 1. Functions Indoor Unit Operation ON/OFF by Remote controller Sensing the Room Temperature Room temperature control Starting Current Control Indoor Fan Speed Control • Room temperature sensor. (Thermistor) • Maintains the room temperature in accordance with the Setting Temperature. • Indoor fan is delayed for 5 seconds at the starting. • Jet, High, Med, Low, Lolow Soft Dry Operation Mode • Intermittent operation of fan at low speed. Airflow Direction Control • The louver can be set at swing up and down automatically. Auto Restart • Although the air-conditioner is turned off by a power failure, it is restarted automatically previous operation mode after power supply. Deice (defrost) control (Heating) • Both the indoor and outdoor fan stops during defrosting. • Hot start after defrost ends. Hot-start Control (Heating) • The indoor fan does not rotate until the evaporator piping temperature will be reached at 25°C(76°F). Compact and light design • To install a unit is very convenient because of smaller size than textile. Low noise Long life filter High head Drain pump • The most advanced low-noise design. • The adoption of turbo fan and round type heat exchanger give the quietest operation. • Long life wrinkle(type) and washable and anti-bacteria filter is adopted. • Built-in drain pump automatically drains water. • A standard drain-head height of up to 700mm(27-9/16inch) is possible. High-Ceiling corresponding Function • According to the height of ceiling, the RPM of indoor fan motor is selected to increase air reaching distance. Central Control(Optional) • It is operating individually or totally by central control function. Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes -9- LGE Internal Use Only Operation Detail 2. Operation Detail (1) The function of main control n Auto Swing Control • This function is to swing the louver up and down automatically. n Soft-Dry Operation • The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of already being set to the best speed for Dry Operation by microcontroller control. n Cooling Mode Operation • When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote controller and the operation diagram is as following Intake Air Temperature Thermo. ON (SET TEMPERATURE +0.5°C(33°F)) Thermo. OFF (SET TEMPERATURE -0.5°C(33°F)) INDOOR FAN Indoor Unit mode 2TH (Remo.+Indoor) Remo. Mode More than 3 minutes Selected Speed Low More than 3 minutes Selected Speed Low Selected Speed Thermal ON ST+0.5 To be selected higher temperature Thermal OFF ST-0.5 To be selected higher temperature contrast Indoor Unit and Remo. ST+0.5 contrast Indoor Unit and Remo. ST-0.5 Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 10 - LGE Internal Use Only Operation Detail n Heating Mode Operation The unit will operate according to the setting by the remote controller and the operation diagram is shown as following. Indoor pipe Temperature 36°C(96°F) 33°C(92°F) 25°C(76°F) 20°C(68°F) Room Temperature Thermal Off Thermal On Minimum 3min Thermal Outdoor fan Indoor fan ON OFF ON ON Setting Stop Low Low fan speed OFF ON 4 Way Setting fan speed Low Low Stop Stop Low Setting fan speed ON Thermal ON ST+2 To be selected lower temperature contrast Indoor Unit and Remo. ST+0 Indoor Unit mode 2TH (Remo.+Indoor) Remo. mode Thermal OFF ST+4 To be selected lower temperature contrast Indoor Unit and Remo. ST+2 n Hot-start Control • The indoor fan does no rotate until the evaporator piping temperature will be reached to 25°C(76°F). • The operation diagram is as following. Pipe temperature 35°C(94°F) 30°C(86°F) 27°C(80°F) 25°C(76°F) 22°C(72°F) LO LOW Indoor fan speed COMP OFF Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes LOW SELECTED FAN LOW LOLOW ON - 11 - LGE Internal Use Only Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 12 1,100 881(Air outlet Hole) 1012 861 88 500 34 106.8 206.6 275.8 57.4 96.5 168.3 27 Air suction grill Air discharge grill 4 (unit : mm) Unit size(7k, 9k, 12k):ø12.7 Unit size(7k, 9k, 12k):ø6.35 Descripition CHASSIS CODE: TU 2. Unit shall be grounded in accordance with the local regulations or applicable national codes. 1. Unit should be installed in compliance with the installation manual in the product box. Note Gas pipe connection 2 3 76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea (Panel Name: PT-UUC) 320.5 453 Liquid pipe connection Name 1 Number ARNU07GTU*2 ARNU09GTU*2 ARNU12GTU*2 Ceiling Cassette 1-way Dimensions 3. Dimensions LGE Internal Use Only 453 354.3 500 46.5 Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 13 - 109.5 1012 1100 88 109.5 453 320.5 34 861 27 106.8 206.3 275.8 96.5 168.3 57.4 Air discharge grill 4 Unit size(7k, 9k, 12k):ø12.7 Unit size(7k, 9k, 12k):ø6.35 Descripition (unit : mm) CHASSIS CODE: TU 2. Unit shall be grounded in accordance with the local regulations or applicable national codes. 1. Unit should be installed in compliance with the installation manual in the product box. Note Air suction grill Gas pipe connection 3 Liquid pipe connection 1 Name 2 Number ARNU07GTU*2 ARNU09GTU*2 ARNU12GTU*2 76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea (Panel Name: PT-UUD) 117 Ceiling Cassette 1-way Dimensions LGE Internal Use Only 247.5 180.6 65.3 453.8 173.8 96.1 91 20.6 57.4 31.7 Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 14 1,201(Air Outlet Hole) 1,420 1332 1176.4 65.1 500 34 453.8 Air discharge grill 4 CHASSIS CODE: TT 2. Unit shall be grounded in accordance with the local regulations or applicable national codes. 1. Unit should be installed in compliance with the installation manual in the product box. 76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea (Panel Name: PT-UTC) Air suction grill 3 Note Gas pipe connection Unit size(18k):ø12.7, (24k):ø15.88 Liquid pipe connection Unit size(18k):ø6.35, (24k):ø9.52 Descripition 1 Name (unit : mm) 2 Number ARNU18GTT*2 ARNU24GTT*2 Ceiling Cassette 1-way Dimensions LGE Internal Use Only 65.3 453.8 247.5 180.6 173.8 97.1 91 500 57.4 31.7 20.6 46.5 - 15 - 34 109.5 1332 1420 Ø14 65.1 15.2 1176.4 22.3 57 132 Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes 109.5 335 453.8 44 Air discharge grill CHASSIS CODE: TT 2. Unit shall be grounded in accordance with the local regulations or applicable national codes. 1. Unit should be installed in compliance with the installation manual in the product box. Note 4 Air suction grill 3 76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea (Panel Name: PT-UTD) 96.5 Gas pipe connection Unit size(18k):ø12.7, (24k):ø15.88 Liquid pipe connection Unit size(18k):ø6.35, (24k):ø9.52 Descripition 2 Name (unit : mm) 1 Number ARNU18GTT*2 ARNU24GTT*2 Ceiling Cassette 1-way Dimensions LGE Internal Use Only Ceiling Mounted Cassette Type (2Way) 1. Functions ....................................................................................17 2. Operation Details........................................................................18 3. Dimensions .................................................................................20 Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 16 - LGE Internal Use Only Functions 1. Functions Indoor Unit Operation ON/OFF by Remote controller Sensing the Room Temperature Room temperature control Starting Current Control Indoor Fan Speed Control • Room temperature sensor. (Thermistor) • Maintains the room temperature in accordance with the Setting Temperature. • Indoor fan is delayed for 5 seconds at the starting. • Jet, High, Med, Low, Lolow Soft Dry Operation Mode • Intermittent operation of fan at low speed. Airflow Direction Control • The louver can be set at swing up and down automatically. Auto Restart • Although the air-conditioner is turned off by a power failure, it is restarted automatically previous operation mode after power supply. Deice (defrost) control (Heating) • Both the indoor and outdoor fan stops during defrosting. • Hot start after defrost ends. Hot-start Control (Heating) • The indoor fan does not rotate until the evaporator piping temperature will be reached at 25°C(76°F). Compact and light design • To install a unit is very convenient because of smaller size than textile. Low noise Long life filter • The most advanced low-noise design. • The adoption of turbo fan and round type heat exchanger give the quietest operation. • Long life wrinkle(type) and washable and anti-bacteria filter is adopted. High head Drain pump • Built-in drain pump automatically drains water. • A standard drain-head height of up to 700mm (27-9/16inch) is possible. High-Ceiling corresponding Function • According to the height of ceiling, the RPM of indoor fan motor is selected to increase air reaching distance. Central Control(Optional) • It is operating individually or totally by central control function. Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 17 - LGE Internal Use Only Operation Detail 2. Operation Detail (1) The function of main control n Auto Swing Control • This function is to swing the louver up and down automatically. n Soft-Dry Operation • The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of already being set to the best speed for Dry Operation by microcontroller control. n Cooling Mode Operation • When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote controller and the operation diagram is as following Intake Air Temperature Thermo. ON (SET TEMPERATURE +0.5°C(33°F)) Thermo. OFF (SET TEMPERATURE -0.5°C(33°F)) INDOOR FAN Indoor Unit mode 2TH (Remo.+Indoor) Remo. Mode More than 3 minutes Selected Speed Low Thermal ON ST+0.5 To be selected higher temperature contrast Indoor Unit and Remo. ST+0.5 Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 18 - More than 3 minutes Selected Speed Low Selected Speed Thermal OFF ST-0.5 To be selected higher temperature contrast Indoor Unit and Remo. ST-0.5 LGE Internal Use Only Operation Detail n Heating Mode Operation The unit will operate according to the setting by the remote controller and the operation diagram is shown as following. Indoor pipe Temperature 36°C(96°F) 33°C(92°F) 25°C(76°F) 20°C(68°F) Room Temperature Thermal Off Thermal On Minimum 3min Thermal Outdoor fan Indoor fan ON OFF ON ON Setting Stop Low Low fan speed OFF ON Setting fan speed Low 4 Way Low Stop Stop Low Setting fan speed ON Thermal ON ST+2 To be selected lower temperature contrast Indoor Unit and Remo. ST+0 Indoor Unit mode 2TH (Remo.+Indoor) Remo. mode Thermal OFF ST+4 To be selected lower temperature contrast Indoor Unit and Remo. ST+2 n Hot-start Control • The indoor fan does no rotate until the evaporator piping temperature will be reached to 25°C(76°F). • The operation diagram is as following. Pipe temperature 35°C(94°F) 30°C(86°F) 27°C(80°F) 25°C(76°F) 22°C(72°F) LO LOW Indoor fan speed COMP OFF Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes LOW SELECTED FAN LOW LOLOW ON - 19 - LGE Internal Use Only Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 20 - 3 4 2 1 640(25-3/16) 550(21-11/16) 28.5(1-1/8) 126.5(5) B TL 225(8-7/8) A A LG Electronics USA, HVAC Division 1000 Sylvan Avenue, Englewood Cliffs, NJ 07632 www.lgusa.com / www.lghvac.com 1050(41-5/16) 889.2(35) 830(32-11/16) 275(10-13/16) 69.5(2-3/4) B 47.9(1-7/8) Name Note (18k) ø12.7(1/2), (24k)ø15.88(5/8) (18k) ø6.35(1/4), (24k)ø9.52(3/8) Descripition [Unit : mm(inch)] 76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea www.lgeaircon.com CHASSIS CODE: TL 2. Unit shall be grounded in accordance with the local regulations or applicable national codes. 1. Unit should be installed in compliance with the installation manual in the product box. Air discharge grill Air suction grill 4 Gas pipe connection 2 Liquid pipe connection 3 1 Number ARNU183TL*2 ARNU243TL*2 Ceiling Cassette 2-way Dimensions 3. Dimensions LGE Internal Use Only Ceiling Mounted Cassette Type (4Way) (1) 1. Functions ....................................................................................22 2. Operation Details........................................................................23 3. Dimensions .................................................................................25 Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 21 - LGE Internal Use Only Functions 1. Functions Indoor Unit Operation ON/OFF by Remote controller Sensing the Room Temperature Room temperature control Starting Current Control Indoor Fan Speed Control • Room temperature sensor. (Thermistor) • Maintains the room temperature in accordance with the Setting Temperature. • Indoor fan is delayed for 5 seconds at the starting. • Jet, High, Med, Low, Lolow Soft Dry Operation Mode • Intermittent operation of fan at low speed. Airflow Direction Control • The louver can be set at swing up and down automatically. Auto Restart • Although the air-conditioner is turned off by a power failure, it is restarted automatically previous operation mode after power supply. Deice (defrost) control (Heating) • Both the indoor and outdoor fan stops during defrosting. • Hot start after defrost ends. Hot-start Control (Heating) • The indoor fan does not rotate until the evaporator piping temperature will be reached at 25°C(76°F). Compact and light design • To install a unit is very convenient because of smaller size than textile. Low noise Long life filter • The most advanced low-noise design. • The adoption of turbo fan and round type heat exchanger give the quietest operation. • Long life wrinkle(type) and washable and anti-bacteria filter is adopted. High head Drain pump • Built-in drain pump automatically drains water. • A standard drain-head height of up to 700mm (27-9/16inch) is possible. High-Ceiling corresponding Function • According to the height of ceiling, the RPM of indoor fan motor is selected to increase air reaching distance. Central Control(Optional) • It is operating individually or totally by central control function. Swirl Swing Control • It is operating swirl swing Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 22 - LGE Internal Use Only Operation Detail 2. Operation Detail (1) The function of main control n Auto Swing Control • This function is to swing the louver up and down automatically. n Soft-Dry Operation • The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of already being set to the best speed for Dry Operation by microcontroller control. n Cooling Mode Operation • When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote controller and the operation diagram is as following Intake Air Temperature Thermo. ON (SET TEMPERATURE +0.5°C(33°F)) Thermo. OFF (SET TEMPERATURE -0.5°C(33°F)) INDOOR FAN More than 3 minutes Selected Speed Indoor Unit mode 2TH (Remo.+Indoor) Remo. Mode Low Thermal ON ST+0.5 To be selected higher temperature contrast Indoor Unit and Remo. ST+0.5 More than 3 minutes Selected Speed Selected Speed Low Thermal OFF ST-0.5 To be selected higher temperature contrast Indoor Unit and Remo. ST-0.5 n Swirl Swing Control Vane 2 Vane 2, 4 is almost vane closed while vane1, 3 is opened. Vane 1, 3 and vane 2,4 turn over minutely Vane 1 Vane 3 Vane 4 Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 23 - LGE Internal Use Only Operation Detail n Heating Mode Operation The unit will operate according to the setting by the remote controller and the operation diagram is shown as following. Indoor pipe Temperature 36°C(96°F) 33°C(92°F) 25°C(76°F) 20°C(68°F) Room Temperature Thermal Off Thermal On Minimum 3min Thermal Outdoor fan Indoor fan ON OFF ON ON Setting Stop Low Low fan speed OFF ON Setting fan speed Low 4 Way Low Stop Stop Low Setting fan speed ON Thermal ON ST+2 To be selected lower temperature contrast Indoor Unit and Remo. ST+0 Indoor Unit mode 2TH (Remo.+Indoor) Remo. mode Thermal OFF ST+4 To be selected lower temperature contrast Indoor Unit and Remo. ST+2 n Hot-start Control • The indoor fan does no rotate until the evaporator piping temperature will be reached to 25°C(76°F). • The operation diagram is as following. Pipe temperature 35°C(94°F) 30°C(86°F) 27°C(80°F) 25°C(76°F) 22°C(72°F) LO LOW Indoor fan speed COMP OFF Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes LOW SELECTED FAN LOW LOLOW ON - 24 - LGE Internal Use Only 6 A CEILING OPENING 700 473 380(Air outlet hole) 376(Inlet Grille) 22.5 5 700 B 4R20 4 523 59.5 84.5 3 A ARROW VIEW 30 19 142.5 2 1 79 53 48 - 25 - 128 570 165 461 570 517 5 570 517 Note (unit : mm) VP25(Φ32) Unit size(5k, 7k, 9k, 12k):ø12.7 Unit size(5k, 7k, 9k, 12k):ø6.35 Descripition B ARROW VIEW 500mm or more* • REQUIRED SPACE 500mm or more* CHASSIS CODE: TR 500mm or more* 500mm or more* 2. Unit shall be grounded in accordance with the local regulations or applicable national codes. 1. Unit should be installed in compliance with the installation manual in the product box. Air suction grill Air discharge grill 5 6 Drain pipe connection Power supply connection 4 Gas pipe connection 3 Liquid pipe connection 2 Name 1 Number ARNU05GTR*2 ARNU07GTR*2 ARNU09GTR*2 ARNU12GTR*2 Ceiling Cassette 4-way 76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea Branch Duct Connection 63 69 34.5 Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes 214 R3 Dimensions 3. Dimensions LGE Internal Use Only 6 A CEILING OPENING 700 473 380(Air outlet hole) 376(Inlet Grille) 22.5 B 5 4R20 4 59.5 523 30 19 142.5 2 1 3 A ARROW VIEW 125 95.5 - 26 79 48 570 165 461 570 517 174 5 517 Power supply connection Air discharge grill Air suction grill 3 4 5 6 Note Gas pipe connection Drain pipe connection 2 Liquid pipe connection Name 1 Number (unit : mm) VP25(Φ32) Unit size(15k, 18k):Ø12.7 Unit size(15k, 18k):Ø6.35 Descripition ARNU15GTQ*2 ARNU18GTQ*2 Ceiling Cassette 4-way 76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea 500mm or more* • REQUIRED SPACE 500mm or more* CHASSIS CODE: TQ 500mm or more* 500mm or more* 2. Unit shall be grounded in accordance with the local regulations or applicable national codes. 1. Unit should be installed in compliance with the installation manual in the product box. B ARROW VIEW Branch Duct Connection 63 68 570 256 Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes 76 94 R3 Dimensions LGE Internal Use Only 700 Ceiling Mounted Cassette Type (4Way) (2) 1. Functions ....................................................................................28 2. Operation Details........................................................................29 3. Dimensions .................................................................................31 Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 27 - LGE Internal Use Only Functions 1. Functions Indoor Unit Operation ON/OFF by Remote controller Sensing the Room Temperature Room temperature control Starting Current Control Indoor Fan Speed Control • Room temperature sensor. (Thermistor) • Maintains the room temperature in accordance with the Setting Temperature. • Indoor fan is delayed for 5 seconds at the starting. • Jet, High, Med, Low, Lolow Soft Dry Operation Mode • Intermittent operation of fan at low speed. Airflow Direction Control • The louver can be set at swing up and down automatically. Auto Restart • Although the air-conditioner is turned off by a power failure, it is restarted automatically previous operation mode after power supply. Deice (defrost) control (Heating) • Both the indoor and outdoor fan stops during defrosting. • Hot start after defrost ends. Hot-start Control (Heating) • The indoor fan does not rotate until the evaporator piping temperature will be reached at 25°C(76°F). Compact and light design • To install a unit is very convenient because of smaller size than textile. Low noise • The most advanced low-noise design. • The adoption of turbo fan and round type heat exchanger give the quietest operation. Long life filter • Long life wrinkle(type) and washable and anti-bacteria filter is adopted. High head Drain pump • Built-in drain pump automatically drains water. • A standard drain-head height of up to 700mm (27-9/16inch) is possible. High-Ceiling corresponding Function • According to the height of ceiling, the RPM of indoor fan motor is selected to increase air reaching distance. Central Control(Optional) • It is operating individually or totally by central control function. Swirl Swing Control • It is operating swirl swing Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 28 - LGE Internal Use Only Operation Detail 2. Operation Detail (1) The function of main control n Auto Swing Control • This function is to swing the louver up and down automatically. n Soft-Dry Operation • The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of already being set to the best speed for Dry Operation by microcontroller control. n Cooling Mode Operation • When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote controller and the operation diagram is as following Intake Air Temperature Thermo. ON (SET TEMPERATURE +0.5°C(33°F)) Thermo. OFF (SET TEMPERATURE -0.5°C(33°F)) INDOOR FAN Indoor Unit mode 2TH (Remo.+Indoor) Remo. Mode More than 3 minutes Selected Speed Low Thermal ON ST+0.5 To be selected higher temperature contrast Indoor Unit and Remo. ST+0.5 Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 29 - More than 3 minutes Selected Speed Low Selected Speed Thermal OFF ST-0.5 To be selected higher temperature contrast Indoor Unit and Remo. ST-0.5 LGE Internal Use Only Operation Detail n Heating Mode Operation The unit will operate according to the setting by the remote controller and the operation diagram is shown as following. Indoor pipe Temperature 36°C(96°F) 33°C(92°F) 25°C(76°F) 20°C(68°F) Room Temperature Thermal Off Thermal On Minimum 3min Thermal Outdoor fan Indoor fan ON OFF ON ON Setting Stop Low Low fan speed OFF ON Setting fan speed Low 4 Way Low Stop Stop Low Setting fan speed ON Thermal ON ST+2 To be selected lower temperature contrast Indoor Unit and Remo. ST+0 Indoor Unit mode 2TH (Remo.+Indoor) Remo. mode Thermal OFF ST+4 To be selected lower temperature contrast Indoor Unit and Remo. ST+2 n Hot-start Control • The indoor fan does no rotate until the evaporator piping temperature will be reached to 25°C(76°F). • The operation diagram is as following. Pipe temperature 35°C(94°F) 30°C(86°F) 27°C(80°F) 25°C(76°F) 22°C(72°F) LO LOW Indoor fan speed COMP OFF Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes LOW SELECTED FAN LOW LOLOW ON - 30 - LGE Internal Use Only 669(SUSPENSION POSITION) 420 393 13-ø 3, 3 Hole 26 31 475 71 B ARROW VIEW 35 Ceiling opening 614(Inlet Grille) 682(SUSPENSION POSITION) ø70 OUTDOOR AIR INTAKE (DIRECT CONNECTION) B 950 25 870-920(CEILING OPENING SPACE) 500(Air outlet Hole) 737 950 420 870-920(CEILING OPENING SPACE) 786(SUSPENSION POSITION) 71 6 2 A 65 40 5 671 108 60 1 350 840 165 53.5 60 82 99 4 3 Branch Duct Connection 80 840 787 787 804 204 300 OR LESS 62 204 154 79 41.5 684 840 BRANCH DUCT CONNECTION 92 4 Air suction grill (unit : mm) VP25(Φ32) Unit size(24k, 28k):ø15.88 Unit size(24k, 28k):ø9.52 Descripition 92 10 350 50 92 165 92 500mm or more* BRANCH DUCT CONNECTION 500mm or more* CHASSIS CODE: TP 500mm or more* 500mm or more* • REQUIRED SPACE 2. Unit shall be grounded in accordance with the local regulations or applicable national codes. 1. Unit should be installed in compliance with the installation manual in the product box. Note 6 A ARROW VIEW 165 Drain pipe connection Power supply connection 3 Air discharge grill Gas pipe connection 5 Liquid pipe connection 1 Name 2 Number ARNU21GTP*2 ARNU24GTP*2 ARNU28GTP*2 Ceiling Cassette 4-way 76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea 13-ø 3, 3 Hole 32 50 - 31 79 Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes 50 4-R20 Dimensions 3. Dimensions LGE Internal Use Only 13-ø 3, 3 Hole 6 35 71 B ø70 OUTDOOR AIR INTAKE (DIRECT CONNECTION) B ARROW VIEW 31 475 Ceiling opening 870-920(CEILING OPENING SPACE) 786(SUSPENSION POSITION) 614(Inlet Grille) 25 2 870-920(CEILING OPENING SPACE) 682(SUSPENSION POSITION) 500(Air outlet Hole) 737 950 110 1 A 60 840 165 350 103 141 246 3 4 Branch Duct Connection 53.5 80 840 78 5 420 300 OR LESS 80 669(SUSPENSION POSITION) 420 393 44 71 950 40 107 246 195 100 52 BRANCH DUCT CONNECTION 43 60 - 32 13-ø 3, 3 Hole 100 Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes 60 4-R20 165 10 350 92 165 92 BRANCH DUCT CONNECTION 500mm or more* 500mm or more* CHASSIS CODE: TN 500mm or more* 500mm or more* • REQUIRED SPACE 2. Unit shall be grounded in accordance with the local regulations or applicable national codes. A ARROW VIEW 92 VP25(Φ32) Unit size(36k):ø15.88 Unit size(36k):ø9.52 Descripition (unit : mm) 1. Unit should be installed in compliance with the installation manual in the product box. Note 76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea 92 5 Air suction grill Air discharge grill 4 6 Drain pipe connection Power supply connection 3 Gas pipe connection 2 Name Liquid pipe connection 1 Number ARNU36GTN*2 Ceiling Cassette 4-way Dimensions LGE Internal Use Only 6 669(SUSPENSION POSITION) 420 393 13-ø 3, 3 Hole 31 475 ø70 B OUTDOOR AIR INTAKE (DIRECT CONNECTION) B ARROW VIEW 35 71 Ceiling opening 682(SUSPENSION POSITION) 110 870-920(CEILING OPENING SPACE) 786(SUSPENSION POSITION) 300 OR LESS 420 614(Inlet Grille) 25 870-920(CEILING OPENING SPACE) 500(Air outlet Hole) 737 950 2 A 1 100 84 5 75 71 288 165 237 350 53.5 Branch Duct Connection 3 4 840 76 60 - 33 136 13-ø 3, 3 Hole BRANCH DUCTCONNECTION 60 Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes 10 350 92 165 92 500mm or more* CHASSIS CODE: TM 500mm or more* 500mm or more* • REQUIRED SPACE 500mm or more* BRANCH DUCT CONNECTION 2. Unit shall be grounded in accordance with the local regulations or applicable national codes. A ARROW VIEW 165 92 VP25(Φ32) Unit size(42k, 48k):ø15.88 Unit size(42k, 48k):ø9.52 Descripition (unit : mm) 1. Unit should be installed in compliance with the installation manual in the product box. Note 76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea 92 5 Air suction grill Air discharge grill 4 6 Drain pipe connection Power supply connection 3 Gas pipe connection 2 Name Liquid pipe connection ARNU42GTM*2 ARNU48GTM*2 Ceiling Cassette 4-way 1 Number 100 4-R20 Dimensions LGE Internal Use Only 950 Art Cool Type(Mirror) 1. Functions ....................................................................................35 2. Operation Details........................................................................36 3. Dimensions .................................................................................43 Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 34 - LGE Internal Use Only Functions 1. Functions Indoor Unit Operation ON/OFF by Remote controller Sensing the Room Temperature • Room temperature sensor. (THERMISTOR) Room temperature control • Maintains the room temperature in accordance with the Setting Temp. Starting Current Control • Indoor fan is delayed for 5 sec at the starting. Indoor Fan Speed Control • High, Med, Low, CHAOS Operation indication Lamps (LED) Signal Receptor Receives the signals from the remote control.(Signal receiving sound: two short beeps or one long beep.) Operation Indication Lamps On/Off : Lights up during the system operation. Sleep Mode : Lights up during Sleep Mode Auto operation. Timer : Lights up during Timer operation. Defrost Mode : Lights up during Defrost Mode or Hot Start operation. Soft Dry Operation Mode • Intermittent operation of fan at low speed. Sleep Mode Auto Control • The fan is switched to low(Cooling), med(Heating) speed. • The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours. Defrost(Deice) control (Heating) Natural Air Control by CHAOS Logic • Both the indoor and outdoor fan stops during defrosting. • The fan is switched to intermittent or irregular operation • The fan speed is automatically switched from high to low speed. Airflow Direction Control • The louver can be set at the desired position or swing up and down automatically. Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 35 - Hot-start Control (Heating) • The indoor fan does not rotate until the evaporator pipe temperature will be reached at 28°C(82°F). LGE Internal Use Only Operation Details 2. Operation Details Function of Controls DISPLAY 1) High quality LCD remote controller supplied Operation Indicator • On while in appliance operation, off while in appliance pause Timer Indicator • On while in timer mode (on/off) and in sleep timer mode, off when timer mode is completed or canceled Defrost Indicator • Off except when hot start during heating mode operation or while in defrost control. Plasma Indicator • On while in plasma mode, off while plasma mode is canceled. Auto restart Indicator • On while auto restart mode, off while auto restart mode is canceled. Auto restart • In case the power comes on again after a power failure, Auto Restarting Operation is the function to operate procedures automatically to the previous operating conditions. If your want to use this operation, press the Auto Restart Button. Power(Forced Operation) • Operation starts, when this button is pressed and stops when you press the button again. n Cooling Mode Operation • When the intake air temperature reaches 0.5°C(33°F) below the setting temp, the compressor and the outdoor fan stop. • When it reaches 0.5°C(33°F) above the setting temp, they start to operate again. Compressor ON Temp=> Setting Temp+0.5°C(33°F) Compressor OFF Temp => Setting Temp-0.5°C(33°F) • While in compressor running, operating with the airflow speed set by the remote controller. While in compressor not running, operating with the low airflow speed regardless of the setting. n Healthy Dehumidification Mode • When the dehumidification operation input by the remote controller is received, the intake air temperature is detected and the setting temp is automatically set according to the intake air temperature. 26°C(78°F) ≤ Intake Air Temp => 25°C(76°F) 24°C(76°F) ≤ Intake Air Temp < 26°C(78°F) => Intake Air Temp-1°C(34°F) 18°C(64°F) ≤ Intake Air Temp < 24°C(76°F) => Intake Air Temp-0.5°C(33°F) Intake Air Temp < 18°C(64°F) => 18°C(64°F) • While in compressor off, the indoor fan repeats low airflow speed and pause. • While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification operation and 4-min compressor off repeat Compressor ON Temp. => Setting Temp+0.5°C(33°F) Compressor OFF Temp. => Setting Temp-0.5°C(33°F) • In 10-min dehumidification operation, the indoor fan operates with the low airflow speed. n Heating Mode Operation Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 36 - LGE Internal Use Only Operation Details • When the intake air Temp. reaches Compressor OFF Temp., the compressor is turned off. When the intake air Temp. reaches Compressor ON Temp., the compressor is turned on. Themo ON Temp. => Setting Temp. +2˚C(36°F) Themo OFF Temp. => Setting Temp.+4°C(39°F) • While in compressor on, when above 38°C(100°F), it operates with setting airflow speed (while in sleep mode, with the medium airflow speed). • While in compressor off, the indoor fan is off when the indoor pipe temp is below 33°C (92°F), when above 35°C(94°F) , it operates with the low airflow speed. • While in defrost control, both of the indoor and outdoor fans are turned off. n Defrost Control • While in heating mode operation in order to protect outdoor unit from freezing, reversed to cooling cycle to defrost of the outdoor unit. n Fuzzy Operation (Outdoor unit C/O Model) • According to the temperature set by Fuzzy rule, when the intake air temp is 0.5°C(33°F) or more below the setting temp, the compressor is turned off. When 0.5°C(33°F) or more above the setting temp, the compressor is turned on. Compressor ON Temp => Setting Temp+0.5°C(33°F) Compressor OFF Temp => Setting Temp+0.5°C(33°F) • At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temp at that time. 26°C(78°F) ≤ Intake Air Temp => 25°C(76°F) 24°C(76°F) ≤ Intake Air Temp < 26°C(78°F) => Intake Air Temp+1°C(34°F) 22°C(72°F) ≤ Intake Air Temp<24°C(76°F) => Intake Air Temp+0.5°C(33°F) 18°C(64°F) ≤ Intake Air Temp<22°C(72°F) => Intake Air Temp Intake Air Temp<18°C(64°F) => 18°C(64°F) • When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule. • While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperature n Fuzzy Operation (Outdoor unit H/P Model) • When any of operation mode is not selected like the moment of the power on or when 3 hrs has passed since the operation off, the operation mode is selected. • When determining the operation mode, the compressor, the outdoor fan, and the 4 way valve are off and only the indoor fan is operated for 15 seconds. Then an operation mode is selected according to the intake air temp at that moment as follows. 24°C(76°F) ≤ Inatake Air Temp => Fuzzy Operation for Cooling 21°C(70°F)≤ Inatake Air Temp<24°C(76°F) => Fuzzy Operation for Dehumidification Inatake Air Temp<21°C(70°F) => Fuzzy Operation for Heating • If any of the operation modes among cooling / dehumidification / heating mode operations is carried out for 10 sec or longer before Fuzzy operation, the mode before Fuzzy operation is operated. Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 37 - LGE Internal Use Only Operation Details 1) Fuzzy Operation for Cooling • According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C(33°F) or more below the setting temp, the compressor is turned off. When 0.5°C(33°F) or more above the setting temp, the compressor is turned on. Compressor ON Temp. => Setting Temp+0.5°C(33°F) Compressor OFF Temp. => Setting Temp+0.5°C(33°F) • At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temp at that time. 26°C(78°F) ≤ Intake Air Temp => 25°C(76°F) 24°C(76°F) ≤ Intake Air Temp < 26°C(78°F) => Intake Air Temp+1°C(34°F) 22°C(72°F) ≤ Intake Air Temp<24°C(76°F) => Intake Air Temp+0.5°C(33°F) 18°C(64°F) ≤ Intake Air Temp<22°C(72°F) => Intake Air Temp Intake Air Temp<18°C(64°F) => 18°C(64°F) • When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule. • While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperature. 2) Fuzzy Operation for Dehumidification • According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C(33°F) or more below the setting temp, the compressor is turned off. When 0.5°C(33°F) or more above the setting temp, the compressor is turned on. Compressor ON Temp. => Setting Temp+0.5°C(33°F) Compressor OFF Temp. => Setting Temp+0.5°C(33°F) • At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temp at that time. 26°C(78°F) ≤ Intake Air Temp => 25°C(76°F) 24°C(76°F) ≤ Intake Air Temp < 26°C(78°F)=> Intake Air Temp+1°C(34°F) 22°C(72°F) ≤ Intake Air Temp<24°C(76°F) => Intake Air Temp+0.5°C(33°F) 18°C(64°F) ≤ Intake Air Temp<22°C(72°F) => Intake Air Temp Intake Air Temp < 18°C(64°F) => 18°C(64°F) • When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule. • While in Fuzzy operation, the airflow speed of the indoor fan repeats the low airflow speed or pause as in dehumidification operation. Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 38 - LGE Internal Use Only Operation Details 3) Fuzzy Operation for Heating • According to the setting temperature selected by Fuzzy rule, when the intake air temp is 3°C(37°F) or more above the setting temp, the compressor is turned off. When below the setting temp, the compressor is turned on. Compressor ON Temp => Setting Temp + 2°C(36°F) Compressor OFF Temp => Setting Temp + 4°C(39°F) • At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temp at that time. 20°C(68°F) ≤ Intake Air Temp => Intake Air Temp + 0.5°C(33°F) Intake Air Temp < 20°C(68°F) => 20°C(68°F) • When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule. • While in Fuzzy operation, the airflow speed of the indoor fan is set to the high or the medium according to the intake air temperature and the setting temperature. n Airflow Speed Selection • The airflow speed of the indoor fan is set to high, medium, low, or chaos by the input of the airflow speed selection key on the remote controller. n On-Timer Operation • When the set time is reached after the time is input by the remote controller, the appliance starts to operate. • The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached. • If the appliance is operating at the time set by the timer, the operation continues. n Off-Timer Operation • When the set time is reached after the time is input by the remote controller, the appliance stops operating. • The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached. • If the appliance is on pause at the time set by the timer, the pause continues. Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 39 - LGE Internal Use Only Operation Details n Off-Timer <=> On-Timer Operation • When the set time is reached after the on/off time is input by the remote controller, the on/off-timer operation is carried out according to the set time. n Sleep Timer Operation • When the sleep time is reached after <1,2,3,4,5,6,7,0(cancel) hr> is input by the remote controller while in appliance operation, the operation of the appliance stops. • While the appliance is on pause, the sleep timer mode cannot be input. • While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperature increases by 1°C(34°F) After another 30 min elapse, it increases by 1°C(34°) again. • When the sleep timer mode is input while in cooling cycle mode, the airflow speed of the indoor fan is set to the low. • When the sleep timer mode is input while in heating cycle mode, the airflow speed of the indoor fan is set to the medium. n Chaos Swing Mode • By the Chaos Swing key input, the vane automatically operates with the Chaos Swing or they are fixed to the desired direction. n Chaos Natural Wind Mode • When the Chaos Natural Wind mode is selected and then operated, the high, medium, or low speed of the airflow mode is operated for 2~15 sec randomly by the Chaos Simulation.” n Jet Cool Mode Operation (Outdoor unit C/O Model) • If the Jet Cool key is input at any operation mode while in appliance operation, the Jet Cool mode operates. • In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation. • In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C(64°F). • When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority. • When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then operated in order that the air outflow could reach further. n Jet Cool Mode Operation (Outdoor unit H/P Model) • While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the other mode operation (cooling, dehumidification, ventilation), the Jet Cool mode is operated.” • In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation. • In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C(64°F). • When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority. • When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then operated in order that the air outflow could reach further. n Auto Restarting Operation • When the power is restored after a sudden power failure while in appliance operation, the mode before the power failure is kept on the memory and the appliance automatically operates in the mode on the memory. • Operation Mode that is kept on the memory Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 40 - LGE Internal Use Only Operation Details - State of Operation ON/OFF - Operation Mode/Setting Temp/Selected Airflow Speed - Sleep Timer Mode/Remaining Time of Sleep Timer (unit of hour) n Forced Operation (Outdoor unit C/O Model) • To operate the appliance by force in case that the remote controller is lost, the forced operation button is on the main unit of the appliance to operate the appliance in the standard conditions. • Press the forced operation button, the forced operation is carried out. • Press the forced operation button once again to stop operation. • The forced operation is carried out in cooling mode with the setting temperature 22°C(72°F) and the high speed of airflow. n Forced Operation (Outdoor unit H/P Model) • To operate the appliance by force in case that the remote controller is lost, the forced operation selection switch is on the main unit of the appliance to operate the appliance in the standard conditions. • Press the forced operation button, the forced operation is carried out. • Press the forced operation button once again to stop operation. • In the forced operation mode, the indoor fan is operated at low speed for around 15 sec and then the operation condition is set according to the intake air temperature as follows. 24°C(76°F) ≤ Intake Air Temp => Cooling Mode Operation, 22°C(72°F), High Speed 21°C(70°F) ≤ Intake Air Temp < 24°C(76°F) => Dehumidification Operation, 23°C(74°F), High Speed Intake Air Temp < 21°C(70°F) => Heating Mode Operation, 24°C(76°F), High Speed n Test Operation Control • To check the condition of the installation when installing the appliance, the appliance is operated at cooling mode, high speed of airflow, compressor-on for 18 min without controlling the room temperature. • After supplying power to the main body, keep pressing the forced operation button for about 3 seconds. • While in test operation, a key can be input by the remote controller. When a key (operation start/stop, operation mode selection, airflow speed selection, temperature control, Jet Cool) is input by the remote controller, the test operation is canceled and the appliance is operated according to the setting by the remote controller. n Protection of the evaporator pipe from frosting • In the temperrature of the indoor pipe is below 0°C(32°F) after 7 minutes from starting the compressor, the compressor and outdoor fan are stopped, and 3 minutes delay of operating of the compressor, when the temperature of the indoor pipe is over 7°C(45°F), the compressor and the outdoor fan are reoperated. • Outdoor fan motor stops when indoor pipe temperature is blow 3°C(37°F) and restarts at the pipe temperature above 6°C(43°F) or after 90 seconds, if the pipe temperature does not rise to 6°C(43°F), outdoor fan motor runs continuously at even below 3°C(37°F). Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 41 - LGE Internal Use Only Operation Details n Buzzer Sounding Operation • When the appliance-operation key is input by the remote controller, the short “beep-beep-” sounds. • When the appliance-pause key is input by the remote controller, the long “beep—” sounds. n Air Cleaner Operation • When an air cleaner function is selected during Air Conditioner operation - Plasma air cleaner function will be operated while in any operation mode with selecting the function. - The function is to be stopped while it is operating with selecting the function. • When an air cleaner function is selected during operation off - The function will be only operated. • When inlet grille of air conditioner is opened during plasma operation, High Voltage Generator(H.V.B) is to be stopped. When inlet grille of air conditioner is closed during plasma operation, High Voltage Generator(H.V.B) will be operated again. Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 42 - LGE Internal Use Only Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 43 - 282(11-1/8) 169(5-5/8) 2 51(2-1/16) 1 LG Electronics USA, HVAC Division 1000 Sylvan Avenue, Englewood Cliffs, NJ 07632 www.lgusa.com / www.lghvac.com 567(22-3/8) 165(6-1/2) W 265(10-1/2) 915(36) H D 282(11-1/8) 169 (5-5/8) D [Unit : mm(inch)] [Unit : mm(inch)] Descripition 282 (11-1/8) H CHASSIS CODE: SE 2. Unit shall be grounded in accordance with the local regulations or applicable national codes. 1. Unit should be installed in compliance with the installation manual in the product box. Note Air suction grill Air discharge grill 1 2 Name 915 (36) ARNU073SE*2 ARNU093SE*2 ARNU123SE*2 ARNU153SE*2 Number W ARNU073SE*2 ARNU093SE*2 ARNU123SE*2 ARNU153SE*2 Model 76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea www.lgeaircon.com 53(2-1/16) ART COOL Mirror Dimensions 3. Dimensions LGE Internal Use Only Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes 804 1107 1 72 58 122 2 281 93 3 200 53 4 10 63 Knockout hole Installation plate 5 - 44 - (unit : mm) Remark 76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea CHASSIS CODE: S8 2. Unit shall be grounded in accordance with the local regulations or applicable national codes. 1. Unit should be installed in compliance with the installation manual in the product box. Note Air suction grille 4 Display & signal receiver Front panel Part Name 3 2 1 No. ARNU18GS8*2 ARNU24GS8*2 ART COOL Mirror Dimensions LGE Internal Use Only 48 299 ArtCoolGallery 1. Functions ....................................................................................46 2. Operation Details........................................................................47 3. Dimensions .................................................................................54 Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 45 - LGE Internal Use Only Functions 1. Functions Indoor Unit Operation ON/OFF by Remote controller Sensing the Room Temperature • Room temperature sensor. (THERMISTOR) Room temperature control • Maintains the room temperature in accordance with the Setting Temp. Starting Current Control • Indoor fan is delayed for 5 sec at the starting. Indoor Fan Speed Control • High, Med, Low, CHAOS Operation indication Lamps (LED) Signal Receptor Receives the signals from the remote control.(Signal receiving sound: two short beeps or one long beep.) Operation Indication Lamps On/Off : Lights up during the system operation. Sleep Mode : Lights up during Sleep Mode Auto operation. Timer : Lights up during Timer operation. Defrost Mode : Lights up during Defrost Mode or Hot Start operation. Soft Dry Operation Mode • Intermittent operation of fan at low speed. Sleep Mode Auto Control • The fan is switched to low(Cooling), med(Heating) speed. • The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours. Defrost(Deice) control (Heating) Natural Air Control by CHAOS Logic • Both the indoor and outdoor fan stops during defrosting. • The fan is switched to intermittent or irregular operation • The fan speed is automatically switched from high to low speed. Airflow Direction Control • The louver can be set at the desired position or swing up and down automatically. Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 46 - Hot-start Control (Heating) • The indoor fan does not rotate until the evaporator pipe temperature will be reached at 28°C(82°F). LGE Internal Use Only Operation Details 2. Operation Details Function of Controls DISPLAY 1) High quality LCD remote controller supplied Operation Indicator • On while in appliance operation, off while in appliance pause Timer Indicator • On while in timer mode (on/off) and in sleep timer mode, off when timer mode is completed or canceled Defrost Indicator • Off except when hot start during heating mode operation or while in defrost control. Plasma Indicator • On while in plasma mode, off while plasma mode is canceled. Auto restart Indicator • On while auto restart mode, off while auto restart mode is canceled. Auto restart • In case the power comes on again after a power failure, Auto Restarting Operation is the function to operate procedures automatically to the previous operating conditions. If your want to use this operation, press the Auto Restart Button. Power(Forced Operation) • Operation starts, when this button is pressed and stops when you press the button again. n Cooling Mode Operation • When the intake air temperature reaches 0.5°C(33°F) below the setting temp, the compressor and the outdoor fan stop. • When it reaches 0.5°C(33°F) above the setting temp, they start to operate again. Compressor ON Temp=> Setting Temp+0.5°C(33°F) Compressor OFF Temp => Setting Temp-0.5°C(33°F) • While in compressor running, operating with the airflow speed set by the remote controller. While in compressor not running, operating with the low airflow speed regardless of the setting. Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 47 - LGE Internal Use Only Operation Details n Healthy Dehumidification Mode • When the dehumidification operation input by the remote controller is received, the intake air temperature is detected and the setting temp is automatically set according to the intake air temperature. 26°C(78°F) ≤ Intake Air Temp => 25°C 24°C(76°F) ≤ Intake Air Temp < 26°C(78°F) => Intake Air Temp-1°C 18°C(64°F) ≤ Intake Air Temp < 24°C(76°F) => Intake Air Temp-0.5°C(33°F) Intake Air Temp < 18°C(64°F) => 18°C(64°F) • While in compressor off, the indoor fan repeats low airflow speed and pause. • While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification operation and 4-min compressor off repeat Compressor ON Temp. => Setting Temp+0.5°C(33°F) Compressor OFF Temp. => Setting Temp-0.5°C(33°F) • In 10-min dehumidification operation, the indoor fan operates with the low airflow speed. n Heating Mode Operation • When the intake air Temp. reaches Compressor OFF Temp., the compressor is turned off. When the intake air Temp. reaches Compressor ON Temp., the compressor is turned on. Themo ON Temp. => Setting Temp. +2˚C(36°F) Themo OFF Temp. => Setting Temp.+4°C(39°F) • While in compressor on, when above 38°C(100°F), it operates with setting airflow speed (while in sleep mode, with the medium airflow speed). • While in compressor off, the indoor fan is off when the indoor pipe temp is below 33°C(92°F) , when above 35°C(94°F) , it operates with the low airflow speed. • While in defrost control, both of the indoor and outdoor fans are turned off. n Defrost Control • While in heating mode operation in order to protect outdoor unit from freezing, reversed to cooling cycle to defrost of the outdoor unit. n Fuzzy Operation (Outdoor unit C/O Model) • According to the temperature set by Fuzzy rule, when the intake air temp is 0.5°C(33°F) or more below the setting temp, the compressor is turned off. When 0.5°C(33°F) or more above the setting temp, the compressor is turned on. Compressor ON Temp => Setting Temp+0.5°C(33°F) Compressor OFF Temp => Setting Temp+0.5°C(33°F) • At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temp at that time. 26°C(78°F) ≤ Intake Air Temp => 25°C(76°F) 24°C(76°F) ≤ Intake Air Temp<26°C(78°F) => Intake Air Temp+1°C(34°F) 22°C(72°F) ≤ Intake Air Temp<24°C(76°F) => Intake Air Temp+0.5°C(33°F) 18°C(64°F) ≤ Intake Air Temp<22°C(72°F) => Intake Air Temp Intake Air Temp<18°C(64°F) => 18°C(64°F) • When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule. • While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperCopyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 48 - LGE Internal Use Only Operation Details ature n Fuzzy Operation (Outdoor unit H/P Model) • When any of operation mode is not selected like the moment of the power on or when 3 hrs has passed since the operation off, the operation mode is selected. • When determining the operation mode, the compressor, the outdoor fan, and the 4 way valve are off and only the indoor fan is operated for 15 seconds. Then an operation mode is selected according to the intake air temp at that moment as follows. 24°C(76°F) ≤ Inatake Air Temp => Fuzzy Operation for Cooling 21°C(70°F) ≤ Inatake Air Temp<24°C(76°F) => Fuzzy Operation for Dehumidification Inatake Air Temp<21°C(70°F) => Fuzzy Operation for Heating • If any of the operation modes among cooling / dehumidification / heating mode operations is carried out for 10 sec or longer before Fuzzy operation, the mode before Fuzzy operation is operated. 1) Fuzzy Operation for Cooling • According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C(33°F) or more below the setting temp, the compressor is turned off. When 0.5°C(33°F) or more above the setting temp, the compressor is turned on. Compressor ON Temp => Setting Temp+0.5°C(33°F) Compressor OFF Temp => Setting Temp+0.5°C(33°F) • At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temp at that time. 26°C(78°F) ≤ Intake Air Temp => 25°C(76°F) 24°C(76°F) ≤ Intake Air Temp<26°C(78°F) => Intake Air Temp+1°C(34°F) 22°C(72°F) ≤ Intake Air Temp<24°C(76°F) => Intake Air Temp+0.5°C(33°F) 18°C(64°F) ≤ Intake Air Temp<22°C(72°F) => Intake Air Temp Intake Air Temp < 18°C(64°F) => 18°C(64°F) • When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule. • While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperature. 2) Fuzzy Operation for Dehumidification • According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C or more below the setting temp, the compressor is turned off. When 0.5°C(33°F) or more above the setting temp, the compressor is turned on. Compressor ON Temp => Setting Temp+0.5°C(33°F) Compressor OFF Temp => Setting Temp+0.5°C(33°F) Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 49 - LGE Internal Use Only Operation Details • At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temp at that time. 26°C(78°F) ≤ Intake Air Temp => 25°C(76°F) 24°C(76°F) ≤ Intake Air Temp<26°C(78°F) => Intake Air Temp+1°C(34°F) 22°C(72°F) ≤ Intake Air Temp<24°C(76°F) => Intake Air Temp+0.5°C(33°F) 18°C(64°F) ≤ Intake Air Temp<22°C(72°F) => Intake Air Temp Intake Air Temp < 18°C (64°F) => 18°C(64°F) • When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule. • While in Fuzzy operation, the airflow speed of the indoor fan repeats the low airflow speed or pause as in dehumidification operation. 3) Fuzzy Operation for Heating • According to the setting temperature selected by Fuzzy rule, when the intake air temp is 3°C(37°F) or more above the setting temp, the compressor is turned off. When below the setting temp, the compressor is turned on. Compressor ON Temp => Setting Temp + 2°C(36°F) Compressor OFF Temp => Setting Temp + 4°C(39°F) • At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temp at that time. 20°C(68°F) ≤ Intake Air Temp => Intake Air Temp + 0.5°C(33°F) Intake Air Temp < 20°C(68°F) => 20°C(68°F) • When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule. • While in Fuzzy operation, the airflow speed of the indoor fan is set to the high or the medium according to the intake air temperature and the setting temperature. n Airflow Speed Selection • The airflow speed of the indoor fan is set to high, medium, low, or chaos by the input of the airflow speed selection key on the remote controller. n On-Timer Operation • When the set time is reached after the time is input by the remote controller, the appliance starts to operate. • The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached. • If the appliance is operating at the time set by the timer, the operation continues. n Off-Timer Operation • When the set time is reached after the time is input by the remote controller, the appliance stops operating. • The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached. • If the appliance is on pause at the time set by the timer, the pause continues. Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 50 - LGE Internal Use Only Operation Details n Off-Timer <=> On-Timer Operation • When the set time is reached after the on/off time is input by the remote controller, the on/off-timer operation is carried out according to the set time. n Sleep Timer Operation • When the sleep time is reached after <1,2,3,4,5,6,7,0(cancel) hr> is input by the remote controller while in appliance operation, the operation of the appliance stops. • While the appliance is on pause, the sleep timer mode cannot be input. • While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperature increases by 1°C(34°F) After another 30 min elapse, it increases by 1°C(34°F) again. • When the sleep timer mode is input while in cooling cycle mode, the airflow speed of the indoor fan is set to the low. • When the sleep timer mode is input while in heating cycle mode, the airflow speed of the indoor fan is set to the medium. n Chaos Swing Mode • By the Chaos Swing key input, the vane automatically operates with the Chaos Swing or they are fixed to the desired direction. n Chaos Natural Wind Mode • When the Chaos Natural Wind mode is selected and then operated, the high, medium, or low speed of the airflow mode is operated for 2~15 sec randomly by the Chaos Simulation.” n Jet Cool Mode Operation (Outdoor unit C/O Model) • If the Jet Cool key is input at any operation mode while in appliance operation, the Jet Cool mode operates. • In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation. • In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C(64°F) • When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority. • When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then operated in order that the air outflow could reach further. n Jet Cool Mode Operation (Outdoor unit H/P Model) • While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the other mode operation (cooling, dehumidification, ventilation), the Jet Cool mode is operated.” • In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation. • In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C(64°F) • When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority. • When the Jet Cool key is input, the upper/lower vanes are reset to those of the initial cooling mode and then operated in order that the air outflow could reach further. n Auto Restarting Operation • When the power is restored after a sudden power failure while in appliance operation, the mode before the power failure is kept on the memory and the appliance automatically operates in the mode on the memory. • Operation Mode that is kept on the memory Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 51 - LGE Internal Use Only Operation Details - State of Operation ON/OFF - Operation Mode/Setting Temp/Selected Airflow Speed - Sleep Timer Mode/Remaining Time of Sleep Timer (unit of hour) n Forced Operation (Outdoor unit C/O Model) • To operate the appliance by force in case that the remote controller is lost, the forced operation button is on the main unit of the appliance to operate the appliance in the standard conditions. • Press the forced operation button, the forced operation is carried out. • Press the forced operation button once again to stop operation. • The forced operation is carried out in cooling mode with the setting temperature 22°C(72°F) and the high speed of airflow. n Forced Operation (Outdoor unit H/P Model) • To operate the appliance by force in case that the remote controller is lost, the forced operation selection switch is on the main unit of the appliance to operate the appliance in the standard conditions. • Press the forced operation button, the forced operation is carried out. • Press the forced operation button once again to stop operation. • In the forced operation mode, the indoor fan is operated at low speed for around 15 sec and then the operation condition is set according to the intake air temperature as follows. 24°C(76°F) ≤ Intake Air Temp => Cooling Mode Operation, 22°C(72°F), High Speed 21°C(70°F) ≤ Intake Air Temp < 24°C(76°F) => Dehumidification Operation, 23°C(74°F), High Speed Intake Air Temp < 21°C(70°F) => Heating Mode Operation, 24°C(76°F), High Speed n Test Operation Control • To check the condition of the installation when installing the appliance, the appliance is operated at cooling mode, high speed of airflow, compressor-on for 18 min without controlling the room temperature. • After supplying power to the main body, keep pressing the forced operation button for about 3 seconds. • While in test operation, a key can be input by the remote controller. When a key (operation start/stop, operation mode selection, airflow speed selection, temperature control, Jet Cool) is input by the remote controller, the test operation is canceled and the appliance is operated according to the setting by the remote controller. n Protection of the evaporator pipe from frosting • In the temperrature of the indoor pipe is below 0°C(32°F) after 7 minutes from starting the compressor, the compressor and outdoor fan are stopped, and 3 minutes delay of operating of the compressor, when the temperature of the indoor pipe is over 7°C(45°F), the compressor and the outdoor fan are reoperated. • Outdoor fan motor stops when indoor pipe temperature is blow 3°C(37°F) and restarts at the pipe temperature above 6°C or after 90 seconds, if the pipe temperature does not rise to 6°C(43°F), outdoor fan motor runs continuously at even below 3°C(37°F). Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 52 - LGE Internal Use Only Operation Details n Buzzer Sounding Operation • When the appliance-operation key is input by the remote controller, the short “beep-beep-” sounds. • When the appliance-pause key is input by the remote controller, the long “beep—” sounds. n Air Cleaner Operation • When an air cleaner function is selected during Air Conditioner operation - Plasma air cleaner function will be operated while in any operation mode with selecting the function. - The function is to be stopped while it is operating with selecting the function. • When an air cleaner function is selected during operation off - The function will be only operated. • When inlet grille of air conditioner is opened during plasma operation, High Voltage Generator(H.V.B) is to be stopped. When inlet grille of air conditioner is closed during plasma operation, High Voltage Generator(H.V.B) will be operated again. Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 53 - LGE Internal Use Only 1 Fix Hole 2 Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 54 1 Hanger Hole H D LG Electronics USA, HVAC Division 1000 Sylvan Avenue, Englewood Cliffs, NJ 07632 www.lgusa.com / www.lghvac.com 500(19-5/8) Pipe Hole W 1 Air discharge grill Air suction grill 1 2 [Unit : mm(inch)] 146 (5-11/16) D Descripition 600 (23-5/8) H [Unit : mm(inch)] 76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea www.lgeaircon.com CHASSIS CODE: SF 2. Unit shall be grounded in accordance with the local regulations or applicable national codes. 1. Unit should be installed in compliance with the installation manual in the product box. Note Name 600 (23-5/8) ARNU073SF*2 ARNU093SF*2 ARNU123SF*2 Number W Model ARNU073SF*2 ARNU093SF*2 ARNU123SF*2 ART COOL Gallery Dimensions 3. Dimensions LGE Internal Use Only 525(20-5/8) Ceiling Concealed Duct Type (Low static) 1. Funtions ......................................................................................56 2. Operation Details........................................................................57 3. Dimensions .................................................................................60 Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 55 - LGE Internal Use Only Functions 1. Funtions Indoor Unit Operation ON/OFF by Remote controller Sensing the Room Temperature • Maintains the room temperature in accordance with the Setting Temperature. Room temperature control Starting Current Control • Indoor fan is delayed for 5 seconds at the starting. • High, Med, Low Indoor Fan Speed Control Soft Dry Operation Mode Auto Restart • Room temperature sensor. (Thermistor) • Intermittent operation of fan at low speed. • Although the air-conditioner is turned off by a power failure, it is restarted automatically previous operation mode after power supply. Deice (defrost) control (Heating) • Both the indoor and outdoor fan stops during defrosting. • Hot start after defrost ends. Hot-start Control (Heating) • The indoor fan does not rotate until the evaporator piping temperature reaches 25°C(76°F). High head height Drain pump • A standard drain-head height of up to 700mm(27-9/16inch) is possible. Central Control(Optional) • It is operating individually or totally by central control function. Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 56 - LGE Internal Use Only Operation Details 2. Operation Details (1) The function of main control n Soft-Dry Operation • The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of already being set to the best speed for Dry Operation by microcontroller control. n Cooling Mode Operation • When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote controller and the operation diagram is as following. Intake Air Temperature Thermo. ON (SET TEMPERATURE +0.5°C(33°F)) Thermo. OFF (SET TEMPERATURE -0.5°C(33°F)) INDOOR FAN COMPRESSOR Indoor Unit mode 2TH (Remo.+Indoor) Remo. Mode More than 3 minutes More than 3 minutes Selecting fan speed Low Selecting fan speed Low Selecting fan speed ON OFF ON OFF ON Thermal ON ST+0.5 To be selected higher temperature contrast Indoor Unit and Remo. ST+0.5 Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 57 - Thermal OFF ST-0.5 To be selected higher temperature contrast Indoor Unit and Remo. ST-0.5 LGE Internal Use Only Operation Details n Heating Mode Operation The unit will operate according to the setting by the remote controller and the operation diagram is shown as following. Indoor unit 40°C(104°F) Heat-Exchanger temperature T ST A T LT T Off T On Intake Air Temperature 3min B Low fan during 10sec Setting Temperature +3°C(37°F) (Thermal OFF) Setting Temperature (Thermal ON) Minimum 3min 1min Thermal Indoor fan OFF OFF ON ON Outdoor fan Off Low Low Setting fan spped Setting fan spped Low 4way valve Low 1min ON ON C Off Off Setting fan spped Low ON • Compressor-off interval : - A While the indoor Heat-Exchanger temperature is higher than 40°C(104°F), fan operates at low speed, when it becomes lower than 40°C(104°F) fan stops. - B For eluminating latent heat-loss, fan operates at low speed for 10 seconds periodically. - C To be operated "Low" except initial Hotstart operation High Static Chassis Low Static BH BG BR B1 B2 CE Convertible CF VE VJ Hotstart On T On 19°C(66°F) 19°C(66°F) 19°C(66°F) 19°C(66°F) 19°C(66°F) 19°C(66°F) 19°C(66°F) 26°C(78°F) 26°C(78°F) Hotstart Off T Off 22°C(72°F) 22°C(72°F) 22°C(72°F) 22°C(72°F) 22°C(72°F) 22°C(72°F) 22°C(72°F) 27°C(80°F) 27°C(80°F) Low temperature T LT 25°C(76°F) 25°C(76°F) 25°C(76°F) 25°C(76°F) 25°C(76°F) 25°C(76°F) 25°C(76°F) 28°C(82°F) 28°C(82°F) Setting Temperature T ST 27°C(80°F) 27°C(80°F) 27°C(80°F) 27°C(80°F) 27°C(80°F) 27°C(80°F) 27°C(80°F) 30°C(86°F) 30°C(86°F) Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 58 - LGE Internal Use Only Operation Details n Hot-Start Control • The indoor fan does not rotate until the indoor unit Hex-Exchanger temperature reaches 30°C(86°F). • The operation diagram is as following. Indoor unit Heat-Exchanger temperature Hotstart Off Hotstart On 1 min 1 min Thermal Outdoor fan Indoor fan ON ON Off Low Setting fan speed 4way Valve Off Low Setting fan speed ON • Initial Hotstart On state ¿ Power Off ‡ On ¡ Operation Off ‡ On ¬ Cooling operation ‡ Heating operation √ Defrost operation Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 59 - LGE Internal Use Only 383(15-1/16) 18(3/4) 18(3/4) 154(6) - 60 - 575(22-5/8) 190(7-7/16) Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes D B 6 14(1/2) 161(6-5/16) 13(1/2) 277(10-7/8) 4 3 190(7-7/16) 65(2-1/2) 60(2-3/8) LG Electronics USA, HVAC Division 1000 Sylvan Avenue, Englewood Cliffs, NJ 07632 www.lgusa.com / www.lghvac.com A C 5 216(8-1/2) 24(11/12) 2 1 Air discharge 5 Note D [Unit : mm(inch)] Unit size(7k,9k,12k,18k):ø6.35(1/4) Unit size(24k):ø9.52(3/8) Unit size(7k,9k,12k,18k):ø12.7(1/2) Unit size(24k):ø15.88(5/8) Descripition 76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea www.lgeaircon.com CHASSIS CODE: B1/B2 2. Unit shall be grounded in accordance with the local regulations or applicable national codes. 1. Unit should be installed in compliance with the installation manual in the product box. Air suction Power supply connection 4 Gas pipe connection Drain pipe connection 2 3 6 C 1100 1008 1131 1072 (43-5/16) (39-11/16) (44-9/16) (42-3/16) Liquid pipe connection Name B 820 794 856 728 (32-5/16) (28-11/16) (33-11/16) (31-5/16) A 1 Number ARNU183B2G2 ARNU243B2G2 ARNU073B1G2 ARNU093B1G2 ARNU123B1G2 ARNU153B1G2 [Unit : mm(inch)] ARNU073B1G2 ARNU093B1G2 ARNU123B1G2 ARNU153B1G2 ARNU183B2G2 ARNU243B2G2 Ceiling Concealed Duct (Low Static) Dimensions 3. Dimensions LGE Internal Use Only Ceiling Concealed Duct Type (Built in) 1. Funtions ......................................................................................62 2. Operation Details........................................................................63 3. Dimensions .................................................................................66 Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 61 - LGE Internal Use Only Functions 1. Funtions Indoor Unit Operation ON/OFF by Remote controller Sensing the Room Temperature • Maintains the room temperature in accordance with the Setting Temperature. Room temperature control Starting Current Control • Indoor fan is delayed for 5 seconds at the starting. • High, Med, Low Indoor Fan Speed Control Soft Dry Operation Mode Auto Restart • Room temperature sensor. (Thermistor) • Intermittent operation of fan at low speed. • Although the air-conditioner is turned off by a power failure, it is restarted automatically previous operation mode after power supply. Deice (defrost) control (Heating) • Both the indoor and outdoor fan stops during defrosting. • Hot start after defrost ends. Hot-start Control (Heating) • The indoor fan does not rotate until the evaporator piping temperature reaches 25°C(76°F). High head height Drain pump • A standard drain-head height of up to 700mm(27-9/16inch) is possible. Central Control(Optional) • It is operating individually or totally by central control function. Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 62 - LGE Internal Use Only Operation Details 2. Operation Details (1) The function of main control n Soft-Dry Operation • The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of already being set to the best speed for Dry Operation by microcontroller control. n Cooling Mode Operation • When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote controller and the operation diagram is as following. Intake Air Temperature Thermo. ON (SET TEMPERATURE +0.5°C(33°F)) Thermo. OFF (SET TEMPERATURE -0.5°C(33°F)) INDOOR FAN COMPRESSOR Indoor Unit mode 2TH (Remo.+Indoor) Remo. Mode More than 3 minutes More than 3 minutes Selecting fan speed Low Selecting fan speed Low Selecting fan speed ON OFF ON OFF ON Thermal ON ST+0.5 To be selected higher temperature contrast Indoor Unit and Remo. ST+0.5 Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 63 - Thermal OFF ST-0.5 To be selected higher temperature contrast Indoor Unit and Remo. ST-0.5 LGE Internal Use Only Operation Details n Heating Mode Operation The unit will operate according to the setting by the remote controller and the operation diagram is shown as following. Indoor unit 40°C(104°F) Heat-Exchanger temperature T ST A T LT T Off T On Intake Air Temperature 3min B Low fan during 10sec Setting Temperature +3°C(37°F) (Thermal OFF) Setting Temperature (Thermal ON) Minimum 3min 1min Thermal Indoor fan OFF OFF ON ON Outdoor fan Off Low Low 1min Setting fan spped Setting fan spped Low 4way valve Low ON ON C Off Off Low Setting fan spped ON • Compressor-off interval : - A While the indoor Heat-Exchanger temperature is higher than 40°C(104°F), fan operates at low speed, when it becomes lower than 40°C(104°F) fan stops. - B For eluminating latent heat-loss, fan operates at low speed for 10 seconds periodically. - C To be operated "Low" except initial Hotstart operation High Static Chassis Low Static BH BG BR Hotstart On T On 19°C(66°F) 19°C(66°F) 19°C(66°F) Hotstart Off T Off 22°C(72°F) 22°C(72°F) Low temperature T LT 25°C(76°F) Setting Temperature T ST 27°C(80°F) VE VJ 19°C(66°F) 19°C(66°F) 19°C(66°F) 19°C(66°F) 26°C(78°F) 26°C(78°F) 22°C(72°F) 22°C(72°F) 22°C(72°F) 22°C(72°F) 22°C(72°F) 27°C(80°F) 27°C(80°F) 25°C(76°F) 25°C(76°F) 25°C(76°F) 25°C(76°F) 25°C(76°F) 25°C(76°F) 28°C(82°F) 28°C(82°F) 27°C(80°F) 27°C(80°F) 27°C(80°F) 27°C(80°F) 27°C(80°F) 27°C(80°F) 30°C(86°F) 30°C(86°F) Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes B1 - 64 - B2 CE Convertible CF LGE Internal Use Only Operation Details n Hot-Start Control • The indoor fan does not rotate until the indoor unit Hex-Exchanger temperature reaches 30°C(86°F). • The operation diagram is as following. Indoor unit Heat-Exchanger temperature Hotstart Off Hotstart On 1 min 1 min Thermal Outdoor fan Indoor fan ON ON Off Low Setting fan speed Off Low Setting fan speed ON 4way Valve • Initial Hotstart On state ¿ Power Off ‡ On ¡ Operation Off ‡ On ¬ Cooling operation ‡ Heating operation √ Defrost operation Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 65 - LGE Internal Use Only C_2 B_3 A_2 A_3 388(15-1/4) C_3 B_2 A_1 B3/B4 618(24-5/16) PBSC30 PBSC40 PBSGB30 PBSGB40 B_2 C_2 359(14-1/8) 56(2-3/16) 359(14-1/8) 56(2-3/16) 277(10-7/8) 6 1 3 24(11/12) 216(8-1/2) 4 190(7-7/16) 5 Air suction Unit size(7k,9k,12k,18k):ø6.35(1/4) Unit size(24k):ø9.52(3/8) Unit size(7k,9k,12k,18k):ø12.7(1/2) Unit size(24k):ø15.88(5/8) Descripition [Unit : mm(inch)] CHASSIS CODE: B3/B4 2. Unit shall be grounded in accordance with the local regulations or applicable national codes. 1. Unit should be installed in compliance with the installation manual in the product box. Air discharge 6 Gas pipe connection Drain pipe connection Power supply connection 2 3 4 5 Liquid pipe connection Name 1 Number 2 Note 65(2-1/2) 60(2-3/8) ARNU073B3G2+PBSGB30(Accessory), PBSC30(Accessory) ARNU093B3G2+PBSGB30(Accessory), PBSC30(Accessory) ARNU123B3G2+PBSGB30(Accessory), PBSC30(Accessory) ARNU153B3G2+PBSGB30(Accessory), PBSC30(Accessory) ARNU183B4G2+PBSGB40(Accessory), PBSC40(Accessory) ARNU243B4G2+PBSGB40(Accessory), PBSC40(Accessory) Ceiling Concealed Duct (Built in) 76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea www.lgeaircon.com A_3 B_3 C_3 821(32-5/16) 274(10-11/16) 42~250(1-9/16~9-13/16) 1100(43-5/16) 274(10-11/16) 42~250(1-9/16~9-13/16) A_2 910(35-13/16) 1188(46-13/16) With Suction Grille Btu/h A_1 7,9,12k 820(32-5/16) 18,24k 1100(43-5/16) 388(15-1/4) LG Electronics USA, HVAC Division 1000 Sylvan Avenue, Englewood Cliffs, NJ 07632 www.lgusa.com / www.lghvac.com 500(19-11/16)(Max) - 66 With Suction Grille & Suction Canvas 190(7-7/16) With Suction Grille & Suction Canvas 575(22-5/8) 250(9-13/16) Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes 190(7-7/16) With Suction Grille Dimensions 3. Dimensions LGE Internal Use Only Ceiling Concealed Duct Type (High Static) 1. Funtions ......................................................................................68 2. Operation Details........................................................................69 3. Dimensions .................................................................................72 Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 67 - LGE Internal Use Only Funtion 1. Funtions Indoor Unit Operation ON/OFF by Remote controller Sensing the Room Temperature • Maintains the room temperature in accordance with the Setting Temperature. Room temperature control Starting Current Control • Indoor fan is delayed for 5 seconds at the starting. • High, Med, Low Indoor Fan Speed Control Soft Dry Operation Mode Auto Restart • Room temperature sensor. (Thermistor) • Intermittent operation of fan at low speed. • Although the air-conditioner is turned off by a power failure, it is restarted automatically previous operation mode after power supply. Deice (defrost) control (Heating) • Both the indoor and outdoor fan stops during defrosting. • Hot start after defrost ends. Hot-start Control (Heating) • The indoor fan does not rotate until the evaporator piping temperature reaches 25°C(76°F) High head height Drain pump • A standard drain-head height of up to 700mm(27-9/16inch) is possible. Central Control(Optional) • It is operating individually or totally by central control function. Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 68 - LGE Internal Use Only Operation Details 2. Operation Details (1) The function of main control n Soft-Dry Operation • The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of already being set to the best speed for Dry Operation by microcontroller control. n Cooling Mode Operation • When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote controller and the operation diagram is as following. Intake Air Temperature Thermo. ON (SET TEMPERATURE +0.5°C(33°F)) Thermo. OFF (SET TEMPERATURE -0.5°C(33°F)) INDOOR FAN COMPRESSOR More than 3 minutes More than 3 minutes Selecting fan speed Low Selecting fan speed Low Selecting fan speed ON OFF ON OFF ON Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 69 - LGE Internal Use Only Operation Details n Heating Mode Operation The unit will operate according to the setting by the remote controller and the operation diagram is shown as following. Indoor unit 40°C(104°F) Heat-Exchanger temperature T ST A T LT T Off T On Intake Air Temperature 3min B Low fan during 10sec Setting Temperature +3°C(37°F) (Thermal OFF) Setting Temperature (Thermal ON) Minimum 3min 1min Thermal Indoor fan OFF OFF ON ON Outdoor fan Off Low Low Setting fan spped Setting fan spped Low 4way valve Low 1min ON ON C Off Off Setting fan spped Low ON • Compressor-off interval : - A While the indoor Heat-Exchanger temperature is higher than 40°C(104°F), fan operates at low speed, when it becomes lower than 40°C(104°F) fan stops. - B For eluminating latent heat-loss, fan operates at low speed for 10 seconds periodically. - C To be operated "Low" except initial Hotstart operation High Static Chassis Low Static BH BG BR Hotstart On T On 19°C(66°F) 19°C(66°F) 19°C(66°F) Hotstart Off T Off 22°C(72°F) 22°C(72°F) Low temperature T LT 25°C(76°F) Setting Temperature T ST 27°C(80°F) VE VJ 19°C(66°F) 19°C(66°F) 19°C(66°F) 19°C(66°F) 26°C(78°F) 26°C(78°F) 22°C(72°F) 22°C(72°F) 22°C(72°F) 22°C(72°F) 22°C(72°F) 27°C(80°F) 27°C(80°F) 25°C(76°F) 25°C(76°F) 25°C(76°F) 25°C(76°F) 25°C(76°F) 25°C(76°F) 28°C(82°F) 28°C(82°F) 27°C(80°F) 27°C(80°F) 27°C(80°F) 27°C(80°F) 27°C(80°F) 27°C(80°F) 30°C(86°F) 30°C(86°F) Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes B1 - 70 - B2 CE Convertible CF LGE Internal Use Only Operation Details n Hot-Start Control • The indoor fan does not rotate until the indoor unit Hex-Exchanger temperature reaches 30°C(86°F). • The operation diagram is as following. Indoor unit Heat-Exchanger temperature Hotstart Off Hotstart On 1 min 1 min Thermal Outdoor fan Indoor fan ON ON Off Low Setting fan speed Off Low Setting fan speed ON 4way Valve • Initial Hotstart On state ¿ Power Off ‡ On ¡ Operation Off ‡ On ¬ Cooling operation ‡ Heating operation √ Defrost operation Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 71 - LGE Internal Use Only - 72 - 7.5 R3 /8) 60(2-3 47(1-7/8) 5 6 882(34-3/4) 212(8-3/8) 355(14) 450(17-11/16) 47(1-7/8) 65(2-9/16) 108(4-3/13) 30(1-3/16) 243(9-9/16) 119(4-11/16) 882(34-3/4) 750(29-1/2) 87(3-7/16) 932(36-11/16) 133(5-1/4) LG Electronics USA, HVAC Division 1000 Sylvan Avenue, Englewood Cliffs, NJ 07632 www.lgusa.com / www.lghvac.com 243(9-9/16) 24(15/16) 64(2-1/2) 21(7/8) 49(15/16) 4 50(1-15/16) 1 2 100(3-15/16) Air suction 6 [Unit : mm(inch)] Unit size(7k,9k,12k,18k):ø6.35(1/4) Unit size(24k):ø9.52(3/8) Unit size(7k,9k,12k,18k):ø12.7(1/2) Unit size(24k):ø15.88(5/8) Descripition CHASSIS CODE: BH 2. Unit shall be grounded in accordance with the local regulations or applicable national codes. 1. Unit should be installed in compliance with the installation manual in the product box. Note Air discharge 5 3 Power supply connection Gas pipe connection Drain pipe connection 2 4 Liquid pipe connection Name 1 Number 3 ARNU073BHA2 ARNU093BHA2 ARNU123BHA2 ARNU153BHA2 ARNU183BHA2 ARNU243BHA2 Ceiling Concealed Duct (High Static) 76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea www.lgeaircon.com 260(10-1/4) 29(1-1/8) 51(2-1/16) 101(3-15/16) 31(1-3/13) 70(2-3/4) 123(4-13/16) 114(4-1/2) 260(10-1/4) 115(4-1/2) 165(6-7/13) 175(6-7/8) 20(3/4) 75(2-15/16) 355(14) 158(6-1/4) 450(17-11/16) Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes 106 127(5) (4-1/8) 48(1-7/8) 52(2-1/16) 140(5-9/16) 745(29-3/8) Dimensions 3. Dimensions LGE Internal Use Only 450(17-11/16) 224(8-7/8) - 73 - 00 ø1 ) /8 60(2-3 152(5-7/8) 232(1-1/4) 49(15/16) 1,182(46-1/2) 232(1-1/4) 1,182(46-5/8) 830(32-11/16) 87(3-7/16) 1,230(48-7/16) 243(9-9/16) 232(1-1/4) 450(17-11/16) 75(2-15/16) 108(4-3/13) 29(1-3/8) 4 LG Electronics USA, HVAC Division 1000 Sylvan Avenue, Englewood Cliffs, NJ 07632 www.lgusa.com / www.lghvac.com 243(9-9/16) 5 6 115(4-1/2) 1 2 102(4) 220(8-5/8) 32(1-3/13) Name Power supply connection Air discharge Air suction 3 4 5 6 Unit size(28k,36k,42k):ø15.88(5/8) Unit size(28k,36k,42k):ø9.52(3/8) Descripition [Unit : mm(inch)] CHASSIS CODE: BG 2. Unit shall be grounded in accordance with the local regulations or applicable national codes. 1. Unit should be installed in compliance with the installation manual in the product box. Note Gas pipe connection Drain pipe connection 2 Liquid pipe connection 1 Number 3 ARNU283BGA2 ARNU363BGA2 ARNU423BGA2 Ceiling Concealed Duct (High Static) 76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea www.lgeaircon.com 261(10-1/4) 51(2-1/16) 53(2-1/16) 47(1-7/8) 20(3/4) 224(8-7/8) 298(11-11/16) 50(1-15/16) 100(3-15/16) 23(15/16) 186(7-5/16) 450(17-11/16) 87(3-7/16) 355(14) 113(4-7/16) 158(6-1/4) Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes 122(4-13/16) 165(6-7/13) 140(5-9/16) 1,043(41) Dimensions LGE Internal Use Only R6 0 /8) 60(2-3 5 241(9-1/2) 50(1-15/16) 6 279(11) 279(11) 215(8-1/2) 114(4-7/16) 120(4-3/4) 1 90(3-9/16) 2 LG Electronics USA, HVAC Division 1000 Sylvan Avenue, Englewood Cliffs, NJ 07632 www.lgusa.com / www.lghvac.com 1,230(48-7/16) 241(9-1/2) 1,004(39-9/16) 118(4-5/8) 1,284(50-9/16) 1,230(48-7/16) 1,092(43) 135(5-5/16) 190(7-7/16) 260(10-1/4) 115(4-9/16) 83(3-1/4) 26(1) 101(3-15/16) 72(2-13/16) 3 [Unit : mm(inch)] Unit size(48k):ø15.88(5/8) Unit size(48k):ø9.52(3/8) Descripition CHASSIS CODE: BR 2. Unit shall be grounded in accordance with the local regulations or applicable national codes. 1. Unit should be installed in compliance with the installation manual in the product box. Note Air suction Air discharge 5 6 Drain pipe connection Power supply connection 4 Gas pipe connection 3 Liquid pipe connection 2 Name 1 Number ARNU483BRA2 Ceiling Concealed Duct (High Static) 76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea www.lgeaircon.com 122(4-13/16) 198(7-3/4) 312(12-1/4) 380(15) 477(18-3/4) 56(2-3/16) 25(1) 303(12) 32(1-3/13) 140(5-9/16) - 74 - 590(23-3/16) 590(23-3/16) 168(6-5/8) Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes 185(7-1/4) 123(4-13/16) 221(8-3/4) 144(5-11/16) 4 Dimensions LGE Internal Use Only - 75 - 460(18-1/13) 460(18-1/13) 688(27) 20(3/4) 440(17-3/8) 318(12-7/13) 115(4-9/16) 4 LG Electronics USA, HVAC Division 1000 Sylvan Avenue, Englewood Cliffs, NJ 07632 www.lgusa.com / www.lghvac.com 1,562(61-1/2) 293(11-7/13) 329(12-15/16) 320(12-5/8) 329(12-15/16) 5 1,220(48) 1,622(63-11/13) 1,562(61-7/13) 6 1,396(54-15/16) 64(2-7/13) 560(22) 688(27) 30(1-3/16) Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes 161 290(11-7/16) (6-3/8) 18(3/4) 358(14) 109(4-1/4) 68(2-5/8) 58(2-1/4) 70(2-3/4) 122(4-7/8) 60(2-3/8) 99 Name Air suction 6 [Unit : mm(inch)] Unit size(96k):ø22.2(7/8) Unit size(76k,96k):ø9.52(3/8) Unit size(76k):ø19.05(3/4) Descripition CHASSIS CODE: B8 2. Unit shall be grounded in accordance with the local regulations or applicable national codes. 1. Unit should be installed in compliance with the installation manual in the product box. Note Air discharge Drain pipe connection Power supply connection Gas pipe connection Liquid pipe connection 3 5 4 3 2 1 Number ) -9/16 76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea www.lgeaircon.com 1 (5 ) 14 0 (3-7/8 120(4-3/4) 70(2-3/4) 2 URNU763B8A2 URNU963B8A2 Ceiling Concealed Duct (High Static) Dimensions LGE Internal Use Only 64(2-1/2) Wall Mountedd Type 1. Functions ....................................................................................77 2. Operation Details........................................................................78 3. Dimensions .................................................................................85 Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 76 - LGE Internal Use Only Functions 1. Functions Indoor Unit Operation ON/OFF by Remote controller Sensing the Room Temperature • Room temperature sensor. (THERMISTOR) Room temperature control • Maintains the room temperature in accordance with the Setting temperature Starting Current Control • Indoor fan is delayed for 5 sec at the starting. Indoor Fan Speed Control • High, Med, Low, CHAOS Operation indication Lamps (LED) Signal Receptor Receives the signals from the remote control.(Signal receiving sound: two short beeps or one long beep.) Operation Indication Lamps On/Off : Lights up during the system operation. Sleep Mode : Lights up during Sleep Mode Auto operation. Timer : Lights up during Timer operation. Defrost Mode : Lights up during Defrost Mode or Hot Start operation. Temperature : Indicate the setting temperature. Soft Dry Operation Mode • Intermittent operation of fan at low speed. Sleep Mode Auto Control • The fan is switched to low(Cooling), med(Heating) speed. • The unit will stopped 1, 2,Logic 3, 4, 5, 6, 7 hours. Natural Air be Control by after CHAOS • The fan is switched to intermittent or irregular operation fan speed is automatically • The Airflow Direction Control switched from high to low speed. Defrost(Deice) control (Heating) • Both the indoor and outdoor fan stops during defrosting. Hot-start Control (Heating) • The indoor fan does not rotate until the evaporator pipe temperature will be reached at 28°C(82°F). • The louver can be set at the desired position or swing up and down automatically. Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 77 - LGE Internal Use Only Operation Details 2. Operation Details Function of Controls DISPLAY (1) High quality LCD remote controller supplied Operation Indicator • On while in appliance operation, off while in appliance pause Timer(on/off) and Sleep timer Indicator • On while in timer mode (on/off) and in sleep timer mode, off when timer mode is completed or canceled Defrost Indicator • Off except when hot start during heating mode operation or while in defrost control. Plasma Indicator • On while in plasma mode, off while plasma mode is canceled. Auto restart • In case the power comes on again after a power failure, Auto Restarting Operation is the function to operate procedures automatically to the previous operating conditions. If your want to use this operation, press the Auto Restart Button. Power(Forced Operation) • Operation starts, when this button is pressed and stops when you press the button again. n Cooling Mode Operation • When the intake air temperature reaches 0.5°C(33°F) below the setting temp, the compressor and the outdoor fan stop. • When it reaches 0.5°C(33°F) above the setting temp, they start to operate again. Compressor ON Temp=> Setting Temp+0.5°C(33°F) Compressor OFF Temp => Setting Temp-0.5°C(33°F) • While in compressor running, operating with the airflow speed set by the remote controller. While in compressor not running, operating with the low airflow speed regardless of the setting. Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 78 - LGE Internal Use Only Operation Details n Healthy Dehumidification Mode • When the dehumidification operation input by the remote controller is received, the intake air temperature is detected and the setting temp is automatically set according to the intake air temperature. 26°C(78°F) ≤ Intake Air Temp => 25°C(76°F) 24°C(76°F) ≤ Intake Air Temp < 26°C(78°F) => Intake Air Temp-1°C(34°F) 18°C(64°F) ≤ Intake Air Temp < 24°C(76°F) => Intake Air Temp-0.5°C(33°F) Intake Air Temp < 18°C(64°F) => 18°C(64°F) • While in compressor off, the indoor fan repeats low airflow speed and pause. • While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification operation and 4-min compressor off repeat Compressor ON Temp. => Setting Temp+0.5°C(33°F) Compressor OFF Temp. => Setting Temp-0.5°C(33°F) • In 10-min dehumidification operation, the indoor fan operates with the low airflow speed. n Heating Mode Operation • When the intake air temp reaches +3°Cabove the setting temp, the compressor is turned off. When below the setting temp, the compressor is turned on. Thermo ON Temp. => Setting Temp. +2°C(36°F) Thermo OFF Temp. => Setting Temp. +4°C(39°F) • While in compressor on, when above 38°C(100°F) , it operates with or setting airflow speed (while in sleep mode, with the medium airflow speed). • While in compressor off, the indoor fan is off when the indoor pipe temp is below 33°C(92°F) , when above 35°C(94°F) , it operates with the low airflow speed. • While in defrost control, both of the indoor and outdoor fans are turned off. n Defrost Control • While in heating mode operation in order to protect outdoor unit from freezing, reversed to cooling cycle to defrost the outdoor unit. n Fuzzy Operation (Outdoor unit C/O Model) • According to the temperature set by Fuzzy rule, when the intake air temp is 0.5°C(33°F) or more below the setting temp, the compressor is turned off. When 0.5°C (33°F) or more above the setting temp, the compressor is turned on. Compressor ON Temp => Setting Temp+0.5°C(33°F) Compressor OFF Temp => Setting Temp+0.5°C(33°F) • At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temp at that time. Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 79 - LGE Internal Use Only Operation Details 26°C(78°F) ≤ Intake Air Temp => 25°C(76°F) 24°C(76°F) ≤ Intake Air Temp<26°C(78°F) => Intake Air Temp+1°C(34°F) 22°C(72°F) ≤ Intake Air Temp<24°C(76°F) => Intake Air Temp+0.5°C(33°F) 18°C(64°F) ≤ Intake Air Temp<22°C(72°F) => Intake Air Temp Intake Air Temp<18°C(64°F) => 18°C(64°F) • When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule. • While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperature n Fuzzy Operation (Outdoor unit H/P Model) • When any of operation mode is not selected like the moment of the power on or when 3 hrs has passed since the operation off, the operation mode is selected. • When determining the operation mode, the compressor, the outdoor fan, and the 4 way valve are off and only the indoor fan is operated for 15 seconds. Then an operation mode is selected according to the intake air temp at that moment as follows. 24°C(76°F) ≤ Inatake Air Temp => Fuzzy Operation for Cooling 21°C(70°F) ≤ Inatake Air Temp<24°C(76°F) => Fuzzy Operation for Dehumidification Inatake Air Temp<21°C(70°F) => Fuzzy Operation for Heating • If any of the operation modes among cooling / dehumidification / heating mode operations is carried out for 10 sec or longer before Fuzzy operation, the mode before Fuzzy operation is operated. 1) Fuzzy Operation for Cooling • According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C(33°F) or more below the setting temp, the compressor is turned off. When 0.5°C(33°F) or more above the setting temp, the compressor is turned on. Compressor ON Temp => Setting Temp+0.5°C(33°F) Compressor OFF Temp => Setting Temp+0.5°C(33°F) • At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temp at that time. 26°C(78°F) ≤ Intake Air Temp => 25°C(76°F) 24°C(76°F) ≤ Intake Air Temp<26°C(78°F) => Intake Air Temp+1°C(34°F) 22°C(72°F) ≤ Intake Air Temp<24°C(76°F) => Intake Air Temp+0.5°C(33°F) 18°C(64°F) ≤ Intake Air Temp<22°C(72°F)=> Intake Air Temp Intake Air Temp < 18°C(64°F) => 18°C(64°F) • When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule. • While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temperature. 2) Fuzzy Operation for Dehumidification • According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C(33°F) or more below the setting temp, the compressor is turned off. When 0.5°C(33°F) or more above the setting temp, the compressor is turned on. Compressor ON Temp => Setting Temp+0.5°C(33°F) Compressor OFF Temp => Setting Temp+0.5°C(33°F) Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 80 - LGE Internal Use Only Operation Details • At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temp at that time. 26°C(78°F) ≤ Intake Air Temp => 25°C(76°F) 24°C(76°F) ≤ Intake Air Temp<26°C(78°F) => Intake Air Temp+1°C(34°F) 22°C(72°F) ≤ Intake Air Temp<24°C(76°F) => Intake Air Temp+0.5°C(33°F) 18°C(64°F) ≤ Intake Air Temp<22°C(72°F) => Intake Air Temp Intake Air Temp < 18°C(64°F) => 18°C(64°F) • When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule. • While in Fuzzy operation, the airflow speed of the indoor fan repeats the low airflow speed or pause as in dehumidification operation. 3) Fuzzy Operation for Heating • According to the setting temperature selected by Fuzzy rule, when the intake air temp is 3°C(37°F) or more above the setting temp, the compressor is turned off. When below the setting temp, the compressor is turned on. Compressor ON Temp => Setting Temp. +2°C(36°F) Compressor OFF Temp => Setting Temp. +4°C(39°F) • At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temp at that time. 20°C(68°F) ≤ Intake Air Temp => Intake Air Temp + 0.5°C(33°F) Intake Air Temp < 20°C(68°F) => 20°C(68°F) • When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule. • While in Fuzzy operation, the airflow speed of the indoor fan is set to the high or the medium according to the intake air temperature and the setting temperature. n Airflow Speed Selection • The airflow speed of the indoor fan is set to high, medium, low, or chaos by the input of the airflow speed selection key on the remote controller. n On-Timer Operation • When the set time is reached after the time is input by the remote controller, the appliance starts to operate. • The timer LED is on when the on-timer is input. It is off when the time set by the timer is reached. • If the appliance is operating at the time set by the timer, the operation continues. n Off-Timer Operation • When the set time is reached after the time is input by the remote controller, the appliance stops operating. • The timer LED is on when the off-timer is input. It is off when the time set by the timer is reached. • If the appliance is on pause at the time set by the timer, the pause continues. Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 81 - LGE Internal Use Only Operation Details n Off-Timer <=> On-Timer Operation • When the set time is reached after the on/off time is input by the remote controller, the on/off-timer operation is carried out according to the set time. n Sleep Timer Operation • When the sleep time is reached after <1,2,3,4,5,6,7,0(cancel) hr> is input by the remote controller while in appliance operation, the operation of the appliance stops. • While the appliance is on pause, the sleep timer mode cannot be input. • While in cooling mode operation, 30 min later since the start of the sleep timer, the setting temperature increases by 1°C(34°F) After another 30 min elapse, it increases by 1°C(34°F) again. • When the sleep timer mode is input while in cooling cycle mode, the airflow speed of the indoor fan is set to the low. • When the sleep timer mode is input while in heating cycle mode, the airflow speed of the indoor fan is set to the medium. n Chaos Swing Mode • By the Chaos Swing key input, the vane automatically operates with the Chaos Swing or they are fixed to the desired direction. n Chaos Natural Wind Mode • When the Chaos Natural Wind mode is selected and then operated, the high, medium, or low speed of the airflow mode is operated for 2~15 sec randomly by the Chaos Simulation.” n Jet Cool Mode Operation (Outdoor unit C/O Model) • If the Jet Cool key is input at any operation mode while in appliance operation, the Jet Cool mode operates. • In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation. • In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C(64°F) • When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority. • During the JET COOL function at any moment, the A/C starts to blow the cool air with side louvers closed at extremely high speed for 30 minutes setting the room temp. automatically to 18°C. n Jet Cool Mode Operation (Outdoor unit H/P Model) • While in heating mode or Fuzzy operation, the Jet Cool key cannot be input. When it is input while in the other mode operation (cooling, dehumidification, ventilation), the Jet Cool mode is operated.” • In the Jet Cool mode, the indoor fan is operated at super-high speed for 30 min at cooling mode operation. • In the Jet Cool mode operation, the room temperature is controlled to the setting temperature, 18°C(64°F) • When the sleep timer mode is input while in the Jet Cool mode operation, the Jet Cool mode has the priority. • During the JET HEAT function at any moment, the A/C starts to blow the hot air with side louvers closed at extremely high speed for 60 minutes setting the room temp. automatically to 30°C(86°F). n Auto Restarting Operation • When the power is restored after a sudden power failure while in appliance operation, the mode before the power failure is kept on the memory and the appliance automatically operates in the mode on the memory. • Operation Mode that is kept on the memory - State of Operation ON/OFF Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 82 - LGE Internal Use Only Operation Details - Operation Mode/Setting Temp/Selected Airflow Speed - Sleep Timer Mode/Remaining Time of Sleep Timer (unit of hour) n Forced Operation • Operation procedures when the remote control can't be used. • The operation will be started if the power button is pressed. • If you want to stop operation, re-press the button. Cooling Model Operating mode Indoor Fan Speed Setting Temperature Cooling High 22°C(72°F) Heat pump Model Room Temp. ≥ 24°C(76°F) 21°C(70°F) ≤ Room Temp. < 24°C(76°F) Room Temp. < 21°C(70°F) Cooling Healthy Dehumidification Heating High High High 22°CC(72°F) 23°C(74°F) 24°C(76°F) • While in forced operation, the key input by the remote control has no effect and the buzzer sounds 10 times to indicate the forced operation. n Test operation • During the TEST OPERATION, the unit operates in cooling mode at high speed fan, regardless of room temperature and resets in 18±1 minutes. • During test operation, if remote controller signal is received, the unit operates as remote controller sets. If you want to use this operation, Press and hold ON/OFF button 3~5 seconds, then the buzzer sound 1 "beep". • If you want to stop the operation, re-press the button. n Protection of the evaporator pipe from frosting • If the indoor pipe temp is below 0°C(32F) in 7 min. after the compressor operates without any pause while in cooling cycle operation mode, the compressor and the outdoor fan are turned off in order to protect the indoor evaporator pipe from frosting. • When the indoor pipe temp is 7°C(45°F) or higher after 3 min. pause of the compressor, the compressor and the outdoor fan is turned on according to the condition of the room temperature. n Buzzer Sounding Operation • When the appliance-operation key is input by the remote control, the short "beep-beep-" sounds. • When the appliance-pause key is input by the remote control, the long "beep—" sounds. • When a key is input by the remote control while the slide switch on the main unit of the appliance is on the forced operation position, the error sound "beep-beep-beep-beep-beep-" is made 10 times to indicate that the remote control signal cannot be received. Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 83 - LGE Internal Use Only Operation Details n Air Cleaner Operation • When an air cleaner function is selected during Air Conditioner operation - Plasma air cleaner function will be operated while in any operation mode with selecting the function. - The function is to be stopped while it is operating with selecting the function. • When an air cleaner function is selected during operation off - The function will be only operated. • When inlet grille of air conditioner is opened during plasma operation, High Voltage Generator(H.V.B) is to be stopped. When inlet grille of air conditioner is closed during plasma operation, High Voltage Generator(H.V.B) will be operated again. Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 84 - LGE Internal Use Only PIPING/WIRING DIRECTION Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 85 PIPE AND DRAIN DIMENSION 567 PIPING DIRECTION PIPING/WIRING DIRECTION Descripition (unit : mm) 165 D (unit : mm) Ø6.35 Flare connection Ø12.7 Flare connection External dia. Ø17 282 H 76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea Higher than eye-level More than 100 mm ※ Required space(unit:mm) CHASSIS CODE: SE More than 100 mm Lower than 2.3m More than 200 mm Note 1. Unit should be installed in compliance with the installation manual in the product box. 2. Unit shall be grounded in accordance with the local regulations or applicable national codes. Name Front panel Air discharge Air suction Liquid pipe Gas pipe Drain pipe Right side piping/wiring connection Left side piping/wiring connection 1 2 3 4 5 6 7 8 895 ARNU07GSE*2 ARNU09GSE*2 ARNU12GSE*2 ARNU15GSE*2 Number W Model ARNU07GSE*2 ARNU09GSE*2 ARNU12GSE*2 ARNU15GSE*2 Wall Mounted Dimensions 3. Dimensions LGE Internal Use Only 265 PIPING/WIRING DIRECTION Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 86 PIPE AND DRAIN DIMENSION 804 PIPING DIRECTION PIPING/WIRING DIRECTION Front panel Air discharge Air suction Liquid pipe Gas pipe Drain pipe Right side piping/wiring connection Left side piping/wiring connection 1 2 3 4 5 6 7 8 Descripition (unit : mm) 178 D Ø6.35 Flare connection Ø12.7 Flare connection External dia. Ø17 300 H (unit : mm) 76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea Higher than eye-level More than 100 mm ※ Required space(unit:mm) CHASSIS CODE: S5 More than 100 mm Lower than 2.3m More than 200 mm Note 1. Unit should be installed in compliance with the installation manual in the product box. 2. Unit shall be grounded in accordance with the local regulations or applicable national codes. Name 1090 ARNU18GS5*2 ARNU24GS5*2 Number W Model ARNU18GS5*2 ARNU24GS5*2 Wall Mounted Dimensions LGE Internal Use Only 281 Ceiling & Floor Ceiling Suspended 1. Funtions ......................................................................................88 2. Operation Details........................................................................89 3. Dimensions .................................................................................92 Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 87 - LGE Internal Use Only Function 1. Function Indoor Unit Operation ON/OFF by Remote controller Sensing the Room Temperature • Maintains the room temperature in accordance with the Setting Temperature. Room temperature control Starting Current Control • Indoor fan is delayed for 5 seconds at the starting. • High, Med, Low Indoor Fan Speed Control Soft Dry Operation Mode Auto Restart • Room temperature sensor. (Thermistor) • Intermittent operation of fan at low speed. • Although the air-conditioner is turned off by a power failure, it is restarted automatically previous operation mode after power supply. Deice (defrost) control (Heating) • Both the indoor and outdoor fan stops during defrosting. • Hot start after defrost ends. Hot-start Control (Heating) • The indoor fan does not rotate until the evaporator piping temperature reaches 25°C(76°F). High head height Drain pump • A standard drain-head height of up to 700mm(27-9/16inch) is possible. Central Control(Optional) • It is operating individually or totally by central control function. Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 88 - LGE Internal Use Only Operation Details 2. Operation Details (1) The function of main control n Soft-Dry Operation • The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of already being set to the best speed for Dry Operation by microcontroller control. n Cooling Mode Operation • When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote controller and the operation diagram is as following. Intake Air Temperature Thermo. ON (SET TEMPERATURE +0.5°C(33°F)) Thermo. OFF (SET TEMPERATURE -0.5°C(33°F)) INDOOR FAN COMPRESSOR Indoor Unit mode 2TH (Remo.+Indoor) Remo. Mode More than 3 minutes More than 3 minutes Selecting fan speed Low Selecting fan speed Low Selecting fan speed ON OFF ON OFF ON Thermal ON ST+0.5 To be selected higher temperature contrast Indoor Unit and Remo. ST+0.5 Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 89 - Thermal OFF ST-0.5 To be selected higher temperature contrast Indoor Unit and Remo. ST-0.5 LGE Internal Use Only Operation Details n Heating Mode Operation The unit will operate according to the setting by the remote controller and the operation diagram is shown as following. Indoor unit 40°C(104°F) Heat-Exchanger temperature T ST A T LT T Off T On Intake Air Temperature 3min B Low fan during 10sec Setting Temperature +3°C(37°F) (Thermal OFF) Setting Temperature (Thermal ON) Minimum 3min 1min Thermal OFF OFF ON ON Outdoor fan Indoor fan Off Low Low Setting fan spped Setting fan spped Low 4way valve Low 1min ON ON C Off Off Low Setting fan spped ON • Compressor-off interval : - A While the indoor Heat-Exchanger temperature is higher than 40°C(104°F), fan operates at low speed, when it becomes lower than 40°C(104°F) fan stops. - B For eluminating latent heat-loss, fan operates at low speed for 10 seconds periodically. - C To be operated "Low" except initial Hotstart operation High Static Chassis Low Static VE VJ 19°C(66°F) 19°C(66°F) 19°C(66°F) 19°C(66°F) 26°C(78°F) 26°C(78°F) 22°C(72°F) 22°C(72°F) 22°C(72°F) 22°C(72°F) 22°C(72°F) 27°C(80°F) 27°C(80°F) 25°C(76°F) 25°C(76°F) 25°C(76°F) 25°C(76°F) 25°C(76°F) 25°C(76°F) 28°C(82°F) 28°C(82°F) 27°C(80°F) 27°C(80°F) 27°C(80°F) 27°C(80°F) 27°C(80°F) 27°C(80°F) 30°C(86°F) 30°C(86°F) BH BG BR Hotstart On T On 19°C(66°F) 19°C(66°F) 19°C(66°F) Hotstart Off T Off 22°C(72°F) 22°C(72°F) Low temperature T LT 25°C(76°F) Setting Temperature T ST 27°C(80°F) Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes B1 - 90 - B2 CE Convertible CF LGE Internal Use Only Operation Details n Hot-Start Control • The indoor fan does not rotate until the indoor unit Hex-Exchanger temperature reaches 30°C(86°F). • The operation diagram is as following. Indoor unit Heat-Exchanger temperature Hotstart Off Hotstart On 1 min 1 min Thermal Outdoor fan Indoor fan ON ON Off Low Setting fan speed Off Low Setting fan speed ON 4way Valve • Initial Hotstart On state ¿ Power Off ‡ On ¡ Operation Off ‡ On ¬ Cooling operation ‡ Heating operation √ Defrost operation Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 91 - LGE Internal Use Only Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes 587 Liquid pipe Gas pipe Suction gille Discharge grille Suspension bracket Right side drain hose hole Left side drain hose hole Wiring connection Piping connection Signal receiver & Operation indicator 1 2 3 4 - 92 - Slit hole Slit hole More than 200mm CHASSIS CODE: VE More than 50mm More than 200mm 76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea More than 50mm More than 200mm ※ Required space(unit:mm) More than 200mm (unit : mm) 200 D (unit : mm) Descripition ø6.35 Flare connection ø12.7 Flare connection 490 H Note 1. Unit should be installed in compliance with the installation manual in the product box. 2. Unit shall be grounded in accordance with the local regulations or applicable national codes. 5 6 7 8 9 10 Name 900 ARNU09GVEA2 ARNU12GVEA2 Number W Model ARNU09GVEA2 ARNU12GVEA2 Ceiling & Floor Dimensions 3. Dimensions LGE Internal Use Only 273 Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 93 - (unit : mm) 220 D (unit : mm) Slit hole Slit hole Slit hole Slit hole Descripition ø6.35 Flare connection ø12.7 Flare connection 650 H CHASSIS CODE: VJ More than 300mm More than 700Um 76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea More than 700mm ※ Required space(unit:mm) Note 1. Unit should be installed in compliance with the installation manual in the product box. 2. Unit shall be grounded in accordance with the local regulations or applicable national codes. 5 6 7 8 9 10 11 Name Liquid pipe Gas pipe Suction gille Discharge grille Suspension bracket Right side drain hose hole Left side drain hose hole Wiring connection Piping connection Right side drain pipe connection Left side drain pipe connection 1 2 3 4 950 ARNU18GVJA2 ARNU24GVJA2 Number W Model ARNU18GVJA2 ARNU24GVJA2 Ceiling Suspended Dimensions LGE Internal Use Only Floor Standing Type 1. Function ......................................................................................95 2. Operation Details........................................................................96 3. Dimensions .................................................................................99 Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 94 - LGE Internal Use Only Function 1. Function Indoor Unit Operation ON/OFF by Remote controller Sensing the Room Temperature • Maintains the room temperature in accordance with the Setting Temperature. Room temperature control Starting Current Control • Indoor fan is delayed for 5 seconds at the starting. • High, Med, Low Indoor Fan Speed Control Soft Dry Operation Mode Auto Restart • Room temperature sensor. (Thermistor) • Intermittent operation of fan at low speed. • Although the air-conditioner is turned off by a power failure, it is restarted automatically previous operation mode after power supply. Deice (defrost) control (Heating) • Both the indoor and outdoor fan stops during defrosting. • Hot start after defrost ends. Hot-start Control (Heating) • The indoor fan does not rotate until the evaporator piping temperature reaches 25°C(76°F). High head height Drain pump • A standard drain-head height of up to 700mm(27-9/16inch) is possible. Central Control(Optional) • It is operating individually or totally by central control function. Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 95 - LGE Internal Use Only Operation Details 2. Operation Details (1) The function of main control n Soft-Dry Operation • The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of already being set to the best speed for Dry Operation by microcontroller control. n Cooling Mode Operation • When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote controller and the operation diagram is as following. Intake Air Temperature Thermo. ON (SET TEMPERATURE +0.5°C(33°F)) Thermo. OFF (SET TEMPERATURE -0.5°C(33°F)) INDOOR FAN COMPRESSOR Indoor Unit mode 2TH (Remo.+Indoor) Remo. Mode More than 3 minutes More than 3 minutes Selecting fan speed Low Selecting fan speed Low Selecting fan speed ON OFF ON OFF ON Thermal ON ST+0.5 To be selected higher temperature contrast Indoor Unit and Remo. ST+0.5 Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 96 - Thermal OFF ST-0.5 To be selected higher temperature contrast Indoor Unit and Remo. ST-0.5 LGE Internal Use Only Operation Details n Heating Mode Operation The unit will operate according to the setting by the remote controller and the operation diagram is shown as following. Indoor unit 40°C(104°F) Heat-Exchanger temperature T ST A T LT T Off T On Intake Air Temperature 3min B Low fan during 10sec Setting Temperature +3°C(37°F) (Thermal OFF) Setting Temperature (Thermal ON) Minimum 3min 1min Thermal Indoor fan OFF OFF ON ON Outdoor fan Off Low Low 1min Setting fan spped Setting fan spped Low 4way valve Low ON ON C Off Off Low Setting fan spped ON • Compressor-off interval : - A While the indoor Heat-Exchanger temperature is higher than 40°C(104°F), fan operates at low speed, when it becomes lower than 40°C(104°F) fan stops. - B For eluminating latent heat-loss, fan operates at low speed for 10 seconds periodically. - C To be operated "Low" except initial Hotstart operation High Static Chassis Low Static VE VJ 19°C(66°F) 19°C(66°F) 19°C(66°F) 19°C(66°F) 26°C(78°F) 26°C(78°F) 22°C(72°F) 22°C(72°F) 22°C(72°F) 22°C(72°F) 22°C(72°F) 27°C(80°F) 27°C(80°F) 25°C(76°F) 25°C(76°F) 25°C(76°F) 25°C(76°F) 25°C(76°F) 25°C(76°F) 28°C(82°F) 28°C(82°F) 27°C(80°F) 27°C(80°F) 27°C(80°F) 27°C(80°F) 27°C(80°F) 27°C(80°F) 30°C(86°F) 30°C(86°F) BH BG BR Hotstart On T On 19°C(66°F) 19°C(66°F) 19°C(66°F) Hotstart Off T Off 22°C(72°F) 22°C(72°F) Low temperature T LT 25°C(76°F) Setting Temperature T ST 27°C(80°F) Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes B1 - 97 - B2 CE Convertible CF LGE Internal Use Only Operation Details n Hot-Start Control • The indoor fan does not rotate until the indoor unit Hex-Exchanger temperature reaches 30°C(86°F). • The operation diagram is as following. Indoor unit Heat-Exchanger temperature Hotstart Off Hotstart On 1 min 1 min Thermal Outdoor fan Indoor fan ON ON Off Low Setting fan speed 4way Valve Off Low Setting fan speed ON • Initial Hotstart On state ¿ Power Off ‡ On ¡ Operation Off ‡ On ¬ Cooling operation ‡ Heating operation √ Defrost operation Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 98 - LGE Internal Use Only - 99 - 148.3 (5-13/16) 13(1/2) 148.3 (5-13/16) 1 635(25) 49(15/16) 190(7-7/16) 161(6-5/16) 203(7-15/16) LG Electronics USA, HVAC Division 1000 Sylvan Avenue, Englewood Cliffs, NJ 07632 www.lgusa.com / www.lghvac.com <Without Case> 978(38-1/2) 794(31-5/16) <With Case> 2 1067(42) 70(2-3/4) 20.4(3/4) Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes 6.28 (1/4) 1067(42) 14(1/2) Air suction grill 1 2 [Unit : mm(inch)] 190 (7-7/16) 203 (7-15/16) D Descripition 639 (31-1/4) 635 (25) H [Unit : mm(inch)] ARNU073CEU2 ARNU093CEU2 ARNU123CEU2 ARNU153CEU2 76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea www.lgeaircon.com CHASSIS CODE: CE 2. Unit shall be grounded in accordance with the local regulations or applicable national codes. Note 1. Unit should be installed in compliance with the installation manual in the product box. Name Air discharge grill Number 978 (38-1/2) 1067 (42) ARNU073CEU2 ARNU093CEU2 ARNU123CEU2 ARNU153CEU2 W Model ARNU073CEA2 ARNU093CEA2 ARNU123CEA2 ARNU153CEA2 ARNU073CEA2 ARNU093CEA2 ARNU123CEA2 ARNU153CEA2 Floor Standing Dimensions 3. Dimensions LGE Internal Use Only 639(31-1/4) 21.4(1-3/16) 639(31-1/4) - 100 - 148.3 (5-13/16) 70 (2-3/4) 2 49.5(1-15/16) 109.8(4-5/16) 30(1-3/16) 148.3 (5-13/16) 1 190(7-7/16) 161(6-5/16) 14(1/2) 203(7-15/16) LG Electronics USA, HVAC Division 1000 Sylvan Avenue, Englewood Cliffs, NJ 07632 www.lgusa.com / www.lghvac.com <Without Case> 1256(49-7/16 1098(43-1/4) 1072(42-3/16) <With Case> 1048.4(41-1/4) 1345(52-15/16) 203 (7-15/16) 635(25) 70(2-3/4) 81.4(3-3/16) Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes 145 (5-11/16) Air suction grill 2 (unit : mm) 190 (7-7/16) 203 (7-15/16) D Descripition 639 (31-1/4) 635 (25) H [Unit : mm(inch)] ARNU183CFU2 ARNU243CFU2 76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea www.lgeaircon.com CHASSIS CODE: CF 2. Unit shall be grounded in accordance with the local regulations or applicable national codes. 1. Unit should be installed in compliance with the installation manual in the product box. Note Air discharge grill 1 1256 (49-7/16) ARNU183CFU2 ARNU243CFU2 Name 1345 (52-15/16) ARNU183CFA2 ARNU243CFA2 Number W Model ARNU183CFA2 ARNU243CFA2 Floor Standing Dimensions LGE Internal Use Only Vertical Air Handling Unit 1. Funtions ....................................................................................102 2. Operation Details......................................................................103 3. Dimensions ...............................................................................107 Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 101 - LGE Internal Use Only Funtions 1. Funtions Indoor Unit Operation ON/OFF by Remote controller Sensing the Room Temperature Room temperature control Starting Current Control Indoor Fan Speed Control Soft Dry Operation Mode Auto Restart • Room temperature sensor. (Thermistor) • Maintains the room temperature in accordance with the Setting Temperature. • Indoor fan is delayed for 5 seconds at the starting. • High, Med, Low • Intermittent operation of fan at low speed. • Although the air-conditioner is turned off by a power failure, it is restarted automatically previous operation mode after power supply. Deice (defrost) control (Heating) • Both the indoor and outdoor fan stops during defrosting. • Hot start after defrost ends. • If the electric heater has been installed, indoor fan continuous will be. Hot-start Control (Heating) • The indoor fan does not rotate until the evaporator piping temperature reaches 25°C(76°F) Central Control(Optional) • It is operating individually or totally by central control function. Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 102 - LGE Internal Use Only Operation Details 2. Operation Details (1) The function of main control n Soft-Dry Operation • The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of already being set to the best speed for Dry Operation by microcontroller control. n Cooling Mode Operation • When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote controller and the operation diagram is as following. Intake Air Temperature Thermo. ON (SET TEMPERATURE +0.5°C(33°F)) Thermo. OFF (SET TEMPERATURE -0.5°C(33°F)) INDOOR FAN COMPRESSOR More than 3 minutes More than 3 minutes Selecting fan speed Low Selecting fan speed Low Selecting fan speed ON OFF ON OFF ON Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 103 - LGE Internal Use Only Operation Details n Heating Mode Operation The unit will operate according to the setting by the remote controller and the operation diagram is shown as following. Indoor unit 40C(104F) Heat-Exchanger temperature T ST A T LT T Off T On Intake Air Temperature 3min Setting Temperature +3C(37F) (Thermal OFF) B Low fan during 10sec Setting Temperature (Thermal ON) Minimum 3min 1min Thermal ON ON Outdoor fan Indoor fan OFF OFF Setting fan spped Off Low Low Low 4way valve Setting fan spped Low C Off Off 1min ON ON Low Setting fan spped ON • Compressor-off interval : - A While the indoor Heat-Exchanger temperature is higher than 40C(104F), fan operates at low speed, when it becomes lower than 40C(104F) fan stops. - B For eluminating latent heat-loss, fan operates at low speed for 10 seconds periodically. - C To be operated "Low" except initial Hotstart operation Vertical Air Handling Unit Chassis NJ NK Hotstart On T On 19°C(66°F) 19°C(66°F) Hotstart Off T Off 22°C(72°F) 22°C(72°F) Low temperature T LT 25°C(76°F) 25°C(76°F) Setting Temperature T ST 27°C(80°F) 27°C(80°F) Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 104 - LGE Internal Use Only Operation Details n Hot-Start Control • The indoor fan does not rotate until the indoor unit Hex-Exchanger temperature reaches 22℃(71.6℉). • The operation diagram is as following. Indoor unit Heat-Exchanger temperature Hotstart Off Hotstart On 1 min 1 min Thermal Outdoor fan Indoor fan ON ON Off Setting fan speed Low Off Low Setting fan speed ON 4way Valve • Initial Hotstart On state ¿ Power Off ‡ On ¡ Operation Off ‡ On ¬ Cooling operation ‡ Heating operation √ Defrost operation High Static Chassis Low Static BH BG BR B1 B2 CE Convertible CF VE VJ Hotstart On T On 19°C(66°F) 19°C(66°F) 19°C(66°F) 19°C(66°F) 19°C(66°F) 19°C(66°F) 19°C(66°F) 26°C(78°F) 26°C(78°F) Hotstart Off T Off 22°C(72°F) 22°C(72°F) 22°C(72°F) 22°C(72°F) 22°C(72°F) 22°C(72°F) 22°C(72°F) 27°C(80°F) 27°C(80°F) Low temperature T LT 25°C(76°F) 25°C(76°F) 25°C(76°F) 25°C(76°F) 25°C(76°F) 25°C(76°F) 25°C(76°F) 28°C(82°F) 28°C(82°F) Setting Temperature T ST 27°C(80°F) 27°C(80°F) 27°C(80°F) 27°C(80°F) 27°C(80°F) 27°C(80°F) 27°C(80°F) 30°C(86°F) 30°C(86°F) Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 105 - LGE Internal Use Only Operation Details n Heater Operation • The unit will operate according to the setting temperature and the indoor unit Heat-Exchanger temperature. • Heater operation diagram is shown as following. Setting temperature (A) A-1℃ (34℉) A-2℃ (36℉) Heater OFF Heater ON Heater ON Indoor unit Heat-Exchanger temperature 45℃ (113℉) 42℃ (108℉) 30℃ (86℉) 28℃ (82℉) Heater 2 Heater 1 ON ON Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes OFF OFF - 106 - ON ON LGE Internal Use Only Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 107 - 5 308(12-1/8) 40(1-9/16) 543(21-3/8) 4 1 65 (2-9/16) 1236(48-5/8) 364(14-5/16) 117.5(4-5/8) 2 LG Electronics USA, HVAC Division 1000 Sylvan Avenue, Englewood Cliffs, NJ 07632 www.lgusa.com / www.lghvac.com 46(1-13/16) 41(1-5/8) 40 254(10) 331(13) 40(1-9/16) 3 Power supply connection Air discharge Air suction 4 5 6 [Unit : mm(inch)] Unit size(18k):ø6.35(1/4) Unit size(24k,30k):ø9.52(3/8) Unit size(18k):ø12.7(1/2) Unit size(24k,30k):ø15.88(5/8) Descripition CHASSIS CODE: NJ 2. Unit shall be grounded in accordance with the local regulations or applicable national codes. 1. Unit should be installed in compliance with the installation manual in the product box. Note Gas pipe connection Drain pipe connection 3 Liquid pipe connection 2 1 Name 76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea www.lgeaircon.com 6 Number ARNU183NJA2 ARNU243NJA2 ARNU303NJA2 ARNU363NJA2 Vertical Air Handling Unit Dimensions 3. Dimensions LGE Internal Use Only 432(17) 457(18) 308 (12-1/8) 540 (21-1/4) 40 (1-9/16) 49 (1-15/16) 52 (2-1/16) Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes 55 (2-3/16) - 108 - 40 (1-9/16) 1418 (55-13/16) 1400 (55-1/8) LG Electronics USA, HVAC Division 1000 Sylvan Avenue, Englewood Cliffs, NJ 07632 www.lgusa.com / www.lghvac.com 5 41 (1-5/8) 4 65 (2-9/16) 2 1 6 3 Name Air discharge 4 5 Descripition Unit size(28k,36k,42k):ø15.88(5/8) Unit size(28k,36k,42k):ø9.52(3/8) CHASSIS CODE: NK 2. Unit shall be grounded in accordance with the local regulations or applicable national codes. 1. Unit should be installed in compliance with the installation manual in the product box. Note Air suction Power supply connection 3 6 Gas pipe connection Drain pipe connection 2 Liquid pipe connection [Unit : mm(inch)] ARNU423NKA2 ARNU483NKA2 ARNU543NKA2 1 Number 118 (4-5/8) 508 (20) 76, Seongsan-dong, Changwon City, Gyeongnam, 641-713, Korea www.lgeaircon.com 362 (14-1/4) 39 (1-9/16) 40 (1-9/16) 430 (16-15/16) Vertical Air Handling Unit Dimensions LGE Internal Use Only 610 (24) 635 (25) Part 3 Trouble shooting guide Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 109 - LGE Internal Use Only Trouble shooting guide Self-diagnosis function ...................................................................111 Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 110 - LGE Internal Use Only Self-diagnosis function Self-diagnosis function Self-Diagnosis Function Error Indicator • This function indicates types of failure in self-diagnosis and occurrence of failure for air condition. • Error mark is displayed on display window of indoor units and wired remote controller, and 7-segment LED of outdoor unit control board as shown in the table. • If more than two troubles occur simultaneously, lower number of error code is first displayed. • After error occurrence, if error is released, error LED is also released simultaneously. Error Display 1st,2nd LED of 7-segment indicates error number, 3rd LED indicates unit number. Ex) 211 : No.21 error of master unit 213 : No.21 error of slave2 011 ’ 051 : No.105 error of master unit Indoor unit related error Display Title Cause of Error 0 1 - Air temperature sensor of indoor unit Air temperature sensor of indoor unit is open or short 0 2 - Inlet pipe temperature sensor of indoor unit Inlet pipe temperature sensor of indoor unit is open or short 0 3 - Transmission error : wired remote controller ↔indoor unit Failing to receive wired remote controller signal in indoor unit PCB 0 4 - Drain pump Malfunction of drain pump 0 5 - Transmission error : outdoor unit ↔indoor unit Failing to receive outdoor unit signal in indoor unit PCB 0 6 - Outlet pipe temperature sensor of indoor unit Outlet pipe temperature sensor of indoor unit is open or short 0 7 - Different operation mode Operation mode between indoor unit and outdoor unit is different 0 9 - Serial No. In case when the serial number marked onEEPROM of Indoor unit is 0 or FFFFFF 1 0 - Poor fan motor operation Disconnecting the fan motor connector/Failure of indoor fan motor lock Air temperature sensor of indoor unit is open or short Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 111 - LGE Internal Use Only Self-diagnosis function Error No. Error Type Error Point 01 Indoor unit air sensor error 02 Indoor unit pipe inlet sensor error 06 Indoor unit pipe outlet sensor error Indoor unit sensor is open/short Main Reasons 1. Indoor unit PCB wrong connection 2. Indoor unit PCB failure 3. Sensor problem (main reason) n Error diagnosis and countermeasure flow chart Is sensor properly connected to PCB? No Connect properly to PCB Yes Is the resistance value of sensor normal?* No Change the sensor Yes Change the PCB ** In case the value is more than 100kΩ (open) or less than 100Ω (short), Error occurs Refer: Resistance value maybe change according to temperature of temp sensor, It shows according to criteria of current temperature(±5% margin) ‘ Normal Air temp sensor: 10°C(50°F) = 20.7kΩ : 25°C(76°F)= 10kΩ : 50°C(122°F)= 3.4kΩ Pipe temp sensor: 10°C(50°F) = 10kΩ : 25°C(76°F)= 5kΩ : 50°C(122°F)= 1.8kΩ CN_PIPE/OUT: Pipe outlet temp sensor CN_PIPE/IN: Pipe inlet temp sensor CN_ROOM: Indoor air temp sensor <Fresh Air Intake Unit> Measure the resistance of outlet pipe temp sensor. <Standard Indoor Unit> Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 112 - LGE Internal Use Only Self-diagnosis function Error No. 03 Error Type No transmission between cabled remote controller & indoor unit Error Point Main Reasons 1. Remote controller fault The remote controller did not receive the sig- 2. Indoor unit PCB fault nal from indoor unit 3. Connector fault, Wrong connection during specific time 4. transmission cable problem n Error diagnosis and countermeasure flow chart Does the error happens again if the remote controller is replaced?* No Replace cabled remote controller Yes Does the error occurred when the cable of remote controller is replaced? No Check connection & transmission cable ** Yes Replace indoor unit PCB *** * If there is no remote controller to replace : Use another unitʼs remote controller doing well ** Check cable : Contact failure of connected portion or extension of cable are main cause Check any surrounded noise ( check the distance with main power cable) ‘ make safe distance from the devices generate electromagnetic wave *** After replacing indoor unit PCB, do Auto Addressing & input unitʼs address if connected to central controller. (All the indoor units connected should be turned on before Auto Addressing CN-REMO : Remote controller connection The PCB can differ from model to model. Check from the right source. Checking transmission cable connection status Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 113 - LGE Internal Use Only Self-diagnosis function Error No. 04 Error Type Error Point Main Reasons Float switch is open due to 1. Drain pump/float switch fault rising of condensate water 2. Improper drain pipe location, cloglevel because of drain ging of drain pipe pump fault or drain pipe 3. Indoor unit PCB fault clogging Drain pump error Error diagnosis and countermeasure flow chart Is the drain pan filled half with condensate water? (half level of float switch)* No Is Float switch short On measuring its resistance? No Replace float switch Yes Yes Replace Indoor PCB or reconnect the connector Is drain pump working? (Sound/drain noise/ contact etc.) No In indoor unit PCB Does the terminal voltage for drain pump has 208/230V output?** Yes No Replace indoor unit PCB Yes Replace Drain Pump Drain pump blocked by foreign particles? Yes Remove it & clean the pump * If the float goes up higher than a half of float switch then the circuit is open & the unit is stopped automatically. Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 114 - LGE Internal Use Only Self-diagnosis function float *** Indoor PCB drain pump connector A:Point to check rotating (Check input of 208/230V) (Marked as CN-DPUMP) Float switch connector Float switch Housing (CN-FLOAT) [***] Standard of drain pipe head height / slope MAX 450 700mm(27-9/16inch) Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 115 - LGE Internal Use Only Self-diagnosis function Error No. 05 Error Type Error Point Main Reasons 1. Auto addressing is not done 2. transmission cable is not connected 3. Short circuit of transmission cable 4. Indoor unit transmission circuit fault No signal transmission between indoor & outdoor 5. Outdoor unit transmission circuit fault 6. Not enough distance between power and transunits. mission cable? Indoor & Outdoor unit transmission error n Error diagnosis and countermeasure flow chart Does all the IDUs show same error code CH05? No Is total number of indoor units connected displayed after auto addressing? No Replace the PCB of indoor unit displayed error Re-connect after check the transmission cable of indoor unit displayed error** Yes END Is outdoor PCB LED blinking? Check the main power supply at the ODU terminal block? No No Replace outdoor PCB after checking Replace TRANS after checking Yes Yes No Is main circuit breaker off? Yes Check the insulation of inverter / constant compressor and replace if required Check the capacity of main circuit breaker and replace if required Improper connection of power supply cable Main power supply problem Check if the transmission cable is properly connected to indoor / outdoor terminal block?* Yes No If all ok, Turn on main circuit breaker Re connect transmission cable Outdoor PCB fault Replace after checking Indoor PCB fault Replace after checking * (Note1) Transmission from IDU is normal if voltage fluctuation(-9V ~ +9V) exists when checking DC voltage of communication terminal between IDU and ODU Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes * If the DC voltage between transmission terminal A, B of indoor unit is fluctuate within (-9V~+9V) then transmission from outdoor unit is normal - 116 - LGE Internal Use Only Self-diagnosis function Error No. Error Type Error Point Indoor unit outlet pipe temperature sensor error 06 Error No. Error Type Refer to CH02 Indoor unit outlet pipe temperature sensor open or short Error Point All Indoor units are not running in same mode 07 Main Reasons The Indoor units started later are operated in different mode from earlier one. Main Reasons 1. Indoor units are in different mode 2. PCB fault 3. cabled remote controller fault j Checking ch07 method IDU doesnʼt operate as Operation mode is flickering at IDU wired remote controller and IDU display window. n Error diagnosis and countermeasure flow chart Is operation mode of outdoor & Indoor units same? No Yes Does error code disappear after set operation mode same?** No Replace Indoor PCB*** Yes END Adjust outdoor main PCB dip switch setting * * Check mode selection setting of wired remote controller. ** Outdoor main PCB dip switch no.5 (Cooling) or no.6 (heating) is in On, different mode operation error may occur because the operation mode is fixed by dip switch setting. © Dip switch Setting © ON 1 1 ON 2 2 3 3 4 4 5 5 6 6 7 7 ON 1 1 1 8 2 3 4 5 6 7 9 10 11 12 13 14 ON 2 2 3 3 4 4 5 5 6 6 7 7 1 8 2 3 4 5 6 7 9 10 11 12 13 14 *** Dissolution method CH07 with remote controller 1) Error removal method : Turn off remote controller by pressing the On/Off button on the cabled remote controller. The error code will be removed automatically after few seconds. With cableless remote controller: Turn off indoor unit, and then turn on by changing the operation mode. The error will disappear. Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 117 - LGE Internal Use Only Self-diagnosis function **** After replacing the indoor unit PCB, make sure to be done to do Auto addressing and input the address of central control ***** If ODU Dry Contact function is set , different mode operation error may be occurred because the operation mode is fixed. Error No. 09 Error Type Error Point Main Reasons 1. Error developed in transmission between the micro- processor and the EEPROM on the surface of the PCB. 2. ERROR due to the EEPROM damage Indoor unit EEPROM error n Error diagnosis and countermeasure flow chart - Replace the indoor unit PCB, and then make sure to perform Auto addressing and input the address of central control Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 118 - LGE Internal Use Only Self-diagnosis function Error No. 10 Error Type Indoor unit BLDC fan motor failure Error Point Main Reasons Indoor BLDC fan motor feedback signal is absent (for 50 sec.) 1. Motor connector connection fault 2. Indoor PCB fault 3. Motor fault n Error diagnosis and countermeasure flow chart Is connector connection proper? No Connect properly Yes No Is fan motor normal?* Replace indoor unit fan motor Yes Replace indoor unit PCB ** * It is normal when check hall sensor of indoor fan motor as shown below Each termainl with the tester Tester 1 4 5 6 7 + - 1 4 5 4 6 4 7 4 Normal resistance(±10%) TH chassis TD chassis hundreds kΩ hundreds kkΩ hundreds kΩ hundreds kΩ <Checking connection state of fan motor connector> ** Replace the indoor unit PCB, and then make sure to do Auto addressing and input the address of central control (Notice: The connection of motor connector to PCB should be done under no power supplying to PCB) Copyright ©2010 LG Electronics. Inc. All right reserved. Only for training and service purposes - 119 - LGE Internal Use Only P/NO : MFL50459505 NOVEMBER, 2010