SAFETY, USE and MAINTENANCE INSTRUCTIONS
ISTRUZIONI DI SICUREZZA, USO E MANUTENZIONE
CODE C010167
Electronic stainless steel waterproof fixtures
series RINO-EX
Rev. 00 del
Plafoniere stagne elettroniche in acciaio inox serie RINO-EX
may 2014
Page 1 of 12
ELECTRONIC STAINLESS STEEL WATERPROOF FIXTURES
For fixed installation
Series RINO-EX - ATEX EXECUTION
PLAFONIERE STAGNE ELETTRONICHE IN ACCIAIO INOX
Per installazione fissa
Serie RINO-EX – ESECUZIONE ATEX
Execution/Esecuzione:
Group II Category 3G 2D
Ex nA IIC T4 Gc
Ex tb IIIC T 85 °C Db
SAFETY, USE and MAINTENANCE INSTRUCTIONS
ISTRUZIONI DI SICUREZZA, USO E MANUTENZIONE
IN COMPLIANCE WITH THE DIRECTIVE 94/9/EC
PALAZZOLI S.p.A.
Via F. Palazzoli, 31
25128 BRESCIA
Tel. +39 030 2015.1 Fax +39 030 2015.217
WEB www.palazzoli.it
e-mail [email protected]
1
The fixtures RINO-EX seriesrunningATEX execution, comply to the
provisions of the community Directive 94/9/EC (ATEX).
The equipments comply fully or for the individual applied parts to the
following harmonized standards:
Le plafoniere della serie RINO-EX in esecuzione ATEX sono conformi ai
requisiti della direttiva 94/9/CE (ATEX)
Le apparecchiature rispettano completamente o per le single parti le
seguenti normative armonizzate:
Directive 94/9/EC
Direttiva 94/9/CE
Standard
Norma
Date
Data
Title
Titolo
EN 60079-0
EN60079-0/A11
2012
2013
Explosive atmospheres - Part 0: Equipment - General requirements
Atmosfere esplosive - Parte 0: Apparecchiature - Prescrizioni generali
EN 60079-15
2010
Explosive atmospheres - Part 15: Equipment protection by type of protection "n"
Atmosfere Esplosive - Parte 15: Apparecchiature con modo di protezione "n"
EN 60079-31
2009
IEC 60079-31
2013
Explosive atmospheres - Part 31: Equipment dust ignition protection by enclosure “t”
Atmosfere Esplosive - Parte 31: Apparecchi con modo di protezione “t” destinati ad essere utilizzati in presenza di
polveri combustibili
Directive2006/95/EC
Direttiva2006/95/CE
Standard
Date
Norma
Data
Title
Titolo
EN 60529
EN 60529/A1
1991
2000
Degrees of protection provided by enclosure (IP code)
Gradi di protezione degli involucri (Codice IP)
EN 60598-1
EN 60598-1/A11
2008
2009
Luminaires – Part 1: General requirements and tests
Apparecchi di illuminazione - Parte 1: Prescrizioni generali e prove
EN 60598-2-1
1989
Luminaires – Part 2: Particular requirements – Section 1: Fixed general purpose luminaires
Apparecchi di illuminazione - Parte 2: Prescrizioni particolari – Sezione 1: Apparecchi fissi per uso generale
LIST OF FIXTURES -EX COVERED BY THIS DOCUMENT
ELENCO DELLE PLAFONIERE -Ex COPERTI DAL PRESENTE DOCUMENTO
Code
Codice
820131EX
820231EX
820331EX
820132EX
820232EX
820332EX
822131EX
822231EX
822331EX
822132EX
822232EX
822332EX
842131EX
842231EX
842331EX
842132EX
842232EX
842332EX
843131EX
843231EX
843331EX
843132EX
843232EX
843332EX
Enclosure
Corpo
Stainless steel
Acciaio inox
Stainless steel
Acciaio inox
Stainless steel
Acciaio inox
Stainless steel
Acciaio inox
Stainless steel
Acciaio inox
Stainless steel
Acciaio inox
Stainless steel
Acciaio inox
Stainless steel
Acciaio inox
Stainless steel
Acciaio inox
Stainless steel
Acciaio inox
Stainless steel
Acciaio inox
Stainless steel
Acciaio inox
Painted steel
Acciaio verniciato
Painted steel
Acciaio verniciato
Painted steel
Acciaio verniciato
Painted steel
Acciaio verniciato
Painted steel
Acciaio verniciato
Painted steel
Acciaio verniciato
Painted steel
Acciaio verniciato
Painted steel
Acciaio verniciato
Painted steel
Acciaio verniciato
Painted steel
Acciaio verniciato
Painted steel
Acciaio verniciato
Painted steel
Acciaio verniciato
Power
Potenza
Lamp
Lampada
Socket type
Portalampade
Reflector
Riflettore
GAS
class
Classe
DUST
Temperature
temperatura
Ta (°C)
Range
intervallo
1x18W
T8
G13
SI
T4
85°C
-20/+50
1x36W
T8
G13
SI
T4
85°C
-20/+50
1x58W
T8
G13
SI
T4
85°C
-20/+50
2x18W
T8
G13
SI
T4
85°C
-20/+40
2x36W
T8
G13
SI
T4
85°C
-20/+40
2x58W
T8
G13
SI
T4
85°C
-20/+40
1x18W
T8
G13
NO
T4
85°C
-20/+50
1x36W
T8
G13
NO
T4
85°C
-20/+50
1x58W
T8
G13
NO
T4
85°C
-20/+50
2x18W
T8
G13
NO
T4
85°C
-20/+40
2x36W
T8
G13
NO
T4
85°C
-20/+40
2x58W
T8
G13
NO
T4
85°C
-20/+40
1x18W
T8
G13
NO
T4
85°C
-20/+50
1x36W
T8
G13
NO
T4
85°C
-20/+50
1x58W
T8
G13
NO
T4
85°C
-20/+50
2x18W
T8
G13
NO
T4
85°C
-20/+40
2x36W
T8
G13
NO
T4
85°C
-20/+40
2x58W
T8
G13
NO
T4
85°C
-20/+40
1x18W
T8
G13
SI
T4
85°C
-20/+50
1x36W
T8
G13
SI
T4
85°C
-20/+50
1x58W
T8
G13
SI
T4
85°C
-20/+50
2x18W
T8
G13
SI
T4
85°C
-20/+40
2x36W
T8
G13
SI
T4
85°C
-20/+40
2x58W
T8
G13
SI
T4
85°C
-20/+40
2
Note: all fixtures codes in the table are equipped with fuse and with
thermoplastic or brass cable gland.
Nota:tutte le plafoniere nella tabella qui sopra sono equipaggiate di fusibile e fornite
con pressacavo plastico o di ottone.
Customized execution without fuse have suffix –XN;
Customized executions with brass cable gland have suffix –XO
Esecuzione su richiesta senza fusibile hanno suffisso –XN;
Esecuzioni su richiesta con pressacavo in ottone hanno suffisso –XO
Example of a code for a 1x18W with brass cable gland.
822131XO
Esempio di codice 1x18W con pressacavo in ottone:
822131XO
MARKINGS OF FIXTURES
MARCATURE DELLEPLAFONIERE
Normal temperature range Ta -20°/+40°C
Range temperature normale Ta -20°/+40°C
Palazzoli
Via F. Palazzoli, 31, 25128 Brescia - Italy
XxYW
XXX V ~XX Hz ta 40°C IP66
xxxxxxEX
0051
TÜV IT xx ATEX xxx
2014Wxx
II 3G Ex nA IIC T4 Gc
II 2D Ex tb IIIC T 85 °C Db
Extended temperature range
Range temperatura esteso
Palazzoli
Via F. Palazzoli, 31, 25128 Brescia - Italy
XxYW
XXX V ~XX Hz ta 50°C IP66
xxxxxxEX
0051
TÜV IT xx ATEX xxx
2014Wxx
II 3G Ex nA IIC T4 Gc
II 2D Ex tb IIIC T 85 °C Db
-20°C ≤ Ta ≤ + 50°C
Legend\Legenda:
xxxxxxEX
Palazzoli product code
Codiceprodotto Palazzoli
0051
CE marking in reference to the ATEX Directive 94/9/EC, applied
together with the EC-type examination procedure as per Annex
VII of Directive 94/9/EC
Marcatura CE in riferimento alla direttiva ATEX 94/9/EC, applicata
contestualmente alla procedura di esame di tipo EC secondo
allegato VII della direttiva 94/9/EC
Electrical apparatus constructed and tested for use in an
explosive atmosphere, in accordance with Annex II of Directive
94/9/EC
Apparato elettrico costruito e testato per essere utilizzato in
atmosfera esplosiva, conformemente all’allegato II della direttiva
94/9/CE
2014 Wxx
Data production: Year andweek of production, in accordance with
Directive 94/9/EC (Annex II)
Data di produzione: anno e settimana di produzione,
conformemente all’allegato II della direttiva 94/9/CE
Voltage - ~
Frequency
Additional technical information, for example the equipment
voltage, Frequency, etc.
Informazioni tecniche addizionali, per esempio la tensione,
frequenza, etc.
XxYW
Power and number of fluorescent lamps (e.g. 2 x 36 W)
Numero e potenza delle lampade fluorescenti (es 2 x 36 W)
II
Group II. Equipment intended for use in places with presence of
explosive atmosphere, other than underground sites, mines,
tunnels, etc., identified according to the criteria as per article 1
and Annex I of Directive 94/9/EC (ATEX)
Apparecchiatura per Gruppo II, per utilizzo in presenza di
atmosfera esplosiva diversa da siti sotterranei, miniere, tunnel etc.
identificata secondo i criteri dell’articolo 1 e allegato I della
direttiva 94/9/CE (ATEX)
3G
3 = Category 3: Equipment designed to be capable of functioning
in conformity with the operated parameters established by the
manufacturer and ensuring a normal level of protection
G = Equipment intended for use in the presence of gas
Equipment suitable for installation in Zone 2
3 = Categoria 3: apparecchiatura progettata per funzionare in
conformità ai parametri operative stabiliti dal costruttore e
assicurando un livello di protezione normale.
G = apparecchiatura intesa per l’utilizzo in presenza di gas
Apparecchiatura adatta all’utilizzo in Zona 2.
2D
2 = Category 2: Equipment designed to be capable of functioning
in conformity with the operated parameters established by the
manufacturer and ensuring a high level of protection
D = Equipment intended for use in the presence of combustible
dust. Equipment suitable for installation in Zone 21
2 = Categoria 2: apparecchiatura progettata per funzionare in
conformità ai parametri operative stabiliti dal costruttore e
assicurando un livello di protezione alto.
D = apparecchiatura intesa per l’utilizzo in presenza di polveri
combustibili. Apparecchiatura adatta all’utilizzo in Zona 21.
Ex
Equipment designed and realized in accordance with harmonized
standardsEN 60079 series (for presumption of conformity to
94/9/EC), which provides a level of protection against explosive
atmospheres ignition suitable for the installation in the declared
Zone.
Apparecchiatura progettata e costruita in accordi con le norme
armonizzate della serie EN 60079 (per presunzione di conformità
alla direttiva 94/9/CE), che garantisce un livello di protezione
contro le atmosfere esplosive adatto all’installazione nelle zone
dichiarate.
nA
Electrical apparatus protected by components not capable of
creating arcs of sparks with type of protection “nA” (in accordance
with the harmonized standard EN 60079-15), intended for use in
presence of gas or flammable vapours
Apparecchiatura elettrica con modo di protezione “nA” (in accordo
con la norma armonizzata EN 60079-15), ovvero protetta
componenti non in grado di originare archi o scintille, idonea per
l’utilizzo in presenza di gas o vapori infiammabili.
IIC
Group II. Equipment intended for use in places with presence of
explosive gas atmosphere other than mines susceptible to
firedamps Group Subdivision IIC: a typical gas is hydrogen
Gruppo II: apparecchiatura intesa per usi in luoghi con presenza
di atmosfere esplosive gassose diversedalle miniere di gas grisou
Gruppo suddivisione IIC: un gas tipico è l’idrogeno.
3
T4
Temperature class Maximum surface temperature T4= 135°C
Classe di temperature: massima temperature superficiale
T4=135°C
Gc
Level of protection “c” - EPL “Gc”: the equipment is not a source
of ignition in normal operations and suitable for the installation in
Zone 2.
Livello di protezione “c” – EPL “Gc”: l’apparecchiatura non è una
sorgente di innesco nel funzionamento normale ed è adatto a
installazione in zona 2.
tb
Electrical apparatus protected against explosive dust atmosphere
ignition by an enclosure providing dust ingress protection and a
means to limit surface temperatures (type of protection “t” in
accordance with the harmonized standard EN 60079-31).
“b”: level of protection b
Apparecchiatura elettrica protetta contro le atmosfere di polveri
esplosive da una custodia con protezione all’ingresso di polvere e
limitazione della temperatura superficiale (tipo di protezione “t”
secondo la norma armonizzata EN60079-31).
“b”: livello di protezione b.
IIIC
Group III. Equipment intended for use in places with presence of
explosive dust atmosphere other than mines susceptible to
firedamps.Group Subdivision IIIC: conductive dust
Gruppo III. Apparecchiatura per utilizzo in presenza di atmosfere
con polvere esplosiva diversa da miniere suscettibili a gas grisou.
Suddivisione IIIC: polveri conduttive.
Maximum surface temperature 85 °C, for dust ignition risk
Massima temperature superficiale 85°C, per rischio di innesco
della polvere
level of protection “b” (EPL “Db”: the equipment is not a source of
ignition in normal operations or during expected malfunctions) and
suitable for the installation in Zone 21
Livello di protezione “b” (EPL “Db”: l’apparecchiatura non è una
sorgente di innesco durante il normale utilizzo o in presenza di un
guasto prevedibile) e adatta all’installazione in Zona 21.
T 85 °C
Db
NB:
La marcatura ATEX è riferita al range di temperatura ambiente
-20°C≤Ta≤40°C o -20°C≤Ta≤50°C come specificato nell’elenco
prodotti.
NB:
The Atex Marking is referred at the ambient temperature standard range of
-20°C≤Ta≤40°C or -20°C≤Ta≤50°C as specified in product list
Zones definition according to Directive 1999/92/EC
Definizione delle zone secondo la Directive 1999/92/CE
In places and for types of installation subject to Directive 99/92/EC the
employer must classify the zones on the basis of Annex I of the same
Directive as regards the danger of the formation of explosive atmospheres
due to the presence of gas or dust.
In luoghi e per tipi di installazione soggetti alla direttiva 99/92/CE il datore
di lavoro deve classificare le zone sulla base dell’allegato I della direttiva
in riferimento al pericolo di formazione di atmosfera esplosiva di gas o
polvere.
Zone classification as per Directive 1999/92/EC:
Classificazione delle zone secondo laDirettiva1999/92/CE:
A place in which an explosive atmosphere consisting of a
mixture with air of flammable substances in the form of gas,
Zone 0
vapour or mist is present continuously or for long periods or
frequently.
A place in which an explosive atmosphere in the form of a
Zone 20
cloud or combustible dust is present continuously, or for long
periods of frequently.
A place in which an explosive atmosphere consisting of a
mixture of air and inflammable substances in the form of gas,
Zone 1
vapour or mist is likely to occur in normal operation
occasionally.
A place in which an explosive atmosphere in the form of a
Zone 21
cloud or combustible dust is likely to occur in normal
operation occasionally.
A place in which an explosive atmosphere consisting of a
mixture of air and inflammable substances in the form of gas,
Zone 2
vapour or mist is not likely to occur in normal operation but, if
it does occur, will persist for a short period only.
A place in which an explosive atmosphere in the form of a
cloud or combustible dust is not likely to occur in normal
Zone 22
operation but, if it does occur, will persist for a short period
only.
Area in cui è presente in permanenza o per lunghi periodi o
spesso un'atmosfera esplosiva consistente in una miscela di aria
e di sostanze infiammabili sotto forma di gas, vapore o nebbia.
Area in cui è presente in permanenza o per lunghi periodi o
spesso un'atmosfera esplosiva sotto forma di nube di polvere
combustibile nell'aria.
Area in cui durante le normali attività è probabile la formazione di
un'atmosfera esplosiva consistente in una miscela di aria e di
sostanze infiammabili sotto forma di gas, vapore o nebbia.
Area in cui occasionalmente durante le normali attività è
probabile la formazione di un'atmosfera esplosiva sotto forma di
nube di polvere combustibile nell'aria.
Area in cui durante le normali attività non è probabile la
formazione di un'atmosfera esplosiva consistente in una miscela
di aria e di sostanze infiammabili sotto forma di gas, vapore o
nebbia e, qualora si verifichi, sia unicamente di breve durata.
Area in cui durante le normali attività non è probabile la
formazione di un'atmosfera esplosiva sotto forma di nube di
polvere combustibile e, qualora si verifichi, sia unicamente di
breve durata.
Installation suitability table as per Annex II § B Directive 1999/92/EC
Tabella di idoneità di installazione come da allegato II § B Direttiva 1999/92/CE
Product Category according to
Directive 94/9/EC
GAS
DUST
for Group II
GAS
POLVERE
Categoria di prodotto secondo
Direttiva 94/9/CE Gruppo II
G
Zone 0
1
D
Zone 20
G
Zone 1
2
D
Zone 21
G
Zone 2
3
D
Zone 22
TEMPERATURE CLASS TABLE (for gas atmosphere)
TABELLA DI CLASSI DI TEMPERATURA (per atmosfere gassose)
Maximum Surface
Temperature (°C)
Massima temperature
superficiale
Temperature Class
Classe di temperatura
450
300
200
135
100
85
T1
T2
T3
T4
T5
T6
WARNING!!
before starting the installation check that the classification of the zones has
been carried out correctly with reference to Directive 1999/92/EC
(For example using harmonized standards EN 60079-10-1 for gas and/or
EN 60079-10-2 for presence of combustible dust)
WARNING!
Do not install the fixtures "RINO-EX" series in areas classified as Zone 0,
ATTENZIONE!!
Prima di installare l’apparecchiatura, verificare che la classificazione delle
aree sia stata eseguita correttamente in accordo alla Direttiva 1999/92/CE
(Per esempio utilizzando le norme armonizzate EN 60079-10-1 per gas e/o
EN 60079-10-2 per la presenza di polvere combustibile)
ATTENZIONE!!
Non installare le plafoniere serie “RINO-EX” in aree classificate Zona 0,
4
Zone 20, Zone 1
Fixtures "RINO-EX" series can be installed only if completely intact.
Ordinary and extraordinary maintenance operations can be performed only
by qualified and skilled personnel.
Fixtures "RINO-EX series should not be modified under any circumstances,
except as specified in these instructions.
Fixtures "RINO-EX series can not be installed in locations with ambient
temperature outside the following temperature range:
-20 °C ≤Ta≤ 40° C or -20 °C ≤Ta≤ 50° C (see product list)
Follow the instruction on the labels affixed to the walls of the housing of the
Fixtures "RINO-EX” series.
For the use of fixtures "RINO-EX" series in aggressive environments,
contact Palazzoli.
Zona 20, Zona 1
Le plafoniere serie “RINO-EX” possono essere installate solo se
completamente integre.
Operazioni di manutenzione ordinaria e straordinaria possono essere
eseguite solo da personale qualificato e specializzato.
Le plafoniere serie “RINO-EX”non devono essere in nessuna circostanza
modificate, tranne per quanto specificato in queste istruzioni.
Le plafoniere serie “RINO-EX”non sono possono essere installate in luoghi
con temperatura ambiente fuori dal seguente intervallo di temperature:
-20°C≤Ta≤40°C o -20 °C ≤Ta≤ 50° C (si rimanda alla lista dei prodotti)
Rispettare le istruzioni riportate sulle etichette apposte sulle pareti della
custodia delle plafoniere serie “RINO-EX”.
Per l’uso delle plafoniere serie “RINO EX” in ambienti aggressivi,
contattare direttamente Palazzoli
WARNING!!
Installations of electrical systems in hazardous areas shall be carried out by
personnel trained on the applicable code of practice, national rules and/or
international standards
(for example EN 60079-14 – Explosive atmospheres - Part 14: Electrical
Installations design, selection and erection)
ATTENZIONE!!
L’installazione di impianti elettrici in zone con pericolo di esplosione deve
essere effettuata da personale esperto, formato e addestrato alla regola
dell’arte, alle leggi, norme nazionali e / o internazionali applicabili.
(per esempio EN 60079-14 - Atmosfere esplosive - Parte 14:
Progettazione, scelta e installazione degli impianti elettrici)
TABLE OF ZONES WHERE THE PALAZZOLI FIXTURES EQUIPMENT CAN BE INSTALLED
TABELLA DELLE ZONE DOVE LE PLAFONIERE POSSONO ESSERE INSTALLATI
94/9/EC Group and Category
94/9/CEGruppo e Categoria
II 3G 2D
Before installingthe fixtures RINO-EX series fixtures and make sure
that:
a)
in places with an atmosphere with the presence of combustible
dust, the ignition temperature of the dust is greater than the
temperature indicated in the marking according to hazardous
areas installations rules (EN 60079-14);
b)
in places with an atmosphere with the presence of gas, the
ignition temperature of the gas is greater than Temperature
Class given in the marking according to hazardous areas
installations rules (EN 60079-14).
1.
GAS
GAS
DUST
POLVERE
Zone 2
Zone 21-22
Prima di procedere all’installazione delle plafoniereserie RINO-EX
assicurarsi che:
a)
nei luoghi con atmosfera esplosiva per la presenza di polvere
combustibile, la temperatura di innesco della polvere sia
superiore alla temperatura riportata in marcatura, in accordo
alle regole di installazione in aree pericolose (EN 60079-14).
b)
nei luoghi con atmosfera esplosiva per la presenza di gas, la
temperatura di innesco del gas sia superiore a quella
specificata dalla classe di temperatura riportata in
marcatura, in accordo alle regole di installazione in aree
pericolose (EN 60079-14).
TECHNICAL DATA
DATI TECNICI
The equipment is realized by a metallic (stainless steel or painted steel)
enclosure with tempered flat glass diffuser.
The glass is fixed on the body through a system of stainless steel clamps.
The enclosures are suitable to withstand an impact (mechanical danger) as
follows:
Risk of mechanical danger
Part of enclosure
Steel body
Glass
High
Maximum Energy Impact
7J
4J
The enclosures are equipped with internal clamp for an earth conductor. For
external case earthing (if required or necessary) an external earth terminal
is provided.
The type and degree of protection are secured by a gasket.
The good condition of all seals should be checked at every opening of
the housing.
The equipment is designed and manufactured with entries into enclosure in
Chapter 3of this document.
Le apparecchiature sono realizzate in custodia metallica (acciaio inox o
acciaio verniciato) con diffusore in vetro temperato piano.
Il vetro è fissato al corpo tramite sistema di ganci in acciaio inox.
Le custodie sono capaci di sopportare un impatto (pericolo meccanico)
come segue:
Rischio meccanico
Parti della custodia
Corpo in acciaio
Vetro
Alto
Massima energia d’impatto
7J
4J
Le custodie sono provviste di morsetto interno per un conduttore di terra.
Per il collegamento equipotenziale della custodia (se necessario o richiesto)
è predisposto un morsetto esterno.
Il tipo e il grado di protezione sono garantiti da una guarnizione.
Il buono stato di conservazione di tutte le guarnizioni deve essere
verificato ad ogni apertura della custodia.
L’apparecchiatura è progettata e prodotta con gli ingressi in custodia indicati
nel capitolo 3 del presente documento.
TECHNICAL INFORMATION - INFORMAZIONI TECNICHE
Maximum rated voltage - Massima tensione nominale
230V c.a.
Frequency – Frequenza
50-60Hz
Insulation class – Classe di isolamento
I
Ambient temperature for use – Temperatura ambiente di utilizzo
-20°C≤Ta≤40°C (-20°C≤Ta≤50°C for/per 1xXX)
See product list table – Vedi tabella prodotti
Degree of protection – Grado di protezione
IP66
Lamp and lamp holder type tipo di lampada e portalampade
T8 – G13
Lamps number and power – Numero e Potenza lampade
1x18W 2x18W 1x36W 2x36W 1x58W 2x58W
(see product list table – vedi tabella elenco prodotti)
Minimum
Maximum
Type of cables for connection
Cross section
[mm2]
[mm2]
Tipo di cavi per la connessione
Sezione
1,5
2,5
Maximum number of connectable cables at each terminal
1
Massimo numero di cavi connettibili ad ogni morsetto
No. ingress into enclosure / type
See clause 2 of this instructions
N. di ingressi in custodia e tipo
Vedi capitolo 2 del presente documento
GAS temperature class and DUST temperature
See product list table – Vedi tabella elenco prodotti
Classe di temperature GAS e temperature POLVERE
Devices not suitable to be covered by heatMounting restrictions
insulating material
Limitazioni per il montaggio
Apparecchi non idonei ad essere ricoperti di
materiale termicamente isolante
5
FASTENERS TECHNICAL
DATA up to diameter M6 (EQUIPMENT)
DATI TECNICI DEI FILETTI
fino a M6 (APPARECCHIATURA)
FASTENERS TECHNICAL DATA
TERMINALS OF THE FIXTURE
DATI TECNICI DEI FILETTI (MORSETTI)
Type of screw
Tipo di filetto
Minimum tightening
torque
Minima coppia di
serraggio
[Nm]
Maximum tightening
torque
Massima coppia di
serraggio
[Nm]
Terminal
M4
2
2,5
Phases
Fasi
M6
2,5
Type
Phase and neutral
Internal earthing terminal
External earthing terminalwith eyelet
4
Minimum tightening
torque
Minima coppia di
serraggio
[Nm]
Maximum tightening
torque
Massima coppia di
serraggio
[Nm]
0,6
1,2
2
3
Earth, internal
Terra interna
Earth, external
Terra esterna
TERMINALS CAPACITY
CAPACITA’ DI CONNESSIONE DEI MORSETTI
Minimum cross-sectional
area
Tipo
Minima sezione
[mm2]
Fase e neutro
1
Terminale terra interna
Terminale terra esterna con occhiello
The equipment shall be installed according to this instructions.
This equipment is intended for fixed installing.
Maximum crosssectional area
Massima sezione
[mm2]
2,5
4
6
L’apparecchiatura deve essere installata conformemente alle presenti
istruzioni.
L’apparecchiatura è intesa per installazione fissa.
OVERALL DIMENSIONS AND MOUNTING POSITIONS
INGOMBRI E POSIZIONI DI MONTAGGIO
Type
Tipo
A
B
[mm]
[mm]
*x18W
690
480
*x36W
1300
1090
*x58W
1600
1395
6
Fixtures must be installed according to this instruction.
These fixtures are intended for fixed use only.
2.
Le plafoniere devono essere installate secondo questa istruzione.
Questi prodotti sono intesi esclusivamente per installazione fissa.
ENTRIES INTO ENCLOSURES
INGRESSI IN CUSTODIA
Type of cable gland
Tipo di pressacavo
Plastic cable gland
Pressacavo plastic
Brass cable gland
Pressacavo in ottone
CABLE GLAND /BLANKING ELEMENT TECHNICAL DATA: TIGHTENING TORQUE
DATI TECNICI PRESSACAVI E TAPPI: COPPIA SERRAGGIO
Minimum tightening torque
Application
Minima coppia di serraggio
Applicazione
[Nm]
Cable gland mounting M20x1,5
6
Pressacavo M20x1,5 (montaggio dado)
Cable gland (on cable) M20x1,5
5
Pressacavo M20x1,5 (su cavo)
Cable gland mounting M20x1,5
6
Pressacavo M20x1,5 (montaggio dado)
Cable gland (on cable) M20x1,5
5
Pressacavo M20x1,5 (su cavo)
Maximum tightening torque
Massima coppia di serraggio
[Nm]
8
7
8
7
GENERAL CONDITIONS FOR SAFE USE - CONDIZIONI GENERALI PER UN USO SICURO
Assembly and start-up must only be done by experienced and
authorised personnel, according to the applicable code of practice,
national rules and/or international standards and on the basis of these
instructions

Position the equipment so that they are easily accessible for cleaning
and maintenance operations.

Install the equipment as far away as possible from heat sources or
areas subject to sudden temperature changes.

Avoid zones where there is the risk of impact with moving parts when:
o
the impact energy could be higher than 10 J

Avoid covering the Enclosures with additional thickness of paint or
other substances, including dust layers, so that heat dissipation
reducing.

POWER SUPPLY: The fixture must be powered by alternate current,
in accordance with par. 2.

The fixture must never be used with continuous current.
Montaggio e messa in servizio devono essere eseguiti solo da
personale autorizzato ed esperto, in accordo allo stato dell’arte,
regolamenti e leggi nazionali e/o norme internazionali e in osservanza
di queste istruzioni.






DO NOT OPEN THE ENCLOSURE WHEN ENERGIZED
DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE MAY BE
PRESENT
Before start-up the installation, verify that the enclosure is correct closed
and positioned according to these instructions
(see clause 6, 4 and 2).
Posizionare l’apparecchio in modo tale da essere facilmente
accessibile per operazioni di pulizia e manutenzione.
Installare l’apparecchio il più lontano possibile da sorgenti di calore o
zone soggette a sbalzi di temperatura.
Evitare zone in cui vi sia il rischio di impatto con parti in movimento,
quando:
o
l’energia di impatto potrebbe essere superiore a 7 J
Evitare di ricoprire la custodia con spessori aggiuntivi di vernici o altre
sostanze, inclusi strati di polvere, tali da ridurne la dissipazione
termica.
ALIMENTAZIONE:la plafoniera deve essere alimentata in corrente
alternata come previsto dal capitolo 2.
La plafoniera non deve mai essere alimentata in corrente continua.
NON APRIRE L’APPARECCHIO QUANDO IN TENSIONE
NON APRIRE QUANDO PUO’ ESSERE PRESENTE UN’ATMOSFERA
ESPLOSIVA
Prima di iniziare l’installazione, verificare che la custodia sia chiusa in modo
corretto e posizionata in accordo a queste istruzioni
(si veda capitoli. 6, 4 e 2)
3.
SPECIFIC CONDITION FOR SAFE USE NECESSARY TO MAINTAIN THE TYPES OF PROTECTION
CONDIZIONI SPECIFICHE PER L’USO SICURO, NECESSARIE AL MANTENIMENTO DEI MODI DI PROTEZIONE

Every screw shall be tightened with the torque according to this
document (see clause 2), to :
o
maintain the degree of protection (IP code) and
consequentially the type of protection Ex “tb”;
o
maintain the type of protection Ex “nA”.
Additional holes and/or entries into enclosure are not permitted,
the only entries in the enclosure shall be made by Palazzoli (see the
information reported in clause 3 of this document).
Substitution of cable glands is allowed but only with components
provided by Palazzoli.
For every entries into enclosure:
o
Use only cable glands provided in the Palazzoli equipment
package.
The mounting of the entries into enclosure or cable glands shall be in
accordance to the following:
o
The mounting of cable glands provided in the Palazzoli
package, shall be carried out with the tightening torque in
accordance to clause 2 of this instructions.
o
The mounting of the cable glands and/or entries shall be
carried out to maintain the types of protection of the
equipment.
o
If the type metal cable gland is used, the additional flat
sealing shall be mounted after the standard O-Ring. The
additional flat sealing shall be positioned between the ORing and the plane hole entries into enclosure.
o
The tightening torque shall be applied on the lock nuts of
the cable glands and/or entries, inside the enclosure. The
parts of the cable glands and/or entries outside the
enclosure shall be maintained in fixed position during the
tightening operation to avoid any gaskets damage.
Modifications to the internal components are not permitted
The terminal wiring connection shall be in accordance to the following:
o
Sheathed cables shall be used.
o
Use only cables in accordance with clause 2 of this
instruction(3x1,5mm2 – max 3x2,5 mm2)
o
Remove sheath only to the extent necessary to separate
the conductors of the cable for connection to terminals.












Ogni vite deve essere serrata con coppia adeguata come da
capitolo 2 sul presente documento per:
o
Mantenere il grado di protezione IP e
conseguentemente il modo di protezione Ex “tb”;
o
Mantenere il modo di protezione Ex “nA”.
Fori e/o ingressi addizionali in custodia non sono permessi nella
custodia, gli unici ingressi devono essere praticati da Palazzoli (vedi
informazioni al capitolo 3 del presente documento).
La sostituzione di pressacavi è permessa ma solo con i componenti
forniti da Palazzoli.
Per ogni ingresso in custodia:
o
Utilizzare solo pressacavi forniti da Palazzoli nelle
confezioni.
Il montaggio degli ingressi in custodia/pressacavi deve rispettare
quanto segue:
o
Il montaggio dei pressacavi presenti nella confezione deve
avvenire conformemente al capitolo 2 delle presenti
istruzioni.
o
Il montaggio dei pressacavi presenti nella confezione deve
avvenire in modo da mantenere il modo di protezione
dell’apparecchiatura
o
Se viene utilizzato il pressacavo tipo metallico, si deve
montare la guarnizione piana in dotazione dopo l’O-Ring
standard del pressacavo. La guarnizione piana deve
essere interposta tra l’O-Ring del pressacavo e il foro
piano dell’ingresso in custodia.
o
La coppia di serraggio deve essere applicata al dado del
pressacavo/ingresso all’interno della custodia, mentre le
parti esterne del pressacavo devono rimanere ferme
durante il serraggio per evitare di danneggiare la
guarnizione.
La modifica di componenti interni è vietata
Per la connessione dei conduttori del cavo di alimentazione, si deve
rispettare quanto segue:
o
Utilizzare solo cavi con guaina.
o
Utilizzare solo cavi secondo quanto previsto dal capitolo 1
del presente documento (3x1,5mm2 – max 3x2,5 mm2).
7
o
o
o
Remove main insulation of the every single wire only to
extent necessary to connect the conductor inside the
terminals. No copper wire shall be out of the terminal.
Tighten the screw of the terminals with the tightening
torque indicated in clause 2 of this document.
o
o
Rimuovere la guaina del cavo solo per lo stretto
necessario a separare i conduttori ed effettuare le
connessioni.
Rimuovere l’isolamento principale di ogni singolo
conduttore del cavo, solo in misura necessaria per
collegare il conduttore all'interno dei terminali. Nessun filo
di rame nudo deve risultare fuori dal morsetto.
Serrare le viti dei morsetti con la coppia prescritta dal
capitolo 1 del presente documento.
4.
CONNECTIONS OF EARTHING OR BONDING CONDUCTORS.
CONNESSIONE DEI CONDUTTORI DI MESSA A TERRA O DI COLLEGAMENTO EQUIPOTENZIALE DELLE MASSE

The equipment shall be earthed in accordance with the relevant code
of practice.
The equipments are provided by internal connection terminal for
earthing;
If an external bonding conductor connections is required by relevant
installation rules or for other reason, connect an earth wire use the

external dedicated earthing terminal, identified by symbol


.
The conductor used for bonding connection must be equipped with
ring terminal and install the conductor according to the instructions
below
The tightening screw according to clause 1 guarantees the electric
continuity.
5.


L’apparecchio deve essere connesso a terra in conformità alla regola
dell’arte.
L’apparecchio è dotato di morsetto interno per la connessione di terra.
Nel caso in cui le norme di riferimento applicabili per l’installazione,
richiedano il collegamento equipotenziale esterno oppure questi si
renda necessario per altre ragioni, collegare il conduttore
equipotenziale al morsetto di terra esterno, identificato con il simbolo
.
Il conduttore utilizzato per la connessione equipotenziale deve essere
dotato di capocorda ad occhiello ed installato secondo quanto indicato
nelle istruzioni seguenti:
Il serraggio della vite in accordo con il paragrafo 1 garantisce la
continuità elettrica.
INSTALLATION
INSTALLAZIONE
The cables enter directly in the enclosure through the cable gland. Only the
cable gland provided withthe product shall be used.
The fixture shall be installed only in positions described in clause 3.
Installation procedure:

Open the enclosure releasing the clamps

Remove the internal frame with electrical components (if the
earth faston (indicated with the arrow in the picture below), it
must be later reconnected.



Fit the chosen fixing accessory to the fixture, as specified in
clause 3.
Fit the fixture to wall, ceiling, pole.
Connect the power supply cable to switch terminals, after
removing the transparent cover and paying particular attention
to:
- remove the indispensable minimum of cable sheath inside the
box
- strip the ends of the conductors and make sure that all the
single wires are correctly inserted in the switch’s terminals
- do nor tin the ends, fit tubular end terminals if necessary
- insert the neutral conductor (light blue) into the terminal
marked with “N”
L’ingresso dei cavi avviene direttamente nella custodia attraverso il
pressacavo.
Devono essere utilizzati esclusivamente i pressacavi forniti insieme al
prodotto.
La plafoniera deve essere installata nelle posizioni descritte al capitolo 3.
Procedura di installazione:

Aprire la plafoniera rilasciando i ganci.

Rimuovere la scocca interna con componenti elettrici, se viene
scollegato il faston di terra (indicato nella freccia nell’immagine),
questo deve essere poi ricollegato.



Montare gli accessori di fissaggio alla plafoniera come
specificato nel capitolo 3.
Montare la plafoniera a muro, a soffitto, su palo o canala.
Connettere I cavi di alimentazione dopo aver rimosso la
protezione trasparente ponendo attenzione a:
- rimuovere il minimo indispensabile della guaina all’interno della
scatola
- spellare le estremità dei conduttori e di fare in modo che tutti i
singoli fili siano inseriti correttamente nei terminali della
morsettiera
- non stagnare il cavo; utilizzare capicorda se necessario
- inserire il conduttore di neutro nel morsetto marcato con “N”
- serrare le viti dei morsetti con le coppie indicate nel capitolo 2
8





6.

- tighten the terminals to the torque given on clause 2
Correctly tighten the cable gland on the power supply cable (see
tightening torque given on clause 2)
Fit the frame with electrical components with screws
Mount lamps
Close the fixture acting on all clamps.
Fix clamps with the screws on clamps to make it impossible to
reopen without tools.




Serrare il pressacavo sul cavo di alimentazione con la coppia
prescritta al capitolo 2.
Rimontare la scocca con viti
Montare le lampade
Chiudere la plafoniera azionando tutti i ganci.
Avvitare I ganci con le viti in dotazione per rendere impossibile
la riapertura senza l’utilizzo di un utensile.
CONDITION IN SERVICE, MAINTENANCE AND REPAIR
CONDIZIONI DI SERVIZIO, MANUTENZIONE E RIPARAZIONE
6.1.
GENERALS
GENERALITA’
Checks andmaintenance onRINO-EXPalazzoli
must be carried outonly by personnelwith years of experienceand
licensedin accordance withthe rule of art, national regulations and
/orapplicable international standards(eg. EN60079-17)
Verifiche e manutenzioni sui RINO-EX di Palazzoli
devono essere eseguite solo da personale di riconosciuta esperienza
ed autorizzato, in accordo con la regola dell’arte, regolamenti nazionali
e/o norme internazionali applicabili (es. EN 60079-17)
The repairofRINO-EXPalazzoli
is not allowed.ContactPalazzolifor repair.
La riparazione dei RINO-EX di Palazzoli
non è permessa. Contattare Palazzoli per la riparazione.
WARNING!!
The components upon which the types of protection depends must be
verified during service
ATTENZIONE!!
I componenti da cui dipende il modo di protezione devono essere
verificati in servizio
WARNING!!
DO NOT OPEN THE ENCLOSURE AND DON’T MAKE MAINTENANCE
WHEN ENERGIZED
DO NOT OPEN AND DON’T MAKE MAINTENANCE WHEN AN
EXPLOSIVE ATMOSPHERE MAY BE PRESENT
ATTENZIONE!!
NON APRIRE L’APPARECCHIO E NON ESEGUIRE OPERAZIONI DI
MANUTENZIONE QUANDO IN TENSIONE
NON APRIRE E NON ESEGUIRE OPERAZIONI DI MANUTENZIONE
QUANDO PUO’ ESSERE PRESENTE UN’ATMOSFERA ESPLOSIVA
6.2.
MAINTENANCE
MANUTENZIONE
Maintenance is required for guarantee the level of protection provided by
the types of protection of this equipment. Periodical verifications are
required. The following operations shall be carried out with the frequency
indicated in the table.
Operation required
Operazione
Fluorescent lamps substitution
Sostituzione tubi fluorescenti
Sono richiesti operazioni di manutenzione al fine di garantire il livello di
protezione fornito dai modi di protezione con cui questa apparecchiatura è
realizzata. Sono richieste verifiche periodiche. Le operazioni di seguito
indicate devono essere eseguite con la frequenza riportata in tabella.
Frequency
Frequenza
When burned
Quando bruciate
1.
2.
3.
4.
5.
6.
7.
1.
2.
3.
4.
5.
6.
7.
Action
Azione
Ensure no explosive atmosphere is present
Open circuit to operate without tension
Clean the fixture from dust before opening
Unscrew the clamps screw and open the
clamps
Substitute the lamp with the new; a
standard T8 fluorescent lamp can be used
Close the clamps and screw back
Turn power on
Assicurarsi che non sia presente atmosfera
esplosiva
Togliere tensione
Pulire la plafoniera dalla polvere prima di
aprire
Svitare le viti dei ganci e aprire i ganci
Sostituire il tubo con uno nuovo; utilizzare
tubi standard T8
Richiudere i ganci e riavvitare
Ridare tensione
9
Fuse substitution
Sostituzione fusibili
When intervened
Quando intervenuto
1.
2.
3.
Check that the gaskets
- are not damaged
- are in place
- the thickness is not compromised by
compression
Each time the enclosure is opened and
reclosed
Act as for lamps for opening enclosure
Unscrew the metal reflector
Substitute fuse with standard fusecomply
with EN 60127-6 and with following ratings:
Type 5x20 mm
2,5 A - 250 V.
1.
Eseguire le stesse operazioni per aprire la
custodia
2.
Svitare la scocca
3.
Sostituire il fusibile con fusibile conforme a
EN 60127-6 e con le seguenti
caratteristiche nominali:
Tipo 5x20 mm
2,5 A - 250 V.
In case of fault contact manufacturer for
substitution
Ogni volta la custodia viene aperta e richiusa
In caso di guasto contattare il costruttore per il
ricambio
Each time the enclosure is reclosed
In case of fault contact manufacturer for
substitution
Controllare che le guarnizioni
- non siano danneggiate
- siano in corretta posizione
- abbiano spessore non compromesso dalla
compressione
Check that the screws are in place, free of
corrosion
Ogni volta la custodia viene aperta e richiusa
Controllare che le viti siano in corretta posizione e
non corrose
Check that the screws are tight with correct torque
Controllare che le viti siano serrate con la corretta
coppia
Check the security of entries and/or cable glands
Annually and each time the enclosure is
opened and reclosed
Annualmente e ogni volta la custodia viene
aperta e richiusa
Annually each time the enclosure is opened
and reclosed
Controllare la sicurezza di ingressi e pressacavi
Annualmente e ogni volta la custodia viene
aperta e richiusa
In zone with presence of combustible dusts, check
if a dust layer is present on upper and plane
surfaces
In zone ove è presente polvere combustibile,
controllare se uno strato di polvere è presente sulle
superfici superiori.
Check the condition of the enclosure:
(enclosure is not damaged)
Controllare le condizioni della custodia (non
danneggiata)
Depending on the frequency of dust deposits
In funzione della frequenza della formazione di
depositi.
Each time the enclosure is opened and
reclosed
Annually
In case of impact
In caso di guasto contattare il costruttore per il
ricambio
Tight with the torque according to this document
(see clause 2)
Serrare le viti con la coppia indicate in capitolo 2.
In case of fault and the substitution is necessary,
the choose of components according to clause 3
and 5 of this document
In caso di guasto e necessità di sostituzione,
scegliere i componenti come da capitoli 3 e 5 del
presente documento.
Clean periodically the surfaces and remove the
dust layer. In case of frequent deposit limiting the
thickness of the layer to less than 5 mm
Pulire periodicamente rimuovendo lo strato di
polvere. In caso di depositi frequenti limitare lo
spessore del deposito a meno di 5 mm.
In case of fault contact manufacturer for
substitution
In caso di guasto contattare il costruttore per la
sostituzione.
Annualmente e ogni volta la custodia viene
aperta e richiusa
In caso di impatto
7.
DISPOSAL OF OLD EQUIPMENT (APPLICABLE TO EUROPEAN UNION AND OTHER EUROPEAN COUNTRIES WITH SEPARATE
COLLECTIONH SYSTEMS)
TRATTAMENTO DEL DISPOSITIVO A FINE VITA (APPLICABILE A TUTTI I PAESI DELL’UNIONE EUROPEA E A TUTTI I PAESI EUROPEI
CON RACCOLTA DIFFERENZIATA)
This symbol on the product or on its packaging indicates that this product
shall not be treated as household waste. Instead it shall be handed over to
the applicable collection point for the recycling of electrical and electronic
equipment. By ensuring this product is disposed of correctly, you will help
prevent potential negative consequences for the environment and human
health, which could otherwise be caused by inappropriate waste handling of
this product. The recycling of materials will help to conserve natural
resources. For more detailed information about recycling of this product,
please contact your local city office, your household waste disposal service
or the shop where you purchased the product.
Questo simbolo sul prodotto o sulla confezione indica che il prodotto non
deve essere considerato come un normale rifiuto domestico, ma deve
invece essere consegnato ad un punto di raccolta appropriato per il riciclo di
apparecchi elettrici ed elettronici. Assicurandovi che questo prodotto sia
smaltito correttamente, voi contribuirete a prevenire potenziali conseguenze
negative per l'ambiente e per la salute che potrebbero altrimenti essere
causate dal suo smaltimento inadeguato. II riciclaggio dei materiali aiuta a
conservar le risorse naturali. Per informazioni più dettagliate circa riciclaggio
di questo prodotto, potete contattare l’ufficio comunale, il servizio locale di
smaltimento rifiuti oppure il negozio dove l’avete acquistato.
10
DICHIARAZIONE CE DI CONFORMITA'
EC DECLARATION OF CONFORMITY
The undersigned, Dr. Ing. Luigi Moretti, representing the following manufacturer
Il sottoscritto, Dr. Ing. Luigi Moretti, rappresentante il seguente costruttore
Palazzoli S.p.A
25128 BRESCIA – Italy – Via F. Palazzoli, 31
Tel. +39 30 2015.1 Fax +39 30 2015.217
http://www.palazzoli.itE-mail: [email protected]
Herewith declares that the product/Dichiara qui di seguito che il prodotto:
FIXTURES in stainless steel and painted enclosure RINO-EX series
PLAFONIERE in acciaio inox e verniciato serie RINO-EX
With the following main features/Con le seguenti principali caratteristiche:
DescriptionDescrizione
Electronic fixtures in stainless steel or painted steel
enclosure
Plafoniere elettroniche in acciaio inox o acciaio verniciato
CodeCodice
See page 2 of the Safety instruction rev. 00 may 2014
Vedi pag 2 delle Istruzioni di sicurezza rev 00 maggio2014
Technical Data / CARATTERISTICHE TECNICHE
Insulating class /Classe Isolamento
Ambient Temperature range / Temperatura ambiente
Degree of protection(IP code) / Grado di protezione (codice IP)
Rated Voltage / Tensione nominale
Frequencies / Frequenze
Rated Power/Potenze
I
-20°C ≤ Ta ≤ + 40°C (-20°C ≤ Ta ≤ + 50°C for 1 lamp/1 tubo)
IP66
230 V c.a.
50-60 Hz
1x18W 2x18W 1x36W 2x36W 1x58W 2x58W
Satisfies the Requirements defined by following Directives/Soddisfa i Requisiti definiti dalle seguenti Direttive:
94/9/CE
ATEX / Atex
2006/95/CE
LVD / BASSA TENSIONE
2004/108/CE
EMC / EMC
2011/65/UE
RoHS / RoHS
2012/19/UE
RAEE / WEEE
and that the standards and/or technical specifications listed at page 2 have been applied.
e che sono state applicate tutte le norme e/o specifiche tecniche indicate a pagina 2.
product marking - marcatura dei prodotti
Normal temperature range Ta -20°/+40°C
Range temperature normale Ta -20°/+40°C
XxYW
PALAZZOLI
xxxxxxEX
II 3G
0051
TÜV IT xx ATEX xxx
2014 Wxx
Extended temperature range
Range temperatura esteso
XXX V ~ XX Hz IP66
PALAZZOLI
xxxxxxEX
Ex nA IIC T4 Gc
XxYW
II 3G
II 2D Ex tb IIIC T 85 °C Db
0051
TÜV IT xx ATEX xxx
2014 Wxx
XXX V ~ XX Hz IP66
Ex nA IIC T4 Gc
II 2D Ex tb IIIC T 85 °C Db
-20°C ≤ Ta ≤ +50°C
Ai sensi della Direttiva 94/9/CE, l’apparecchiatura è oggetto del certificato di esame CE del tipo (allegato III) N.:
According to Directive 94/9/EC, above mentioned equipment is subject of EC-type examination certificate (annex III) No.:
TÜV IT 14 ATEX 033
emesso da / issued by:TÜV ITALIA S.r.l.
Via Giosuè Carducci, 125 edificio 23 20099 Sesto San Giovanni (MI)
Organismo Notificato N. / Notified Body No.: 0948
Ultime due cifre dell'anno in cui è stata apposta la marcatura CE: 14
Last two digits of the year in which the CE marking was affixed: 14
Brescia, 20/05/2014
Il Legale Rappresentante
11
DICHIARAZIONE CE DI CONFORMITA'
EC DECLARATION OF CONFORMITY
standards and/or technical specifications applied
Norme e/o specifiche tecniche applicate
Directive 94/9/EC
Direttiva 94/9/CE
Standard
Norma
Date
Data
Title
Titolo
EN 60079-0
EN60079-0/A11
2012
2013
Explosive atmospheres - Part 0: Equipment - General requirements
Atmosfere esplosive - Parte 0: Apparecchiature - Prescrizioni generali
EN 60079-15
2010
Explosive atmospheres - Part 15: Equipment protection by type of protection "n"
Atmosfere Esplosive - Parte 15: Apparecchiature con modo di protezione "n"
EN 60079-31
2009
IEC 60079-31
2013
Explosive atmospheres - Part 31: Equipment dust ignition protection by enclosure “t”
Atmosfere Esplosive - Parte 31: Apparecchi con modo di protezione “t” destinati ad
essere utilizzati in presenza di polveri combustibili
Directive 2006/95/CE
Direttiva2006/95/CE
Standard
Norma
Date
Data
Title
Titolo
EN 60529
EN 60529/A1
1991
2000
Degrees of protection provided by enclosure (IP code)
Gradi di protezione degli involucri (Codice IP)
EN 60598-1
EN 60598-1/A11
2008
2009
Luminaires – Part 1: General requirements and tests
Apparecchi di illuminazione - Parte 1: Prescrizioni generali e prove
1989
Luminaires – Part 2: Particular requirements – Section 1: Fixed general purpose
luminaires
Apparecchi di illuminazione - Parte 2: Prescrizioni particolari – Sezione 1: Apparecchi
fissi per uso generale
EN 60598-2-1
Directive 2004/108/CE
Direttiva 2004/108/CE
Standard
Norma
Date
Data
Title
Titolo
EN 55015
EN 55015/A1
EN 55015/A2
2006
2007
2009
Limits and methods of measurement of radio disturbance characteristics of electrical
lighting and similar equipment
Limiti e metodi di misura delle caratteristiche di radiodisturbo degli apparecchi di
illuminazione elettrici e degli apparecchi analoghi
EN 61547
2009
Equipment for general lighting purposes - EMC immunity requirements
Apparecchiature per illuminazione generale - Prescrizioni di immunità EMC
EN 61000-3-2
EN 61000-3-2/A1
EN 61000-3-2/A2
2006
2009
2009
Electromagnetic compatibility (EMC) - Part 3-2: Limits - Limits for harmonic current
emissions (equipment input current ≤ 16 A per phase)
Compatibilità elettromagnetica (EMC) - Parte 3-2: Limiti - Limiti per le emissioni di
corrente armonica (apparecchiature con corrente di ingresso ≤ 16 A per fase)
EN 61000-3-3
2008
Electromagnetic compatibility (EMC) - Part 3-3: Limits - Limitation of voltage changes,
voltage fluctuations and flicker in public low-voltage supply systems, for equipment with
rated current ≤ 16 A per phase and not subject to conditional connection
Compatibilità elettromagnetica (EMC) - Parte 3-3: Limiti - Limitazione delle variazioni di
tensioni, fluttuazioni di tensione e del flicker in sistemi di alimentazione in bassa tensione
per apparecchiature con corrente nominale ≤ 16 A per fase e non soggette ad
allacciamento su condizione
12