Transcript
14 3.8 HORIZONTAL TERMINATION (HT) < (VT) See graph to determine the required vertical rise VT for the required horizontal run HT. Simple venting configuration (only one 90° elbow) 39 40 30 REQUIRED VERTICAL RISE IN FEET VT 20 10 0 2.5 5 7.5 10 12.5 15 17.5 20 HORIZONTAL VENT RUN PLUS OFFSET IN FEET HT The shaded area within the lines represents acceptable values for HT and VT For vent configurations requiring more than one 90° elbow, the following formulas apply: Formula 1: HT < VT Formula 2: HT + VT < 40 feet Example: V1 = 3 FT V2 = 8 FT VT = V1 + V2= 3 FT + 8 FT = 11 FT H1 = 2.5 FT H2 = 2 FT HR = H1 + H2 = 2.5 + 2 = 4.5 FT HO = .03 (three 90° elbows - 90°) = .03 (270° - 90°) = 5.4 FT HT = HR + HO = 4.5 + 5.4 = 9.9 FT HT + VT = 9.9 + 11 = 20.9 FT Formula 1: HT < VT 9.9 < 11 Formula 2: HT + VT < 40 FT 20.9 < 40 Since both formulas are met, this vent configuration is acceptable. 90° V2 90° H1 90° V1 16.10 W415-0098 / H / 03.19.12 H2