OPERATION CONDITION ENGLISH Use this air conditioner under the following temperature range Single Split Outdoor Unit (CU-E7MKE, CU-E9MKE, CU-E12MKE, CU-E15MKE, CU-E18MKE, CU-E21MKE) Indoor Temperature (°C) COOLING HEATING Max. Min. Max. Min. *DBT 32 16 30 16 Outdoor *WBT 23 11 - *DBT 43 5 24 -5 *WBT 26 4 18 -6 NOTICE: • This model is not suitable for 24 hours non-stopping operation in heating mode below -5°C. When the outdoor temperature is below -5°C and you use this model out of above conditions, the outdoor unit might be frozen up and stop operation for protection control. Single Split Outdoor Unit (CU-E7MKE-3, CU-E9MKE-3, CU-E12MKE-3) Indoor Temperature (°C) COOLING HEATING Max. Min. Max. Min. *DBT 32 16 30 16 Outdoor *WBT 23 11 - *DBT 43 5 24 -15 *WBT 26 4 18 -16 NOTICE: • This model is not suitable for 24 hours non-stopping operation in heating mode below -15°C. When the outdoor temperature is below -15°C and you use this model out of above conditions, the outdoor unit might be frozen up and stop operation for protection control at -18°C. Multi Split Outdoor Unit (CU-2E15LBE, CU-2E18LBE, CU-3E18LBE, CU-4E23LBE, CU-4E27CBPG) Indoor Temperature (°C) COOLING HEATING Max. Min. Max. Min. *DBT 32 16 30 16 *WBT 23 11 - Outdoor Outdoor CU-2E15LBE, CU-2E18LBE, CU-4E27CBPG CU-3E18LBE, CU-4E23LBE *DBT 43 16 24 -10 *DBT 46 -10 24 -15 *WBT 26 11 18 -11 *WBT 26 18 -16 * DBT: Dry bulb temperature * WBT: Wet bulb temperature 3