Download INSTALLATION MANUAL - Energy Alternatives
Transcript
INSTALLATION MANUAL Please read and study this manual completely before installation or use of any Day4 Energy Inc. (Day4 Energy) photovoltaic modules. This manual applies to the following products: Day4 Energy 36/ 48MC series photovoltaic modules. INTRODUCTION • To avoid the risk of electric shock and injury, be sure to completely ground all Day4 Energy modules (US and Canada only). With proper installation, operation and maintenance, Day4 Energy modules will provide you with clean, renewable solar electricity for many years. This manual contains important installation, maintenance and safety information. Retain this manual for future reference. The word “module(s)” as used in this manual refers to one or more Day4 Energy 36/ 48MC series photovoltaic modules. • To avoid the danger of electric shock, fire and injury, do not disassemble the Day4 Energy module, or remove any part installed by Day4 Energy or any authorized dealer or integrator. • Unauthorized persons should not open the cover of the junction box as this increases chances of dangerous electric shock, may cause damage to the module and will void the warranty. Only a qualified licensed professional should attempt to open the cover of the junction box. Disclaimer of Liability Day4 Energy does not assume responsibility and expressly disclaims liability for loss, damage or expense arising out of or in any way connected with installation, operation, use or maintenance by using this manual. Day4 Energy assumes no responsibility for any infringement of patents or other rights of third parties which may result from the use of Day4 Energy modules. No license is granted by implication or under any patent or patent rights. The information in this manual is believed to be reliable, but does not constitute an expressed and/or implied warranty. Day4 Energy reserves the right to make changes to the product, specifications or manual without prior notice and on its sole discretion. • To avoid the risk of electric shock or injury, provide suitable protection to prevent direct contact with solar electric systems with voltage greater than 30V. • Use caution when carrying Day4 Energy modules. It is recommended that two or more persons carry the module by its frame and use nonslip gloves. • Do not carry a Day4 Energy module by its connecting wires or junction box. • Do not drop anything on the surface of a Day4 Energy module. A damaged surface can cause electric shock and injury. General Information • To avoid the hazard of electric shock and fire, be sure that all system components are compatible with Day4 Energy modules. Components should not subject the module to mechanical or electrical hazards. The installation of photovoltaic Day4 Energy modules requires a great degree of skill and should only be performed by qualified licensed professionals, including, without limitation, licensed contractors and licensed electricians. • Since sparks may occur, do not install the Day4 Energy module where flammable gases or vapors are present. WARNING • Never leave a Day4 Energy module unsupported or unsecured. • All instructions should be read and understood before attempting to install, wire, operate or maintain the photovoltaic Day4 Energy module. Contact with electrically active parts of the module such as terminals can result in burns, sparks and lethal shock whether the module is connected or disconnected. • Do not drop a Day4 Energy module. • Do not use or install a broken or damaged Day4 Energy module. • Day4 modules with damaged back-sheets should never be installed or operated. • Some transformer-less inverters are not suitable for use with photovoltaic modules in specific applications. Check with the inverter manufacturer, the inverter installation manual and attain the inverter manufacturer’s approval prior to use. • To avoid the risk of fire or damage, do not artificially concentrate sunlight on a Day4 Energy module. • Do not touch the junction box terminals. This can cause electric shock and injury. • The installer assumes the risk of any injury that might occur during installation, including, without limitation, the risk of electric shock and or fire. • Do not change the wiring of bypass diodes. • Do not install Day4 Energy modules as a building integrated photovoltaic (BIPV) module or above a flammable material. • Day4 Energy modules generate DC electrical energy when exposed to sunlight or simulated sunlight sources. Although a single module produces only a low voltage and current, shocks and burns are still a potential risk. • Do not run reverse current through a Day4 Energy module in the attempt to de-ice the module or for any other purpose. • Do not stand or walk on the surface of a Day4 Energy module as you may cause damage to the frame or other parts of the module. • To avoid the danger of electric shock and injury, cover the front glass surface of the Day4 Energy module with a dense, opaque material during installation and handling. CAUTION • The shock hazard increases as Day4 Energy modules are connected in parallel producing higher current. The shock risk increases as modules are connected in series producing higher voltages. • Use a Day4 Energy module for its intended purpose only. (Please refer to the Day4 Energy 36/ 48MC warranty document.) • To avoid reducing module function, damage, inoperable conditions and other unknown troubles, do not treat the back-sheet or front surface with paint or adhesives. • To avoid the peril of electric shock, work only under dry conditions with dry modules and tools. • To avoid the risk of injury and damage to the module, do not stand or step on a Day4 Energy module. • Do not disconnect connectors under load. • To avoid the threat of electric shock and/or fire, do not puncture or damage the back-sheet of a Day4 Energy module. To avoid the peril of electric shock and injury, children and unauthorized persons should not be allowed near the installation of modules. 1 GENERAL SAFETY 2. Observe the requirements described in sections of this manual labeled “Installation” and “Specifications”. Follow all permission, installation and inspection requirements. 3. Grounding of the Day4 Energy module frame is required. When ground wires greater than 6 mmC (No. 10 AWG) are required the installer will need to provide suitable terminal connectors. • Before installing Day4 Energy modules, contact the appropriate authorities to determine permissions, installation and inspection requirements to be followed. IEC 61730 Application Class A Information • Electrically ground Day4 Energy modules for all systems of any voltage (only applicable in the USA and Canada). If not otherwise specified it is recommended that requirements of the latest National Electrical Code (USA) or Canadian Electric Code (Canada) or any other applicable national or international electrical standards be used. (applies to Europe only): Day4 Energy modules are designed to pass the criteria of application class A requirements according to IEC 61730-part1. To satisfy IEC 61730 requirements when installing the Day4 Energy modules be sure to: • Be sure that the construction or structure (roof, facade, etc.) where the Day4 Energy modules are being installed has enough strength to support the added module and structure weight. For modules that are to be mounted on roofs, special construction or structures may be required for proper installation. Both roof construction and module installation design have an effect on the fire resistance of a building. Improper installation may contribute to fire hazards. Additional devices such as ground fault, fuses and disconnects may be required. 1. Use only double insulated stranded copper type cable. The cable should be resistant to UV, water, ozone, fluids, salt, general weathering and abrasion. The cable should be halogen free and flame retardant for the Day4 Energy module and interconnect wiring. Be sure the cable is certified according to IEC 60228 class 5. 2. Observe the requirements described in sections of this manual labeled “Installation” and “Specifications”. • Do not use Day4 Energy modules of different specifications in the same system. 3. Equipotential bonding of the Day4 Energy modules and module frame is recommended. The equipotential bonds between modules may only be connected and approved by a qualified electrician. • Follow all safety precautions of other system components used. • Do not change or alter Day4 Energy modules or apply improper means, such as, but not limited to, mirrors and/or other optical systems of any kind. Do not operate the modules under artificially concentrated sunlight such as an optical system and/or in direct contact with solar thermal systems. Option 1: Connect the module frame using cables [16 mmC (0.64 inC)] with cable lugs. Use the holes [diameter 4 mm (0.16 in)] for this purpose. To create the conductive connection (frame is anodized), use a self-tapping screw [diameter 5 mm (0.20 in)] or a serrated washer. Option 2: Create an electrical connection between the frames and the mounting system by using serrated lock nuts (see “Installation”, Figure 1 – Example B). UL Listing Information (applies to USA and Canada only): To satisfy UL requirements when installing Day4 Energy modules be sure to: 4. Do not apply any external voltage higher than Voc labeled on the module. 1. Use only stranded single-conductor wire of listed type USE-2, 12 AWG, rated 90°C, 600 V, sunlight resistant for Day4 Energy modules and interconnect wiring that is exposed to weather. 5. Refer to the module label for maximum series fuse rating. INSTALLATION • Please contact your Day4 Energy authorized representative with questions regarding mounting profiles for modules. General • Please read this guide completely before installation or use of Day4 Energy modules. This section contains electrical and mechanical specifications needed before using your modules. Notes on Installation • Clearance between the Day4 Energy module frame and the mounting surface is required to allow cooling air to circulate around the back of the module. This also allows any condensation or moisture to dissipate. The module should never be sealed to the mounting surface with sealant preventing air from circulating under the module. • Do not mount damaged Day4 Energy modules. • Day4 Energy modules should be firmly fixed in place in a manner suitable to withstand all expected loads, including wind and snow loads. • In order to determine the maximum annual yield, the optimum orientation and tilt of the Day4 Energy modules must be identified. Sunlight shining vertically onto the modules will give the best conditions to generate maximum power. To avoid performance drops in series circuits, ensure all modules have the same orientation and tilt. Modules should be of the same power class. • Do not drill additional mounting holes into module frames, as this will void the warranty. • Day4 Energy modules must not be fitted as overhead or vertical glazing. • Day4 Energy modules must be installed in a way that ensures the junction box is in the uppermost position. • Even the slightest partial shading like from dirt deposits will cause a reduction in yield. A module is considered “shadow-free” if it is un-obscured across its entire surface for the entire year. Even on the shortest day of the year unobstructed sunlight should reach the module. • Day4 Energy modules should not be mounted without a frame. Removal of the factory supplied frame is not permitted. • The appropriate material should be used for mounting hardware to prevent the module frame, mounting structure and hardware itself from corrosion. Please note that: • Install Day4 Energy modules where they are not shaded by obstacles like buildings and trees. Pay special attention to avoid partial shading by objects during the daytime. Do not operate the module if it is shadowed or otherwise covered in its entirety or partially by debris, leaves, tree branches, dirt, bird droppings, snow, ice and/or any other substance or objects capable of preventing the light from illuminating the front surface of the module in a uniform unobstructed manner (refer to section in this manual labeled “Notes on Installation”). The recommended standoff height minimum to satisfy the UL fire class C rating is 10.16 cm (4 in). Other mounting methods will affect the fire class rating. The fire class rating of the PV module installation must meet the code requirements as well as the requirements of the specific place of installation. Please refer to Figure 1 for proper installation. 2 FIGURE 1 FIGURE 2 EXAMPLE A: CLAMPING ON EXAMPLE A EXAMPLE B: BOLTING EXAMPLE B 1 2 3 4 5 Stainless steel M8 nut Stainless steel serrated washer Aluminum clamping plate EPDM washer 2mm (0.78 in) Stainless steel M8 t-head bolt It is recommended that a torque wrench be used for installation. In Figure 1 - Example A the tightening torque (using stainless steel M8 bolts) should be approximately 15-20 Nm (11-15 ft-lb). Use the existing holes for securing the module. Do not drill additional holes as doing so would void the warranty. Use appropriate corrosion-proof fastening materials. Each module must be securely fastened at a minimum of 4 points. The frame has been stress tested for mounting on the long sides. The module must not be secured by its short sides. This method offers maximum loading capacities on the module surface. (See Figure 2) Europe only: Day4 Energy modules have been evaluated by third party testing for a maximum positive design loading of 5400 N/mC and a maximum negative design load of 2400 N/mC. USA and Canada only: Day4 Energy modules have been evaluated by UL for a maximum positive or negative design loading of 1436.4 N/mC (30 lbs/ftC). Day4 Energy modules have been evaluated by UL for mounting using the four provided mounting holes in the frame (refer to Figure 2 – Example B). WIRING Day4 Energy Module Wiring • The maximum number of Day4 Energy modules that can be wired in series or parallel design is dependent on legal requirements, maximum current and voltage ratings as indicated on the module label, installation design, space and further specifications of additional equipment such as inverters and converters. General All wiring methods should be in accordance with the NEC in USA or CEC in Canada or any other code, electrical code, law or bylaw applicable for the place of installation. • All wiring should be completed by a qualified licensed professional. • Day4 Energy modules must have the same amperage when connected in series. When connected in parallel, the modules must have the same voltage. The modules must not be connected together to create a voltage higher than the permitted system voltage according to protection class A. • Wiring should be protected to help ensure personal safety and to prevent damage. • All Day4 Energy modules connected in series should be of the same model class and/or type. • The Day4 Energy 48MC series modules can be used for “off-grid” installations, like charging batteries, if electronic equipment such as a power tracker is used to control module output parameters and provides accurate electrical output according to off-grid appliance specifications. • Do not connect Day4 Energy modules in parallel without using a connection box. • Cable used for any wiring should be sized according to applicable electrical codes. • Any cable used in the installation should conform to the requirements of IEC 60228 class 5 (Europe only). • Please contact your local licensed installer regarding the use of Day4 Energy 48MC series modules in off-grid applications and in combination with charge controllers or similar equipment. • Day4 Energy modules contain factory installed bypass diodes. If these modules are incorrectly connected to each other the bypass diodes, cables or junction boxes may be damaged. 3 DIODES Array Wiring The term “array” is used to describe the assembly of several Day4 Energy modules on a support structure with associated wiring. Use insulated copper wire that is suitable for outdoor use and is insulated to withstand the maximum possible system open circuit voltage. Check local codes for further requirements. Bypass Diodes Day4 Energy modules in series strings that are partially shaded may cause reverse voltage across cells or modules because current from other cells in the same series is forced to flow through the shaded area. This may cause undesirable heating to occur. The use of a diode to bypass the shaded area can minimize both heating and reduce the array current. Earth Ground Wiring All Day4 Energy modules are equipped with factory installed bypass diodes. The factory installed diodes provide proper circuit protection for the systems within the specified system voltage so that no other additional bypass diodes are required. Contact your authorized Day4 Energy representative for the proper diode type if it is necessary to add or change diodes due to system specifications. Refer to the module label for correct diode size. (applies to USA and Canada only) Ground should be carried out by securing the Day4 Energy module or array frame to avoid the hazards of electric shock or fire. The array frame should be grounded in accordance with NEC Article 250 (USA) or CEC (Canada). Contact local authorities to determine the necessary grounding code requirements. Proper grounding is achieved by connecting the module frames and structural members contiguously together using a suitable “grounding conductor”. It is recommended to utilize a UL listed grounding lug made of stainless steel. Use a tin-plated or beryllium grounding lug if the grounding method involves attachment of a grounding lead to the module frame. Standard Operating Conditions It is recommended that Day4 Energy modules be operated under “Standard Operating Conditions” (SOC). An installation location with conditions different from SOC or with other “Special Conditions” (see below) should be avoided. SOC of Day4 Energy modules are as follows: The grounding conductor, grounding lead, or strap may be copper, copper alloy, or another material acceptable for use as an electrical conductor per NEC/CEC. The grounding conductor must make a connection to earth using a suitable earth ground electrode. Ensure positive electrical contact through the anodizing on the module’s frame by utilizing one of the following grounding methods: 1.) Standard Operating Conditions • The Day4 Energy module should be operated only in terrestrial applications. No space or other “Special Conditions” (see below). Attach the grounding conductor: • The operating temperature of the module should be within -40°C (-40°F) to 90°C (194°F). 1. To one of the 4 mm (0.16 in) holes marked ‘ground’ with a nut, bolt or screw assembly and a serrated washer, external toothed washer, or a paint piercing washer for attachment of the grounding lug to the Day4 Energy module frame. • The relative humidity should be within 45% to 85%. • The installation place should be less than 1,000 m (3,280 ft) above sea level. Installations more than 1,000 m (3,280 ft) are allowed only if the wind pressure load for a module is less than 2,170 N/mC (45 lbs/ftC). 2. To electrically conductive metal, such as that of a support structure which has been bonded to the module frame through a bonding or external tooth washer, or a welded, or a soldered for brazed joint or other suitable means as described above. 2.) Special Conditions 3. With two or more screws or two full threads of a single screw engaging the module frame metal. • Operating temperature and installation place conditions are different from SOC. Attention: Do not allow dissimilar metals such as copper and aluminum to come in contact with each other. Use grounding lugs made of stainless steel, beryllium or tin-plated. Never use self-tapping screws to connect the grounding conductor. • The salt damage is extreme at the installation location. • The hail and snow damage is severe at the installation location. • The sand and dust damage is severe at the installation location. • The air pollution, chemically active vapors, acid rain, soot, or other pollutants are extreme at the installation location. Day4 Energy Module Terminations A junction box as a terminal enclosure is equipped for electrical connections on Day4 Energy modules. Day4 Energy modules are equipped with Tyco Solarlok Interconnection Systems in either UL compliant or IEC compliant versions, output cables, and male and female cable couplers. Use the Tyco Solarlok couplers for electrical connections only. Please contact your Day4 Energy authorized representative with questions regarding other electrical connections for Day4 Energy modules. Junction Box and Terminals Day4 Energy modules are equipped with one junction box with terminals for both positive and negative polarity and bypass diodes. One terminal is dedicated to each polarity with the polarity symbols engraved onto the body of the junction box. No modifications to the junction box are permitted. Conduit For applications where wire conduits are used, follow the applicable codes for outdoor installation of wires in conduits. Verify that all fittings are properly installed to protect wires against damage and prevent moisture intrusion. 4 SPECIFICATIONS MAINTENANCE Notes on Specification Some maintenance is recommended to maintain optimal output performance of the Day4 Energy modules. If the module surface becomes dirty, it may reduce output power. It is recommended to clean the surface of the module with plenty of water and a soft cloth or sponge. A mild non-abrasive detergent may be applied for persistent dirt. Never scratch or rub away any dirt when dry. Do not use a high pressure cleaner or automated cleaning equipment. • Rated electrical characteristics are within 3.5% of the values measured at Standard Test Conditions (STC). STC are: Irradiance of 1000 W/mC, 25°C cell temperature and solar spectral irradiance per IEC 60904-3 (AM1.5 solar spectral irradiance). • The current output for the Day4 Energy modules is shown in the Specifications as measured at Standard Test Conditions. These conditions may not be frequently observed in actual practice. It is also recommended to inspect the Day4 Energy module’s electrical and mechanical connections annually. All fastenings should be tight and secure and free of corrosion. All cable connections should be secure, tight, clean and free of corrosion. Cables may not be damaged in any way. • Under normal conditions a Day4 Energy module may experience conditions that produce more current and/or voltage than reported at Standard Test Conditions. Accordingly, the values of Isc and Voc marked on listed module should be multiplied by a safety factor of 1.25 when determining voltage ratings, conductor capacities, fuse sizes, and size of controls connected to the module output. To avoid the risk of electric shock and/or injury, it is recommended an authorized professional carry out the electrical and/or mechanical inspection and/or maintenance is required. Take care that the lid of the junction box is tightly secured and electrical connectors are properly connected and free of corrosion. If modules are stored prior to installation, ensure that no water, dirt, dust, etc. accumulates on the module’s back side. The contacts and the junction box especially, must be kept free of any moisture. Inside storage is strongly recommended. Electrical ratings at STC: Maximum system voltage rating: (V) IEC 61215/ IEC61730 rating = 1000; (V) UL 1703 rating = 600 Day4 36MC Maximum power rating (W) 115 120 125 130 135 140 145 Voltage rating (V) Current rating (A) 16.80 16.95 17.21 17.55 17.78 17.98 18.24 6.89 7.08 7.30 7.46 7.60 7.79 7.95 Voltage rating (V) Current rating (A) 22.30 22.60 22.95 23.04 23.40 23.70 23.82 24.00 6.97 7.08 7.19 7.38 7.48 7.60 7.77 7.92 Short circuit current rating (A) 7.60 7.70 7.90 8.05 8.10 8.20 8.30 Open circuit voltage rating (V) 20.98 21.23 21.52 21.90 22.05 22.28 22.57 Short circuit current rating (A) 7.55 7.70 7.80 7.90 8.05 8.10 8.20 8.30 Open circuit voltage rating (V) 28.00 28.30 28.60 28.80 29.20 29.40 29.51 29.70 The return of any Day4 Energy module will not be accepted by Day4 Energy unless prior written authorization has been given by Day4 Energy. As part of our policy of continuous improvement Day4 Energy reserves the right to change product specifications at any time without prior notice and its sole discretion. Day4 48MC Maximum power rating (W) 155 160 165 170 175 180 185 190 USA: Refer to Section 690-8 of the U.S. National Electrical Code for an additional multiplying factor of 1.25 which may be applicable. Manufactured by Day4 Energy Inc. #401, 4621 Canada Way, Burnaby, BC Canada V5G 4X8 office: 604 297 0444 fax: 604 297 0445 email: [email protected] web: www.day4energy.com Specifications and design are subject to change without notice. The features, functions and appearance of Day4 MC modules may differ from details given due to continual product development. For updated documentation please contact Day4 Energy Inc. or check our web site: www.day4energy.com. Installation_Manual_111209_EN_SNGL 5