7 Set up with the display and adjustment module Setup/Current output mode In this menu item you can select the switching behaviour of the sensor. You can choose between an 8 - 16 mA characteristics or a 16 - 8 mA characteristics. Inthismenuitemyoucanalsodefinetheswitchingbehaviourincase of fault. You can select if the current output should output 22 mA or < 3.6 mA in case of fault. Setup/Relay In this menu item you can select which mode the sensor should operate in. Youcanchoosebetweenoverfillanddryrunprotection. The relay outputs of the sensor react accordingly. Overfillprotection=therelaywilldeenergise(safecondition)when the max. level is reached. Dry run protection = the relay will deenergise (safe condition) when the min. level is reached. Make sure that you have selected the correct characteristics. See menu item "Setup/Current output mode". 43389-EN-131119 Lock setup - adjustment With this menu item you safeguard the sensor parameters against unauthorizedorunintentionalmodifications. To avoid possible errors during parameterization in a non-safe user environment,averificationprocedureisusedthatmakesitpossible to detect parameterization errors reliably. For this, safety-relevant parametersmustbeverifiedbeforetheyarestoredinthedevice.In normal operating condition, the instrument is also locked against parameter changes through unauthorized access. MINITRAC 31 • 4 … 20 mA/HART - four-wire 47