Chapter 3 Installation And Cable Connection
PG push-pull output
VCC
VCC
0V
Use shielded cable
+24V
OCI
PGP
●
●
●
●
●
●
D
I
21
EV3000
interface board
CN4
+5V
COM
A
VCC
●
A
A+
A
-
GND
B
B
B+
●
●
Interface circuit is
●
GND
PE
Grounding the
shielded cable
Figure 3-16
the same as A
B-
●
Cable connection of push-pull output PG
Note
+24V
+5V
During cable connection, be careful not to short PGP with COM,
or the R11 resistor may be damaged.
8V~24V
4.7KΩ
PLC
6) Notes on relay cable connection
X1、X2 . . . X7
FWD and REV
Please refer Table 3-1 for the selection of relay cable.
Surge suppressing circuit should be added for the inductive
load (such as relay, contactor), for example: RC circuit (be
careful that the leakage current should be lower than the
relay maintenance current), voltage sensitive resistor, or
diode (used in DC circuit, but the polarity must be paid
attention). The components of suppressing circuits must be
as close to the relays as possible, as shown in Figure 3-17.
+ Vdc
AC 220V
Coil of relay or contactor
Relay
terminal
Coil of relay or contactor
R:100~500 Ω
C:0.1~0.2uF
Relay
terminal
Figure 3-17
Connection to external power supply
!
Attention
External 24V power supply must be isolated from mains by at
least Basic Insulation. Failure to observe this requirement will
cause risk of electric shock.
Note
When the customer power source PLC terminal is used, the COM
terminal cannot be used at the same time.
3. Setting jumpers and switch on the control board and
DC snubber circuit
RC snubber circuit
Figure 3-19
Inside the
inverter
Surge suppressing circuit
7) Notes on connection of power supply terminals
Terminal for digital value input can be powered by the
inverter's 24V power supply, shown in Figure 3-18.
interface board
Before usage, all the jumpers on the control board and
interface boards must be set up in right mode. Position of
jumpers and switches on the control board is shown in
Figure 3-20, function of jumper is shown in Table 3-9.
CN1
+5V
PLC
CN2
CN2
+24V
Control board
Programmable
relay
4.7KΩ
Keypad
socket
Fault relay
CN3
COM
Figure 3-18
DSPA
CN1
X1、X2 . . . X8
FWD and REV
Inside the
inverter
Interface board
Connection to internal 24V power supply
DSPM
DI
OFF
OCI
When X8 terminal is used, recommended voltage range of
external power supply is 18~24V.
CN6
In the figure, recommended voltage range of external power
supply is 8~24V (suitable for X1~X7 terminals).
CN3
Terminal for digital value input can be powered by external
power supply (user power supply), this power supply should
be connected with PLC terminal, shown in Figure 3-19.
ON
CN4
V
S1
CN11
I
CN10
Figure 3-20
EV3000 Series Inverter User Manual
Jumpers and switch on the control board