plug-in
r3: minimum set point allowed
Determines the minimum value which can be set for the set point. This parameter prevents the user from setting the set point lower
than the value indicated by r3. Def.: -50
r4: maximum set point allowed
Determines the maximum value which can be set for the set point. This parameter prevents the user from setting the set point
higher than the value indicated by r4. Def.: +60
r5: regulator 2 probe
Selects the probe to be used by regulator 2 (that is, the regulator associated with set point 2) for the operation of the connected load. If set
to zero, probe S1 is used, otherwise probe S2 is used.
Def.: 0. Available in the models with two probes.
5.7
c0
c1
c2
c3
c4
c = regulation timings management parameters
control times
output activation delay at instrument on
minimum on time for the regulation outputs
minimum off time for the regulation outputs
regulators start-up interlock
minimum time between the activation of two outputs
type
C
C
C
C
C
min.
0
0
0
0
0
max.
199
15
15
1
199
uom
sec
min
min
sec
def
0
0
0
0
0
Table. 5.7.1
c0: output activation delay from instrument on
When power supply is applied, the activation of the regulation outputs is delayed by a time (minutes) equal to the value set for this
parameter. This delay allows the load to be protected against repeated starts in the case of frequent power failures. For example,
setting c0=6 forces the load to wait 6 seconds before starting from when power returns. In the case, for example, of systems with
many units, parameter C0 can also be used to avoid simultaneous starts of the controls, by simply setting a different value for C0
on each regulator.
Fig. 5.7.1
Def.: c0=0 (no delay for the activation of the control outputs when the instrument is switched on).
Available on all models.
Warning: this parameter should not be set to "1".
Cod. +030220291 – rel. 1.2 dated 24/02/05