Download split system air conditioner technical & service manual
Transcript
TECHNICAL & SERVICE MANUAL ADR518CW AE518SC AE518SC3 / AER518SCL3 ADR518HW AE518SH AE518SH3 / AER518SH3 ® SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT OUTDOOR UNIT 0.8180.224.0 OCTOBER 01 TABLE OF CONTENTS A SPECIFICATIONS...........................................................................................................PAGE...3 B MAJOR COMPONENT SPECIFICATION.....................................................................................9 C OTHERS COMPONENT SPECIFICATIONS................................................................................16 D OPERATING RANGE....................................................................................................................21 E DIMENSIONALE DATA.................................................................................................................22 F FUNCTION.....................................................................................................................................24 G REFRIGERANT FLOW DIAGRAM................................................................................................31 H ELECTRIC WIRING DIAGRAM.....................................................................................................32 I TROUBLESHOOTING COOLING MODEL...................................................................................36 L SAME PARTS OF AIR CONDITIONER DO NOT OPERATE........................................................43 M AIR CONDITIONER OPERATES,BUT ABNORMALITIES OCCUR.............................................44 N TROUBLESHOOTING HEATING MODEL....................................................................................45 O SAME PARTS OF AIR CONDITIONER DO NOT OPERATE.......................................................52 P AIR CONDITIONER OPERATES,BUT ABNORMALITIES OCCUR............................................55 Q IS SENSOR IS DEFECTIVE..........................................................................................................56 R CHECKING ELECTRICAL ...........................................................................................................59 H A SPECIFICATIONS 1) UNIT SPECIFICATIONS UNIT MODEL INDOOR UNIT OUTDOOR UNIT ADR518CW AE518SC Power source 220 / 230 / 240V - 1 - 50 Hz PERFORMANCES COOLING BTU/h Capacity 16,900 W (Kcal/h) Air circulation (high - med - low) 4.950 (4,250) m3/h 780 External static pressure (high speed) mm w.g. (Pa) Moisture removal (high speed) l/h ELECTRICAL Umidità asportataRATINGS (alta velocità) 5 (49) at shipment - 10 (98) using the Booster cable 2,8 l/h 0,9 Voltage rating V 230 Available voltage range V 198 ÷ 264 Running ampere A 9.5 Power input W 2,06 Power factor % 94 Compressor locked rotor amperes A 46 W/W 2.4 C.O.P. FEATURES Controls Microprocessor Control unit Remote control Temperature control I.C. thermostat Timer ON/OFF 12 hours Fan speed indoor / outdoor 3 + auto / 2 auto Air filter Washable, easy access (accessory) Compressor Rotary (hermetic) Refrigerant / ref. control / amount charged at ship g Operation sound Outdoor Hi / Lo Max. tubing length 42 / 37 / 32 Max. allowable tubing length Limit of elevation difference between the two units 51 / 44 (3 m) dB-A m Required amount of additional refrigerant Refrigerant tube diameter R22 / capillary tube / 1.710 g Indoor Hi / Me / Lo (1 m) dB-A (with factory R22 charge) 10 m ....(with.R22.addition)....................20 g/m 25 m 7 Narrow tube mm (in.) 6.35 (1/4”) Wide tube mm (in.) 12.7 (1/2”) Accessory Booster cable DIMENSIONS AND WEIGTH INDOOR UNIT OUTDOOR UNIT Higth mm 316 630 Width mm 750 830 Depth mm 665 305 Net weigth kg 42 52 Shipping volume m3 0,33 0,3 Shipping weight (approx.) kg 44 57 Data subject to change without notice. NOTA. Rating conditions: Cooling: Outside air temp.: 35°C DB, indoor unit entering air temp.: 27°C DB / 19°C WB 3 UNIT MODEL INDOOR UNIT OUTDOOR UNIT ADR518CW AE518SC3 Power source 400V - 3N - 50 Hz (4 wires) PERFORMANCES COOLING BTU/h Capacity 16,900 W (Kcal/h) Air circulation (high - med - low) 4.950 (4250) m3/h 780 External static pressure (high speed) mm w.g. (Pa) Moisture removal (high speed) l/h ELECTRICAL Umidità asportataRATINGS (alta velocità) 5 (49) at shipment - 10 (98) using the Booster cable 2,8 l/h 0,9 Voltage rating V 400 Available voltage range V 342 ÷ 440 Running ampere A 4.0 Power input W 1.96 Power factor % 84 Compressor locked rotor amperes A 21.5 C.O.P. W/W 2.5 FEATURES Controls Microprocessor Control unit Remote control Temperature control I.C. thermostat Timer ON/OFF 12 hours Fan speed indoor / outdoor 3 + auto / 2 auto Air filter Washable, easy access (accessory) Compressor Rotary (hermetic) Refrigerant / ref. control / amount charged at ship g Operation sound Outdoor Hi / Lo Max. tubing length 42 / 37 / 32 Required amount of additional refrigerant Limit of elevation difference between the two units 51 / 44 (3 m) dB-A m Max. allowable tubing length Refrigerant tube diameter R22 / capillary tube / 1.405 g Indoor Hi / Me / Lo (1 m) dB-A (with factory R22 charge) 10 m ....(with.R22.addition).....................20 g/m 25 7 m Narrow tube mm (in.) 6,35 (1/4”) Wide tube mm (in.) 12,7 (1/2”) Accessory Booster cable DIMENSIONS AND WEIGTH INDOOR UNIT OUTDOOR UNIT Higth mm 316 630 Width mm 750 830 Depth mm 665 305 Net weigth kg 42 52 Shipping volume m3 0,33 0,3 Shipping weight (approx.) kg 44 57 Data subject to change without notice. NOTA. Rating conditions: Cooling: Outside air temp.: 35°C DB, indoor unit entering air temp.: 27°C DB / 19°C WB 4 UNIT MODEL INDOOR UNIT OUTDOOR UNIT ADR518CW AER518SCL3 Power source 400V - 3N - 50 Hz (4 wires) PERFORMANCES COOLING BTU/h Capacity 17.400 W (Kcal/h) Air circulation (high - med - low) 5900 (5070) m3/h 780 External static pressure (high speed) mm w.g. (Pa) 5 (49 at shipment - 10 (98) using the Booster cable Moisture removal (high speed) l/h 2.8 ELECTRICAL Umidità asportataRATINGS (alta velocità) l/h 0,9 Voltage rating V 400 Available voltage range V 342 : 440 Running ampere A 3.6 Power input W 2.000 Power factor % 80 Compressor locked rotor amperes A 21.5 C.O.P. W/W 2,3 FEATURES Controls Microprocessor Control unit Remote control Temperature control I.C. thermostat Timer ON/OFF 12 hours Fan speed indoor / outdoor 3 + auto / 2 auto Air filter Washable, easy access (accessory) Compressor Rotary (hermetic) Refrigerant / ref. control / amount charged at ship g Operation sound Outdoor Hi / Lo Max. tubing length 42 / 37 / 32 Required amount of additional refrigerant Limit of elevation difference between the two units 51/ 44 (3 m) dB-A m Max. allowable tubing length Refrigerant tube diameter R407C / capillary tube / 1.710 g Indoor Hi / Me / Lo (1 m) dB-A m (with factory R407C charge) 10 (with R407C addition) g/m 30 25 7 m Narrow tube mm (in.) 6,35 (1/4”) Wide tube mm (in.) 12.7(1/2") Accessory Booster cable DIMENSIONS AND WEIGTH INDOOR UNIT OUTDOOR UNIT mm 316 630 Width mm 750 830 Depth mm 665 305 Higth Net weigth kg 42 52 Shipping volume m3 0.33 0.3 Shipping weight (approx.) kg 44 57 Data subject to change without notice. NOTA. Rating conditions: Cooling: Outside air temp.: 35°C DB, indoor unit entering air temp.: 27°C DB / 19°C WB 5 INDOOR UNIT OUTDOOR UNIT UNIT MODEL ADR518HW AE518SH Power source 220 / 230 / 240V - 1 - 50 Hz PERFORMANCES COOLING BTU/h Capacity W (Kcal/h) Air circulation (high - med - low) HEATING 16.900 20500 4.950 (4.257) 6000(5160) m3/h 750 External static pressure (high speed) mm w.g. (Pa) Moisture removal (high speed) l/h ELECTRICAL Umidità asportataRATINGS (alta velocità) 5 (49) at shipment - 10 (98) using the Booster cable 2.8 --- l/h 0,9 Voltage rating V 230 Available voltage range V Running ampere A 9.8 Power input W 2.100 Power factor % 93 Compressor locked rotor amperes A C.O.P. 198 ÷ 264 10.3 2.150 90 57 W/W 2.35 2.8 FEATURES Controls Microprocessor Control unit Remote control Temperature control I.C. thermostat Timer ON/OFF 12 hours Fan speed indoor / outdoor 3 + auto / 2 auto Air filter Washable, easy access (accessory) Compressor Rotary (hermetic) Refrigerant / ref. control / amount charged at ship g R22 / capillary tube / 1.87 g 42 / 37 / 32 Indoor Hi / Me / Lo (1 m) dB-A Operation sound Outdoor Hi / Lo Max. tubing length m Max. allowable tubing length Required amount of additional refrigerant Limit of elevation difference between the two units Refrigerant tube diameter 51 / 44 (3 m) dB-A (standard refrigerant charge) 10 m ....(with.R22.addition).....................30 g/m 25 7 m Narrow tube mm (in.) 6,35 (1/4”) Wide tube mm (in.) 12.7 (1/2”) Accessory Booster cable DIMENSIONS AND WEIGTH Higth mm Width mm Depth mm INDOOR UNIT OUTDOOR UNIT 316 630 750 665 830 305 Net weigth kg 42 52 Shipping volume m3 0,33 0.3 Shipping weight (approx.) kg 44 57 Data subject to change without notice. NOTA. Rating conditions: Cooling: Outside air temp.: 35°C DB, indoor unit entering air temp.: 27°C DB / 19°C WB 6 INDOOR UNIT OUTDOOR UNIT UNIT MODEL ADR518HW AE518SH3 Power source 400V - 3N - 50 Hz (4 wires) PERFORMANCES COOLING BTU/h Capacity W (Kcal/h) Air circulation (high - med - low) HEATING 16.100 19.800 4.700 (4.042) 5.800(6.744) m3/h 750 External static pressure (high speed) mm w.g. (Pa) Moisture removal (high speed) l/h ELECTRICAL Umidità asportataRATINGS (alta velocità) 5 (49) at shipment - 10 (98) using the Booster cable 2.8 --- l/h 0,9 Voltage rating V 400 Available voltage range V Running ampere A 3.8 Power input W 2.000 Power factor % 93 Compressor locked rotor amperes A C.O.P. 342 ÷ 440 4.0 2.100 90 22 W/W 2.35 2.76 FEATURES Controls Microprocessor Control unit Remote control Temperature control I.C. thermostat Timer ON/OFF 12 hours Fan speed indoor / outdoor 3 + auto / 2 auto Air filter Washable, easy access (accessory) Compressor Rotary (hermetic) Refrigerant / ref. control / amount charged at ship g R22 / capillary tube / 2.450g 42 / 37 / 32 Indoor Hi / Me / Lo (1 m) dB-A Operation sound Outdoor Hi / Lo Max. tubing length m Max. allowable tubing length Required amount of additional refrigerant Limit of elevation difference between the two units Refrigerant tube diameter 51 / 44 (3 m) dB-A (standard refrigerant charge) 10 m ....(with.R22.addition).....................30 g/m 25 7 m Narrow tube mm (in.) 6,35 (1/4”) Wide tube mm (in.) 12.7 (1/2”) Accessory Booster cable DIMENSIONS AND WEIGTH INDOOR UNIT OUTDOOR UNIT mm 316 630 Width mm 750 830 Depth mm 665 305 Higth Net weigth kg 42 52 Shipping volume m3 0,33 0.3 Shipping weight (approx.) kg 44 57 Data subject to change without notice. NOTA. Rating conditions: Cooling: Outside air temp.: 35°C DB, indoor unit entering air temp.: 27°C DB / 19°C WB 7 INDOOR UNIT OUTDOOR UNIT UNIT MODEL ADR518HW AER518SH3 Power source 400V - 3N - 50 Hz (4 wires) PERFORMANCES COOLING BTU/h Capacity W (Kcal/h) Air circulation (high - med - low) HEATING 16.400 21.500 4.800 (4.128) 6300(5418) m3/h 750 External static pressure (high speed) mm w.g. (Pa) Moisture removal (high speed) l/h ELECTRICAL Umidità asportataRATINGS (alta velocità) 5 (49) at shipment - 10 (98) using the Booster cable 2.8 --- l/h 0,9 Voltage rating V 400 Available voltage range V Running ampere A 4.0 Power input W 2.150 Power factor % 93 Compressor locked rotor amperes A C.O.P. 342 ÷ 440 4.2 2.250 90 22 W/W 2.23 2.8 FEATURES Controls Microprocessor Control unit Remote control Temperature control I.C. thermostat Timer ON/OFF 12 hours Fan speed indoor / outdoor 3 + auto / 2 auto Air filter Washable, easy access (accessory) Compressor Rotary (hermetic) Refrigerant / ref. control / amount charged at ship g R407C / capillary tube / 1.600 g 42 / 37 / 32 Indoor Hi / Me / Lo (1 m) dB-A Operation sound Outdoor Hi / Lo Max. tubing length m Max. allowable tubing length Required amount of additional refrigerant Limit of elevation difference between the two units Refrigerant tube diameter 51 / 44 (3 m) dB-A (standard refrigerant charge) 10 m ....(with.R407C.addition)................30 g/m 25 7 m Narrow tube mm (in.) 6,35 (1/4”) Wide tube mm (in.) 12.7 (1/2”) Accessory Booster cable DIMENSIONS AND WEIGTH Higth mm INDOOR UNIT OUTDOOR UNIT 316 630 Width mm 750 830 Depth mm 665 305 Net weigth kg 42 52 Shipping volume m3 0,33 0.3 Shipping weight (approx.) kg 44 57 Data subject to change without notice. NOTA. Rating conditions: Cooling: Outside air temp.: 35°C DB, indoor unit entering air temp.: 27°C DB / 19°C WB 8 B MAJOR COMPONENT SPECIFICATIONS INDOOR UNIT UNIT MODEL ADR518CW / ADR518HW Power source 220 / 230 / 240V -1 - 50 Hz REMOTE CONTROL UNIT CONTROLLER P.C.B. POW-U186GH Controls Microprocessor RCS-U251G Control circuit fuse 250V - 3A FAN Centrifugal Number ... dia. / length mm 2 ... Ø 200 / L 230 FAN MOTOR Model ... Number K48410M01526 ... 1 Power source V 220 / 230 / 240-1-50 Hz No. di poli ... giri/min (230V-max) 4 ... 1040 Nominal output W Coil resistance (Ambient temp. 20°C) Ω 70 WHT - BRN : 181,1 ORG - VLT : 136,8 YEL - ORG : 151,4 BLK - YEL : 120,6 WHT - VLT : 112,7 VLT - PNK : 144,2 Internal type 130 ± 18 SAFETY DEVICES Operating temp. Open °C Close °C 179 ± 15 µF Run capacitor 5 VAC 440 DRAIN PUMP Model Rated PC Voltage AC 230V - 50 Hz Input 114.7 W Total head capacity 0.4 m / 0.6 l/m HEAT EXCHANGER Coil Aluminum plate fin / Copper tube Rows Fin pitch Fase area 3 mm 1,8 0,125 m2 EXTERNAL FINISH Insulated galvanized metal sheet 9 Outdoor Unit Controller PCB AE518SC3 Part No. POW-C181BL Control circuit fuse 250V – 5A Type Rotary (Hermetic) Compressor model C-2R173H8V- 80817C88D 380 – 400 V – 3N ~ 50 Hz Source Nominal output W Compressor oil ... Amount cc Coil resistance (Ambient temp. 25°C) Ω 1,700 SUNISO 4GSD-T ... 800 C – R : 6.369 Compressor C – S : 6.073 R – S : 6.217 Type Safety devices Overload relay Operating temp. Open °C Close °C HOE-10TB TH-5A 125 ± 5 — — — 5A µF Run capacitor — VAC — Crank case heater 240V 30W Type Propeller Q´ty ... Dia. mm 1 ... ø400 Fan motor model ... Q´ty SMEN 19 TFB6055 ... 1 220 – 230 V ~ 50 Hz Source No. of poles ... rpm (220 V, High) Fan & Fan Motor External protector — Automatic reclosing Operating amp.(Ambient temp. 25°C) 6 ... 910 Nominal output W Coil resistance (Ambient temp. 20°C) Ω 43 WHT – BRN : 77.7 WHT - YEL : 366 WHT – PNK : 211 Safety devices Type Operating temp. Run capacitor Heat Exch. Coil Internal protector Internal type Open °C 130 ± 5 Close Automatic reclosing µF 2.0 VAC 400 Coil Aluminum plate fin / Copper tube Rows Fin pitch Face area 2 mm 1.8 m2 0.508 External Finish Acrylic baked-on enamel finish DATA SUBJECT TO CHANGE WITHOUT NOTICE. 10 Outdoor Unit AE518SC Controller PCB — Type Rotary (Hermetic) Compressor Compressor model PH36VTRT Nominal output W 1,600 Compressor oil ... Amount cc DIAMOND... 900 Coil resistance (Ambient temp. 20°C) Ω C – R : 1.06 C – S : 2.03 Type Safety devices Internal protector (OLR) Overload relay Operating temp. — Open °C Automatic opening 155 ± 5 Close °C Automatic reclosing 90 ± 10 Operating amp. (Ambient temp. 25 C) Run capacitor Trip in 3 to 10 sec at 54A µF 55.0 VAC 450 Crank case heater — Type Propeller Number ... Dia. mm 1 ... ø 400 Fan motor model ... Number Smen 19TFB6055 ... 1 Fan & Fan Motor No. of poles ... rpm (230 V, High) 6 ... 910 Nominal output W Coil resistance (Ambient temp. 20°C) Ω 43 WHT – BRN : 77.7 ± 7% WHT – YEL : 366.0 ± 7% WHT – PNK : 211.0 ± 7% Safety devices Type Operating temp. Thermal protector Open °C 130 ± 5 Close Heat Exch. Coil Run capacitor Automatic reclosing µF 2.0 VAC 440 Coil Aluminum plate fin / Copper tube Rows Fin pitch Face area 2 mm 1.8 m2 0.508 External Finish Acrylic baked-on enamel finish DATA SUBJECT TO CHANGE WITHOUT NOTICE. 11 Outdoor Unit Controller PCB AER518SCL3 Part No. POW-C181BL Control circuit fuse 250V – 5A Type Rotary (Hermetic) Compressor model C-2RN173H8W 80807088 380 – 400 V – 3N ~ 50 Hz Source Nominal output W 1,700 Compressor oil ... Amount cc FV68S ... 800 Coil resistance (Ambient temp. 25°C) Ω C – R : 6.369 Compressor C – S : 6.073 R – S : 6.217 Type Safety devices Overload relay Operating temp. HOE-10TB TH-5A °C Automatic opening — Close °C Automatic reclosing — — µF Run capacitor 5A — VAC — Crank case heater 240V 30W Type Propeller Q´ty ... Dia. mm 1 ... ø400 Fan motor model ... Q´ty SMEN 19 TFB6047 ... 1 220 – 230 V ~ 50 Hz Source No. of poles ... rpm (220 V, High) Fan & Fan Motor External protector — Open Operating amp.(Ambient temp. 25°C) 6 ... 910 Nominal output W Coil resistance (Ambient temp. 20°C) Ω 43 WHT – BRN : 83.4 WHT – PNK : 218.7 Safety devices Type Operating temp. Run capacitor Heat Exch. Coil Internal protector Internal type Open °C 130 ± 5 Close Automatic reclosing µF 2.0 VAC 440 Coil Aluminum plate fin / Copper tube Rows Fin pitch Face area 2 mm 1.8 m2 0.508 External Finish Acrylic baked-on enamel finish DATA SUBJECT TO CHANGE WITHOUT NOTICE. 12 Outdoor Unit AE518SH Controller PCB POW – C186GH Type Rotary (Hermetic) Compressor Compressor model SCI PH36VTRT Nominal output W Compressor oil ... Amount cc Coil resistance (Ambient temp. 20°C) Ω 1600 DIAMOND....900 C – R : 1.06 C – S : 2.03 Type Safety devices Internal protector Overload relay Operating temp. MRA-8967-9200 Open °C Close °C 160 ± 5 84± 11 Operating amp.(Ambient temp. 25°C) Run capacitor Trip in 6 to 16 sec. at 55 A µF 55.0 VAC 450 Crank case heater 240V 30W Type Propeller Number ... Dia. mm 1 ... ø 400 Fan motor model ... Number Smen 19TFB6055 ... 1 Fan & Fan Motor No. of poles ... rpm (230 V, High) 6 ... 900 Nominal output W Coil resistance (Ambient temp. 20°C) Ω 50 WHT – BRN : 77.7 ± 7% WHT – YEL : 366.0 ± 7% WHT – PNK : 211 ± 7% Safety devices Type Operating temp. Internal protector Open °C 130 ±8 Close Run capacitor Heat Exch. Coil External (OLR) Automatic reclosing µF 2.0 VAC 440 Coil Aluminum plate fin / Copper tube Rows Fin pitch Face area 2 mm 1.6 m2 0.453 External Finish Acrylic baked-on enamel finish DATA SUBJECT TO CHANGE WITHOUT NOTICE. 13 Outdoor Unit AE518SH3 380 - 400 V - 3N ~ 50 Hz 220 - 240 V ~ 50 Hz POW-C186GH Power source Control circuit CONTROLLER PCB COMPRESSOR Type Compressor model Source Nominal output Compressor oil ... Amount C-R C-S R-S Coil resistance (Ambient temp. 25°C) Safety devices: Type Overload relay Open Close Operating amp. (Ambient temp. 25°C) Operating temp. °C °C µF VAC Run capacitor Crank case heater FAN AND FAN MOTOR Type Number ... Dia. Fan motor model ... Number Source No. of poles ... rpm (220 V) Nominal output Coil resistance (Ambient temp. 20°C) Safety devices: W cc Ω Ω Ω mm WHT - BRN WHT - YEL WHT - PNK Type Operating temp. Open Close W Ω Ω Ω °C µF VAC Run capacitor HEAT EXCH. COIL Coil Rows Fin pitch Face area EXTERNAL FINISH mm m2 Rotary (Hermetic) C-R173H8M-806-389-88 380 - 400 V - 3N ~ 50 Hz 1700 SUNISO4CS ... 800 5,62 5,51 5,62 Internal protector External protector // HOE-10TB TH-7A 120 ± 5 // Automatic reclosing // // 5A // // 240 V - 30 W Propeller 1 ... Ø400 Smen 19TFB6055 ... 1 220 - 240 V ~ 50 Hz 6 ... 900 50 77,7 366,0 211,0 Internal protector 130 ± 8 Automatic reclosing 2 440 Aluminum plate fin / Copper tube 2 1,6 0,453 Acrylic baked-on enamel finish Data subject to change without notice. 14 Outdoor Unit AER518SH3 380 - 400 V - 3N ~ 50 Hz 220 - 240 V ~ 50 Hz POW-C186GH Power source Control circuit CONTROLLER PCB COMPRESSOR Type Compressor model Source Nominal output Compressor oil ... Amount C-R C-S R-S Coil resistance (Ambient temp. 25°C) Safety devices: Type Overload relay Open Close Operating amp. (Ambient temp. 25°C) Operating temp. °C °C µF VAC Run capacitor Crank case heater FAN AND FAN MOTOR Type Number ... Dia. Fan motor model ... Number Source No. of poles ... rpm (220 V) Nominal output Coil resistance (Ambient temp. 20°C) Safety devices: W cc Ω Ω Ω mm WHT - BRN WHT - YEL WHT - PNK Type Operating temp. Open Close W Ω Ω Ω °C µF VAC Run capacitor HEAT EXCH. COIL Coil Rows Fin pitch Face area EXTERNAL FINISH mm m2 Rotary (Hermetic) C-2RN173H8A 80242088 380 - 400 V - 3N ~ 50 Hz 1700 FV68S ... 800 5,62 5,51 5,62 Internal protector External protector // HOE-10TB TH-7A 120 ± 5 // Automatic reclosing // // 5A // // 240 V - 30 W Propeller 1 ... Ø400 Smen 19TFB6055 ... 1 220 - 240 V ~ 50 Hz 6 ... 900 50 77,7 366,0 211,0 Internal protector 130 ± 8 Automatic reclosing 2 440 Aluminum plate fin / Copper tube 2 1,6 0,453 Acrylic baked-on enamel finish Data subject to change without notice. 15 C OTHER COMPONENT SPECIFICATIONS Outdoor Unit AE518SC Power Relay G7L-2A-TUB Coil rating AC 200 – 240V, 50/60Hz Coil resistance kΩ (at 23°C) ( 21 ± 15% ) Contact rating AC 220V, 25A Thermostat (Fan Speed Control 23S) Switching temp. MQT5S-27YZJ °C Contact rating Outdoor Unit high ➞ LOW +0 23.5°C –2.5 low ➞ HIGH 27.0°C +0 –3 AC 220V, 3A AE518SC3 Negative Phase Relay (47C) RDR-S400 Rating AC 415V, 3-phase 50Hz Contact rating AC 400V, 1A Operation Positive phase: ON Negative phase: OFF Electro Magnetic Contactor (MG) HOE-10TB TH-5A Magnetic contactor Coil rating Coil resistance AC 220–240V, 50Hz / AC 240–260V, 60Hz Ω (at 25°C) 1,260 ± 10% Contact rating (Main) AC 440V, 8A Thermal relay (Overcurrent relay) MQT5S-27YZJ 5A Operating amperes 16 Outdoor Unit AER518SCL3 Thermistor (Coil sensor TH3 / Air sensor TH4) Resistance PBC-41E-S4 / PBC-41E-S8 kΩ –20°C 40.1 ± 5% –10°C 24.4 ± 5% 30°C 4.4 ± 5% 0°C 15.3 ± 5% 40°C 3.0 ± 5% 10°C Solid State Relay (SSR) 20°C 6.5 ± 5% 9.9 ± 5% 50°C 2.1 ± 5% G3L-205TL-TS1 Input Rated voltage DC 12V Control voltage range DC 0V to 6.4V Load voltage range AC 75V to 264V, 50Hz Negative Phase Relay (47C) RDR-S400 Rating AC 415V, 3-phase 50Hz Contact rating AC 400V, 1A Operation Positive phase: ON Negative phase: OFF Electro Magnetic Contactor (MG) HOE-10TB TH-5A Magnetic contactor Coil rating Coil resistance AC 220–240V, 50Hz / AC 240–260V, 60Hz Ω (at 25°C) 1,260 ± 10% Contact rating (Main) AC 440V, 8A Thermal relay (Overcurrent relay) MQT5S-27YZJ 5A Operating amperes Transformer (TR2) Rating ATR-J105-I Primary AC 230V, 50Hz Secondary 19V, 0.526A Capacity Coil resistance 10VA Ω (at 22°C) Thermal cut-off temp. 205 ± 10% 2.0 ± 10% 150°C Power Relay HH62S DC24V Coil rating Coil resistance Primary (WHT – WHT): Secondary (BRN – BRN): DC 24V kΩ (at 23°C) 650 ± 10% Contact rating AC 250V, 10A 17 Outdoor Unit AE518SH Power Relay (PR) DFU24D1-F Coil rating Coil resistance DC 24V Ω (at 20°C) 650 ± 10% Contact rating AC 250V, 20A Starting Relay (SR) AMVL300A Coil rating Coil resistance AC 300V, 50Hz kΩ (at 23°C) 13.3 ± 2% Contact rating 20A AC Operating voltage AC 185 – 217V, 50Hz Return voltage AC 60 – 120V, 50Hz Thermostat (Defrost thermo. 23D) Operating temp. TRS02-12MSR °C Thermostat (Fan Speed Control 23S) Switching temp. Diff. 8 deg. below high ➞ LOW °C 23.5°C ±1.5 +0 low ➞ HIGH 50Hz, 27.0°C AC 220-240V, 6W –3 Ω (at 20°C) AC 220V, 3A 1.740 ± 7% 4-way Valve (20S) LB64012 (Coil), V26-110B (Valve) Coil rating Coil resistance 12 ± 2 MQT5S-27YZJ Coil rating Contact rating Coil resistance ON AC 220-240V, 50Hz, 6W Ω (at 20°C) 1.740 ± 7% Starting Capacitor C4; C5 Capacitor 125 µF - 165V Resistor 18KΩ - 2W 18 Outdoor Unit AE518SH3 Electro Magnetic Contactor (MG) HOE-10TB TH-5A Magnetic contactor Coil rating Coil resistance AC 220–240V, 50Hz / AC 240–260V, 60Hz Ω (at 25°C) 1,260 ± 10% Contact rating (Main) AC 440V, 8A Thermal relay (Overcurrent relay) Operating amperes 5A Negative Phase Relay (47C) RDR-S400 Rating AC 415V, 3-phase 50Hz Contact rating AC 400V, 1A Operation Positive phase: ON Negative phase: OFF Relay (PR) MY2-TSDF Coil rating Coil resistance DC 24V Ω (at 20°C) 650 ± 10% Contact rating AC 200V, 5A 4-way Valve (SC) LB64012 (Coil), V26-110B (Valve) Coil rating Coil resistance AC 220/240V, 50Hz, 6W Ω (at 20°C) 1,740 ± 7% Thermostat (Defrost thermo. 23D) Operating temp. TRS02-12MSR °C Thermostat (Fan Speed Control 23S) Switching temp. ON 12 ± 2 Diff. 8 deg. below MQT5S-27YZJ °C high → LOW low → HIGH Contact rating 23.5°C ± 1.5 27.0°C +0 –3 AC 220V, 3A 19 Outdoor Unit AER518SH3 Electro Magnetic Contactor (MG) HOE-10TB TH-5A Magnetic contactor Coil rating Coil resistance AC 220–240V, 50Hz / AC 240–260V, 60Hz Ω (at 25°C) 1,260 ± 10% Contact rating (Main) AC 440V, 8A Thermal relay (Overcurrent relay) Operating amperes 5A Negative Phase Relay (47C) RDR-S400 Rating AC 415V, 3-phase 50Hz Contact rating AC 400V, 1A Operation Positive phase: ON Negative phase: OFF Relay (PR) MY2-TSDF Coil rating Coil resistance DC 24V Ω (at 20°C) 650 ± 10% Contact rating AC 200V, 5A 4-way Valve (SC) LB64012 (Coil), V26-110B (Valve) Coil rating Coil resistance AC 220/240V, 50Hz, 6W Ω (at 20°C) 1,740 ± 7% Thermostat (Defrost thermo. 23D) Operating temp. TRS02-12MSR °C Thermostat (Fan Speed Control 23S) Switching temp. ON 12 ± 2 Diff. 8 deg. below MQT5S-27YZJ °C high → LOW low → HIGH Contact rating 23.5°C ± 1.5 27.0°C +0 –3 AC 220V, 3A 20 D OPERATING RANGE Function Cooling Temperature INDOOR UNIT OUTDOOR UNIT Indoor air intake temp. Outdoor air intake temp. Maximum 35°C BS / 22.5°C BU 52°C BS Minimum 19°C BS / 14°C BU,5 19°C BS Referred to the systems - ADR518CW - AER518SCL3 only (3 phase and low ambient version) Function Cooling INDOOR UNIT OUTDOOR UNIT Indoor air intake temp. Outdoor air intake temp. Maximum 35°C BS / 22°C BU 50°C BS Minimum 19°C BS / 14°C BU,5 -15°C BS Temperature 21 6 125 Dimension: mm 120 175 4 - ø3.1 (HOLE) 8 107 7 15 25 665 (HOLE) 150 310 150 220 480 220 35 210 195 (SUSPENSION BOLT PITCH) 830 280 150 32 150 750 35 46 (OVERALL DIM.) 74 46 29 120 256 42 32 20 5 26 4 (OVERALL DIM.) 1 170 145 252 160 30 2 6 (HOLE) 2 - ø3.3 Refrigerant gas line (Wide tube - ø 12.70) Drain connection (outside diam. 32) Electrical junction box Mounting for suspention Duct connection for discharge (ø 200) Duct connection for suction Fresh air intake (ø 150) 3 4 5 6 7 8 Refrigerant liquid line (Narrow tube - ø 6.35) LEGEND 30 120 3 38 310 20 2 1 60 REMOTE CONTROL UNIT 285 692 20 8 - ø3,1 5 - ø3,3 (HOLE OPPOSITE SIDE) 590 38 13 107 (SUSPENSION BOLT PITCH) 20 22 200 665 100 15 50 117 200 E DIMENSIONAL DATA Indoor unit ADR518SW Outdoor Unit 538 146 337 307 Air intake 4 – ø12 holes Air discharge Wide tube service valve ø12.7 (1/2") Narrow tube service valve ø6.35 (1/4") 305 19 95 61 630 830 Unit : mm 23 F FUNCTION 1) ROOM TEMPERATURE CONTROL Cooling • Room temperature control is obtained by cycling the compressor ON and OFF under control of the room temperature sensor in the remote control unit. ROOM TEMPERATURE MORE THAN 5 MINUTES WITHIN 3 MINUTES WITHIN 5 MINUTES THERMO OFF SET T + 0,5 ϒC TEMPERATURE T ϒC THERMO ON THERMO OFF MORE THAN 5 MINUTES MORE THAN 3 MINUTES THERMO ON THERMO OFF 3 MINUTES 5 MINUTES COMPRESSOR ON OFF ON OFF ON OUTDOOR FAN ON OFF ON OFF ON INDOOR FAN SET SPEED (MANUAL) NOTA • The control circuit will not attempt to turn the compressor ON until the compressor has been OFF for at least 3 minutes. To protect the compressor from stalling out when trying to start against the high side refrigerant pressure, the control circuit has a built-in automatic time delay to allow the internal pressure to equalize. • As a protective measure, the control circuit switches the compressor OFF after 5 minutes or more of compressor operation. • Thermo ON: When the room temperature is above T + 1°C (T°C is set temperature). Compressor ➔ ON. • Thermo OFF: When the room temperature in equal to or below set temperature T°C. Compressor ➔ OFF. 24 Heating MORE THAN 5 MINUTES THERMO OFF THERMO ON THERMO OFF SET TEMP. T°C T-0.5°C ROOM TEMP. 5 MINUTES 5 MINUTES OFF ON OFF ON OFF OUTDOOR FAN OFF ON OFF ON OFF INDOOR FAN OFF COMPRESSOR 30 SECONDS LL SET SPEED LL ❆ STANDBY LAMP OFF ON 30 SECONDS SET SPEED ❆ OFF LL ❆ OFF ON ON INDOOR HEAT EXCH. COIL TEMP. 35°C 25°C SOLENOID COIL (4-WAY VALVE) OFF ON (REVERSING CYCLE) OPERATION BUTTON OFF ON ❆ COLD DRAFT PREVENTION L L = Low low speed • The control circuit will not attempt to turn the compressor ON until the compressor has been OFF for at least 5 minutes. To protect the compressor from stalling out when trying to start against the high side refrigerant pressure, the control circuit has a built-in automatic time delay to allow the internal pressure to equalize. • As a protective measure, the control circuit switches the compressor OFF after 5 minutes or more of compressor operation. • Thermo ON: when the room temperature is below T -1°C (T°C is set temperature). Compressor ➔ ON. • Thermo OFF: when the room temperature is equal to or above set temperature T°C. Compressor ➔ OFF. 25 2) FREEZE PREVENTION (COOLING) • This function prevents freezing of the indoor heat exchange coil. • When the compressor has been running for 10 minutes or more and the temperature of the indoor heat exchange coil falls below –1°C, the control circuit stops the compressor for at least 6 minutes. THERMO OFF THERMO ON ROOM TEMP. SET TEMP. T +0.5°C T°C INDOOR HEAT EXCH. COIL TEMP. AFTER 6 MINUTES 6 MINUTES –1°C MORE THAN 10 MINUTES MORE THAN 10 MINUTES OFF ON COMPRESSOR INDOOR FAN ON OFF ON SET SPEED ON SET SPEED 3) OVERLOAD PREVENTION (HEATING) • This function prevents overheating of the indoor heat exchange coil. For indoor units ADR518HW only INDOOR HEAT EXCH. COIL TEMP. °C 61 59 52 49 OUTDOOR FAN INDOOR FAN COMPRESSOR OFF ON HoMoL H ➔ H, ON M ➔ M, ON L ➔ M H = High speed M = Medium speed L = Low speed • When the temperature of the indoor heat exchange coil rises above 59°C, and if the indoor fan is L (low speed), then the fan speed changes from L (low speed) to M (medium speed). • When the temperature of the indoor heat exchange coil rises above 61°C, the outdoor fan stops. 26 4) DEFROSTING OPERATION (Heating) • When the capacity of the unit has been decreesed due to frosting up of the outdoor heat exchanger during heating, the temperature drop gradient is detected by the microcomputer-controlled temperature sensing system, and defrosting operation is started. DEFROSTING FLOWCHART Compressor ON A Temperature of indoor heat exchanger coil is lower than 45°C B C Integrated operating time of compressor is longer than 3 hours Integrated operating time of compressor is longer than 1.5 hours YES Temperature in indoor heat exchanger coil drops 0.8 deg/6 min. or more and repeats 3 times continuously. YES Thermo OFF (Compressor OFF) YES Compressor keeps running for 5 minutes Temperature of indoor heat exchanger coil is lower than 53°C. YES Integrated operating time of compressor is more than 20 minutes. YES YES Defrosting thermo in the outdoor unit is OFF. (Below 4°C) YES NO Thermo ON (Compressor ON) Defrosting begins. Cold-draft prevention. Defrosting time is over 11.5 minutes. Temperature of outdoor heat exchange coil is higher than 12°C. Release of defrosting. 27 5) DEFROSTING MODE TIMING CHART START OF DEFROSTING RELEASE OF DEFROSTING MAX. 11 MINUTES 32 SECONDS COMPRESSOR ON OUTDOOR FAN ON OFF ON 32 SECONDS OFF ON OFF ON 2 SECONDS SOLENOID COIL (4-WAY VALVE) INDOOR FAN 2 SECONDS ON OFF SET SPEED OFF STANDBY LAMP ON OFF ON LL ON SET SPEED OFF ON INDOOR HEAT EXCH. COIL TEMP. 35°C RELEASE OF COLD DRAFT PREVENTION L L = Low low speed 6) OUTDOOR FAN SPEED CONTROL (COOLING) • To optimize performance of the air conditioner, the outdoor fan speed is switched automatically according to the outdoor temperature. • If the outdoor air temperature falls below 28.5°C, the fan speed switches to LOW. • If the outdoor air temperature rises above 31.5°C for 5 minutes or longer, the fan speed switches to HIGH. • This function does not become active in heating operation. 31,5 OUTDOOR AIR TEMPERATURE (°C) OUTDOOR FAN SPEED 28,5 H L H = High speed L = Low speed 28 H 3) For AER518SCL3 only (3 phase and low ambient version) • When the outside ambient temperature decreases, the rotation speed of the outdoor fan is regulated by means of the outdoor heat-exchanger sensor to prevent liquid back. • The rotation speed varies with indoor temperature conditions (Hatching area). • The unit is protected against high pressure by means of the outside temperature sensor, and thus when the outside ambient temperature reaches 30°C respectively, the fan speed is forced to high. CONDITIONS: ROOM TEMPERATURE 19,4°C DB / 13,9°C WB 220V - 50 HZ 1000 ▲ ▲ ▲ 600 ▲ 400 ▲ ▲ ROTATION SPEED OF FAN (rpm) ▲ 800 ▲ 900 rpm 200 0 -10 -5 0 5 10 15 20 OUTDOOR AMBIENT TEMPERATURE (°C) 29 25 30 35 G REFRIGERANT FLOW DIAGRAM COOLING MODE Indoor unit Outdoor unit HEAT PUMP MODE Indoor unit Outdoor unit 30 WARNING WARNING ELECTRIC WIRING DIAGRAMS ADR518CW TP1 BLK BLK 1 WHT 2 GRN/YEL ORG 4 E RED RY BRN GRY 9 9 GRY 8 8 WHT 7 7 VLT 6 6 ORG 5 5 YEL 4 4 BLK 3 3 BRN 2 2 PNK 1 1 GRY GRY 1 1 2 2 VLT ORG YEL BLK 6 5 4 3 2 1 BLK BLK 1 2 3 4 1 2 3 4 1 1 2 2 UNIT TH2 (ROOM) 12P PNK BRN BRN 6 5 4 3 2 1 VLT ORG YEL BLK BRN TH1 (COIL) WHT TH 1 1 2 2 WHT SUP 1 1 BODY THERMO 2 2 4 9 1 12 FMI BLK BLK 1 1 WHT PR 2 2 WHT TR 235V P-C C1 FMI PCB1 GRN/YEL 19V GRN/YEL S-0 E LFS BLK 1 1 BLK 2 2 BLK BLK 1 2 FS GRN/YEL DP E BLK 1 1 BLK 2 2 BLU WHT DP1 DP2 REMOCON2 REMOCON1 BLK SEC 1 1 2 2 BRN 1 1 SS 5 5 E REMOTE CONTROL SWITCH 1 1 SS 12 12 ADR518HW 19V S-O E 1 1 BLU 2 2 WHT DP1 DP2 1 FS 2 BLK BLK 1 1 BLK 2 2 BLK BLK BLK C1 DP E GRN/YEL LFS E GRN/YEL FMI GRY GRY WHT VLT ORG YEL BLK BRN PNK 12 12 1 1 SS 1 1 SS 5 5 BLK BRN 1 1 SEC 2 2 PCB1 1 1 VLT ORG YEL BLK BRN REMOTE CONTROL SWITCH P-O 235V 2 2 BLK BLK 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 BRN 1 GRY GRY 1 1 2 2 12P 1 1 BODY 6 6 VLT 4 THERMO 2 2 5 5 ORG 9 4 4 YEL 1 3 3 BLK 12 1 1 PR FMI 2 2 BRN WHT WHT TR TH2 (ROOM) TH1 (COIL) TH UNIT 1 1 2 2 1 2 3 4 1 2 3 4 1 1 2 2 WHT WHT BLK WHT GRN/YEL BRN RED ORG YEL E SUP BLK 1 2 4 5 6 7 PNK 31 REMOCON2 REMOCON1 TP1 GRN/YEL H To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts Outdoor Unit AE518SC AE518SC3 WARNING 34 To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts Outdoor Unit AER518SCL3 WARNING 33 To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts Outdoor Unit AE518SH WARNING 34 To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts Outdoor unit AE518SH3 To avoid electrical shock hazard, be sure to WARNING disconnect power before checking, servicing and/or cleaning any electrical parts. 35 Outdoor unit AER518SH3 To avoid electrical shock hazard, be sure to WARNING disconnect power before checking, servicing and/or cleaning any electrical parts. 36 I TROUBLESHOOTING (cooling model) 1) CHECK BEFORE AND AFTER “TROUBLESHOOTING” a) Check power supply wiring. • WARNING: If the following troubleshooting must be done with power being supplied, be careful about any uninsulated live part that can cause ELECTRIC SHOCK. b) Check inter-unit wiring. • Check that inter-unit wiring (both the power wiring and control wiring) is correctly connected to the indoor unit from the outdoor unit. OUTDOOR UNIT ADR518CW- AE518SC POWER SUPPLY 50 Hz - Single-phase 220/230/240 V POWER SUPPLY GROUND INTER-UNIT WIRING ➀ ➁ ➂ ➃ ➀ ➁ ➂ ➃ ➄ OUTDOOR UNIT ADR518CW- AER/AE518SCL3 POWER SUPPLY 50 Hz - 3-phase 400V 4 Wires GROUND POWER SUPPLY L1 L2 L3 N INDOOR UNIT INDOOR UNIT INTER-UNIT WIRING ➀ ➁ ➂ ➃ ➄ ➅ ➆ ➇ ➀ ➁ ➂ ➃ ➄ ➅ ➆ ➇ (c) Check power supply • Check that voltage is in specified range (± 10% of the rating). • Check that power is being supplied Single-phase systems Three-phase systems L L1 400V 400V L2 230V 400V L3 N N 37 230VV 2) SYSTEMATIC CHART OF “TROUBLESHOOTING” Air conditioner does not operate. Circuit breaker trips (or fuse blows). Neither indoor unit nor outdoor unit runs. When circuit breaker is set to ON, it trips in a few moments. Measure insulation resistance of power supply wires. Circuit breaker trips in several minutes after turning air conditioner ON. Check capacity of circuit breaker. Meaure resistance of electrical components. Power is not supplied. Check power supply. Function of compressor winding protection works. Indoor unit sensor are defective. Open or short circuit. 38 Limit float switch has operated “OPEN”. Check drain pump and drain hose. Indoor unit installed upside - down. Reposition the indoor unit. 3) AIR CONDITIONER DOES NOT OPERATE (a) Circuit breaker trips (or fuse blows) • When circuit breaker is set to ON, it trips in a few moments. (Resetting is not possible). • Measure insulation resistance there is a possibility of ground fault. If resistance value is 1MΩ or less, insulation is defective. ADR518CW - AE518SC a Circuit breaker b Unità esterna Outdoor unit x x 3 4 5 6 7 8 z Power supply ADR518CW- AER/AE518SCL3 Power sypply Circuit breaker L1 L2 L3 N 5 6 7 8 Indoor unit d 1 x 2 x z 4 x 5 x 1 x 2 z x 4 5 Inter-uni wiring Ground a Unità esterna c Unità esterna b Unità esterna x x x x 5 6 z7 Outdoor unit 5 6 7 8 1 c Unità esterna Indoor unit d x x x x 2 x z 4 x x 1 2 z x 4 Inter-unit wiring 8 Ground • Set circuit breaker to OFF. ➀ • ➁ • ➂ • ➃ Remove power supply wires from terminal plate in outdoor unit. Measure insulation resistance of power supply wires. OK Do rewiring Remove inter-unit wires from terminal plate in outdoor unit. Measure insulation resistance of outdoor unit. Insulation of outdoor unit is defective. YES Measure insulation resistance of electrical parts in outdoor unit. Remove inter-unit wires from terminal plate in intdoor unit. Measure insulation resistance of intdoor unit. Insulation of indoor unit is defective. YES Measure insulation resistance of electrical parts in indoor unit. Measure insulation resistance of inter-unit wires. OK Do rewiring. 38 (b) Circuit breaker trips in several minutes after turning air conditioner ON. • There is a possibility of short circuit. Check capacity of circuit breaker. Capacity of circuit breaker is suitable? NO Replace it with suitable one. (larger capacity). YES Measure resistance of compressor motor winding. OK Measure resistance of outdoor fan motor winding. Outdoor unit AE518SC3 AER518SCL3ONLY Measure coil resistance of magnetic contactor. (MG or 52C) OK (c) Neither indoor unit nor outdoor unit runs Check power supply. Is power being supplied to wall receptacle? Circuit breaker is tripped. Reset the breaker. Power failure. Wait for recovery or contact power company. NO Leds of remote control unit are light Check is drain flow prevented? YES Check drain hose. NO Check if the drain pump is working. Measure resistance of drain pump motor winding. NO Replace drain pump. YES Check function of limit float switch. Float in high position: open circuit. Float in down position: short circuit. (Normal condition) NO Replace limit float switch. YES Check installation of indoor unit is it installed upside - down? YES 40 Reposition the indoor unit. (d) Check fuse on PCB Ass’y in indoor unit Check fuse on PCB Ass’y in indoor unit for continuity. (F) If fuse blows, there is a possibility of short circuit. Measure resistance of primary winding of transformer. (TR) Measure coil resistance of power relay or magnetic contactor in outdoor unit. (PR - MG - 52C) OK Measure resistance of indoor fan motor winding. (FMI) OK OK Measure resistance of drain pump winding. e) PCB Ass’y in indoor unit is defective. Check transformer in indoor unit Check whether transformere is detective. Measure resistance of primary and secondary winding. (TR) f) Check indoor fan motor protector Wait for 30 minutes and then try to run. Air conditioner starts running. Air conditioner does not run again. Indoor fan motor internal protector trips. Check fan rotation. Turn fan gently once or twice by hand. Fan cannot be turned Check fan casing for foreign matter on inside. Remove foreign matter or repair. Fan motor burnout or foreign matter in bearing. Repair or replace. 4) ONLY OUTDOOR UNIT DOES NOT RUN a) Outdoor unit does not run when air conditioner is in following conditions. • During thermo OFF. • During freeze prevention (for at least 6 minutes). • During drain pump works (for at least 12 minutes). b) PCB Ass’y in indoor unit is defective. 39 • Check power relay in outdoor unit (only for AE518SC) • Check coil resistance of power relay. OK • PCB Ass’y defective. • Check negative phase relay (only for AE518SC/SCL3-AER/AE518SH3) • Check negative phase relay to see if it has operated. (47C) YES • Rewire power supply wires. 5) COMPRESSOR MOTOR DOES NOT RUN (only for AE518SC) a) Single phase systems 230V - 1 - 50 Hz • Check compressor motor capacitor. (C1) • Check overload relay and/or compressor motor internal protector. (OLR - 49C) OK It has tripped • Measure resistance of compressor motor winding. • Is outdoor heat exchanger coil dirty or are there obstacles near air suction inlet of outdoor unit? NO • Check power supply voltage. Is voltage abnormally low? NO • Is temperature of compressor abnormally high? YES • Refrigerant gas shortage. 42 b) Three - phase systems 400V - 3N - 50 Hz • Measure resistance of compressor motor winding. Is temperature of compressor abnormally high? YES Is outdoor heat exchanger coil dirty or are there obstacles near air suction inlet? NO Refrigerant gas shortage. YES YES Clean heat exchanger or remove obstacles. Charge refrigerant gas. • Check compressor motor overcurrent relay (51C). It’s operated • Check power supply voltage. Is voltage abnormally low? NO 90% or more of rated voltage • Check compressor. There is a possibility of locked rotor. 43 L SOME PARTS OF AIR CONDITIONER DO NOT OPERATE 1) ONLY INDOOR FAN DOES NOT RUN Check fan rotation. Turn fan gently once or twice by hand. Fan cannot be turned Fan turn normal Check fan motor capacitor. NO Check fan casing for foreign matter on inside. Remove foreign matter or repair. Fan motor burnout or foreign matter in bearing. Repair or replace. Replace capacitor. OK Measure resistance of fan motor winding. NO Replace fan motor. OK Check output of fan motor terminals on PCB Ass’y. 2) FUNCTION OF OUTDOOR FAN SPEED CONTROL DOES NOT WORK PROPERLY (only for SAP-C188E5) • Check thermostat in outdoor unit. (23S) 3) Only for low ambient version units (AE518SCL3) • Check electronic fan speed regulator (SSR) ONLY OUTDOOR FAN DOES NOT RUN Check fan rotation. Turn fan gently once or twice by hand. Fan cannot be turned. Check fan casing for foreign matter on inside. Remove foreign matter or repair. Fan motor burnout or foreign matter in bearing. Repair or replace. Measure the resistance of outdoor fan motor winding. OK OK Check fan motor capacitor. 44 Defrost controller (POW-C92 GH) is defective in outdoor unit. M AIR CONDITIONER OPERATES, BUT ABNORMALITIES OCCUR a) POOR COOLING Check installation position of remo- YES Change installation position of te control unit. remote control unit. Does cool air from air conditioner reach position directly? Is cooling load too large? Review cooling load estimate. Refrigerant flow failure Temperature diffeMeasure temperatures of rence is small Possibility of suction and discharge air gas shortage. of air conditioner. Charge refrigerant gas (R22 R407C) Temperature difference between suction and discharge air is large enough (approx. 10°C or more). Air filter is clogged Check for clogging of air filter. Air circulation is a little b) Clean filter Refrigerant gas shortage. Charge refrigerant gas. Compressor is defective. Replace. Service valves are not fully open. Open the valves fully. Air filter is clogged. Clean filter in the air intake grille. Is fan speed set to LOW? Set the fan speed to either MEDIUM or HIGH. Long extension of ducts. Use the booster cable. Refrigerant tubes between indoor and outdoor units are not insulated. Insulate wide and narrow tubes separately. Excessive cooling Is remote control unit installed at a place where it can detect room temperature properly! NO 45 Change installation position of remote control unit. N TROUBLESHOOTING (HEATING MODEL) 1) CHECK BEFORE AND AFTER “TROUBLESHOOTING” a) Check power supply wiring. • WARNING: If the following troubleshooting must be done with power being supplied, be careful about any uninsulated live part that can cause ELECTRIC SHOCK. • Check that power supply wires are correctly connected to terminals: Single-phase system –No. 1 and No. 2 on the terminal plate in the outdoor unit. Three-phase system – A D R 5 1 8 H W / A E 5 1 8 S H - No. 1, 2, on the terminal plate in the outdoor unit. – ADR518HW / AE/AER518SH3 - No. 8, 9, 10 and 11 on terminal plate in the outdoor unit. b) Check inter-unit wiring. • Check that inter-unit wiring (both the power wiring and control wiring) is correctly connected to the indoor unit from the outdoor unit. ADR518HW - AE518SH POWER SUPPLY 50 Hz - Single-phase 220/230/240 V OUTDOOR UNIT POWER SUPPLY GROUND a b c d e f g INTER-UNIT POWER WIRING INDOOR UNIT a b c d e f g GROUND INTER-UNIT CONTROL WIRING ADR518HW - AE/AER518SH3 POWER SUPPLY 50 Hz - 3-phase 400V 4 Wires OUTDOOR UNIT GROUND L1 POWER SUPPLY L2 L3 N a b c d e f g h i j k l INTER-UNIT POWER WIRING INDOOR UNIT GROUND INTER-UNIT CONTROL WIRING 46 a b c d e f g (c) Check power supply • Check that voltage is in specified range (± 10% of the rating). • Check that power is being supplied Single-phase systems Three-phase systems L L1 400V 220V L2 400V 400V N L3 N (d) Check lead wires and connectors in indoor and outdoor units. • Check that coating of lead wires is not damaged. • Check that lead wires and connectors are connected firmly. • Check that wiring is correct. 47 230 V 2) SYSTEMATIC CHART OF “TROUBLESHOOTING” Air conditioner does not operate. Circuit breaker trips (or fuse blows). Neither indoor unit nor outdoor unit runs. When circuit breaker is set to ON, it trips in a few moments. Measure insulation resistance of power supply wires. Circuit breaker trips in several minutes after turning air conditioner ON. Check capacity of circuit breaker. Meaure resistance of electrical components. Power is not supplied. Check power supply. Function of compressor winding protection works. Indoor unit sensor are defective. Open or short circuit. 48 Limit float switch has operated “OPEN”. Check drain pump and drain hose. Indoor unit installed upside - down. Reposition the indoor unit. 3) AIR CONDITIONER DOES NOT OPERATE (a) Circuit breaker trips (or fuse blows) • When circuit breaker is set to ON, it trips in a few moments. (Resetting is not possible). • Measure insulation resistance there is a possibility of ground fault. If resistance value is 1MΩ or less, insulation is defective. Inter-unit power wiring ADR518HW- AE518SH a Unità esterna Power supply Circuit breaker Outdoor unit 1 2 3 4 5 6 7 x x 3 4 z56 Ground 7 8 b c Unità esterna d Indoor unit x 1 x 2 3 x 4 x 5 x 6 x 7 x x x x x x Inter-unit control wiring Inter-unit power wiring ADR518CW - AE/AER518SH3 a b Outdoor unit 1 x 2 x 3 4 x 5 x 6 x 7 x z Ground Power supply L1 Unitx L2 x x x L3 Circuit breaker N 8 9 10 11 12 Unità esterna 8 49 c Indoor unit Unità esterna d x 1 x 2 3 x 4 x 5 x 6 x 7 Inter-unit control wiring • Set circuit breaker to OFF. ➀ • ➁ • ➂ • ➃ Remove power supply wires from terminal plate in outdoor unit. Measure insulation resistance of power supply wires. OK Do rewiring Remove inter-unit wires from terminal plate in outdoor unit. Measure insulation resistance of outdoor unit. Insulation of outdoor unit is defective. YES Measure insulation resistance of electrical parts in outdoor unit. Remove inter-unit wires from terminal plate in intdoor unit. Measure insulation resistance of intdoor unit. Insulation of indoor unit is defective. YES Measure insulation resistance of electrical parts in indoor unit. Measure insulation resistance of inter-unit wires. OK Do rewiring. 50 (b) Circuit breaker trips in several minutes after turning air conditioner ON. • There is a possibility of short circuit. Check capacity of circuit breaker. Capacity of circuit breaker is suitable? NO Replace it with suitable one. (larger capacity). YES In case of Heating operation: Measure resistance of 4-way valve’s winding. (20S or SC). Measure resistance of outdoor fan motor winding. OK Measure resistance of indoor fan motor winding. OK (c) Neither indoor unit nor outdoor unit runs (leds of remote control unit are light) Check power supply. Is power being supplied to wall receptacle? Check is drain flow prevented? Circuit breaker is tripped. Reset the breaker. Power failure. Wait for recovery or contact power company. NO YES Check drain hose. NO Check if the drain pump is working. Measure resistance of drain pump motor winding. NO Replace drain pump. YES Check function of limit float switch. Float in high position: open circuit. Float in down position: short circuit. (Normal condition) NO Replace limit float switch. YES Check installation of indoor unit it is installed upside - down? YES 51 Reposition the indoor unit. (d) Check fuse on PCB Ass’y in indoor unit Check fuse on PCB Ass’y in indoor unit for continuity. If fuse blows, there is a possibility of short circuit. Measure resistance of primary winding of transformer. Measure coil resistance of power relay or magnetic contactor in outdoor unit. OK Measure resistance of indoor fan motor winding. OK OK Measure resistance of drain pump winding. e) PCB Ass’y in indoor unit is defective. Check transformer in indoor unit Check whether transformere is detective. Measure resistance of primary and secondary winding. f) Check indoor fan motor protector Wait for 30 minutes and then try to run. Air conditioner starts running. Air conditioner does not run again. Indoor fan motor internal protector trips. Check fan rotation. Turn fan gently once or twice by hand. Fan cannot be turned Check fan casing for foreign matter on inside. Remove foreign matter or repair. Fan motor burnout or foreign matter in bearing. Repair or replace. 4) ONLY OUTDOOR UNIT DOES NOT RUN a) Outdoor unit does not run when air conditioner is in following conditions. • During thermo OFF. • During freeze prevention (for at least 6 minutes). • During drain pump works (for at least 12 minutes). b) PCB Ass’y in indoor unit is defective. 52 O SOME PARTS OF AIR CONDITIONER DO NOT OPERATE 1) ONLY INDOOR FAN DOES NOT RUN Check fan rotation. Turn fan gently once or twice by hand. Fan cannot be turned Fan turn normal Check fan motor capacitor. NO Check fan casing for foreign matter on inside. Remove foreign matter or repair. Fan motor burnout or foreign matter in bearing. Repair or replace. Replace capacitor. OK Measure resistance of fan motor winding. NO Replace fan motor. OK Check output of fan motor terminals on PCB Ass’y. 2) ONLY OUTDOOR FAN DOES NOT RUN Check fan rotation. Turn fan gently once or twice by hand. Fan cannot be turned. Check fan casing for foreign matter on inside. Remove foreign matter or repair. Fan motor burnout or foreign matter in bearing. Repair or replace. Measure the resistance of outdoor fan motor winding. OK OK Check fan motor capacitor. 53 Defrost controller (POW-C92 GH) is defective in outdoor unit. 3) ONLY COMPRESSOR DOES NOT RUN a) Single phase systems 230V - 1 - 50 Hz Measure resistance of compressor motor winding. OK Check compressor motor capacitor. (Either C1 or BC). OK Check power supply voltage. Voltage is abnormally low. NO Contact power utility company to have power voltage restored to normal YES 90% or more of rated voltage. Check compressor. There is a possibility of locked rotor. Either overload relay or internal protector is working. (Either OLR or 49C). YES Temperature of compressor is abnormally high. YES Outdoor unit SAP-C188EH5 Measure coil resistance of starting relay (SR) and OK power relay (PR). Refrigerant gas shortage. YES Charge refrigerant gas (R22). YES Replace compressor. NO Rotor may be locked up. 54 b) Three-phase systems 400V - 3N - 50 Hz Check negative phase relay (47C) to see if it has operated. YES Rewire power supply wires. NO Check magnetic contactor. (MG) O.K. Check thermal relay (51C) to see if it has operated. YES Check power supply voltage. Voltage is abnormally low. NO Contact power utility company to have power voltage restored to normal YES 90% or more of rated voltage. Check compressor. There is a possibility of locked rotor. Check compressor motor internal protector. (49C) Temperature of compressor is abnormally high. YES Refrigerant gas shortage. NO Compressor is defective. 55 Charge refrigerant gas. P AIR CONDITIONER OPERATES, BUT ABNORMALITIES OCCUR a) POOR COOLING OR POOR HEATING Refrigerant flow failure Check installation position of YES Change installation position of remote control unit. remote control unit. Does cool or heat air from air conditioner reach position directly? Is heating or cooling load too large? Review heating or cooling load estimate. 4 way valve is defective. Replace. Temperature Measure temperatures of difference is small Possibility of suction and discharge air gas shortage. of air conditioner. Charge refrigerant gas (R22 or 407c) Temperature difference between suction and discharge air is large enough (approx. 10°C or more). Air filter is clogged Check for clogging of air filter. Refrigerant gas shortage. Charge refrigerant gas. Compressor is defective. Replace. Service valves are not fully open. Open the valves fully. Air filter is clogged. Clean filter in the air intake grille. Is fan speed set to LOW? Set the fan speed to either MEDIUM or HIGH. Long extension of ducts. Use the booster cable. Refrigerant tubes between indoor and outdoor units are not insulated. Insulate wide and narrow tubes separately. Cold air is discharged 4 way valve is defective. Replace. Cold draft prevention is mal function “STANDBY” is displayed. Replace P.C.B. Ass’y in the indoor unit. Indoor coil sensor is defective. Replace. Air circulation is a little b) Clean filter Excessive cooling or heating Is remote control unit installed at a place where it can detect room temperature properly! NO 56 Change installation position of remote control unit. Q IF A SENSOR IS DEFECTIVE Indoor coil temp. thermistor (TH) is defective. Open When thermistor opens, the air conditioner will be in the following conditions as the controller tries to detect extremely low indoor coil temperature. IN COOLING MODE - Function of freeze prevention continues to work. That is the controller turns both compressor and outdoor fan motor periodically ON and OFF for several minutes. Short When thermistor is short, the air conditioner will be in the following conditions as the controller tries to detect extremely high indoor coil temperature. IN COOLING MODE - Function of freeze prevention will not work even when the frost builds up on indoor heat exchanger coil. Room temp. thermistors are defective (BTH and RTH). Open When thermistor opens, the air conditioner will be in the following conditions as the controller tries to detect extremely low room temperature. IN COOLING MODE - The air conditioner soon stops and will not start again. (Thermo. OFF). Neither outdoor fan nor compressor runs. Short When thermistor is short, the air conditioner will be in the following conditions as the controller tries to detect extremely high room temperature. IN COOLING MODE - The air conditioner continues to operate. (Thermo. ON). Both the outdoor fan and compressor do not stop. As a result, the room becomes too cold. NOTE Thermistor Structure Definition of Open or Short Circuit of Sensor (Thermistor) OPEN - A lead wire is broken or disconnected or the circuit inside the temperature sensor is open. SHORT - The protective cover of a lead wire has been damaged, and the exposed wire is touching another metal part, or both lead wires have become exposed and are touching each other. Alternatively, the circuit inside the temperature sensor is closed. 57 S CHECKING ELECTRICAL COMPONENTS 1) Measurement of Insulation Resistance • The insuration is in good condition if the resistance exceeds 1 MΩ. (a) Power Supply Wires Clamp the earthed wire of the power supply wires with the lead clip of the insulation resistance tester and measure the resistance by placing a probe on either of the power wires (Fig. 1). Then measure the resistance between the earthed wire and the other power wires (Fig. 1). (b) Indoor Unit Clamp an aluminium plate fin or copper tube with the lead clip of the insulation resistance tester and measure the resistance by placing a probe on ➀, and then ➁ on the terminal plate (Fig. 2). (c) Outdoor Unit Clamp a metallic part of the unit with the lead clip of the insulation resistance tester and measure the resistance by placing a probe on ➀, and then ➁ on the terminal plate (Fig. 2). (d) Measurement of Insulation Resistance for Electrical Parts Disconnect the lead wires of the disired electric part from terminal plate, PCB Ass’y, capacitor, etc. Similarly disconnect the connector. Then measure the insuration resistance. (Fig. 1 to 4). Refer to Electric Wiring Diagram. If the probe cannot enter the poles because the hole is too narrow then use a probe with a thinner pin. 58 2) Checking Continuity of Fuse on PCB Ass’y • Remove PCB Ass’y from electrical component box. Then pull out the fuse from PCB Ass’y (Fig. 5). • Check continuity of fuse by the multimeter (Fig. 6). 3) Checking Motor Capacitor Remove the lead wiers from the capacitor terminals, and then place a probe on the capacitor terminals as shown in Fig. 7. Observe the deflection of the pointer, setting the resistance measuring range of the multimeter to the maximum value. The capacitor is “good” if the pointer bounces to a great extent and then gradually returns to its original position. The range of deflection and deflection time deffer according to capacity of the capacitor. 59 Tel. +39 0331 755111 - Fax +39 0331 776240 www.argoclima.it Printed in italy Via Varese, 90 - 21013 Gallarate - Va - Italy