Split System Submittal Data
System: 36XW72R
Indoor/Outdoor: XHW3672R/C3672R
Grille: PNR-XH3642
Ceiling Recessed Air Conditioner
Job Name:
Location:
Engineer:
Submitted to:
Submitted by:
Reference:
Power
Circuit Ampacity
Fuse Size, Max.
Compressor
No. used
R.L. Amps - L.R.
Outdoor Unit
Fan type
Dia. (in.) - No. Speeds
Type Drive - No. Speeds
No. Poles
No. Motors
CFM
F.L. Amps
Coil Type
Fin Type - Pipe Type
Rows - F.P.I.
Face Area
Tube Size
Approval:
Date:
Construction:
Unit #:
Drawing #:
General Data (at 230V)
V/PH/Hz
230/208/1/60
(A)
15-35 Indoor-Outdoor
(A)
15-35 Indoor-Outdoor
DC Motor
1
16.4-17.5
(A)
Propeller
18-7/64-1
Direct Inverter
8 - 830
1 - 90
1942
17.3
(RPM)
(W)
(High)
(A)
(sq.ft.)
(in.)
Aluminum Fin & Copper Pipe
Slit Plate - Inner Rifed
2 - 14.1
7.26
3/8”
Refrigerant
Lbs. - R410a (outdoor unit)
Control
Connection
Line Length, Max (ft.)
Lift Difference, Max (ft.)
Line Size
Line Size
Dimensions
Indoor Unit
Outdoor Unit
Weight
Net
Shipping
Shipping Volume
Indoor Unit
Fan type
Dia. & Length (in.) - No. Speeds
No. Speeds
(RPM, High)
No. Poles
(W)
No. Motors
(HI/Med/Lo)
CFM
Indoor Sound Rating
(Hi) (dB-A)
(A)
F.L. Amps
Coil Type
Fin Type - Pipe Type
Rows - F.P.I.
Face Area
Tube Size
Drain Connection Size
Turbo
17-7/16-1
3 & Auto
6-467
1 - 60
1050/840/720
44
0.9
Aluminum Plate Fin & Copper Tube
Slit Plate - Inner Rifed
2-14.9
(sq.ft.)
8.2
(in.)
9/32”
(in.)
1-17/64
R410A
6.17
Electric Expansion Valve
Flare
165
50 (outdoor lower), 100 (outdoor higher)
(in. O.D. Discharge)
3/8”
(in. O.D. Suction)
5/8”
(in.)
(Uncrated)
(Crated)
(Uncrated)
(Crated)
(lbs.)
(lbs.)
(cu.ft.)
HxWxD
14-31/64 x 45-9/32 x 33-55/64
12-13/32 x 44-19/64 x 33-9/32
30-23/32 x 37 x 13-3/8
34-31/32 x 39-31/32 x 16-3/32
Indoor
60
71
Outdoor
143
161
Indoor
10.6
Outdoor
13.0
Performance Data @ ARI Standard Conditions (230/208V)
Cooling
Total Capacity
(BTU/H)
32,600 (9,500-32,600)
Sensible Capacity
(BTU/H)
20,160
Latent Capacity
(BTU/H)
12,440
SEER
14.6
Dehumidification
(Pints/H)
10.6
(A)
18.7/20.7
Amps
(W)
3,950/3,950
Power Inputs
Outdoor Sound Rating
(dB-A)
52
Dimensions
Features
Options
ControlsDimensional Data for 36X72R
Microprocessor Refrigerant Line Set
unit : XH3672R
Remote Indoor
Controller
LCD Wired Type, Temp. Sensor Built In Fresh Air Intake
Temperature Control
IC Thermostat Airduct Extension
Timer
72 Hr. ON/OFF Condensate Drain Pump
Night Setback
Built-In Wireless Remote Controller
Air Louver
(Horizontal)
Manual Non-Removeable Locking Remo-con Bracket
(Vertical)
Automatic
Power Failure Automatic Restart
Built-In Operating Range
Self-Diagnosis
Indoor Air Intake Temp.
Built-In
Dimensional
Data
for
36X72R
Air Filter
Maximum
95F
DB/71F WB
Washable, Anti-Mold Cooling
Indoor unit : XH3672R
Minimum
67F DB/57F WB
Sanyo Commercial Solutions
A Division of SANYO North America
1300 Michael Drive
Wood Dale, IL 60191 USA
www.sanyohvac.com
Available
Available
Knock-out
Standard
Available
Available
Outdoor Air Intake Temp.
109F DB