Download Fedders C10 User's Manual

Transcript
Residential & Light Commercial HVAC
C10
High Efficiency Series
10 SEER Remote Condensing Units
PERFORMANCE:
Efficiency rating of 10.0 SEER
Cooling capacities from 11⁄2 to 5 tons
Rated in accordance with D.O.E. test standards
FEATURES:
Quiet, top air discharge
G-90 galvanized steel exterior cabinet with
1000-hour salt spray, powder-coated finish
Long-life copper tubes, aluminum fin refrigerant coils
State-of-the-art compressors
Powder-coated fan guard
Full louvered panel to protect coil
Large wrap-around coil surface
Control box located for easy access to electrical controls
Formed base with 21⁄2” ground clearance
Factory-installed liquid line filter dryer
WARRANTY:
Limited 10-year warranty on compressor
Limited 5-year warranty on all parts
C10 High Efficiency Series
MODEL SPECIFICATIONS
MODEL NUMBER
C1018BBD1VF
C1024BBD1VF C1030BBD1VF C1036BBD1VF C1036BBD3VF
PERFORMANCE DATA
NOMINAL COOLING BTU/H
18 000
22 400
28 600
34 000
SEER BTU/H-W
10.0
10.0
10.0
10.0
CFM
600
800
1000
1200
VOLTS/HZ/PHASE
208-230/60/1
208-230/60/1
208-230/60/1
208-230/60/1
208-230/60/3
VOLTAGE RANGE
197-253
197-253
197-253
197-253
187-253
OPERATING CURRENT AMPS
➀
9.8
10.8
11.4
17.0
12.7
MIN. WIRE AMPACITY
13.0
14.5
20.0
21.7
16.0
MAX. HACR BREAKER
➁
20
20
30
30
25
COMPRESSOR DATA
RLA
8.8
9.8
11.4
15.2
10.9
LRA
49
60
75
96
70
FAN DATA
DIAMETER
18 INCH / 3 BLADE
18 INCH / 3 BLADE
18 INCH / 3 BLADE
18 INCH / 3 BLADE
MOTOR TYPE
PSC
PSC
PSC
PSC
HP (W) / FLA
1/6 / 1.0
1/6 / 1.0
1/6 / 1.0
1/6 / 1.0
RPM
1075
1075
1075
1075
CFM
1800
1800
1800
1800
OUTDOOR COIL
TYPE
ENHANCED ALUMINUM PLATE FIN / RIFLED COPPER TUBE
FACE AREA
8.0
8.0
8.0
9.8
O.D. / F.P.I.-ROWS
5/16 / 18-1
5/16 / 22-1
3/8 / 22-1
3/8 / 18-1
REFRIGERANT LINE CONNECTIONS (SERVICE VALVE PORT I.D.)
LIQUID
3/8 ID
3/8 ID
3/8 ID
3/8 ID
VAPOR
3/4 ID
3/4 ID
3/4 ID
3/4 ID
WEIGHTS
NET WEIGHT — lbs.
119
119
128
139
SHIPPING WEIGHT — lbs.
125
125
134
146
C1036BBD4VF
460/60/3
415-508
5.9
15.0
15
4.7
33
1/4 / 1.2
COOLING PERFORMANCE DATA MATCHING EVAPORATOR COIL
COOLING DATA AT EXTENDED OUTDOOR AMBIENTS °F.M.B.T.U.H.
RATINGS AT STANDARD CONDITIONS
OUTDOOR
UNIT
MODEL*
EVAPORATOR
COIL➂
BTUH
SEER
CFM
C1018BBD
E3009A
18 000
10
600
C1024BBD
E3009A
22 400
10
800
C1030BBD
E3618A
28 600
10
1000
C1036BBD
E3618A
34 000
10
1200
C1042BBD
E4824A
40 000
10
1300
C1048BBD
E6026A
45000
10
1600
C1060CBD
E6037A
56 000
10
1750
TOTAL
SENSIBLE
TOTAL
SENSIBLE
TOTAL
SENSIBLE
TOTAL
SENSIBLE
TOTAL
SENSIBLE
TOTAL
SENSIBLE
TOTAL
SENSIBLE
80
85
90
95
100
105
110
115
20 200
14 500
25 500
18 300
31 300
22 500
36 400
26 200
43 000
31 000
49 700
35 800
58 800
42 300
19 700
14 200
24 700
17 800
30 500
22 000
36 000
25 900
42 000
30 200
48 500
34 900
57 900
41 700
19 100
13 750
23 800
17 100
29 800
21 500
35 500
25 600
41 000
29 500
47 300
34 000
56 900
41 000
18 000
13 000
22 400
16 100
28 600
19 300
34 000
24 500
40 000
28 800
46 000
33 100
56 000
40 300
17 600
12 700
22 200
15 900
28 000
20 200
32 400
23 300
38 500
27 700
44 400
32 000
54 000
38 900
16 800
12 100
21 500
15 500
27 000
19 400
30 700
22 100
37 000
26 600
43 000
31 000
52 000
37 400
15 900
11 400
20 700
14 900
26 000
18 700
29 100
20 900
35 500
25 560
41 500
29 900
50 000
36 000
15 000
10 800
19 900
14 330
25 000
18 000
27 500
19 800
34 000
24 500
39 800
28 600
48 000
34 600
*Basic model number only. See unit nomenclature on the last page for exact model number.
FOOTNOTES:
➀ Amps at 104˚F OD temp. 80˚F DB / 67˚F WB indoor temp. ➁ Time delay type fuse for HACR Circuit Breaker. ➂ For indoor coils nomenclature see
indoor coil specification sheet. ➃ Air Handler includes Evaporator Coil.
MODEL SPECIFICATIONS
MODEL NUMBER
C1042BBD1VF C1048BBD1VF C1048BBD3VF C1048BBD4VF C1060CBD1VF C1060CBD3VF C1060CBD4VF
PERFORMANCE DATA
NOMINAL COOLING BTU/H
40 000
45 000
56 000
SEER BTU/H-W
10.0
10.0
10.0
CFM
1300
1600
1750
VOLTS/HZ/PHASE
208-230/60/1 208-230/60/1 208-230/60/3
460/60/3
208-230/60/1 208-230/60/3
VOLTAGE RANGE
197-253
197-253
187-253
415-508
197-253
187-253
OPERATING CURRENT AMPS
➀
20.7
26.7
16.6
8.7
29.2
18.8
MIN. WIRE AMPACITY
26.4
31.8
19.3
11.0
36.0
23.0
MAX. HACR BREAKER
➁
35
50
30
15
60
35
COMPRESSOR DATA
RLA
18.5
24.5
14.8
7.5
27.0
16.6
LRA
103
137
91
46
150
124
FAN DATA
DIAMETER
18 INCH / 4 BLADE
18 INCH / 4 BLADE
22 INCH / 3 BLADE
MOTOR TYPE
PSC
PSC
PSC
HP (W) / FLA
1/5 / 1.8
1/5 / 1.8
1/4 / 1.2
1/4 / 2.2
RPM
1075
1075
1075
CFM
2 400
2 400
3 400
OUTDOOR COIL
TYPE
ENHANCED ALUMINUM PLATE FIN / RIFLED COPPER TUBE
FACE AREA
12.0
12.0
18.3
O.D. / F.P.I.-ROWS
3/8 / 18-1
3/8 / 22-1
3/8 / 18-1
REFRIGERANT LINE CONNECTIONS (SERVICE PORT I.D.)
LIQUID
3/8 ID
3/8 ID
3/8 ID
VAPOR
3/4 ID
7/8 ID
7/8 ID
WEIGHTS
NET WEIGHT — lbs.
148
150
201
SHIPPING WEIGHT — lbs.
156
158
210
460/60/3
415-508
9.1
12.0
15
7.9
59
1/4 / 1.2
COOLING PERFORMANCE DATA MATCHING AIR HANDLER
COOLING DATA AT EXTENDED OUTDOOR AMBIENTS °F.M.B.T.U.H.
RATINGS AT STANDARD CONDITIONS
OUTDOOR
UNIT
MODEL*
AIR
HANDLER➃
BTUH
SEER
CFM
C1018BBD1
A24B1
18 000
10
600
C1024BBD1
A24B1
22 400
10
800
C1030BBD1
A36B1
28 600
10
1000
C1036BBD1
A36B1
34 000
10
1200
C1042BBD1
A42B1
40 000
10
1300
C1048BBD1
A48B2
45 000
10
1600
C1060CBD1
A60B1
56 000
10
1750
TOTAL
SENSIBLE
TOTAL
SENSIBLE
TOTAL
SENSIBLE
TOTAL
SENSIBLE
TOTAL
SENSIBLE
TOTAL
SENSIBLE
TOTAL
SENSIBLE
80
85
90
95
100
105
110
115
20 200
14 500
25 500
18 150
31 300
21 900
36 400
26 300
43 000
31 400
49 700
34 950
58 800
41 400
19 700
14 100
24 700
17 600
30 500
22 700
36 000
25 900
42 000
30 850
48 500
57 900
57 900
41 000
19 100
13 700
23 800
17 150
29 800
22 150
35 500
26 450
41 000
30 000
47 300
33 600
56 900
40 550
18 000
12 900
22 400
16 700
28 600
21 450
34 000
25 600
40 000
29 400
46 000
32 400
56 000
40 300
17 600
12 700
22 200
16 000
28 000
21 100
32 400
24 450
38 500
28 000
44 400
31 850
54 000
39 000
16 800
12 150
21 500
15 550
27 000
20 400
30 700
23 250
37 000
26 900
43 000
31 100
52 000
37 600
15 900
11 500
20 700
15 000
26 000
19 650
29 100
22 100
35 500
25 600
41 500
30 700
50 000
36 400
15 000
10 900
19 900
14 350
25 000
18 750
27 500
20 650
34 000
24 550
39 800
29 000
48 000
35 050
Residential & Light Commercial – 10 SEER Remote Condensing Units
CONDENSER DIMENSIONS (INCHES)
MODEL
C1018BVF
C1024BVF
C1030BVF
C1036BVF
C1042BVF
C1048BVF
C1060CVF
C
A
UNIT
B
C
A
SHIPPING
B
211/2
211/2
221/2
231/2
231/2
211/2
211/2
211/2
211/2
211/2
291/2
211/2
211/2
211/2
211/2
211/2
291/2
221/2
221/2
261/2
321/2
321/2
321/2
231/2
231/2
231/2
231/2
231/2
311/2
231/2
231/2
231/2
231/2
231/2
311/2
MODEL KEY: Residential & Light Commercial – Outdoor Unit
UNIT
EFFICIENCY
C
23
23
23
27
33
33
33
B
A
REMOTE
CONDENSER
AIR CONDITIONER
C
10
NOMINAL
CAPACITY
CHASSIS
MODEL
VERSION
24
B
B
OPTION LEVEL
D = STANDARD UNIT R-22
E = STANDARD UNIT R-407
F = HIGH & LOW PRESSURE SWITCH
MODEL KEY: Air Handler
D
X– V
X
A
V = VALVE SWEAT TYPE FITTING
1 = 230/208 VOLT, 1 PHASE, 60 Hz
2 = 220/240 VOLT, 1 PHASE, 50 Hz
3 = 230/208 VOLT, 3 PHASE, 60 Hz
4 = 460 VOLT, 3 PHASE, 60 Hz
5 = 230 VOLT, 3 PHASE, 50 Hz
6 = 380 VOLT, 3 PHASE, 50 Hz
24 B
CE
IFIED TO A
RI
C
O
IT
UN
TIO
MPLYING
DI
A
N
R
AIR
Y
CO
U
MAN FACTU
RT
NING
A
E
TI
FI
T
IO
F
UIPMEN
•
R
Q
C
S TA T I O N S E C T D
ANDAR
O
C
I
NS
2
0
•
E
R
EVAPORATOR
DESIGNATION
S
R
1
A
RE
NOMINAL
BTU/H
R
Fedders Unitary Products
505 Martinsville Rd.
Liberty Corner, NJ 07938
(908) 604-8686
Form No. F-C10-0804
MODEL
REVISION
MODEL
SERIES
BRAND
1
Rated in Accordance with ARI Standard 210/240.
Certification Applies Only When Used with
Proper Components as Listed with ARI.
All product specifications reflect available information at the printing of this brochure.
Fedders reserves the right to revise or modify products and/or specifications without notice.
©2004 Fedders Unitary Products. Fedders is a registered trademark of Fedders North America, Inc.
Related documents
Fedders CH12 User's Manual
Fedders CH12 User's Manual