Download AEC FP3000 Specifications
Transcript
Underwriters Laboratories (UL) File number (S 8485) Fire Alarm Equipment SAFETY HI-TECH The model series SHC8000 of the Quaestor-SZU Releasing Fire Control Panel is suitable as follows: • Local Signaling Unit, Cross Zone and Releasing • Commercial protected-premises control unit • Types of signaling services are SLC Class B, Style 4, NFPA 72 conventional IDC Class B and Style C or Class B, Style B, automatic fire alarm, manual fire alarm • Non-coded Signaling • Compatibility IDAXT0110 Install detectors with spacing as specified in section 90.19 of UL 864, 9th edition where units employing the multiple detector operation shall include guidelines for installing of a minimum of two detectors in each protected space and to reduce the detector installation spacing to 0.7 times the linear spacing in accordance with National Fire Alarm Code, NFPA 72. Also reference 55.3.1 and 55.3.2 of UL 864, 9th edition for these detector spacing requirements. NFPA SAFETY HI-TECH This product satisfies releasing operation under: • Carbon dioxide extinguishing systems, NFPA 12 • Halon 1301 fire extinguishing systems, NFPA 12A • Sprinkler systems, NFPA 13 • Water spray fixed systems for fire protection, NFPA 15 • Foam-water sprinkler and foam-water spray systems, NFPA 16 • Dry chemical extinguishing systems, NFPA 17 • Wet chemical extinguishing systems, NFPA 17A • Water mist, NFPA 750 • Clean agent fire extinguishing systems, NFPA 2001 SAFETY HI-TECH Quaestor-SZU Releasing Fire Control Panel - Installation and Operation Manual Revision E03.04 SHM80001