Download Siemens SIPART PS2 6DR50xx Technical data
Transcript
Design and Functional Principle 2.3.4 Mounting Kit The positioner can be mounted on almost all actuators with the appropriate mounting kit. 2.3.5 Purge air switching (not in the explosion proof version) The purge air switch is accessible above the pneumatic terminal strip with the housing open (figure 2-7). In the IN position the inside of the housing is purged with very small amounts of clean, dry instrument air. In the OUT position the purge air is fed directly to the outside air. Figure 2-7 Purge air switch on the valve block, view of the positioner onto pneumatic connection side with cover open 2.3.6 Restrictors In order to achieve travel times of > 1.5 s in small actuators, the air rate can be reduced with the restrictors Y1 and Y2 (figure 2-8, in explosion proof version, see figure 2-5, page 19). By turning to the right the air rate is reduced up to shutting off. To set the restrictors it is advisable to close them and then open them slowly (see initialization RUN3). In the case of double-acting valves make sure that both chokes are set approximately equal. Hexagon socket 2.5 mm Y1 Y2 Figure 2-8 22 Restrictors SIPART PS2 Manual A5E00074631--06