Charging Procedures Important The charge is critical on all Manitowoc ice machines. Use a scale to ensure the proper charge is installed. 1. Be sure the toggle switch is in the OFF position. MANIFOLD SET CLOSED OPEN LOW SIDE ACCESS VALVE HIGH SIDE ACCESS VALVE REFRIGERANT CYLINDER VACUUM PUMP/ RECOVERY UNIT OPEN SCALE CLOSED CHARGING CONNECTIONS SV3055 2. Close the vacuum pump valve and the low side manifold gauge valve. 3. Open the high side manifold gauge valve. 4. Open the refrigerant cylinder and add the proper refrigerant charge (shown on nameplate) through the discharge access valve. 5. Let the system “settle” for 2 to 3 minutes. 6. Place the toggle switch in the ICE position. Part Number 80-1230-9 6/08 217