265485-XTG-B-1208
TECHNICAL
GUIDE 50Hz
®
®
MagnaDRY™
SINGLE PACKAGE AIR CONDITIONERS AND
SINGLE PACKAGE GAS/ELECTRIC UNITS
DESCRIPTION
YORK® Predator® MagnaDRY™ units are convertible single
packages with a common footprint cabinet and common roof curb
for all 7-1/2 ton models. All units have two compressors with independent refrigeration circuits. The units were designed for light
commercial applications and can be easily installed on a roof
curb, slab, roof jack, or frame.
All Predator® MagnaDRY™ units are self-contained and assembled on rigid full perimeter base rails allowing for 3-way forklift
access and overhead rigging. Every unit is completely charged,
wired, piped, and tested at the factory to provide a quick and easy
field installation.
All units are convertible between side and down airflow. A single
economizer design is used on side and down discharge applications, as well as all tonnage sizes.
DR090
7-1/2 NOMINAL TONS
The Predator® MagnaDRY™ provides energy-savings, efficient
removal of moisture through a balanced coil design. Because the
unit doesn’t increase sensible cooling, it allows temperatures to
be maintained within the confort zone. Unlike competitive systems, you’re not subjected to over cooling. You save through more
efficient matching of dehumidification and cooling needs. This
makes the MagnaDRY™ perfect for applications that need to
remove large amounts of moisture or maintain low humidity levels.
ISO 9001
Certified Quality
Management System
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
265485-XTG-B-1208
TABLE OF CONTENTS
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
FACTORY INSTALLED OPTIONS . . . . . . . . . . . . . . 5
FIELD INSTALLED ACCESSORIES . . . . . . . . . . . . 6
NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . 10
LIST OF FIGURES
Fig. #
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
2
Pg. #
PREDATOR® COMPONENT LOCATION . . . . . . . . . . . 3
REHEAT CONTROL BOARD . . . . . . . . . . . . . . . . . . . . 8
DR090 REHEAT CONTROLS . . . . . . . . . . . . . . . . . . . . 9
DR090 MOISTURE REMOVAL (ALTERNATE MODE) IMPERIAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
DR090 MOISTURE REMOVAL (NORMAL MODE) IMPERIAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
DR090 MOISTURE REMOVAL (ALTERNATE MODE) METRIC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
DR090 MOISTURE REMOVAL (NORMAL MODE) METRIC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
UNIT 4 POINT LOAD . . . . . . . . . . . . . . . . . . . . . . . . . . 25
UNIT CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . 25
UNIT 6 POINT LOAD . . . . . . . . . . . . . . . . . . . . . . . . . . 26
UNIT DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
PREDATOR® ROOF CURB DIMENSIONS . . . . . . . . 27
SUNLINE™ TO PREDATOR® TRANSITION ROOF
CURB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
BOTTOM DUCT OPENINGS (FROM ABOVE) . . . . . . 28
REAR DUCT DIMENSIONS . . . . . . . . . . . . . . . . . . . . . 29
DOWNFLOW ECONOMIZER HOOD DETAIL . . . . . . . 29
FACTORY INSTALLED DOWNFLOW
ECONOMIZER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
FIELD INSTALLED DOWNFLOW ECONOMIZER W/
POWER EXHAUST . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
FIELD INSTALLED HORIZONTAL ECONOMIZER W/
POWER EXHAUST . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
SLAB ECONOMIZER DOWNFLOW W/POWER
EXHAUST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
SLAB ECONOMIZER END RETURN W/POWER
EXHAUST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
TYPICAL LOW VOLTAGE FIELD WIRING . . . . . . . . . 33
FIELD WIRING DISCONNECT - COOLING UNIT WITH
OR WITHOUT ELECTRIC HEAT . . . . . . . . . . . . . . . . . 34
FIELD WIRING DISCONNECT - COOLING UNIT WITH
GAS HEAT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
TYPICAL DR090 COOLING UNIT WITH GAS HEAT
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
TYPICAL DR090 COOLING UNIT WITH/WITHOUT
ELECTRIC HEAT WIRING DIAGRAM . . . . . . . . . . . . . 36
TYPICAL DR090 REHEAT WIRING DIAGRAM . . . . . 37
LIST OF TABLES
Tbl. #
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Pg. #
PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
CAPACITY RATINGS IMPERIAL . . . . . . . . . . . . . . . . 12
CAPACITY RATINGS METRIC . . . . . . . . . . . . . . . . . . 12
DR090 COOLING CAPACITY - IMPERIAL . . . . . . . . . 13
DR090 COOLING CAPACITY - METRIC . . . . . . . . . . 14
DR090 COOLING CAPACITY (ALTERNATE
REHEAT MODE) - IMPERIAL . . . . . . . . . . . . . . . . . . . 15
DR090 COOLING CAPACITY (ALTERNATE REHEAT
MODE) - METRIC . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
ELECTRICAL DATA 7-1/2 TON . . . . . . . . . . . . . . . . . 19
BLOWER PERFORMANCE 7-1/2 TON STANDARD
MOTOR - SIDE DUCT (IMPERIAL) . . . . . . . . . . . . . . . 20
BLOWER PERFORMANCE 7-1/2 TON STANDARD
MOTOR - SIDE DUCT (METRIC) . . . . . . . . . . . . . . . . 20
BLOWER PERFORMANCE 7-1/2 TON OPTIONAL
MOTOR - SIDE DUCT (IMPERIAL) . . . . . . . . . . . . . . 20
BLOWER PERFORMANCE 7-1/2 TON OPTIONAL
MOTOR - SIDE DUCT (METRIC) . . . . . . . . . . . . . . . . 21
BLOWER PERFORMANCE 7-1/2 TON STANDARD
MOTOR - DOWNSHOT (IMPERIAL) . . . . . . . . . . . . . . 21
BLOWER PERFORMANCE 7-1/2 TON STANDARD
MOTOR - DOWNSHOT (METRIC) . . . . . . . . . . . . . . . 21
BLOWER PERFORMANCE 7-1/2 TON OPTIONAL
MOTOR - DOWNSHOT (IMPERIAL) . . . . . . . . . . . . . . 22
BLOWER PERFORMANCE 7-1/2 TON OPTIONAL
MOTOR - DOWNSHOT (METRIC) . . . . . . . . . . . . . . . 22
ADDITIONAL STATIC RESISTANCE (IMPERIAL) . . . 23
18 ADDITIONAL STATIC RESISTANCE (METRIC) . . . . 24
19 ELECTRIC HEAT MINIMUM SUPPLY
AIR - IMPERIAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20 ELECTRIC HEAT MINIMUM SUPPLY
AIR - METRIC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
21 INDOOR BLOWER SPECIFICATIONS . . . . . . . . . . . .
22 4 POINT LOAD WEIGHT . . . . . . . . . . . . . . . . . . . . . . .
23 6 POINT LOAD WEIGHT . . . . . . . . . . . . . . . . . . . . . . .
24 UNIT WEIGHT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
25 UNIT HEIGHT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
26 UNIT CLEARANCES . . . . . . . . . . . . . . . . . . . . . . . . . .
27 ECONOMIZER USAGE . . . . . . . . . . . . . . . . . . . . . . . .
25
25
25
25
26
26
26
27
30
Johnson Controls Unitary Products
265485-XTG-B-1208
Simplicity™ control board
Filter access
Disconnect location
w/screw connector for T-stat
(2” throw-away)
(optional
disconnect
switch)
wiring and network connections
Filter drier
(solid core)
Terminal block for
hi-voltage connection
Condenser section
Second model
nameplate
inside hinged
access panel
Slide-out motor and
blower assembly for
easy adjustment
and service
Dual stage
cooling for
maximum
comfort
Belt-drive
blower motor
Power ventor motor
Compressor #2
access (highefficiency
compressor
w/crankcase
heater)
20-gauge aluminized steel tubular
heat exchanger for
long life (stainless
steel option)
Base rails w/forklift
slots (three sides)
and lifting holes
Two-stage gas
heating to maintain
warm, comfortable
temperature
Roof curbs in eight- and
fourteen-inch heights. Roof
curbs for transitioning from
York Sunline™ footprint to
the DR Series footprints are
also available (field-installed
accessory)
Slide-out drain pan
with steel 3/4” NPT,
female connection
Toolless
door latch
Side entry power
and control wiring
knockouts
Intelligent control
board for safe and
efficient operation
Compressor #1 access
(high-efficiency compressor
w/crankcase heater)
FIGURE 1 - PREDATOR® COMPONENT LOCATION
FEATURES
•
•
Both the unit control board and ignition control board utilize flash codes to aid in diagnosis of unit malfunctions.
Unique alarm codes quickly identify the source of the
unit alarm.
Standard Efficiency– All standard efficiency units have
a minimum EER of 10.5 (3.08 CoP). Gas/electric units
have electronic spark ignition and power vented combustion with steady state efficiencies of 80%.
All units use the same standard filter size. This standardization removes any confusion on which filter sizes
are needed for replacement.
Service Friendly – The Predator® incorporates a number of enhancements which improve serviceability.
The non-corrosive drain pan slides out of the unit to permit easy cleaning. The drain pan is accessed by removing the drain pan cover plate on the rear of the unit.
Once the plate is removed, the drain pan slides out
through the rear of the unit.
The motor and blower slide out of the unit as a common
assembly. This facilitates greater access to all the indoor
airflow components, thus simplifying maintenance and
adjustment.
Service time is reduced through the use of hinged, toolless panels. Such panels provide access to frequently
inspected components and areas, including the control
box, compressors, filters, indoor motor & blower, and the
heating section. The panels are screwed in place at the
factory to prevent access by children or other unauthorized persons. It is recommended that the panels be
secured with screws once service is complete.
Service windows have been placed in both condenser
section walls. Rotation of the cover allows easy access
to the condenser coils for cleaning or inspection.
Johnson Controls Unitary Products
All Predator® units have a second model nameplate
located inside the control access door. This is to prevent
deterioration of the nameplate through weathering.
•
Environmentally Aware – For improved Indoor Air
Quality, foil faced insulation is used exclusively throughout the units.
•
Balanced Heating – The Predator® offers “Ultimate Heating Comfort” with a balance between 1st and 2nd stage
gas heating. The 1st stage of a gas heat Predator® unit
provides 60% of the heating capacity. Balanced heating
allows the unit to better maintain desired temperatures.
3
265485-XTG-B-1208
•
Convertible Airflow Design – The side duct openings
are covered when they leave the factory. If a side supply/return is desired, the installer simply removes the two
side duct covers from the outside of the unit and installs
them over the down shot openings. No panel cutting is
required. Convertible airflow design allows maximum
field flexibility and minimum inventory.
•
System Protection - Suction line freezestats are supplied
on all units to protect against loss of charge and coil frosting when the economizer operates at low outdoor air temperatures while the compressors are running. Every unit
has solid-core liquid line filter-driers and high and lowpressure switches. Internal compressor protection is standard on all compressors. Crankcase heaters are standard
on reciprocating compressors. Scroll compressors do not
require crankcase heaters. Phase Monitors are standard
on units with scroll compressors. This accessory monitors
the incoming power to the unit and protects the unit from
phase loss and reversed phase rotation.
•
Advanced Controls - Simplicity™ control boards have
standardized a number of features previously available
only as options or by utilizing additional controls.
•
Low Ambient - An integrated low-ambient control
allows all units to operate in the cooling mode down
to 0°F (-17.8°C) outdoor ambient without additional
assistance. Optionally, the control board can be
programmed to lockout the compressors when the
outdoor air temperature is low or when free cooling
is available.
The Simplicity® control board used in this product
will effectively operate the cooling system down to
0°F when this product is applied in a comfort cooling
application for people. An economizer is typically
included in this type of application. When applying
this product for process cooling applications (computer rooms, switchgear, etc.), please reference
applications bulletin AE-011-07 or call the applications department for Unitary Products @ 1-877UPG-SERV for guidance. Additional accessories
may be needed for stable operation at temperatures
below 30° F.
•
•
4
Anti-Short Cycle Protection - To aid compressor
life, an anti-short cycle delay is incorporated into the
standard controls. Compressor reliability is further
ensured by programmable minimum run times. For
testing, the anti-short cycle delay can be temporarily
overridden with the push of a button.
Fan Delays - Fan on and fan off delays are fully programmable. Furthermore, the heating and cooling
fan delay times are independent of one another. All
units are programmed with default values based
upon their configuration of cooling and heat.
•
Safety Monitoring - The control board monitors the
high and low-pressure switches, the freezestats, the
gas valve, if applicable, and the temperature limit
switch on gas and electric heat units. The unit control board will alarm on ignition failures, compressor
lockouts and repeated limit switch trips.
•
Nuisance Trip Protection and Strikes - To prevent
nuisance trouble calls, the control board uses a
“three times, you’re out” philosophy. The high and
low-pressure switches and the freezestats must trip
three times within two hours before the unit control
board will lock out the associated compressor.
•
On Board Diagnostics - Each alarm will energize a
trouble light on the thermostat, if so equipped, and
flash an alarm code on the control board LED. Each
high and low-pressure switch alarm as well as each
freezestat alarm has its own flash code. The control
board saves the five most recent alarms in memory,
and these alarms can be reviewed at any time.
Alarms and programmed values are retained
through the loss of power.
•
Reliable – From the beginning – All units undergo computer automated testing before they leave the factory.
Units are tested for refrigerant charge and pressure, unit
amperage, and 100% functionality. For the long term –
All Predator® units are painted with a long lasting, powder paint that stands up over the life of the unit. The paint
used has been proven by a 1000 hour salt spray test.
•
Flexible Placement – All models and configurations
share the same cabinet/footprint and thus the same roof
curb. You have the flexibility to set one curb and choose
the correct tonnage size and heating option after the
internal loads have been determined.
To further simplify planning and installation, Predator®
cabinets are designed to fit your roof. With the optional
roof curb, the unit ductwork is designed to fit around 24”
(610 mm) on-center joists or between 48” (1219 mm) oncenter joists.
The drain pan can be rotated to drain to either the front
or the rear of the unit. Additionally, the drain pan can be
piped to drain through the roof curb. As it is sometimes
difficult to have a level installation, the drain pan features
a generous slope to ensure proper drainage.
•
Full Perimeter Base Rails – The permanently attached
base rails provide a solid foundation for the entire unit and
protect the unit during shipment. The rails offer forklift
access from 3 sides, and rigging holes are available so that
an overhead crane can be used to place the units on a roof.
•
Easy Installation – Gas and electric utility knockouts are
supplied in the unit underside as well as the side of the
unit. A clearly identified location is provided to mount a
field supplied electrical disconnect switch. Utility connections can be made quickly and with a minimum
amount of field labor.
All units are shipped with 2” (51 mm) filters installed.
Johnson Controls Unitary Products
265485-XTG-B-1208
•
Wide Range of Indoor Airflows – All indoor fan motors
are belt-drive type providing maximum flexibility to handle
most airflow requirements. For high static applications,
factory installed alternate indoor fan motors are available. With the optional indoor fan motor, all units can supply nominal airflow at a minimum of 1.5” (375 Pa) ESP.
FACTORY INSTALLED OPTIONS
•
Motorized Outdoor Air Damper - The motorized outdoor air damper includes a slide-in/plug-in damper
assembly with an outdoor air hood and filters. The outdoor air dampers open to the preset position when the
indoor fan motor is energized. The damper has a range
of 0% to 100% outdoor air entry. Factory installed option
or field installed accessory.
•
Alternate Indoor Blower Motor - For applications with
high static restrictions, units are offered with optional
indoor motors that provide higher static output and/or
higher airflow, depending upon the installer’s needs.
•
Aluminized Steel Gas Heat Exchanger - For applications in non-corrosive environments.
•
Stainless Steel Gas Heat Exchanger - For applications
in corrosive environments, this option provides a full
stainless steel heat exchanger assembly.
•
Electric Heaters - The electric heaters range from 9kW
to 54kW and are available in all the voltage options of the
base units. All heaters are dual staged. All heaters are
intended for single point power supply.
•
Disconnect Switch - For gas heat units and cooling
units with electric heat, a HACR breaker sized to the unit
is provided. For cooling only units, a switch sized to the
largest electric heat available for the particular unit is
provided. Factory installed option only.
•
Smoke Detectors - The smoke detectors stop operation
of the unit by interrupting power to the control board if
smoke is detected within the air compartment. Available
for both the supply and/or return air.
YORK® offers several equipment options factory installed, for
the Predator® line.
•
Optional Factory Installed Economizers - Predator
units offer a variety of optional factory installed economizers with low leak dampers. The outdoor air enthalpy
sensor enables economizer operation if the outdoor
enthalpy is less than the setpoint of the economizer logic
module. See Table 27 to determine the correct economizer for your application.
•
•
•
•
Downflow Economizer - (With barometric relief) The economizer is provided with a single enthalpy
input. The economizer is 2% low leakage type, and is
shipped installed and wired. The installer needs only
to assemble and mount the outdoor air hood (Provided). The economizer has spring return, fully modulating damper actuators and is capable of introducing
up to 100% outdoor air. As the outdoor air intake
dampers open, the return air dampers close. The
changeover from mechanical refrigeration to economizer operation is regulated by the standard single
enthalpy input. There is an optional input dual dry
bulb available. To meet regulated air standards, the
economizer control accepts an optional CO2 input for
demand ventilation. With single enthalpy input, the
economizer control monitors outdoor air. The dual
enthalpy kit provides a second input used to monitor
the return air. With a dual input kit installed, the economizer control compares the values of the two
enthalpy or temperature inputs and positions the
dampers to provide the maximum efficiency possible.
Horizontal Economizer - (Without barometric
relief) - All features as the downflow economizer
exist except you must order the barometric relief
separately. You must order a 1EH0408 if you are
installing a power exhaust. You can order a
1RD0411 Barometric Relief for horizontal flow
economizers only.
BAS Ready Economizer - (With barometric relief)
- The economizer is provided with an actuator that
requires a 0-10V DC input from an external source
(i.e., field installed building automation system controller). Power exhaust options are available. The
economizer is 2% low leakage type with spring
return and fully modulating dampers capable of
introducing up to 100% outside air. Also include 2”
(51 mm) pleated filters.
Power Exhaust (Downflow only) - This accessory
installs in the unit with a down flow economizer.
Johnson Controls Unitary Products
Factory installed smoke detectors in the return air,
may be subjected to freezing temperatures during
"off" times due to out side air infiltration. These
smoke detectors have an operational limit of 32 °F
to 131°F. Smoke detectors installed in areas that
could be out side those limitations will have to be
moved to prevent having false alarms.
•
Phase Monitors - Designed to prevent unit damage.
The phase monitor will shut the unit down in an out-of
phase condition. (Standard on units with Scroll Compressors.)
•
Coil Guard - Customers can purchase a coil guard kit to
protect the condenser coil from damage. Additionally,
this kit stops animals and foreign objects from entering
the space between the inner condenser coil and the
main cabinet. This is not a hail guard kit.
•
Dirty Filter Switch - This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option
or field installed accessory.
5
265485-XTG-B-1208
•
Technicoat Condenser Coils - The condenser coils are
coated with a phenolic coating for protection against corrosion due to harsh environments.
•
Barometric Relief Damper - Zero to 100% capacity
barometric relief dampers for use with horizontal flow, or
field installed slab economizers.
•
Technicoat Evaporator Coil - The evaporator coils are
coated with a phenolic coating for protection against corrosion due to harsh environments.
•
•
Novar® BAS Control - The Novar® building automation
system controller is factory installed. Incudes supply air
sensor, return air sensor, dirty filter indicator switch, and
air proving switch.
Power Exhaust - This accessory installs in the unit with
a down flow economizer. Power exhaust plugs into the
connector in the unit bulkhead. You must purchase
1EH0408 barometric relief/power exhaust hood when
applying to a horizontal flow application.
•
Manual Outdoor Air Damper - Like the motorized outdoor air damper, each manual outdoor air damper
includes a slide-in damper assembly with an outdoor air
hood and filters. Customers have a choice of dampers
with ranges of 0% to 100% or 0% to 35% outdoor air
entry.
•
Motorized Outdoor Air Damper - The motorized outdoor air damper includes a slide-in/plug-in damper
assembly with an outdoor air hood and filters. The outdoor air dampers open to the preset position when the
indoor fan motor is energized. The damper has a range
of 0% to 100% outdoor air entry. Factory installed option
or field installed accessory.
•
Smoke Detectors - The smoke detectors stop operation
of the unit by interrupting power to the control board if
smoke is detected within the air compartment.
•
CO2 Sensor - Senses CO2 levels and automatically
overrides the economizer when levels rise above the
preset limits.
•
Dirty Filter Switch - This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high
pressure drop across the filters.
•
Coil Guard - Field installed decorative wire coil guard.
•
Hail Guard - This kit includes a sloped hood which
installs over the outside condenser coil and prevents
damage to the coil fins from hail strikes. Field installed
accessory only.
•
Flue Exhaust Extension Kit - In locations with wind or
weather conditions which may interfere with proper
exhausting of furnace combustion products, this kit can
be installed to prevent the flue exhaust from entering
nearby fresh air intakes.
•
-60°F Gas Heat Kit - For installations which require gas
heat units to perform in low ambient temperatures, a gas
section heating kit is available. This kit provides electric
heat in the gas heat controls section to ensure the gas
valve and controls will continue to function properly at
extremely low temperatures.
•
Gas Heat High Altitude Kit - This kit converts a gas
heat unit to operate at high altitudes, 2,000 to 6,000 feet.
Conversion kits are available for natural gas and propane.
•
Johnson Controls BAS Control - The Johnson Control
YK-UNT-1126 building automation system controller is
factory installed. Includes supply air sensor, return air
sensor, dirty filter indicator switch, and air proving switch.
•
CPC BAS Control - The Computer Process Controls
Model 810-3060 ARTC Advanced Rooftop building automation system controller is factory installed. Includes
supply air sensor, return air sensor, dirty filter indicator
switch, and air proving switch.
•
Honeywell BAS Control - The Honeywell W7750C
building automation system controller is factory installed.
Includes air supply sensor, return air sensor, dirty filter
indicator switch, and air proving switch.
FIELD INSTALLED ACCESSORIES
YORK®
offers several equipment accessories for field installation, for the Predator® line.
•
•
•
6
Downflow Economizer - (With barometric relief) - The
economizer is provided with a single enthalpy input. The
economizer is 2% low leakage type. The economizer has
spring return, fully modulating damper actuators and is
capable of introducing up to 100% outdoor air. As the
outdoor air intake dampers open, the return air dampers
close. The changeover from mechanical refrigeration to
economizer operation is regulated by the standard single
enthalpy input. There is an optional input dual dry bulb
available. To meet regulated air standards, the economizer control accepts an optional CO2 input for demand
ventilation. With single enthalpy input, the economizer
control monitors outdoor air. The dual enthalpy kit provides a second input used to monitor the return air. With
a dual input kit installed, the economizer control compares the values of the two enthalpy or temperature
inputs and positions the dampers to provide the maximum efficiency possible
Horizontal Economizer - (Without barometric relief) All features as the downflow economizer exist except
you must order the barometric relief separately. You
must order a 1EH0408 if you are installing a power
exhaust. You can order a 1RD0411 Barometric Relief
for horizontal flow economizer.
Dual Enthalpy Control, Accessory - This kit contains
the required components to convert a single enthalpy
economizer to dual enthalpy.
Johnson Controls Unitary Products
265485-XTG-B-1208
•
Gas Heat Propane Conversion Kit - This kit converts a
gas-fired heater from natural gas to propane. It contains
the main burner orifices and gas valve replacement
springs.
•
Gas Piping Kit - Contains pipe nipples, fittings and gas
cock required for gas supply connection with external
shut off.
•
Electric Heaters - The electric heaters range from 9 kW
to 54kW and are available in all the voltage options of the
base units. All heaters are dual staged. Cooling units
include an adapter panel for easy installation of the electric heaters. Necessary hardware and connectors are
included with the heaters. All heaters are intended for
single point power supply.
•
Low Limit / Compressor Lockout Kit
1.
2.
Compressor Lockout (CLO): To prevent mechanical (compressorized) operation of the unit during
cold outdoor conditions where there is a risk of
returning liquid refrigerant back to the compressors.
Low Limit Control (LLC): To prevent the supply air
from dropping below a specified setpoint by utilizing
the units first stage heating means when there is a
demand for cooling during cold outside conditions.
•
Metal Frame Filter Kit - Metal frame with polyester filter
medium.
•
Permanent Filters - Permanent filters are available.
•
Roof Curbs - The roof curbs have insulated decks and
are shipped disassembled The roof curbs are available
in 8” (203 mm) and 14” (356 mm) heights. For applications with security concerns, burglar bars are available
for the duct openings of the roof curbs.
•
Roof Curb Transition - Single Piece Adapter (10” (254
mm) High) - Roof curbs for transitioning from Sunline™
units to Predator® Magnum. Fits 7.5 to 12.5 Sunline™
roof curbs only.
“NORMAL” MODE
When the reheat control board (RCB) detects a need for
dehumidification (24VAC) at "HUM" via the field supplied
dehumidistat connected to RHTB-1 and RHTB-2 and there is
not a call for cooling, it energizes the hot gas relay (HGR),
which energizes the 3-way valve (SOL 3), the condenser coil
valve (SOL 2), and de-energizes the reheat coil bleed valve
(SOL 1). The Y1 signal is passed to the unit control board
(UCB), which engages circuit # 1, resulting in circuit #1
reheat mode operation.
When the room thermostat calls for first stage cooling, with or
without a call for dehumidification, the RCB senses a signal
through "Y1", de-energizing the HGR, which de-energizes
SOL 3 and SOL 2 and energizes SOL 1, engaging circuit #1,
resulting in circuit #1 cooling mode operation.
When the room thermostat calls for second stage cooling, the
RCB senses a signal through "Y1" & "Y2" and engages circuit
#1 and circuit #2 in cooling mode.
Indoor blower operation is initiated upon a call for first stage
cooling, second stage cooling or dehumidification.
Anytime there is a call for 2 stages of cooling, the unit will not
operate in the reheat mode, even if there is a call for dehumidification at "HUM".
The unit will not operate in the reheat mode if there is any call
for heating.
On units with economizers, the unit will not operate in the
reheat mode if there is a call for cooling and the economizer
is operating as first stage of cooling.
All safety devices function as previously described.
"ALTERNATE” MODE
When the RCB detects a need for dehumidification (24VAC)
at "HUM" via the field supplied dehumidistat connected to
RHTB-1 and RHTB-2, and there is not a call for cooling, it
energizes the HGR, which energizes the SOL 3, SOL 2, and
de-energizes SOL 1. The unit then operates with circuit #1 in
reheat mode and circuit #2 in cooling mode.
•
Burglar Bars - Mount in the supply and return openings
to prevent entry into the duct work.
When the room thermostat calls for first stage cooling while
there is still a call for dehumidification, no operational change
is made. The call for cooling is ignored and the unit continues
to operate with circuit #1 in reheat mode and circuit #2 in
cooling mode.
•
Thermostat - The units are designed to operate with 24volt electronic and electro-mechanical thermostats. All
units (with or without an economizer) operate with twostage heat/two-stage cool or two-stage cooling only thermostats, depending upon unit configuration.
When the room thermostat calls for second stage cooling, the
RCB senses a signal through "Y1" and "Y2" and de-energizes the HGR, which de-energizes SOL 3 and SOL 2, and
energizes SOL 1. Both circuits operate in the cooling mode.
REHEAT MODE SEQUENCE OF OPERATION
The reheat control board allows the user to select two different modes of operation via a jumper connection on the
board. (See Figure 2.) Each mode is described below. Refer
to Figures 2 and 3 when reading this section.
Indoor blower operation is initiated upon a call for first stage
cooling, second stage cooling or dehumidification.
Anytime there is a call for 2 stages of cooling, the unit will not
operate in the reheat mode, even if there is still a call for
dehumidification at "HUM".
The unit will not operate in the reheat mode if there is any call
for heating.
All safety devices function as previously described.
Johnson Controls Unitary Products
7
265485-XTG-B-1208
R
Y1
P4
Y2
K1
G
W1
K2
W2
OCC
K4
C
K3
COM
`
P6
P5
P3
HGRR
HGR
MODE
SELECTION
JUMPER
HUM
DEHUMIDISTAT
HARNESS
CONNECTION
FIGURE 2 - REHEAT CONTROL BOARD
8
Johnson Controls Unitary Products
265485-XTG-B-1208
FIGURE 3 - DR090 REHEAT CONTROLS
Johnson Controls Unitary Products
9
265485-XTG-B-1208
NOMENCLATURE
7.5 Ton York® Model Number Nomenclature
D R 090 N10 A 7 A AA 3 0 1 2 4 A
Product Category
Product Style
D = A/C, Single Pkg., R-22
A = Style A
B = Style B
C = Style C
Product Identifier
Configuration Options (not required for all units)
These four digits will not be assigned until a quote is requested, or an order placed.
R = Reheat
SS Drain Pan
Honeywell Controller, DFS, APS
Nominal Cooling Capacity
Simplicity IntelliComfort Controller
090 = 7.5 Ton
Simplicity IntelliComfort Controller w/ModLinc
2" Pleated filters
BAS Ready Unit with Economizer
Heat Type and Nominal Heat Capacity
Shipping Bag
Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned
C00 = Cooling Only. No heat installed
Gas Heat Options
Product Generation
N10 = 100 MBH Output Aluminized Steel
N15 = 150 MBH Output Aluminized Steel
S10 = 100 MBH Output Stainless Steel
S15 = 150 MBH Output Stainless Steel
3 = Third Generation
Additional Options
Electric Heat Options
AA = None
AB = Phase Monitor
AC = Coil Guard
AD = Dirty Filter Switch
AE = Phase Monitor & Coil Guard
AF = Phase Monitor & Dirty Filter Switch
AG = Coil Guard & Dirty Filter Switch
AH = Phase Monitor, Coil Guard & Dirty Filter Switch
E09 = 9 KW
E18 = 18 KW
E24 = 24 KW
E36 = 36 KW
E54 = 54 KW
Airflow
A = Std. Motor
B = Std. Motor/Econo./Barometric Relief (Downflow
Only)
C = Std. Motor/Econo./Power Exhaust (Downflow Only)
D = Std. Motor/Motorized Damper (Downflow Only)
E = Std. Motor/Horizontal Economizer (No Baro.)
F = Std. Motor/Slab Econo./Power Exhaust
(Downflow Only)
G = Std. Motor/Slab Econo./Barometric Relief
(Downflow Only)
N = Hi Static
P = Hi Static/Econo./Barometric Relief
(Downflow Only)
Q = Hi Static/Econo./Power Exhaust
(Downflow Only)
R = Hi Static/Motorized Damper (Downflow Only)
S = Hi Static/Horizontal Economizer (No Baro.)
T = Hi Static/Slab Econo./Power Exhaust
(Downflow Only)
U = Hi Static/Slab Econo./Barometric Relief
(Downflow only)
Voltage
7 = 380/415-3-50
RC = Coil Guard, Shipping Bag & American Flag
TA = Technicoat Condenser Coil
TJ = Technicoat Evaporator Coil
TS = Technicoat Evaporator & Condenser Coils
ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be
located in digits 15-18.
Installation Options
A = No Options Installed
B = Option 1
C = Option 2
D = Options 1 & 2
E = Option 3
F = Option 4
G = Options 1 & 3
H = Options 1 & 4
J = Options 1, 2 & 3
K = Options 1, 2, & 4
L = Options 1,3 & 4
M = Options 1, 2, 3, & 4
N = Options 2 & 3
P = Options 2 & 4
Q = Options 2, 3, & 4
R = Options 3 & 4
S = Option 5
T = Options 1 & 5
U = Options 1, 3, & 5
V = Options 1, 4, & 5
W = Options 1, 3, 4, & 5
X = Options 3 & 5
Y = Options 4 & 5
Z = Options 3, 4 & 5
Options
1 = Disconnect
2 = Non-Pwr'd Conv. Outlet
3 = Smoke Detector S.A.
4 = Smoke Detector R.A.
5 = Pwr'd Conv. Outlet
10
Johnson Controls Unitary Products
265485-XTG-B-1208
TABLE 1: PHYSICAL DATA
Models
Component
090
Evaporator
Blower
Evaporator
Coil
Blower, Centrifugal
Dia. X Wd. in.
(Dia. X Wd. mm.)
15 x 15
(381 x 381)
Motor, Standard - HP (kW)
1-1/2 (1.1)
Motor, Optional - HP (kW)
2 (1.5)
Rows
3
Fins per 2.54 cm (1 in.)
15
Height - in. (mm.)
2
Face Area - ft. (m )
Rows
2
13
Height - in. (mm.)
28 (710)
Face Area - ft.2 (m2)
7.8 (0.72)
Quantity
2
Propeller Dia. - in. (mm.) ea.
24 (610)
Motor - HP (kW) ea.
3/4 (0.56)
Airflow - CFM (m3/s) ea.
3700 (1.75)
Coils
2
Rows (each)
1
Condenser Fan
Fins per inch 2.54 cm (1 in.)
20
Height - in. (mm.)
44 (1120)
Face Area - ft.2 (m2)
14.5 (1.35)
Refrigerant
Charge
System 1 - lb. (kg.)
8.0 (3.63)
System 2 - lbs. (kg.)
6.375 (2.89)
Quantity
2
Type
Recip
Size
Wd. x Ht. x Thickness in.
(Wd. x Ht. x Thickness mm.)
25 x 20 x 2
(635 x 508 x 51)
Quantity
4
Compressors
Air Filters
32 (810)
10.6 (0.98)
Fins per 2.54 cm (1 in.)
Reheat Coil
Condenser Coil
2
Johnson Controls Unitary Products
11
265485-XTG-B-1208
TABLE 2: CAPACITY RATINGS IMPERIAL
Cooling Capacity
Model
(80 / 67-95°F)
Cooling Cap. (MBH)
Sound
Rating
(dB)
Nominal
Electric
Heat
Capacity
(kW)1
Gas Heat Capacity
Input
(MBH)
Output
(MBH)
Temp
Rise (°F)
Gas Line
Size
(in. OD)
Options
MBH
EER
DR
90
10.5
85
7, 14,
18, 27
-
-
-
-
10
-
-
-
-
120
96
15-45
3/4
15
-
-
-
-
180
144
30-60
3/4
090
1. Electric heaters rated at 415V. See table 8 for kW ratings at 380V.
TABLE 3: CAPACITY RATINGS METRIC
Cooling Capacity
Model
(27/19-35°C)
Cooling Cap.
(kW)
090
(26.4)
Sound
Rating
(dB)
Nominal
Electric
Heat
Capacity
(kW)1
Gas Heat Capacity
Input
(kW)
Output
(kW)
Temp
Rise
(°C)
Gas Line
Size
(mm. OD)
Options
kW
CoP2
DR
26.4
3.08
85
7, 14,
18, 27
-
-
-
-
10
-
-
-
-
35.1
28.1
8.3-25
19.05
15
-
-
-
-
52.7
42.2
17-33
19.05
1. Electric heaters rated at 415V. See tables 8 for kW ratings at 380V
2. CoP = Co-efficient of Performance (CoP = Cooling Capacity (kW) / Power Input (kW))
12
Johnson Controls Unitary Products
265485-XTG-B-1208
TABLE 4: DR090 COOLING CAPACITY - IMPERIAL
Air On
Evap. Coil
CFM
2250
2625
3000
3375
3750
2250
2625
3000
3375
3750
2250
2625
3000
3375
3750
1.
2.
Temperature of Air on Condenser Coil 75°F
WB
(°F)
Tot.
Cap.1
(MBH)
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
114.7
101.8
91.1
86.8
118.1
104.8
93.8
89.4
121.5
107.9
96.5
92.0
125.3
111.2
99.5
94.9
129.0
114.5
102.5
97.8
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
Tot.
Input2
(kW)
Temperature of Air on Condenser Coil 85°F
Sensible Capacity (MBH)1
Return Dry Bulb (°F)
86
83
80
77
74
71
6.4
61.3 56.1 50.9 45.7 40.4
6.2
74.2 69.0 63.8 58.6 53.3 48.1
6.0
87.3 82.0 76.8 71.5 66.3 61.1
6.0
86.8 86.1 80.8 75.6 70.4 65.1
6.6
66.6 60.7 54.8 48.9 42.9
6.5
80.5 74.6 68.6 62.7 56.8 50.9
6.2
91.9 89.3 82.6 76.7 70.8 64.9
6.2
89.4 89.0 87.0 81.1 75.2 69.3
6.8
71.9 65.3 58.7 52.1 45.5
6.7
86.7 80.1 73.5 66.9 60.3 53.7
6.5
96.5 96.5 88.5 81.9 75.3 68.7
6.5
92.0 92.0 93.2 86.6 80.0 73.4
6.8
77.1 69.9 62.7 55.5 48.4
6.7
92.9 85.7 78.6 71.4 64.2 57.1
6.5
99.5 99.5 95.5 88.3 81.1 74.0
6.5
94.9 94.9 95.5 88.3 81.1 74.0
6.9
82.2 74.5 66.7 59.0 51.3
6.7
99.1 91.4 83.7 75.9 68.2 60.4
6.5
102. 102. 102. 94.7 87.0 79.2
6.5
97.8 97.8 97.8 90.0 82.3 74.5
Temperature of Air on Condenser Coil 95°F
96.3
7.8
54.5 49.3 44.0 38.8 33.6
86.8
7.6
67.9 62.7 57.4 52.2 47.0 41.7
78.4
7.4
78.4 73.3 68.0 62.8 57.6 52.3
77.7
7.4
77.7 74.9 69.7 64.4 59.2 54.0
99.9
7.9
60.0 54.0 48.1 42.1 36.2
90.0
7.7
74.6 68.6 62.7 56.7 50.8 44.8
81.4
7.4
81.4 78.8 74.2 68.3 62.3 56.4
80.6
7.4
80.6 79.2 76.0 70.1 64.1 58.2
103.5
8.0
65.4 58.7 52.1 45.4 38.7
93.3
7.7
81.2 74.6 67.9 61.3 54.6 47.9
84.3
7.5
84.3 84.3 80.4 73.8 67.1 60.5
83.5
7.5
83.5 83.5 82.4 75.7 69.1 62.4
104.8
8.0
69.5 62.3 55.1 47.9 40.7
94.4
7.8
86.3 79.1 71.9 64.6 57.4 50.2
85.4
7.6
85.4 85.4 83.4 76.2 69.0 61.8
84.6
7.5
84.6 84.6 84.0 76.8 69.6 62.3
106.1
8.1
73.6 65.9 58.1 50.3 42.6
95.6
7.8
91.3 83.6 75.8 68.0 60.3 52.5
86.4
7.6
86.4 86.4 86.4 78.6 70.9 63.1
85.6
7.6
85.6 85.6 85.6 77.8 70.1 62.3
Temperature of Air on Condenser Coil 115°F
80.5
8.8
49.7 44.7 39.6 34.6 29.6
71.4
8.5
60.8 55.7 50.7 45.7 40.7 35.6
65.5
8.3
65.5 63.4 58.4 53.4 48.4 43.3
66.3
8.3
66.3 63.9 58.9 53.9 48.8 43.8
83.1
8.9
54.7 49.0 43.3 37.6 31.9
73.7
8.6
66.9 61.2 55.5 49.7 44.0 38.3
67.6
8.4
67.6 66.6 63.9 58.2 52.4 46.7
68.4
8.4
68.4 67.2 64.4 58.7 53.0 47.2
85.7
9.0
59.8 53.4 47.0 40.6 34.2
76.0
8.7
73.0 66.6 60.2 53.8 47.4 41.0
69.7
8.5
69.7 69.7 69.3 62.9 56.5 50.1
70.5
8.5
70.5 70.5 69.9 63.5 57.1 50.7
85.7
9.1
62.8 56.1 49.3 42.6 35.8
76.0
8.8
74.5 69.9 63.1 56.4 49.6 42.9
69.7
8.6
69.7 69.7 69.5 62.8 56.0 49.2
70.5
8.6
70.5 70.5 70.2 63.5 56.7 49.9
85.7
9.2
65.9 58.8 51.6 44.5 37.4
76.1
8.9
76.1 73.2 66.1 59.0 51.8 44.7
69.7
8.7
69.7 69.7 69.7 62.6 55.5 48.4
70.6
8.7
70.6 70.6 70.6 63.4 56.3 49.2
68
Tot.
Cap.1
(MBH)
42.9
55.8
59.9
45.0
58.9
63.4
47.1
62.1
66.8
49.9
66.8
66.8
52.7
71.5
66.8
105.5
94.3
84.7
82.3
109.0
97.4
87.6
85.0
112.5
100.6
90.4
87.8
115.0
102.8
92.4
89.7
117.5
105.0
94.4
91.7
36.5
47.1
48.7
38.9
50.4
52.2
41.3
53.8
55.7
43.0
54.6
55.1
44.7
55.3
54.5
88.4
79.1
72.0
72.0
91.5
81.9
74.5
74.5
94.6
84.7
77.0
77.0
95.2
85.2
77.5
77.6
95.9
85.8
78.1
78.1
30.6
38.3
38.8
32.6
41.0
41.5
34.6
43.7
44.3
36.1
42.5
43.2
37.6
41.2
42.1
72.6
63.8
59.0
60.6
74.7
65.6
60.7
62.3
76.7
67.4
62.4
64.0
76.1
66.8
61.9
63.5
75.5
66.3
61.4
63.0
Tot.
Input2
(kW)
Sensible Capacity (MBH)1
Return Dry Bulb (°F)
86
83
80
77
74
71
7.1
57.9 52.7 47.5 42.2 37.0
6.9
71.1 65.8 60.6 55.4 50.1 44.9
6.7
82.9 77.6 72.4 67.2 61.9 56.7
6.7
82.3 80.5 75.3 70.0 64.8 59.6
7.2
63.3 57.3 51.4 45.5 39.6
7.1
77.5 71.6 65.7 59.7 53.8 47.9
6.8
86.6 84.0 78.4 72.5 66.6 60.6
6.8
85.0 84.1 81.5 75.6 69.7 63.7
7.4
68.6 62.0 55.4 48.7 42.1
7.2
84.0 77.3 70.7 64.1 57.4 50.8
7.0
90.4 90.4 84.5 77.8 71.2 64.6
7.0
87.8 87.8 87.8 81.2 74.5 67.9
7.4
73.3 66.1 58.9 51.7 44.5
7.2
89.6 82.4 75.2 68.0 60.8 53.6
7.0
92.4 92.4 89.4 82.2 75.1 67.9
7.0
89.7 89.7 89.7 82.5 75.3 68.2
7.5
77.9 70.2 62.4 54.7 46.9
7.3
95.2 87.5 79.7 72.0 64.2 56.5
7.0
94.4 94.4 94.4 86.7 78.9 71.2
7.0
91.7 91.7 91.7 83.9 76.2 68.4
Temperature of Air on Condenser Coil 105°F
8.3
52.1 47.0 41.8 36.7 31.6
8.1
64.3 59.2 54.1 49.0 43.8 38.7
7.8
72.0 68.4 63.2 58.1 53.0 47.8
7.8
72.0 69.4 64.3 59.1 54.0 48.9
8.4
57.4 51.5 45.7 39.9 34.0
8.1
70.7 64.9 59.1 53.2 47.4 41.6
7.9
74.5 72.7 69.1 63.2 57.4 51.6
7.9
74.5 73.2 70.2 64.4 58.5 52.7
8.5
62.6 56.1 49.5 43.0 36.5
8.2
77.1 70.6 64.1 57.5 51.0 44.5
8.0
77.0 77.0 74.9 68.4 61.8 55.3
8.0
77.0 77.0 76.1 69.6 63.1 56.5
8.6
66.2 59.2 52.2 45.2 38.2
8.3
80.4 74.5 67.5 60.5 53.5 46.5
8.1
77.5 77.5 76.5 69.5 62.5 55.5
8.1
77.6 77.6 77.1 70.1 63.1 56.1
8.6
69.8 62.3 54.9 47.4 40.0
8.4
83.7 78.4 70.9 63.5 56.1 48.6
8.1
78.1 78.1 78.1 70.6 63.2 55.7
8.1
78.1 78.1 78.1 70.6 63.2 55.7
Temperature of Air on Condenser Coil 125°F
9.3
47.3 42.3 37.4 32.5 27.6
9.0
57.2 52.3 47.4 42.4 37.5 32.6
8.8
59.0 58.5 53.6 48.7 43.8 38.8
8.8
60.6 58.4 53.5 48.6 43.6 38.7
9.4
52.1 46.6 41.0 35.4 29.8
9.1
63.0 57.4 51.8 46.3 40.7 35.1
8.9
60.7 60.4 58.7 53.1 47.5 41.9
8.9
62.3 61.2 58.6 53.0 47.4 41.8
9.5
57.0 50.8 44.5 38.2 32.0
9.2
67.4 62.6 56.3 50.1 43.8 37.5
9.0
62.4 62.4 62.4 57.5 51.2 45.0
9.0
64.0 64.0 63.6 57.4 51.1 44.8
9.7
59.5 53.0 46.5 39.9 33.4
9.3
66.8 65.3 58.8 52.3 45.7 39.2
9.1
61.9 61.9 61.9 56.0 49.5 43.0
9.1
63.5 63.5 63.3 56.8 50.3 43.7
9.8
62.0 55.2 48.4 41.6 34.8
9.4
66.3 66.3 61.2 54.4 47.6 40.8
9.2
61.4 61.4 61.4 54.6 47.8 41.0
9.2
63.0 63.0 63.0 56.2 49.4 42.6
68
39.7
51.5
54.3
41.9
54.7
57.8
44.2
57.9
61.3
46.4
60.7
61.0
48.7
63.4
60.7
33.6
42.7
43.8
35.8
45.7
46.9
37.9
48.8
50.0
39.6
48.5
49.2
41.2
48.3
48.3
27.7
33.9
33.8
29.5
36.3
36.2
31.3
38.7
38.6
32.7
36.5
37.2
34.0
34.2
35.8
These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW
of the supply air blower motor.
These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products
13
265485-XTG-B-1208
TABLE 5: DR090 COOLING CAPACITY - METRIC
Air On
Evap. Coil
3
m /s
1.06
1.24
1.42
1.59
1.77
1.06
1.24
1.42
1.59
1.77
1.06
1.24
1.42
1.59
1.77
1.
2.
14
WB
(°C)
Temperature of Air on Condenser Coil 24°C
Tot.
1
Cap.
(kW)
22
19
17
14
22
19
17
14
22
19
17
14
22
19
17
14
22
19
17
14
34
30
27
25
35
31
27
26
36
32
28
27
37
33
29
28
38
34
30
29
22
19
17
14
22
19
17
14
22
19
17
14
22
19
17
14
22
19
17
14
28
25
23
23
29
26
24
24
30
27
25
24
31
28
25
25
31
28
25
25
22
19
17
14
22
19
17
14
22
19
17
14
22
19
17
14
22
19
17
14
24
21
19
19
24
22
20
20
25
22
20
21
25
22
20
21
25
22
20
21
Sensible Capacity (kW)1
Return Dry Bulb (°F)
Tot.
2
Input
(kW)
Temperature of Air on Condenser Coil 29°C
30
28
27
25
23
22
6.4
18.0 16.4 14.9 13.4 11.8
6.2
21.8 20.2 18.7 17.2 15.6 14.1
6.0
25.6 24.0 22.5 21.0 19.4 17.9
6.0
25.5 25.2 23.7 22.2 20.6 19.1
6.6
19.5 17.8 16.1 14.3 12.6
6.5
23.6 21.8 20.1 18.4 16.6 14.9
6.2
26.9 26.2 24.2 22.5 20.7 19.0
6.2
26.2 26.1 25.5 23.8 22.0 20.3
6.8
21.1 19.1 17.2 15.3 13.3
6.7
25.4 23.5 21.5 19.6 17.7 15.7
6.5
28.3 28.3 25.9 24.0 22.1 20.1
6.5
27.0 27.0 27.3 25.4 23.4 21.5
6.8
22.6 20.5 18.4 16.3 14.2
6.7
27.2 25.1 23.0 20.9 18.8 16.7
6.5
29.2 29.2 28.0 25.9 23.8 21.7
6.5
27.8 27.8 28.0 25.9 23.8 21.7
6.9
24.1 21.8 19.6 17.3 15.0
6.7
29.1 26.8 24.5 22.2 20.0 17.7
6.5
30.0 30.0 30.0 27.8 25.5 23.2
6.5
28.7 28.7 28.7 26.4 24.1 21.8
Temperature of Air on Condenser Coil 35°C
7.8
16.0 14.4 12.9 11.4 9.8
7.6
19.9 18.4 16.8 15.3 13.8 12.2
7.4
23.0 21.5 19.9 18.4 16.9 15.3
7.4
22.8 22.0 20.4 18.9 17.4 15.8
7.9
17.6 15.8 14.1 12.3 10.6
7.7
21.9 20.1 18.4 16.6 14.9 13.1
7.4
23.8 23.1 21.8 20.0 18.3 16.5
7.4
23.6 23.2 22.3 20.5 18.8 17.1
8.0
19.2 17.2 15.3 13.3 11.4
7.7
23.8 21.9 19.9 18.0 16.0 14.0
7.5
24.7 24.7 23.6 21.6 19.7 17.7
7.5
24.5 24.5 24.1 22.2 20.2 18.3
8.0
20.4 18.3 16.1 14.0 11.9
7.8
25.3 23.2 21.1 18.9 16.8 14.7
7.6
25.0 25.0 24.4 22.3 20.2 18.1
7.5
24.8 24.8 24.6 22.5 20.4 18.3
8.1
21.6 19.3 17.0 14.8 12.5
7.8
26.8 24.5 22.2 19.9 17.7 15.4
7.6
25.3 25.3 25.3 23.0 20.8 18.5
7.6
25.1 25.1 25.1 22.8 20.5 18.3
Temperature of Air on Condenser Coil 46°C
8.8
14.6 13.1 11.6 10.1 8.7
8.5
17.8 16.3 14.9 13.4 11.9 10.4
8.3
19.2 18.6 17.1 15.6 14.2 12.7
8.3
19.4 18.7 17.3 15.8 14.3 12.8
8.9
16.0 14.4 12.7 11.0 9.4
8.6
19.6 17.9 16.3 14.6 12.9 11.2
8.4
19.8 19.5 18.7 17.0 15.4 13.7
8.4
20.0 19.7 18.9 17.2 15.5 13.8
9.0
17.5 15.7 13.8 11.9 10.0
8.7
21.4 19.5 17.6 15.8 13.9 12.0
8.5
20.4 20.4 20.3 18.4 16.6 14.7
8.5
20.7 20.7 20.5 18.6 16.7 14.9
9.1
18.4 16.4 14.5 12.5 10.5
8.8
21.8 20.5 18.5 16.5 14.5 12.6
8.6
20.4 20.4 20.4 18.4 16.4 14.4
8.6
20.7 20.7 20.6 18.6 16.6 14.6
9.2
19.3 17.2 15.1 13.0 11.0
8.9
22.3 21.5 19.4 17.3 15.2 13.1
8.7
20.4 20.4 20.4 18.3 16.3 14.2
8.7
20.7 20.7 20.7 18.6 16.5 14.4
Tot.
1
20
Cap.
(kW)
12.6
16.4
17.6
13.2
17.3
18.6
13.8
18.2
19.6
14.6
19.6
19.6
15.4
21.0
19.6
31
28
25
24
32
29
26
25
33
29
26
26
34
30
27
26
34
31
28
27
10.7
13.8
14.3
11.4
14.8
15.3
12.1
15.8
16.3
12.6
16.0
16.2
13.1
16.2
16.0
26
23
21
21
27
24
22
22
28
25
23
23
28
25
23
23
28
25
23
23
9.0
11.2
11.4
9.6
12.0
12.2
10.1
12.8
13.0
10.6
12.5
12.7
11.0
12.1
12.3
21
19
17
18
22
19
18
18
22
20
18
19
22
20
18
19
22
19
18
18
Sensible Capacity (kW)1
Return Dry Bulb (°C)
Tot.
2
Input
(kW)
30
28
27
25
23
22
7.1
17.0 15.4 13.9 12.4 10.8
6.9
20.8 19.3 17.8 16.2 14.7 13.2
6.7
24.3 22.8 21.2 19.7 18.2 16.6
6.7
24.1 23.6 22.1 20.5 19.0 17.5
7.2
18.5 16.8 15.1 13.3 11.6
7.1
22.7 21.0 19.2 17.5 15.8 14.0
6.8
25.4 24.6 23.0 21.2 19.5 17.8
6.8
24.9 24.7 23.9 22.2 20.4 18.7
7.4
20.1 18.2 16.2 14.3 12.3
7.2
24.6 22.7 20.7 18.8 16.8 14.9
7.0
26.5 26.5 24.8 22.8 20.9 18.9
7.0
25.7 25.7 25.7 23.8 21.8 19.9
7.4
21.5 19.4 17.3 15.2 13.0
7.2
26.3 24.2 22.0 19.9 17.8 15.7
7.0
27.1 27.1 26.2 24.1 22.0 19.9
7.0
26.3 26.3 26.3 24.2 22.1 20.0
7.5
22.8 20.6 18.3 16.0 13.8
7.3
27.9 25.6 23.4 21.1 18.8 16.5
7.0
27.7 27.7 27.7 25.4 23.1 20.9
7.0
26.9 26.9 26.9 24.6 22.3 20.1
Temperature of Air on Condenser Coil 41°C
8.3
15.3 13.8 12.3 10.8 9.3
8.1
18.9 17.4 15.9 14.3 12.8 11.3
7.8
21.1 20.0 18.5 17.0 15.5 14.0
7.8
21.1 20.3 18.8 17.3 15.8 14.3
8.4
16.8 15.1 13.4 11.7 10.0
8.1
20.7 19.0 17.3 15.6 13.9 12.2
7.9
21.8 21.3 20.2 18.5 16.8 15.1
7.9
21.8 21.5 20.6 18.9 17.2 15.4
8.5
18.3 16.4 14.5 12.6 10.7
8.2
22.6 20.7 18.8 16.9 14.9 13.0
8.0
22.6 22.6 21.9 20.0 18.1 16.2
8.0
22.6 22.6 22.3 20.4 18.5 16.6
8.6
19.4 17.3 15.3 13.3 11.2
8.3
23.6 21.8 19.8 17.7 15.7 13.6
8.1
22.7 22.7 22.4 20.4 18.3 16.3
8.1
22.7 22.7 22.6 20.5 18.5 16.5
8.6
20.4 18.3 16.1 13.9 11.7
8.4
24.5 23.0 20.8 18.6 16.4 14.2
8.1
22.9 22.9 22.9 20.7 18.5 16.3
8.1
22.9 22.9 22.9 20.7 18.5 16.3
Temperature of Air on Condenser Coil 52°C
9.3
13.9 12.4 11.0 9.5
8.1
9.0
16.8 15.3 13.9 12.4 11.0 9.6
8.8
17.3 17.2 15.7 14.3 12.8 11.4
8.8
17.7 17.1 15.7 14.2 12.8 11.3
9.4
15.3 13.6 12.0 10.4 8.7
9.1
18.5 16.8 15.2 13.6 11.9 10.3
8.9
17.8 17.7 17.2 15.6 13.9 12.3
8.9
18.3 17.9 17.2 15.5 13.9 12.2
9.5
16.7 14.9 13.0 11.2 9.4
9.2
19.7 18.3 16.5 14.7 12.8 11.0
9.0
18.3 18.3 18.3 16.9 15.0 13.2
9.0
18.8 18.8 18.6 16.8 15.0 13.1
9.7
17.4 15.5 13.6 11.7 9.8
9.3
19.6 19.1 17.2 15.3 13.4 11.5
9.1
18.1 18.1 18.1 16.4 14.5 12.6
9.1
18.6 18.6 18.6 16.6 14.7 12.8
9.8
18.2 16.2 14.2 12.2 10.2
9.4
19.4 19.4 17.9 16.0 14.0 12.0
9.2
18.0 18.0 18.0 16.0 14.0 12.0
9.2
18.5 18.5 18.5 16.5 14.5 12.5
20
11.6
15.1
15.9
12.3
16.0
16.9
12.9
17.0
18.0
13.6
17.8
17.9
14.3
18.6
17.8
9.8
12.5
12.8
10.5
13.4
13.7
11.1
14.3
14.7
11.6
14.2
14.4
12.1
14.1
14.2
8.1
9.9
9.9
8.6
10.6
10.6
9.2
11.3
11.3
9.6
10.7
10.9
10.0
10.0
10.5
These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW
of the supply air blower motor.
These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products
265485-XTG-B-1208
TABLE 6: DR090 COOLING CAPACITY (ALTERNATE REHEAT MODE) - IMPERIAL
Air On
Evap. Coil
CFM
2250
2625
3000
3375
3750
2250
2625
3000
3375
3750
2250
2625
3000
3375
3750
1.
2.
Temperature of Air on Condenser Coil 75°F
WB
(°F)
Tot.
Cap.1
(MBH)
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
48.7
43.9
40.2
40.8
50.8
45.7
41.9
42.6
52.9
47.6
43.6
44.3
54.6
49.2
45.0
45.8
56.3
50.7
46.4
47.2
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
38.6
34.1
29.1
33.4
40.0
35.3
30.2
34.6
41.3
36.6
31.2
35.8
42.3
37.4
32.0
36.6
43.3
38.3
32.7
37.5
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
29.3
24.9
21.3
25.3
30.1
25.6
21.9
26.0
31.0
26.3
22.5
26.8
30.4
25.8
22.1
26.3
29.8
25.3
21.7
25.8
Tot.
Input2
(kW)
Temperature of Air on Condenser Coil 85°F
Sensible Capacity (MBH)1
Return Dry Bulb (°F)
86
83
80
77
74
71
6.8
6.4
8.0
7.4
6.9
6.3
5.7
5.2
6.2
18.0 17.4 16.8 16.3 15.7 15.2
5.8
23.4 22.8 22.2 21.7 21.1 20.6
6.8
6.4
12.6 11.7 10.8 9.9
9.0
8.1
6.2
26.4 25.5 24.6 23.7 22.8 21.9
5.8
33.8 33.6 32.8 31.8 30.9 30.0
6.7
6.4
17.3 16.0 14.8 13.5 12.2 11.0
6.2
34.9 33.7 32.4 31.2 29.9 28.6
5.8
44.3 44.3 43.3 42.0 40.7 39.5
6.7
6.4
20.3 18.8 17.3 15.7 14.2 12.7
6.2
40.7 40.0 39.4 37.9 36.4 34.8
5.8
45.8 45.8 45.2 43.7 42.2 40.7
6.7
6.4
23.3 21.6 19.8 18.0 16.2 14.5
6.2
46.4 46.4 46.4 44.6 42.8 41.1
5.7
47.2 47.2 47.2 45.4 43.6 41.9
Temperature of Air on Condenser Coil 95°F
7.3
7.0
1.9
1.8
1.6
1.5
1.4
1.2
6.7
6.1
6.0
5.9
5.8
5.6
5.5
6.3
7.8
7.7
7.6
7.4
7.3
7.2
7.3
7.0
5.4
5.0
4.6
4.2
3.9
3.5
6.7
17.5 17.1 16.7 16.3 15.9 15.5
6.3
21.8 21.7 21.4 21.0 20.6 20.2
7.4
7.1
8.9
8.3
7.6
7.0
6.3
5.7
6.7
28.8 28.1 27.5 26.8 26.1 25.5
6.4
35.8 35.8 35.3 34.6 34.0 33.3
7.4
7.1
11.7 10.8 9.9
9.1
8.2
7.4
6.8
30.7 30.4 30.1 29.2 28.4 27.5
6.4
36.6 36.6 36.4 35.5 34.7 33.8
7.5
7.2
14.4 13.3 12.3 11.2 10.1 9.1
6.8
32.7 32.7 32.7 31.7 30.6 29.5
6.4
37.5 37.5 37.5 36.4 35.3 34.3
Temperature of Air on Condenser Coil 115°F
7.9
28.2 28.5 28.8 29.0 29.3
7.5
7.2
6.9
8.0
5.2
5.3
5.3
5.4
5.4
7.6
7.2
7.0
8.0
7.6
2.4
2.3
2.1
1.9
1.7
1.6
7.3
20.1 19.9 19.8 19.6 19.4 19.2
7.0
26.8 26.8 26.8 26.6 26.4 26.2
8.1
7.7
3.7
3.4
3.2
2.9
2.6
2.4
7.3
20.9 20.8 20.7 20.4 20.2 19.9
7.0
26.3 26.3 26.3 26.0 25.7 25.5
8.1
7.7
4.9
4.6
4.2
3.9
3.5
3.2
7.4
21.7 21.7 21.7 21.3 21.0 20.6
7.1
25.8 25.8 25.8 25.4 25.1 24.7
68
Tot.
Cap.1
(MBH)
4.6
14.6
20.0
7.2
21.0
29.1
9.7
27.4
38.2
11.2
33.3
39.2
12.7
39.3
40.1
43.6
39.0
34.6
37.1
45.4
40.5
36.0
38.6
47.1
42.1
37.4
40.0
48.5
43.3
38.5
41.2
49.8
44.5
39.6
42.3
1.1
5.4
7.0
3.1
15.1
19.9
5.0
24.8
32.7
6.5
26.7
32.9
8.0
28.5
33.2
33.9
29.5
25.2
29.3
35.0
30.5
26.0
30.3
36.2
31.4
26.9
31.3
36.4
31.6
27.0
31.4
36.6
31.8
27.2
31.6
1.4
19.1
26.1
2.1
19.7
25.2
2.9
20.3
24.4
24.6
20.2
17.3
21.2
25.2
20.7
17.7
21.8
25.8
21.2
18.1
22.3
24.4
20.0
17.1
21.1
23.1
18.8
16.1
19.9
Tot.
Input2
(kW)
Sensible Capacity (MBH)1
Return Dry Bulb (°F)
86
83
80
77
74
71
7.0
6.7
4.9
4.6
4.2
3.9
3.6
3.2
6.4
12.0 11.7 11.4 11.0 10.7 10.3
6.0
15.6 15.2 14.9 14.6 14.2 13.9
7.1
6.7
9.0
8.4
7.7
7.1
6.4
5.8
6.4
21.9 21.3 20.6 20.0 19.3 18.7
6.1
27.8 27.6 27.1 26.4 25.8 25.1
7.1
6.7
13.1 12.2 11.2 10.2 9.3
8.3
6.5
31.8 30.9 29.9 29.0 28.0 27.1
6.1
40.0 40.0 39.3 38.3 37.4 36.4
7.1
6.8
16.0 14.8 13.6 12.4 11.2 10.0
6.5
35.7 35.2 34.7 33.6 32.4 31.2
6.1
41.2 41.2 40.8 39.6 38.4 37.2
7.1
6.8
18.9 17.4 16.0 14.6 13.2 11.8
6.5
39.6 39.6 39.6 38.1 36.7 35.3
6.1
42.3 42.3 42.3 40.9 39.5 38.1
Temperature of Air on Condenser Coil 105°F
7.6
12.9 13.0 13.1 13.1 13.2
7.3
6.9
6.6
7.7
7.3
2.4
2.2
2.0
1.8
1.7
1.5
7.0
5.8
5.6
5.4
5.2
5.1
4.9
6.6
6.8
6.8
6.8
6.6
6.4
6.3
7.7
7.3
5.7
5.3
4.9
4.4
4.0
3.6
7.0
24.4 24.0 23.6 23.2 22.8 22.4
6.7
31.3 31.3 31.0 30.6 30.2 29.8
7.7
7.4
7.7
7.1
6.6
6.0
5.4
4.9
7.1
25.8 25.6 25.4 24.8 24.3 23.7
6.7
31.4 31.4 31.3 30.8 30.2 29.6
7.8
7.4
9.6
8.9
8.2
7.5
6.8
6.1
7.1
27.2 27.2 27.2 26.5 25.8 25.1
6.8
31.6 31.6 31.6 30.9 30.2 29.5
Temperature of Air on Condenser Coil 125°F
8.3
24.6 24.6 24.6 24.6 24.6
7.8
7.5
7.2
8.3
11.2 11.4 11.7 12.0 12.2
7.8
7.5
7.3
8.3
7.9
7.6
15.8 15.8 15.9 16.0 16.0 16.1
7.3
22.3 22.3 22.3 22.3 22.3 22.3
8.4
7.9
7.6
16.0 16.0 16.0 16.1 16.1 16.1
7.4
21.1 21.1 21.1 21.1 21.1 21.1
8.5
8.0
0.2
0.2
0.2
0.2
0.2
0.3
7.7
16.1 16.1 16.1 16.1 16.1 16.1
7.4
19.9 19.9 19.9 19.9 19.9 19.9
68
2.9
10.0
13.5
5.1
18.0
24.5
7.4
26.1
35.4
8.9
30.0
36.0
10.3
33.9
36.6
1.3
4.7
6.1
3.2
22.0
29.4
4.3
23.2
29.1
5.4
24.4
28.8
16.2
22.3
16.2
21.1
0.3
16.1
19.9
These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW
of the supply air blower motor.
These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products
15
265485-XTG-B-1208
TABLE 7: DR090 COOLING CAPACITY (ALTERNATE REHEAT MODE) - METRIC
Air On
Evap. Coil
3
m /s
1.06
1.24
1.42
1.59
1.77
1.06
1.24
1.42
1.59
1.77
1.06
1.24
1.42
1.59
1.77
1.
2.
16
WB
(°C)
Temperature of Air on Condenser Coil 24°C
Tot.
1
Cap.
(kW)
22
19
17
14
22
19
17
14
22
19
17
14
22
19
17
14
22
19
17
14
14
13
12
12
15
13
12
12
16
14
13
13
16
14
13
13
17
15
14
14
22
19
17
14
22
19
17
14
22
19
17
14
22
19
17
14
22
19
17
14
11
10
9
10
12
10
9
10
12
11
9
10
12
11
9
11
13
11
10
11
22
19
17
14
22
19
17
14
22
19
17
14
22
19
17
14
22
19
17
14
9
7
6
7
9
7
6
8
9
8
7
8
9
8
6
8
9
7
6
8
Sensible Capacity (kW)1
Return Dry Bulb (°F)
Tot.
2
Input
(kW)
Temperature of Air on Condenser Coil 29°C
30
28
27
25
23
22
6.8
6.4
2.3
2.2
2.0
1.8
1.7
1.5
6.2
5.3
5.1
4.9
4.8
4.6
4.4
5.8
6.8
6.7
6.5
6.4
6.2
6.0
6.8
6.4
3.7
3.4
3.2
2.9
2.6
2.4
6.2
7.7
7.5
7.2
6.9
6.7
6.4
5.8
9.9
9.8
9.6
9.3
9.1
8.8
6.7
6.4
5.1
4.7
4.3
4.0
3.6
3.2
6.2
10.2 9.9
9.5
9.1
8.8
8.4
5.8
13.0 13.0 12.7 12.3 11.9 11.6
6.7
6.4
5.9
5.5
5.1
4.6
4.2
3.7
6.2
11.9 11.7 11.5 11.1 10.7 10.2
5.8
13.4 13.4 13.3 12.8 12.4 11.9
6.7
6.4
6.8
6.3
5.8
5.3
4.8
4.2
6.2
13.6 13.6 13.6 13.1 12.6 12.0
5.7
13.8 13.8 13.8 13.3 12.8 12.3
Temperature of Air on Condenser Coil 35°C
7.3
7.0
0.6
0.5
0.5
0.4
0.4
0.4
6.7
1.8
1.8
1.7
1.7
1.6
1.6
6.3
2.3
2.3
2.2
2.2
2.1
2.1
7.3
7.0
1.6
1.5
1.4
1.2
1.1
1.0
6.7
5.1
5.0
4.9
4.8
4.7
4.5
6.3
6.4
6.4
6.3
6.2
6.0
5.9
7.4
7.1
2.6
2.4
2.2
2.0
1.9
1.7
6.7
8.4
8.2
8.0
7.9
7.7
7.5
6.4
10.5 10.5 10.3 10.2 10.0 9.8
7.4
7.1
3.4
3.2
2.9
2.7
2.4
2.2
6.8
9.0
8.9
8.8
8.6
8.3
8.1
6.4
10.7 10.7 10.7 10.4 10.2 9.9
7.5
7.2
4.2
3.9
3.6
3.3
3.0
2.7
6.8
9.6
9.6
9.6
9.3
9.0
8.7
6.4
11.0 11.0 11.0 10.7 10.4 10.0
Temperature of Air on Condenser Coil 46°C
7.9
8.3
8.4
8.4
8.5
8.6
7.5
7.2
6.9
8.0
1.5
1.5
1.6
1.6
1.6
7.6
7.2
7.0
8.0
7.6
0.7
0.7
0.6
0.6
0.5
0.5
7.3
5.9
5.8
5.8
5.7
5.7
5.6
7.0
7.8
7.8
7.8
7.8
7.7
7.7
8.1
7.7
1.1
1.0
0.9
0.8
0.8
0.7
7.3
6.1
6.1
6.1
6.0
5.9
5.8
7.0
7.7
7.7
7.7
7.6
7.5
7.5
8.1
7.7
1.4
1.3
1.2
1.1
1.0
0.9
7.4
6.3
6.3
6.3
6.2
6.1
6.0
7.1
7.6
7.6
7.6
7.4
7.3
7.2
Tot.
1
20
Cap.
(kW)
1.4
4.3
5.9
2.1
6.2
8.5
2.8
8.0
11.2
3.3
9.8
11.5
3.7
11.5
11.7
13
11
10
11
13
12
11
11
14
12
11
12
14
13
11
12
15
13
12
12
0.3
1.6
2.1
0.9
4.4
5.8
1.5
7.3
9.6
1.9
7.8
9.7
2.3
8.3
9.7
10
9
7
9
10
9
8
9
11
9
8
9
11
9
8
9
11
9
8
9
0.4
5.6
7.6
0.6
5.8
7.4
0.8
5.9
7.1
7
6
5
6
7
6
5
6
8
6
5
7
7
6
5
6
7
6
5
6
Sensible Capacity (kW)1
Return Dry Bulb (°C)
Tot.
2
Input
(kW)
30
28
27
25
23
22
7.0
6.7
1.4
1.3
1.2
1.1
1.0
0.9
6.4
3.5
3.4
3.3
3.2
3.1
3.0
6.0
4.6
4.5
4.4
4.3
4.2
4.1
7.1
6.7
2.6
2.5
2.3
2.1
1.9
1.7
6.4
6.4
6.2
6.1
5.9
5.7
5.5
6.1
8.2
8.1
7.9
7.7
7.6
7.4
7.1
6.7
3.8
3.6
3.3
3.0
2.7
2.4
6.5
9.3
9.1
8.8
8.5
8.2
7.9
6.1
11.7 11.7 11.5 11.2 10.9 10.7
7.1
6.8
4.7
4.3
4.0
3.6
3.3
2.9
6.5
10.5 10.3 10.2 9.8
9.5
9.1
6.1
12.1 12.1 12.0 11.6 11.3 10.9
7.1
6.8
5.5
5.1
4.7
4.3
3.9
3.4
6.5
11.6 11.6 11.6 11.2 10.8 10.3
6.1
12.4 12.4 12.4 12.0 11.6 11.2
Temperature of Air on Condenser Coil 41°C
7.6
3.8
3.8
3.8
3.9
3.9
7.3
6.9
6.6
7.7
7.3
0.7
0.6
0.6
0.5
0.5
0.4
7.0
1.7
1.6
1.6
1.5
1.5
1.4
6.6
2.0
2.0
2.0
1.9
1.9
1.8
7.7
7.3
1.7
1.5
1.4
1.3
1.2
1.1
7.0
7.2
7.0
6.9
6.8
6.7
6.6
6.7
9.2
9.2
9.1
9.0
8.9
8.7
7.7
7.4
2.2
2.1
1.9
1.8
1.6
1.4
7.1
7.6
7.5
7.4
7.3
7.1
7.0
6.7
9.2
9.2
9.2
9.0
8.9
8.7
7.8
7.4
2.8
2.6
2.4
2.2
2.0
1.8
7.1
8.0
8.0
8.0
7.8
7.6
7.4
6.8
9.3
9.3
9.3
9.1
8.9
8.6
Temperature of Air on Condenser Coil 52°C
8.3
7.2
7.2
7.2
7.2
7.2
7.8
7.5
7.2
8.3
3.3
3.4
3.4
3.5
3.6
7.8
7.5
7.3
8.3
7.9
7.6
4.6
4.6
4.7
4.7
4.7
4.7
7.3
6.5
6.5
6.5
6.5
6.5
6.5
8.4
7.9
7.6
4.7
4.7
4.7
4.7
4.7
4.7
7.4
6.2
6.2
6.2
6.2
6.2
6.2
8.5
8.0
0.1
0.1
0.1
0.1
0.1
0.1
7.7
4.7
4.7
4.7
4.7
4.7
4.7
7.4
5.8
5.8
5.8
5.8
5.8
5.8
20
0.8
2.9
4.0
1.5
5.3
7.2
2.2
7.7
10.4
2.6
8.8
10.6
3.0
9.9
10.7
0.4
1.4
1.8
0.9
6.4
8.6
1.3
6.8
8.5
1.6
7.1
8.4
4.7
6.5
4.7
6.2
0.1
4.7
5.8
These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW
of the supply air blower motor.
These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products
265485-XTG-B-1208
Moisture Removal Rate
(lbs Water/Hour)
DR090 Moisture Removal @ 3000 cfm
Alternate Mode @ various
indoor (dry bulb / wet bulb) conditions
70
60
50
40
30
20
10
0
65
75
85
95
105
Outdoor Temperature (°F)
75db/71wb
85db/71wb
80db/71wb
80db/67wb
75db/67wb
85db/67wb
FIGURE 4 - DR090 MOISTURE REMOVAL (ALTERNATE MODE) - IMPERIAL
Moisture Removal Rate
(lbs Water/Hour)
DR090 Moisture Removal @ 3000 cfm
Normal Mode @ various
indoor (dry bulb / wet bulb) conditions
30
25
20
15
10
5
65
75
85
95
105
Outdoor Temperature (°F)
75db/71wb
85db/71wb
80db/71wb
80db/67wb
75db/67wb
85db/67wb
FIGURE 5 - DR090 MOISTURE REMOVAL (NORMAL MODE) - IMPERIAL
Johnson Controls Unitary Products
17
265485-XTG-B-1208
Moisture Removal Rate
(kg Water/Hour)
DR090 Moisture Removal @ 1.42 m3/s
Alternate Mode @ various
indoor (dry bulb / wet bulb) conditions
30
25
20
15
10
5
0
18.3
29.4
23.9
35.0
40.6
Outdoor Temperature (°C)
23.9db/21.7wb
29.4db/21.7wb
26.7db/21.7wb
26.7db/19.4wb
23.9db/19.4wb
29.4db/19.4wb
FIGURE 6 - DR090 MOISTURE REMOVAL (ALTERNATE MODE) - METRIC
Moisture Removal Rate
(kg Water/Hour)
DR090 Moisture Removal @ 1.42 m3/s
Normal Mode @ various
indoor (dry bulb / wet bulb) conditions
14
12
10
8
6
4
2
18.3
29.4
23.9
35.0
40.6
Outdoor Temperature (°C)
23.9db/21.7wb
29.4db/21.7wb
26.7db/21.7wb
26.7db/19.4wb
23.9db/19.4wb
29.4db/19.4wb
FIGURE 7 - DR090 MOISTURE REMOVAL (NORMAL MODE) - METRIC
18
Johnson Controls Unitary Products
265485-XTG-B-1208
TABLE 8: ELECTRICAL DATA 7-1/2 TON
Compressors
Voltage1
RLA
ea.
380
415
7.3
7.3
LRA
ea.
58.0
58.0
OD
Fan
Motors
Supply Blower
Motor FLA
FLA
ea.
1.1
1.1
1.5
HP
4.3
4.3
2
HP
5.2
5.2
Pwr Exh
Motor
Electric
Heater
Model No.
Actual Heater
kW
Amps
1.5
HP
FLA
2.2
2.2
Min. Circuit
Ampacity
(Amps)
2
HP
MCA
w/Power
Exhaust
(Amps)
1.5
HP
2
HP
Max Fuse2
Size (Amps)
Max Fuse Size
w/Power
Exhaust
(Amps)
1.5
HP
2
HP
1.5
HP
2
HP
None
--
--
22.9
23.8 25.1 26.0
30
30
30
30
2TP04520950
5.6
8.5
22.9
23.8 25.1 26.0
30
30
30
30
2TP04521850
11.3
17.2
26.8
28.0 29.6 30.7
30
30
30
35
2TP04522450
15.0
22.8
33.9
35.0 36.6 37.7
35
35
40
40
2TP04523650
21.3
32.4
45.8
47.0 48.6 49.7
50
50
50
50
None
--
--
22.9
23.8 25.1 26.0
30
30
30
30
2TP04520950
6.7
9.3
22.9
23.8 25.1 26.0
30
30
30
30
2TP04521850
13.5
18.8
28.9
30.0 31.6 32.7
30
30
35
35
2TP04522450
17.9
24.9
36.5
37.6 39.3 40.4
40
40
40
45
2TP04523650
25.4
35.3
49.5
50.7 52.3 53.4
50
60
60
60
1. Unit voltage limitations: minimum utilization 342 volts, maximum utilization 457 volts.
2. Maximum HACR breaker of the same amp size is acceptable.
Johnson Controls Unitary Products
19
265485-XTG-B-1208
TABLE 9: BLOWER PERFORMANCE 7-1/2 TON STANDARD MOTOR - SIDE DUCT (IMPERIAL)
Turns Open
ESP
(iwg)
0
1
2
3
4
5
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
0.2
-
-
-
-
-
-
-
-
-
-
-
-
3580
1340
1.44
3351
1203
1.29
0.4
-
-
-
-
-
-
-
-
-
3436
1368
1.47
3158
1213
1.30
2929
1076
1.15
0.6
-
-
-
-
-
-
3310
1402
1.50
2983
1229
1.32
2705
1073
1.15
2475
936
1.00
0.8
-
-
-
3138
1423
1.53
2762
1232
1.32
2435
1058
1.14
-
-
-
-
-
-
1.0
2858
1414
1.52
2433
1205
1.29
2057
1013
1.09
-
-
-
-
-
-
-
-
-
TABLE 10: BLOWER PERFORMANCE 7-1/2 TON STANDARD MOTOR - SIDE DUCT (METRIC)
Turns Open
ESP
(Pa)
0
1
2
3
4
5
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
50
-
-
-
-
-
-
-
-
-
-
-
-
1.69
1.34
1.07
1.58
1.20
0.96
100
-
-
-
-
-
-
-
-
-
1.62
1.37
1.09
1.49
1.21
0.97
1.38
1.08
0.86
149
-
-
-
-
-
-
1.56
1.40
1.12
1.41
1.23
0.98
1.28
1.07
0.86
1.17
0.94
0.75
199
-
-
-
1.48
1.42
1.14
1.30
1.23
0.99
1.15
1.06
0.85
-
-
-
-
-
-
249
1.35
1.41
1.13
1.15
1.20
0.96
0.97
1.01
0.81
-
-
-
-
-
-
-
-
-
TABLE 11: BLOWER PERFORMANCE 7-1/2 TON OPTIONAL MOTOR - SIDE DUCT (IMPERIAL)
Turns Open
ESP
(iwg)
20
0
1
2
3
4
5
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
0.2
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
3938
1666
1.79
0.4
-
-
-
-
-
-
-
-
-
-
-
-
3925
1764
1.89
3576
1523
1.63
0.6
-
-
-
-
-
-
-
-
-
3901
1868
2.00
3524
1611
1.73
3176
1370
1.47
0.8
-
-
-
-
-
-
3862
1971
2.11
3457
1697
1.82
3080
1440
1.54
2732
1199
1.29
1.0
-
-
-
3801
2065
2.22
3368
1776
1.90
2963
1502
1.61
2586
1245
1.34
-
-
-
1.2
3712
2145
2.30
3251
1840
1.97
2818
1550
1.66
2413
1276
1.37
-
-
-
-
-
-
1.4
3101
1883
2.02
2640
1577
1.69
-
-
-
-
-
-
-
-
-
-
-
-
1.6
2423
1576
1.69
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Johnson Controls Unitary Products
265485-XTG-B-1208
TABLE 12: BLOWER PERFORMANCE 7-1/2 TON OPTIONAL MOTOR - SIDE DUCT (METRIC)
Turns Open
ESP
(Pa)
0
1
2
3
4
5
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
50
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1.86
1.67
1.33
100
-
-
-
-
-
-
-
-
-
-
-
-
1.85
1.76
1.41
1.69
1.52
1.22
149
-
-
-
-
-
-
-
-
-
1.84
1.87
1.49
1.66
1.61
1.29
1.50
1.37
1.10
199
-
-
-
-
-
-
1.82
1.97
1.58
1.63
1.70
1.36
1.45
1.44
1.15
1.29
1.20
0.96
249
-
-
-
1.79
2.07
1.65
1.59
1.78
1.42
1.40
1.50
1.20
1.22
1.24
1.00
-
-
-
299
1.75
2.15
1.72
1.53
1.84
1.47
1.33
1.55
1.24
1.14
1.28
1.02
-
-
-
-
-
-
349
1.46
1.88
1.51
1.25
1.58
1.26
-
-
-
-
-
-
-
-
-
-
-
-
398
1.14
1.58
1.26
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
TABLE 13: BLOWER PERFORMANCE 7-1/2 TON STANDARD MOTOR - DOWNSHOT (IMPERIAL)
Turns Open
ESP
(iwg)
0
1
2
3
4
5
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
0.2
-
-
-
3727
1624
1.74
3532
1506
1.62
3325
1372
1.47
3107
1222
1.31
2877
1056
1.13
0.4
3554
1606
1.72
3370
1505
1.61
3175
1387
1.49
2968
1253
1.34
2750
1103
1.18
2521
937
1.01
0.6
3195
1493
1.60
3011
1391
1.49
2816
1273
1.37
2609
1140
1.22
2391
990
1.06
2161
823
0.88
0.8
2806
1372
1.47
2622
1270
1.36
2427
1153
1.24
2220
1019
1.09
-
-
-
-
-
-
1.0
2361
1232
1.32
2178
1131
1.21
-
-
-
-
-
-
-
-
-
-
-
-
TABLE 14: BLOWER PERFORMANCE 7-1/2 TON STANDARD MOTOR - DOWNSHOT (METRIC)
Turns Open
ESP
(Pa)
0
1
2
3
4
5
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
50
-
-
-
1.76
1.62
1.30
1.67
1.51
1.20
1.57
1.37
1.10
1.47
1.22
0.98
1.36
1.06
0.84
100
1.68
1.61
1.29
1.59
1.50
1.20
1.50
1.39
1.11
1.40
1.25
1.00
1.30
1.10
0.88
1.19
0.94
0.75
149
1.51
1.49
1.19
1.42
1.39
1.11
1.33
1.27
1.02
1.23
1.14
0.91
1.13
0.99
0.79
1.02
0.82
0.66
199
1.32
1.37
1.10
1.24
1.27
1.02
1.15
1.15
0.92
1.05
1.02
0.82
-
-
-
-
-
-
249
1.11
1.23
0.99
1.03
1.13
0.90
-
-
-
-
-
-
-
-
-
-
-
-
Johnson Controls Unitary Products
21
265485-XTG-B-1208
TABLE 15: BLOWER PERFORMANCE 7-1/2 TON OPTIONAL MOTOR - DOWNSHOT (IMPERIAL)
Turns Open
ESP
(iwg)
0
1
2
3
4
5
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
CFM
Watts
BHP
0.2
-
-
-
-
-
-
-
-
-
-
-
-
3786
1702
1.83
3476
1489
1.60
0.4
-
-
-
-
-
-
-
-
-
3727
1791
1.92
3409
1570
1.68
3099
1357
1.46
0.6
-
-
-
3994
2117
2.27
3661
1881
2.02
3335
1652
1.77
3018
1431
1.54
2708
1218
1.31
0.8
-
-
-
3590
1969
2.11
3256
1733
1.86
2931
1504
1.61
2613
1283
1.38
2304
1070
1.15
1.0
3516
2053
2.20
3174
1809
1.94
2841
1573
1.69
2515
1344
1.44
2198
1123
1.21
-
-
-
1.2
3091
1880
2.02
2749
1636
1.76
2416
1400
1.50
2090
1171
1.26
-
-
-
-
-
-
1.4
2658
1692
1.82
2316
1448
1.55
-
-
-
-
-
-
-
-
-
-
-
-
1.6
2218
1486
1.59
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
TABLE 16: BLOWER PERFORMANCE 7-1/2 TON OPTIONAL MOTOR - DOWNSHOT (METRIC)
Turns Open
ESP
(Pa)
0
1
2
3
4
5
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
m3/s
In
(kW)
Out
(kW)
50
-
-
-
-
-
-
-
-
-
-
-
-
1.79
1.70
1.36
1.64
1.49
1.19
100
-
-
-
-
-
-
-
-
-
1.76
1.79
1.43
1.61
1.57
1.26
1.46
1.36
1.09
149
-
-
-
1.89
2.12
1.69
1.73
1.88
1.50
1.57
1.65
1.32
1.42
1.43
1.15
1.28
1.22
0.97
199
-
-
-
1.69
1.97
1.58
1.54
1.73
1.39
1.38
1.50
1.20
1.23
1.28
1.03
1.09
1.07
0.86
249
1.66
2.05
1.64
1.50
1.81
1.45
1.34
1.57
1.26
1.19
1.34
1.08
1.04
1.12
0.90
-
-
-
299
1.46
1.88
1.50
1.30
1.64
1.31
1.14
1.40
1.12
0.99
1.17
0.94
-
-
-
-
-
-
349
1.25
1.69
1.35
1.09
1.45
1.16
-
-
-
-
-
-
-
-
-
-
-
-
398
1.05
1.49
1.19
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
NOTES FOR TABLES 9 THROUGH 16:
•
“Turns Open” refers to the setting of the variable pitch
motor sheave, where “0 Turns Open” is fully closed.
•
Blower performance includes dry coil and 2” (51mm)
throw-away filters.
•
Blower performance for gas heat includes the maximum
number of heat tubes available for each tonnage.
•
ESP (External Static Pressure) given is that available for
the supply and return air duct system. All internal resistances have been deducted from the total static pressure
of the blower.
22
Johnson Controls Unitary Products
265485-XTG-B-1208
TABLE 17: ADDITIONAL STATIC RESISTANCE (IMPERIAL)
CFM
Cooling Only1
Electric Heat KW2
Economizer2 3
9
18
24
36
54
0.10
1900
0.06
0.02
0.05
0.06
0.07
0.08
2100
0.07
0.02
0.06
0.07
0.08
0.09
0.11
2300
0.08
0.02
0.07
0.08
0.09
0.10
0.13
2500
0.09
0.02
0.08
0.09
0.10
0.11
0.14
2700
0.11
0.03
0.09
0.10
0.12
0.13
0.16
2900
0.12
0.03
0.10
0.11
0.13
0.14
0.18
3100
0.14
0.03
0.12
0.13
0.15
0.16
0.20
3300
0.16
0.03
0.13
0.14
0.17
0.18
0.22
3500
0.18
0.04
0.15
0.16
0.19
0.20
0.24
3700
0.20
0.04
0.17
0.18
0.21
0.22
0.26
3900
0.23
0.04
0.19
0.20
0.23
0.24
0.28
4100
0.25
0.04
0.21
0.22
0.25
0.26
0.31
4300
0.28
0.05
0.23
0.24
0.28
0.29
0.34
4500
0.30
0.05
0.25
0.26
0.30
0.31
0.37
4700
0.33
0.05
0.28
0.29
0.33
0.34
0.40
4900
0.36
0.05
0.30
0.31
0.35
0.37
0.43
5100
0.39
0.06
0.33
0.34
0.38
0.40
0.46
5300
0.42
0.06
0.35
0.37
0.41
0.43
0.49
5500
0.45
0.06
0.38
0.40
0.44
0.46
0.53
5700
0.48
0.06
0.41
0.43
0.47
0.49
0.56
5900
0.52
0.07
0.44
0.46
0.50
0.53
0.59
6100
0.56
0.07
0.47
0.49
0.53
0.56
0.62
6300
0.60
0.07
0.50
0.53
0.56
0.59
0.65
1. Add these resistance values to the available static resistance in the respective Blower Performance Tables.
2. Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.
3. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return
air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
Johnson Controls Unitary Products
23
265485-XTG-B-1208
TABLE 18: ADDITIONAL STATIC RESISTANCE (METRIC)
m3/s
Cooling Only1
Electric Heat kW2
Economizer2 3
9
18
24
36
54
0.89
14.9
5.0
12.4
14.9
17.4
19.9
24.8
0.99
17.4
5.0
14.9
17.4
19.9
22.4
27.3
1.08
19.9
5.0
17.4
19.9
22.4
24.8
32.3
1.18
22.4
5.0
19.9
22.4
24.8
27.3
34.8
1.27
27.3
7.5
22.4
24.8
29.8
32.3
39.7
1.36
29.8
7.5
24.8
27.3
32.3
34.8
44.7
1.46
34.8
7.5
29.8
32.3
37.3
39.7
49.7
1.55
39.7
7.5
32.3
34.8
42.2
44.7
54.6
1.65
44.7
9.9
37.3
39.7
47.2
49.7
59.6
1.74
49.7
9.9
42.2
44.7
52.2
49.7
64.6
1.83
57.1
9.9
47.2
49.7
57.1
59.6
69.5
1.93
62.1
9.9
52.2
54.6
62.1
64.6
77.0
1.02
69.5
12.4
57.1
59.6
69.5
72.0
84.4
2.12
74.5
12.4
62.1
64.6
74.5
77.0
91.9
2.21
82.0
12.4
69.5
72.0
82.0
84.4
99.3
2.30
89.4
12.4
74.5
77.0
86.9
91.9
106.8
2.40
96.9
14.9
82.0
84.4
94.4
99.3
114.2
2.49
104.3
14.9
86.9
91.9
101.8
106.8
121.7
2.59
111.8
14.9
94.4
99.3
109.3
114.2
131.6
2.68
119.2
14.9
101.8
106.8
116.7
121.7
139.1
2.77
129.1
17.4
109.3
114.2
124.2
131.6
146.5
2.87
139.1
17.4
116.7
121.7
131.6
139.1
154.0
2.96
149.0
17.4
124.2
131.6
139.1
146.5
161.4
1. Add these resistance values to the available static resistance in the respective Blower Performance Tables.
2. Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.
3. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return
air duct system is less than 62.1 Pa, the unit will deliver less m3/s during full economizer operation.
24
Johnson Controls Unitary Products
265485-XTG-B-1208
TABLE 19: ELECTRIC HEAT MINIMUM SUPPLY AIR
- IMPERIAL
HEATER
kW
TABLE 20: ELECTRIC HEAT MINIMUM SUPPLY AIR
- METRIC
UNIT MODEL SIZE, NOMINAL TONS
HEATER
UNIT MODEL SIZE, NOMINAL TONS
7.5
VOLTAGE
7.5
MINIMUM SUPPLY AIR CFM
9
2250
9
18
2250
18
380/415
VOLTAGE
kW
MINIMUM SUPPLY AIR m3/s
1.06
1.06
380/415
24
2250
24
1.06
36
2250
36
1.06
MOTOR SHEAVE
BLOWER SHEAVE
TABLE 21: INDOOR BLOWER SPECIFICATIONS
MOTOR
MODEL
BELT
HP
RPM
Eff.
SF
Frame
Datum Dia. (in.)
Bore (in.)
Model
Datum Dia. (in.)
Bore (in.)
Model
1-1/2
1725
80%
1.15
56
3.4 - 4.4
7/8
1VM50
7.5
1
AK79
A55
2
1725
80%
1.15
56
3.4 - 4.4
7/8
1VM50
6.5
1
AK69
A53
DR090
TABLE 22: 4 POINT LOAD WEIGHT
Location (lbs. (kg.))
Model
090
A
B
C
D
250
(113.4)
215
(97.5)
309
(140.2)
374
(169.6)
Y
X
FRONT
LEFT
F R O N T
L E F T
B
A
C
Unit Model Number
X
Y
DR090
41 (1041)
24 (610)
D
FIGURE 9 - UNIT CENTER OF GRAVITY
FIGURE 8 - UNIT 4 POINT LOAD
Johnson Controls Unitary Products
25
265485-XTG-B-1208
TABLE 23: 6 POINT LOAD WEIGHT
Locations (lbs. (kg.))
Model
090
A
B
C
D
E
F
171
(77.6)
154
(69.9)
139
(63.0)
201
(91.2)
225
(102.0)
258
(117.0)
TABLE 24: UNIT WEIGHT
Model
Shipping Weight
lbs. (kg)
Operating Weight
lbs. (kg)
090
1163 (527.5)
1148 (520.7)
F R O N T
L E F T
D
C
B
A
E
F
FIGURE 10 - UNIT 6 POINT LOAD
30-11/32
(770)
8
Power
Entry
Ø 2-1/2
(65)
4-1/4
(110)
See Detail
B
Control
Entry
Ø 7/8
(22)
Power
Entry
Ø 2-1/2
(65)
59
(1500)
17-3/16
30-3/16
(435)
(765)
6-3/16
24-3/16
(155)
(615)
LEFT
11-1/2
(290)
Convenience
Power
Outlet
Entry
Ø 7/8
(22)
27
(685)
FRONT
For Drain
Dimensions
See Detail D
89
(2260)
For Baserail
Dimensions
See Detail C
NOTE: (xxx) indicates dimensions
given in millimeters
FIGURE 11 - UNIT DIMENSIONS
TABLE 25: UNIT HEIGHT
26
Unit Model Number
X
DR090
50 3/4 (1289)
Johnson Controls Unitary Products
265485-XTG-B-1208
G a s P ip e In le t
2 -3 /8
(6 0 )
DETAIL C
DETAIL B
5 -1 /4
(1 3 5 )
3 -3 /4
(9 5 )
B a s e
P a n
1 7 -1 3 /1 6
(4 5 0 )
V ie w o f W a ll A c r o s s fr o m
C o il
3 -9 /1 6
(9 0 )
TABLE 26: UNIT CLEARANCES 1
Top2
72(1830)
Right
12(305)
Front
36(915)
Left
36(915)
Rear3
36(915)
Bottom4
0(0)
DETAIL D
1. In inches and millimeters, in.(mm).
2. Units must be installed outdoors. Overhanging structure or shrubs should not obstruct condenser air discharge outlet.
3. To remove the slide-out drain pan, a rear clearance of
60” (1525 mm) is required. If space is unavailable, the
drain pan can be removed through the front by separating the corner wall.
4. Units may be installed on combustible floors.
5 -3 /8
(1 3 5 )
R IG H T
8 0 -5 /8
(2 0 5 0 )
IN S U L A T E D D E C K U N D E R
C O N D E N S E R S E C T IO N
2 0
(5 1 0 )
S U P P L Y
6
2 0
(5 1 0 ) (1 5 0 )
2 T Y P .
(5 0 )
R E T U R N
3 0
(7 6 0 )
IN S U L A T E D D E C K U N D E R
C O M P R E S S O R S E C T IO N
5 0 -1 /2
(1 2 8 5 )
8
1 4
O R
(2 0 5 )
(3 5 5 )
F R O N T
N O T E : (X X X ) IN D IC A T E S
D IM E N S IO N S IN
M IL L IM E T E R S
FIGURE 12 - PREDATOR® ROOF CURB DIMENSIONS
Johnson Controls Unitary Products
27
265485-XTG-B-1208
2 T Y P
(5 0 )
2 3
(5 8 5 )
3 0 -1 /2
(7 7 5 )
5 0 -1 /2
(1 2 8 5 )
4
(1 0 0 )
2 6
(6 6 0 )
R E T U R N
8 0 -5 /8
(2 0 5 0 )
S U P P L Y
1 0
(2 5 5 )
7 6 -5 /8
(1 9 4 5 )
F R O N T
5 9 -1 /4
(1 5 0 5 )
9 4
(2 3 9 0 )
6 4 -1 /4
(1 6 3 0 )
R IG H T
FIGURE 13 - SUNLINE™ TO PREDATOR® TRANSITION ROOF CURB
3 2 -1 1 /1 6
(8 3 0 )
6 -1 3 /1 6
(1 7 5 )
6 -1 3 /1 6
(1 7 5 )
N O T E : (X X X ) IN D IC A T E S
D IM E N S IO N S IN
M IL L IM E T E R S
6 -1 3 /1 6
(1 7 5 )
2 4
(6 1 0 )
2 7 -1 /2
(7 0 0 )
L E F T
2 1
(5 3 5 )
1 8
(4 5 5 )
1 9 -3 /1 6
(4 8 5 )
2 1 -3 /1 6
(5 4 0 )
1 7 -3 /1 6
(4 3 5 )
1 2 -5 /1 6
(3 1 5 )
1 4 -2 3 /3 2
(3 7 5 )
1 6 -3 /8
(4 1 5 )
1 8 -1 /1 6
(4 6 0 )
B o
C o
C o
O u
E n
tto m
n tro
n v e
tle t
try
P o w e r,
l a n d
n ie n c e
W ir in g
F R O N T
B o tto m g a s
s u p p ly e n tr y
6 3 -1 /2
(1 6 1 0 )
FIGURE 14 - BOTTOM DUCT OPENINGS (FROM ABOVE)
28
Johnson Controls Unitary Products
265485-XTG-B-1208
18-1/4
(465)
REAR DUCT DIMENSIONS
DR090
“A”
“B”
“C”
28 1/4
(717)
18 1/16
(459)
28 1/4
(717)
A
Return
Air
DIMENSION
MODEL
Supply
Air
18-1/4
(465)
B
2-31/32
(75)
5-5/32
(130)
C
NOTE: (XXX) indicates millimeters
31-11/16
(805)
FIGURE 15 - REAR DUCT DIMENSIONS
58 1/4
(148)
88 1/4
(224.2)
39 1/2
(100)
or
47 1/2
(120.7)
Outside Air
Intake Hood
35 3/4
(90.8)
Relief Hood for
Power Exhaust or
Barometric Relief
26
(66)
25 3/4
(65.4)
26
(66)
30 1/4
(76.8)
FIGURE 16 - DOWNFLOW ECONOMIZER HOOD DETAIL
Johnson Controls Unitary Products
29
265485-XTG-B-1208
TABLE 27: ECONOMIZER USAGE
Application
Description
Model
Bottom Return
Downflow economizer with barometric relief
2EE04705424
Side Return
Horizontal economizer without barometric relief
2EE047055241
ERV or End Return
Slab Economizer, 50” tall cabinet
2EE047052242
1. Barometric relief must be ordered seperately and installed in duct work.
2. Barometric relief or fresh air hood not included. Must be ordered seperately.
2EE04705424
Fresh Air Hood
2EE04705424
2EE04705424
2EE04705424
Fresh Air Damper Return Air Damper
Barometric Relief Damper
2EE04705424
Barometric Relief Hood
FIGURE 17 - FACTORY INSTALLED DOWNFLOW ECONOMIZER
2EE04705424
Fresh Air Hood
2EE04705424
2EE04705424
Fresh Air Damper Return Air Damper
2PE047032XX
Power Exhaust
2EE04705424
Barometric Relief Damper
2EE04705424
Barometric Relief Hood
FIGURE 18 - FIELD INSTALLED DOWNFLOW ECONOMIZER W/POWER EXHAUST
30
Johnson Controls Unitary Products
265485-XTG-B-1208
2EE04705524
Return Air Damper
Field Installed
Duct Work
2EE04705524
Fresh Air Damper
2PE047032XX
Power Exhaust
1EH0408
Barometric
Relief Damper
1EH0408
Barometric
Relief Hood
2EE04705524
Fresh Air Hood
FIGURE 19 - FIELD INSTALLED HORIZONTAL ECONOMIZER W/POWER EXHAUST
1EH0409
Fresh Air Hood
2EE04705X24
Slab Economizer
2PE047032XX
Power Exhaust
1EH0409 Barometric
Relief Damper
1EH0409 Barometric
Relief Hood
FIGURE 20 - SLAB ECONOMIZER DOWNFLOW W/POWER EXHAUST
Johnson Controls Unitary Products
31
265485-XTG-B-1208
1EH0409
Fresh Air Hood
Field Installed
Duct Work
2EE04705X24
Slab Economizer
1EH0409
Barometric Relief Hood
1EH0409
Barometric Relief Damper
2PE047032XX
Power Exhaust
FIGURE 21 - SLAB ECONOMIZER END RETURN W/POWER EXHAUST
32
Johnson Controls Unitary Products
265485-XTG-B-1208
THERMOSTAT
TERMINALS
1
( RCB )
REHEAT
CONTROL BOARD
RC
RH
R
Y1
Y1
Y2
Y2
W1
W1
W2
W2
G
G
C
C
X1
OCC
X3
TERMINAL BLOCK
RH
2
X4
A1
HUM
1
A2
HUM
2
T
DEHUMIDISTAT 3
3
T
4
TO REMOTE SENSOR
2ET04701324 IF USED
1 Electronic programmable Thermostat 2ET0770010024
( includes subbase).
2 Terminals A1 and A2 provide a relay output to close the
outdoor economizer dampers when the thermostat
switches to the set-back position.
3
Dehumidistat closes on rise in humidity.
TYPICAL
THERMOSTAT
RC
R
RH
Y1
Y1
Y2
Y2
G
G
W1
W1
W2
W2
OCC
C
C
( RCB )
REHEAT
CONTROL
BOARD
TERMINAL
BLOCK
RH
1
2
DEHUMIDISTAT 1
3
4
HUM
1
Dehumidistat closes on rise in humidity.
FIGURE 22 - TYPICAL LOW VOLTAGE FIELD WIRING
Johnson Controls Unitary Products
33
265485-XTG-B-1208
TERMINAL BLOCK TB1
FIELD SUPPLIED
DISCONNECT
GROUND
LUG
THREE
PHASE
POWER
SUPPLY
FIGURE 23 - FIELD WIRING DISCONNECT - COOLING UNIT WITH OR WITHOUT ELECTRIC HEAT
CONTACTOR 1M
GROUND
LUG
T1
T2
T3
L1
L2
L3
FIELD SUPPLIED
DISCONNECT
THREE
PHASE
POWER
SUPPLY
FIGURE 24 - FIELD WIRING DISCONNECT - COOLING UNIT WITH GAS HEAT
34
Johnson Controls Unitary Products
265485-XTG-B-1208
FIGURE 25 - TYPICAL DR090 COOLING UNIT WITH GAS HEAT WIRING DIAGRAM
Johnson Controls Unitary Products
35
265485-XTG-B-1208
FIGURE 26 - TYPICAL DR090 COOLING UNIT WITH/WITHOUT ELECTRIC HEAT WIRING DIAGRAM
36
Johnson Controls Unitary Products
265485-XTG-B-1208
FIGURE 27 - TYPICAL DR090 REHEAT WIRING DIAGRAM
Johnson Controls Unitary Products
37
265485-XTG-B-1208
GUIDE SPECIFICATIONS
PREDATOR® MagnaDRY™
DR 090
GENERAL
Units shall be manufactured by Unitary Products in an ISO
9001 certified facility. YORK® Predator® MagnaDRY™ units
are convertible single packages with a common footprint cabinet and common roof curb. All units have two compressors
with independent refrigeration circuits to provide 2 stages of
cooling. The units were designed for light commercial applications and can be easily installed on a roof curb, slab, or
frame. All Predator® MagnaDRY™ units are self-contained
and assembled on rigid full perimeter base rails allowing for
3-way forklift access and overhead rigging. Every unit is completely charged, wired, piped, and tested at the factory to provide a quick and easy field installation. All units are
convertible between side and down airflow. Independent
economizer designs are used on side and down discharge
applications, as well as all tonnage sizes. Predator® MagnaDRY™ units are available in the following configurations:
cooling only, cooling with electric heat, and cooling with gas
heat. Electric heaters are available as factory-installed
options or field-installed accessories.
evaporator fan performance without removing panels or creating bypass of the coils. Condensate pan shall be slide out
design, constructed of a non corrosive material, internally
sloped and conforming to ASHRAE 62-B9 standards. Condensate connection shall be a minimum of ¾” I.D. female and
be rigid mount connection.
INDOOR (EVAPORATOR) FAN ASSEMBLY
Fan shall be a belt drive assembly and include an adjustable
pitch motor pulley. Job site selected brake horsepower shall
not exceed the motors nameplate horsepower rating plus the
service factor. Units shall be designed to operate within the
service factor. Fan wheel shall be double inlet type with forward curve blades, dynamically balanced to operate
smoothly throughout the entire range of operation. Airflow
design shall be constant volume. Bearings shall be sealed
and permanently lubricated for longer life and no maintenance. Entire blower assembly and motor shall be slide out
design.
OUTDOOR (CONDENSER) FAN ASSEMBLY
DESCRIPTION
Units shall be factory assembled, single package, (Elec/Elec,
Gas/Elec), designed for outdoor installation. Units shall have
a minimum EER of 10.5 (3.08 CoP). They shall have built in
field convertible duct connections for down discharge supply/
return or horizontal discharge supply/return and be available
with factory installed options or field installed accessories.
The units shall be factory wired, piped and charged with R-22
refrigerant and factory tested prior to shipment. All unit wiring
shall be both numbered and color coded. The cooling performance shall be rated in accordance with DOE and ARI test
procedures. Units shall be CSA certified to ANSI Z21.47 and
UL 1995/CAN/CSA No. 236-M90 standards.
The outdoor fans shall be of the direct drive type, discharge
air vertically, have aluminum blades riveted to corrosion
resistant steel spider brackets and shall be dynamically balanced for smooth operation. The outdoor fan motors shall
have permanently lubricated bearings internally protected
against overload conditions and staged independently. A
cleaning window shall be provided on two sides of the units
for coil cleaning.
REFRIGERANT COMPONENTS
Compressors:
A.
Shall be fully hermetic type, direct drive, internally protected with internal high-pressure relief and over temperature protection. The hermetic motor shall be suction gas
cooled and have a voltage range of + or – 10% of the
unit nameplate voltage.
B.
Shall have internal spring isolation and sound muffling to
minimize vibration and noise, and be externally isolated
on a dedicated, independent mounting.
UNIT CABINET
Unit cabinet shall be constructed of galvanized steel with
exterior surfaces coated with a non-chalking, powder paint
finish, certified at 1000 hours salt spray test per ASTM-B117
standards. Indoor blower sections shall be insulated with up
to 1/2” (1.27 cm) thick insulation coated on the airside. Aluminum foil faced insulation shall be used in the unit’s compartments and be fastened to prevent insulation from entering the
air stream. Cabinet doors shall be hinged with tool-less
access for easy servicing and maintenance. Full perimeter
base rails shall be provided to assure reliable transit of equipment, overhead rigging, fork truck access and proper sealing
on roof curb applications. Disposable 2” filters shall be furnished and be accessible through hinged access door. Fan
performance measuring ports shall be provided on the outside of the cabinet to allow accurate air measurements of
38
Coils:
A.
Evaporator and condenser coils shall have aluminum
plate fins mechanically bonded to seamless internally
enhanced copper tubes with all joints brazed. Special
Phenolic coating shall be available as a factory option.
B. Evaporator and condenser coils shall be of the direct
expansion, draw-thru design.
Johnson Controls Unitary Products
265485-XTG-B-1208
Refrigerant Circuit and Refrigerant Safety Components shall
include:
A.
Independent fixed-orifice or thermally operated expansion devices.
B.
Solid core filter drier/strainer to eliminate any moisture or
foreign matter.
C.
Accessible service gage connections on both suction
and discharge lines to charge, evacuate, and measure
refrigerant pressure during any necessary servicing or
troubleshooting, without losing charge.
D.
The unit shall have two independent refrigerant circuits,
equally split in 50% capacity increments.
Unit Controls:
A.
Unit shall be complete with self-contained low-voltage
control circuit protected by a resettable circuit breaker on
the 24-volt transformer side.
B.
Unit shall incorporate a lockout circuit which provides
reset capability at the space thermostat or base unit
should any of the following standard safety devices trip
and shut off compressor:
C.
Loss-of-charge/Low-pressure switch.
(1) High-pressure switch.
(2) Freeze-protection thermostat, evaporator coil. If any
of the above safety devices trip, an LED (light-emitting
diode) indicator shall flash a diagnostic code that indicates which safety switch has tripped.
air entering temperature of 40 ºF/4.4°C. Burners shall be of
the in-shot type, constructed of aluminum-coated steel. All
gas piping shall enter the unit cabinet at a single location,
through either the side or bottom, without any field modifications. An integrated control board shall provide timed control
of evaporator fan functioning and burner ignition. Heating
section shall be provided with the following minimum protection:
A.
Primary and auxiliary high-temperature limit switches.
B.
Induced draft pressure sensor.
C.
Flame roll out switch (manual reset).
D.
Flame proving controls.
NOTE: Unit shall have two independent stages of capacity
(60% 1st stage, 100% 2nd stage).
ELECTRIC HEATING SECTION (IF EQUIPPED)
An electric heating section, with nickel chromium elements,
shall be provided in a range of 9 thru 54 KW, offering two
states of capacity all sizes. The heating section shall have a
primary limit control(s) (automatic reset) to prevent the heating element system from operating at an excessive temperature. The Heating Section assembly shall slide out of the unit
for easy maintenance and service. Units with Electric Heating
Sections shall be wired for a single point power supply with
branch circuit fusing (where required).
UNIT OPERATING CHARACTERISTICS
Unit shall be capable of starting and running at 125 ºF/52°C
outdoor temperature, exceeding maximum load criteria of
ARI Standard 340/360. The compressor, with standard controls, shall be capable of operation down to 0 ºF/-17.8°C outdoor temperature. Unit shall be provided with fan time delay
to prevent cold air delivery before heat exchanger warms up.
(Gas heat only)
D.
Unit shall incorporate “AUTO RESET” compressor over
temperature, over current protection.
E.
Unit shall operate with conventional thermostat designs
and have a low voltage terminal strip for easy hook-up.
F.
Unit control board shall have on-board diagnostics and
fault code display.
G.
Standard controls shall include anti-short cycle and low
voltage protection, and permit cooling operation down to
0 ºF/-17.8°C.
H.
Control board shall monitor each refrigerant safety
switch independently.
STANDARD LIMITED WARRANTIES - Compressor – 5
Years, Heat Exchanger – 10 Years, Elect. Heat Elem. – 5
Years, Parts – 1 Year
I.
Control board shall retain last 5 fault codes in non-volatile memory, which will not be lost in the event of a power
loss.
FACTORY INSTALLED OPTIONAL OUTDOOR AIR (Shall
be made available by either/or):
GAS HEATING SECTION (IF EQUIPPED)
Heat exchanger and exhaust system shall be constructed of
aluminized steel and shall be designed with induced draft
combustion with post purge logic, energy saving direct spark
ignition, and redundant main gas valve. The heat exchanger
shall be of the tubular type, constructed of T1-40 aluminized
steel for corrosion resistance and allowing minimum mixed
Johnson Controls Unitary Products
ELECTRICAL REQUIREMENTS - All unit power wiring shall
enter unit cabinet at a single factory provided location and be
capable of side or bottom entry to minimize roof penetrations
and avoid unit field modifications. Separate side and bottom
openings shall be provided for the control wiring.
1.
ELECTRONIC ENTHALPY AUTOMATIC ECONOMIZER – Outdoor and return air dampers that are interlocked and positioned by a fully-modulating, springreturn damper actuator. The maximum leakage rate for
the outdoor air intake dampers shall not exceed 2%
when dampers are fully closed and operating against a
pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor and return
39
2.
air damper assembly to take in outdoor air to meet the
minimum ventilation requirement of the conditioned
space during normal operation. During economizer operation, a mixed-air temperature control shall modulate the
outdoor and return air damper assembly to prevent the
supply air temperature from dropping below 55 ºF/
12.8°C. Changeover from compressor to economizer
operation shall be provided by an integral electronic
enthalpy control that feeds input into the basic module.
The outdoor intake opening shall be covered with a rain
hood that matches the exterior of the unit. Water eliminator/filters shall be provided. Simultaneous economizer/
compressor operation is also possible. Dampers shall
fully close on power loss. Available with barometric relief
or power exhaust.
•
COIL GUARD - Designed to prevent condenser coil
damage.
•
BAS CONTROLS - Include supply air sensor, return air
sensor, dirty filter indicator and air proving switch.
•
DIRTY FILTER SWITCH – This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally highpressure drop across the filters.
•
BREAKER – An HACR breaker can be factory installed
on gas heat units or cooling units with electric heat.
•
DISCONNECT SWITCH - A disconnect can be factory
installed on a cooling only units sized for the largest electric heat available.
MOTORIZED OUTDOOR AIR DAMPERS – Outdoor
and return air dampers that are interlocked and positioned by a 2-position, spring-return damper actuator.
The maximum leakage rate for the outdoor air intake
dampers shall not exceed 2% when dampers are fully
closed and operating against a pressure differential of
0.5 IWG. A unit-mounted potentiometer shall be provided
to adjust the outdoor and return air damper assembly to
take in the design CFM of outdoor air to meet the ventilation requirements of the conditioned space during normal
operation. Whenever the indoor fan motor is energized,
the dampers open up to one of two pre-selected positions – regardless of the outdoor air enthalpy. Dampers
return to the fully closed position when the indoor fan
motor is de-energized. Dampers shall fully close on
power loss.
•
STAINLESS STEEL HEAT EXCHANGER – For applications in a corrosive environment, this option provides a
full stainless steel heat exchanger assembly.
•
STAINLESS STEEL DRAIN PAN - Provides years of
trouble free operation in corrosive environments.
•
SMOKE DETECTOR – A smoke detector can be factory
mounted and wired in the supply and/or return air compartments.
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
•
ROOF CURB - 14” and 8” high, full perimeter knockdown
curb, with hinged design for quick assembly.
•
BAROMETRIC RELIEF DAMPER – (Unit mounted –
Downflow, Duct Mounted – Horizontal) – Contains a rain
hood, air inlet screen, exhaust damper and mounting
hardware. Used to relieve internal air pressure through
the unit during economizer operation.
•
PROPANE CONVERSION KIT – Contains new orifices
and gas valve springs to convert from natural to L.P. gas.
•
-60 ºF GAS HEAT KIT – Provides an electric heat kit for
the gas compartment for use in extreme low ambient
conditions.
•
ECONOMIZER (Downflow and Horizontal flow)
•
POWER EXHAUST – (Unit mount – Downflow, Duct
mount – Horizontal flow)
•
DUAL ENTHALPY KIT - Provides a second input to
economizer to monitor return air.
ADDITIONAL FACTORY INSTALLED OPTIONS
•
•
•
•
ALTERNATE INDOOR BLOWER MOTOR – For applications with high restrictions, units are available with
optional indoor blower motors that provide higher static
output and/or higher airflow.
CONVENIENCE OUTLET (POWERED/NON-POWERED) – Unit can be provided with an optional 120VAC
GFCI outlet with cover on the corner of the unit housing
the compressors.
ELECTRIC HEAT - Electric Heaters range from 7 kW to
27 kW and are available in all the voltage options of the
base unit.
PHASE MONITOR - Designed to prevent damage in outof-phase condition.
Subject to change without notice. Printed in U.S.A.
Copyright © 2009 by Johnson Controls, Inc. All rights reserved.
Johnson Controls Unitary Products
5005 York Drive
Norman, OK 73069
265485-XTG-B-1208
Supersedes: 265485-YTG-A-0806