Download Mitsubishi FDC100VN Specifications

Transcript
High Performance Air-Conditioning
FD series
Inverter Packaged Air-Conditioners
50/60Hz
10P01E-A-0
Our new advanced technology has realized high efficiency, strong heating
and long piping.
This contributes to the environmental protection through energy saving
and permits installation of the units (4~6HP) considering a heating
operation under temperature conditions down to -20˚C and design
flexibility has been improved by extension of piping length to 100m.
NEW
1.5~2.5HP
3HP
4~6HP
Line up
HP
1.5
2
2.5
3
4
5
6
8
10
Hyper Inverter
High efficiency
,
The industry s highest COP
levels are achieved by our
latest technologies, such as
new high efficient twin rotary
compressors and the
combination with new Hyper
inverter outdoor units.
EER in cooling
3.62
COP in heating
4.09
3.09
3.50
Micro Hyper
Micro Hyper
Micro Hyper
Micro Hyper
Micro Hyper
Micro Hyper
4HP
5HP
6HP
4HP
5HP
6HP
(comparison of FDT series)
2
3.71
2.81
Long piping
Strong heating
(in case of 4~6HP)
(in case of 4~6HP)
-20°C : Heating operation down to -20°C
-15°C : Nominal heating capacity maintained at -15°C
Height
difference
Heating
-20°C
(Outdoor higher
than Indoor)
Piping
length
30m
+20°C
Cooling
-15°C
+43°C
50
-30
100m
-20
-10
0
10
20
30
40
50
Max.heating capacity (kW)
Hyper Inverter Micro Inverter
FDC100VSX(4HP, 3phase 380V)
12.5
FDC125VSX(5HP, 3phase 380V)
16.0
FDC140VSX(6HP, 3phase 380V)
16.5
Leading powerful heating capacity in the industry
Thanks to optimization of refrigeration control with use of electric
expansion valve and development of new twin rotary compressors,
max heating capacity has been increased.
Hyper Inverter series can reach the set temperature very quickly,
keeping nominal heating capacity when outdoor temperature is -15°C.
It is effective to be used even in cold area.
(kW)
18.0
14.5
14.0
Temperature of supply air can reach 40°C
in 4 minutes after start up under low
temperature operation conditions (at both
indoor and outdoor temperature of 2°C)
and can reach 50°C in 8 minutes after that.
Heating capacity
Heating capacity (in case of 5HP)
Keeping nominal heating
capacity at -15°C
50°C
Hyper Inverter
nominal
heating
capacity
14.0kW
Micro Inverter
8.8
0
-15°C
2°C
7°C
Hyper Inverter
40°C
30°C
20°C
Micro Inverter
nominal heating capacity
model name
(kW at outdoor temperature of 7°C)
heating capacity
at outdoor temperature of -15°C
FDT100VSX(4HP, 3phase 380V)
11.2kW
11.2kW
FDT125VSX(5HP, 3phase 380V)
14.0kW
14.0kW
FDT140VSX(6HP, 3phase 380V)
16.0kW
16.0kW
10°C
0°C
4minutes
8minutes
Please refer to our technical manual for installation conditions, operation range and heating/cooling capacities.
3
Micro Inverter
Compact Design of outdoor units
Line up
HP
1.5
2
2.5
3
4
5
6
8
10
Height
Height
Micro Inverter
185mm
390mm
Height
455mm
Width
Width
380mm
380mm
FDC100VN/VS (4.0HP)
FDC125VN/VS (5.0HP)
FDC140VN/VS (6.0HP)
FDC200VS (8.0HP)
4.0HP
5.0HP
6.0HP
8.0HP
10.0HP
82
118
125
225
225
74
74
74
122
140
*Reduction
-8
-44
-51
-103
-85
4.0HP
5.0HP
6.0HP
8.0HP
10.0HP
* Comparison with former models
Size reduction and high efficiency
performance on the
DC twin rotary compressors
(Micro Inverter 4-6HP)
Reduction in height by 22.3%
Reduction in volume by 44.1%
ø133mm
Height at 342mm
Height at 440 mm
Employment of DC twin rotary compressor has enabled to
utilize a high-speed range of up to 120 rps at the maximum
to secure the required capacity.
Optimum compressor control has been realized by
employing the vector control* and the starting current has
been improved significantly compared with former models.
Moreover, vibration has been reduced.
4
FDC250VS (10.0HP)
Fits into elevators
Former model New model
Former
compressor
350mm
350mm
Easy installation
Outside diameter of shell
ø185mm
Depth
Depth
New model
DC rotary compressor
* Vector control means
a. technique to realize
an optimum control by
converting the current
wave to a smooth
sinusoidal waveform
Former model New model *Reduction
328
467
467
1643
1643
303
303
303
467
540
8%
35%
35%
72%
67%
* Comparison with former models
Improved efficiency
of heat exchanger
Redesigning the fins to a straight shape has reduced the
pressure loss of the airflow in the heat exchanger. Surface
treatment on the fin has enhanced the frost resistance
capacity compared with former models.
Owing to the reduction in the size of heat exchanger, the
appropriate number of circuits for each HP has been
applied. Employment of a high-speed motor has
increased the airflow
and enabled to keep
the cooling capacity
under a condition of
higher outdoor air
temperatures*.
* Limitation of use is around
43: at the maximum.
Former model
New model
Controllability
Reliability in the protection of compressor has been
improved by optimizing the controls of oil return,
electronic expansion valve, etc.
High technology
POINT
DC fan motor uses less energy
POINT
Optimization of heat exchanger path.
More efficient heating and cooling
POINT
Super heat control with low pressure
sensor, works better in tough conditions
POINT
High efficiency refrigeration circuit
POINT
Newly developed High efficiency DC
scroll compressor
1
1
2
2
3
3
4
4
5
FDC200VS
970
mm
m
m
370
(8.0HP)
Employment of the scroll inverter
compressors(8/10HP)
5
Energy labeling “Class A”
A control over wide range of capacity and a high efficiency has
been realized by inverter-driven scroll compressors.
In addition, the starting current significantly is improved.
The size has also been reduced by 3.2% in height and 31.8% in
volume.
MHI models have cleared the class A standard,
the highest energy saving level, with their high
COP (coefficient of performance).
A
CLASS
Employment of DC fan motor
A
Employment of DC fan motor has enabled to realize an
excellent efficiency of approx. 60% higher than former models.
Wide range of operation
B
C
D
E
F
Manufacturer
Outside unit
Inside unit
More efficient
A
B
C
D
E
F
G
G
Our new advanced technology has expanded the heating and
cooling operation range.
This permits installation of the units under a low outdoor
temperature conditions down to -20°C In heating operation and
-15°C in cooling operation.
Air-conditioner
Energy
Less efficient
Annual energy consumption,
kWh in cooling mode
(Actual consumption will
depend on how the appliance is used
and climate)
Cooling output
nergy fficiency atio
Type
(FDC 100/125/140)
Cooling only
Cooling + Heating
Air cooled
Water cooled
Heat output
kW
Heating performance
Heating
-20°C
kW
Full load (the higher the better)
A: higher
+20°C
G: lower
Noise
(dB(A) re 1 pW)
Cooling
-15°C
-30
-20
-10
0
10
20
+43°C
30
40
Further information is contained
in product brochures
Air-conditioner
Energy Label Directive 2002/31/EC
50
5
Ceiling Cassette -4way- Indoor units
FDT.FDTC
Individual flap control system
According to room temperature conditions, four
directions of air flow can be controlled by individual flap
as preferred.
As individual flap control is available even after
installation, installation area became wider than before.
Due to optimization of outlet design of air flow with our
new advanced technology, sufficient air flow is secured
and long reach of air flow is realized.(FDT)
Previous
New
Flap control system
Selection of louver position is possible.
Louvers can be set at different angles.
is not applicable to the Individual flap control
*RCH-E3
system and the Flap control system.
Upper
position
Movable
range
Lower
position
For person who is far
from the indoor unit
The thinnest design
Thanks to new design of heat exchanger changed from 2 parts to 1 part, the
height of indoor unit is reduced drastically.
Furthermore applying DC
fan motors, the highest
energy efficiency level,
reduction of weight and
significant compact design
are realized.
Shape of heat exchanger
Previous
New
FDT125~140
365mm
298
reduction!!
mm
FDT40~71
270mm
246
mm
6
18%
For both persons who are
feeling hot or cold
9%
reduction!!
Can cool both the kitchen
and the guests
High efficiency
• Reduction of air flow pressure loss
• Increase of heat transfer efficiency
Expansion of outlet air flow area realizes
reduction of pressure loss caused by air flow
in the indoor unit. Load of fan motor is
decreased and efficiency is increased.
Applying high efficient piping in heat exchanger and
optimization of heat exchanger (2parts 1part)
increases heat transfer efficiency.
Achieved COP 5.67
based on 50% capacity of FDT100V in heating operation
Air-conditioners are generally selected with the operation under the most severe ambient temperature conditions.
The inverter constantly adjusts compressor output to meet the exact demand of the indoor units.
i.e. In case that selecting the capacity of an inverter air-conditioner based on heating operation at -5°C, its capacity drops by
50% at 7°C(ISO-TI measurement condition) and operation period at 50% capacity is normally longer than that at 100% of
nominal heating capacity.
Considering annual electrical power consumption of inverter air-conditioners, it is quite important to give the first priority to 50%
actual capacity and selecting inverter air-conditioners is the best solution for saving energy and protecting the environment.
Convenience
XR1
XR2
XR3
XR4
XR1
CnT
A dry contact is
equipped on an
indoor unit to
meet a possible
need for signal
output on the site.
Monitoring Function
XR2
XR3
XR4
XR5
common
output1 (run)
output2 (heat)
output3 (comp on)
output4 (alarm)
in put
Power
source
Signal output
XR5
XR1~5 : approx. DC12v
Equipped with RS232C
for connection directly
to your PC monitoring
and service tasks made
simple with our service
software (“Mente PC”).
New remote control
Applying nonpolar 2-core in new remote control line
for all indoor units, it is very convenient for installation
including renewal case.
Previous
-core
New
-core
Consideration on the Environment
Employment of lead-free solder
Adapt to RoHS
In order to comply with RoHS standard, the new inverter
series products use lead-free solder. It was considered to be
too difficult to use lead-free solder because it requires higher
soldering temperatures at assembling, which could jeopardize
the reliability of assembly, etc. PbF soldering method
developed by us, however, has enabled a higher reliability for
lead-free printed circuit boards.
*"RoHS" is the abbreviation of the new European standard, which means
Restriction of Hazardous Substances.
Employment of the new refrigerant
All models of the New inverter series use a new
refrigerant R410A characterized by the ozone
depletion coefficient being 0.
Energy Conservation
A High Performance and Excellent Energy Conservation
are achieved at the same time by an increased capacity of
heat exchanger and employment of high efficiency DC
motor etc.
7
SINGLE [OUTDOOR UNIT : INDOOR UNIT = 1 : 1]
HP
kW
Btu/h
kcal/h
1.5
4.0
13,700
3,440
2.0
5.0
17,100
4,300
2.5
6.0
19,100
4,816
3.0
7.1
23,900
6,020
4.0
10.0
34,100
8,600
FDT40VD
FDT50VD
FDT60VD
FDT71VD
FDT100VD
SRC40ZIX-S
SRC50ZIX-S
SRC60ZIX-S
FDC71VNX
FDC100VNX
FDC100VSX
FDTC40VD
FDTC50VD
FDTC60VD
SRC40ZIX-S
SRC50ZIX-S
SRC60ZIX-S
FDU71VD
FDU100VD
FDC71VNX
FDC100VNX
FDC100VSX
Indoor
unit
Outdoor
unit
1phase
3phase
1phase
Set
3phase
Indoor
unit
Outdoor
unit
1phase
Set 1phase
Indoor
unit
Outdoor
unit
1phase
3phase
1phase
Set
3phase
*
*
*
Indoor
unit
FDUM50VD
FDUM60VD
FDUM71VD
FDUM100VD
SRC50ZIX-S
SRC60ZIX-S
FDC71VNX
FDC100VNX
FDC100VSX
FDEN40VD
FDEN50VD
FDEN60VD
FDEN71VD
FDEN100VD
SRC40ZIX-S
SRC50ZIX-S
SRC60ZIX-S
FDC71VNX
FDC100VNX
FDC100VSX
Outdoor
unit
1phase
3phase
1phase
Set
3phase
Indoor
unit
Outdoor
unit
1phase
3phase
1phase
Set
3phase
8
Micro Inverter
5.0
12.5
42,700
10,750
6.0
14.0
47,800
12,040
4.0
10.0
34,100
8,600
5.0
12.5
42,700
10,750
6.0
14.0
47,800
12,040
FDT125VD
FDT140VD
FDT100VD
FDT125VD
FDT140VD
FDC125VNX
FDC125VSX
FDC140VNX
FDC140VSX
FDC100VN
FDC100VS
FDC125VN
FDC125VS
FDC140VN
FDC140VS
FDU125VD
FDU140VD
FDU100VD
FDU125VD
FDC140VNX
FDC140VSX
FDC100VN
FDC100VS
FDC125VN
FDC125VS
8.0
20.0
68,300
17,200
10.0
25.0
85,400
21,500
FDU140VD
FDU200VD
FDU250VD
FDC140VN
FDC140VS
FDC200VS
FDC250VS
NEW
NEW
FDC125VNX
FDC125VSX
*
*
*
*
*
*
*
*
*
*
FDUM140VD
FDUM100VD
FDUM125VD
FDUM140VD
FDC125VNX
FDC125VSX
FDC140VNX
FDC140VSX
FDC100VN
FDC100VS
FDC125VN
FDC125VS
FDC140VN
FDC140VS
FDEN125VD
FDEN140VD
FDEN100VD
FDEN125VD
FDEN140VD
FDC140VNX
FDC140VSX
FDC100VN
FDC100VS
FDC125VN
FDC125VS
FDC140VN
FDC140VS
FDUM125VD
NEW
NEW
FDC125VNX
FDC125VSX
*Not available in 60Hz
9
[ INDOOR UNIT ]
A
CEILING CASSETTE -4way-
FDT
CLASS
Wired remote control
FDT 40/50/60/71/
100/125/140VD
1 Arrangement of installation
balance of indoor unit
Point
Checking from access ports with
detachable covers at each corner,
arrangement of installation balance of
indoor unit can be available without
removing a panel. Workability is improved
and time of installation is reduced.
3 Easy checking of drain pan
Point
Easy checking of drain pan
condition is available by
removing corner lid only.
Due to new design
changing fan motor is
available without removing
a panel. Temporally setting
of drain pan is also
available.
RC-E4
RCH-E3
RCN-T-36W-E
(Option)
(Option)
(Option)
2 Installation Workability
Point
For wireless control simply
insert the infrared receiver
kit on a corner of the panel
wireless remote control
RCN-T-36W-E
4 700mm Drain Pump
Point
Drain can be discharged
upwards by 700mm from the
ceiling surface. It allows a
piping layout with a high
degree of freedom
Depending on the installation
location and 260mm flexible
hose as a standard
equipment supports easy
workability.
Outline drawing (Unit:mm)
Model FDT40,50,60,71VD
10
Wireless remote control
Model 100,125,140VD
Flexible hose
less than
700mm
SPECIFICATIONS
Set model name
Indoor name
Outdoor name
FDT40ZIXVD
FDT40VD
SRC40ZIX-S
FDT50ZIXVD
FDT50VD
SRC50ZIX-S
4.0
(1.8~4.7)
4.5
(2.0~5.4)
0.93/1.15
4.30/3.91
A/A
5(12)
5.0
(2.2~5.6)
5.4
(2.5~6.3)
1.29/1.29
3.88/4.19
A/A
Indoor unit
Range of Outdoor unit
usage
FDT71VNXVD
FDT71VD
FDC71VNX
FDT100VNXVD
FDT100VD
FDC100VNX
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
Power source
Nominal cooling capacity
kW
ISO-T1(JIS)
(Min~Max)
Nominal heating capacity
kW
ISO-T1(JIS)
(Min~Max)
Power Consumption Cooling/Heating
kW
COP
Cooling/Heating
Energy label
Cooling/Heating
Inrush current (Max. running current)
A
Indoor
Sound Ievel*1
dB(A)
Outdoor
Indoor
Air flow
CMM
Outdoor
Exterior dimensions Height x Width x Depth mm
kg
Unit+Panel
Net weight
Panel
Air filter, Q'ty
Remote control(option)
Exterior dimensions Height x Width x Depth mm
kg
Net weight
Type of compressor
kg(m)
Ref.amount precharged
ø
Ref.piping size Liquid/Gas
m
Ref.piping length
m
Vertical height O/U is higher
m
O/U is lower
difference
Cooling
O/U
Operating
temperature range Heating
O/U
FDT60ZIXVD
FDT60VD
SRC60ZIX-S
5.6
(2.8~6.3)
6.7
(3.1~7.1)
1.57/1.85
3.57/3.62
A/A
5(14)
Hi:33 Me:31 Lo:30
47
Hi:18 Me:16 Lo:14
48
Hi:18 Me:16 Lo:14
7.1
(3.2~8.0)
8.0
(3.6~9.0)
1.90/2.07
3.74/3.86
A/A
5(17)
Hi:35 Me:33 Lo:31
Cooling:51 Heating:48
Hi:21 Me:19 Lo:17
Cooling:60 Heating:50
10.0
(4.0~11.2)
11.2
(4.0~12.5)
2.50/2.58
4.00/4.34
A/A
5(24)
Hi:40 Me:37 Lo:35
Cooling:48 Heating:50
Hi:27 Me:24 Lo:20
100
Unit:298x840x840 Panel:35x950x950
32.5(Unit:27 Panel:5.5)
FDT125VSXVD
FDT125VD
FDC125VSX
FDT140VSXVD
FDT140VD
FDC140VSX
40
Unit:246x840x840 Panel:35x950x950
27.5(Unit:22 Panel:5.5)
29.5(Unit:24 Panel:5.5)
T-PSA-3AW-E
Pocket Plastic net x1 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-T-36W-E
640x800(+71)x290
1,300x970x370
750x880(+88)x340
43
105
60
Scroll
Rotary
1.4(15)
4.5(30)
2.95(30)
6.35/12.7
9.52/15.88
30
100
50
20
30
30
20
15
15
-15~43*2
-20~20
-15~20
SPECIFICATIONS
Set model name
Indoor name
Outdoor name
Power source
Range of Outdoor unit
usage
Indoor unit
Nominal cooling capacity
kW
ISO-T1(JIS)
(Min~Max)
Nominal heating capacity
kW
ISO-T1(JIS)
(Min~Max)
Power Consumption Cooling/Heating
kW
COP
Cooling/Heating
Energy label
Cooling/Heating
Inrush current (Max. running current)
A
Indoor
Sound Ievel*1
dB(A)
Outdoor
Indoor
Air flow
CMM
Outdoor
Exterior dimensions Height x Width x Depth mm
kg
Unit+Panel
Net weight
Panel
Air filter, Q'ty
Remote control(option)
Exterior dimensions Height x Width x Depth mm
kg
Net weight
Type of compressor
kg(m)
Ref.amount precharged
ø
Ref.piping size Liquid/Gas
m
Ref.piping length
m
Vertical height O/U is higher
m
O/U is lower
difference
Cooling
O/U
Operating
temperature range Heating
O/U
FDT125VNXVD
FDT125VD
FDC125VNX
FDT140VNXVD
FDT140VD
FDC140VNX
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
FDT100VSXVD
FDT100VD
FDC100VSX
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
14.0
12.5
(5.0~16.0)
(5.0~14.0)
16.0
14.0
(4.0~20.0)
(4.0~18.0)
4.19/4.20
3.28/3.43
3.34/3.81
3.81/4.08
A/A
A/A
5(26)
5(15)
Hi:42 Me:40 Lo:37
Hi:43 Me:41 Lo:38
Hi:40 Me:37 Lo:35
Hi:42 Me:40 Lo:37
Hi:43 Me:41 Lo:38
Cooling:48 Heating:50
Cooling:48 Heating:50 Cooling:49 Heating:52
Cooling:49 Heating:52
Hi:30 Me:27 Lo:23
Hi:27 Me:24 Lo:20
Hi:30 Me:27 Lo:23
100
Unit:298x840x840 Panel:35x950x950
32.5(Unit:27 Panel:5.5)
T-PSA-3AW-E
Pocket Plastic net x1 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-T-36W-E
1,300x970x370
105
Rotary
4.5(30)
9.52/15.88
100
30
15
-15~43*2
-20~20
12.5
(5.0~14.0)
14.0
(4.0~17.0)
3.28/3.43
3.81/4.08
A/A
14.0
(5.0~16.0)
16.0
(4.0~18.0)
4.19/4.20
3.34/3.81
A/A
10.0
(4.0~11.2)
11.2
(4.0~16.0)
2.50/2.58
4.00/4.34
A/A
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*21 :: IfIndicates
* a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 40/50ZIXVD 39dB, 60ZIXVD 46dB, 71VNXVD 46dB, 100/125/140VNXVD 51dB, 100/125/140VSXVD 51dB
Air flow: 40/50ZIXVD 20CMM, 60ZIXVD 28CMM, 71VNXVD 28CMM, 100/125/140VNXVD 37CMM, 100/125/140VSXVD 37CMM
11
[ INDOOR UNIT ]
A
CEILING CASSETTE -4way Compact (600 X 600mm)-
FDTC
CLASS
Fits into standard
600 x 600 ceiling
FDTC 40/50/60VD
Wireless remote control
Wired remote control
1 Quiet operation
RCN-TC-24W-ER
(Option)
(Option)
Point
(Sound level in the Lo mode)
3dB
Down
(dB)
35dB
35
RCH-E3
(Option)
2 “CLEARER”Air Flow
Point
36
RC-E4
New shape & angled louver redirects the air
current away from the ceiling, to reduce
ceiling stains
34
32dB
33
32
30dB
31
30
3 Installation Workability
5dB
Down
29
28
27
Point
For wireless control simply insert the
infrared receiver kit on a corner of the
panel
26
25
Previous
(Cooling/Heating)
New
(Cooling)
New
(Heating)
wireless
remote control
FDTC40/50/60VD
4 Compact Concept
Point
The industry's lowest level 248mm height.
248
Panel size (700x700) is suitable for 600x600 ceiling
panel. All indoor unit size is (WxD: 570x570). It brings
easy installation for 600x600 ceiling panel.
Ultra slim design at just 248mm
above the ceiling
12
RCN-TC-24W-ER
5 Comfortable and Convenient
Point
• All units are 18.5kg, light
weight unit.
• Thanks to width and depth
of exterior dimensions of a
indoor unit are 570mm
each, the installation work
can be conducted smoothly
with a beautiful finishing in
2x2 ceiling size.
• 600mm Drain Pump is mounted.
Drain can be discharged upward by 600 mm
from the ceiling surface close to the indoor unit.
It allows a piping layout with a high degree of
freedom depending on the installation location.
Flexible hose
600mm
Outline drawing (Unit:mm)
SPECIFICATIONS
FDTC40ZIXVD
FDTC40VD
SRC40ZIX-S
Set model name
Indoor name
Outdoor name
Nominal cooling capacity
ISO-T1(JIS)
(Min~Max)
Nominal heating capacity
ISO-T1(JIS)
(Min~Max)
Power Consumption Cooling/Heating
Cooling/Heating
COP
Cooling/Heating
Energy label
Inrush current (Max. running current)
Indoor
kW
kW
kW
A
4.0
(1.8~4.7)
4.5
(2.0~5.4)
1.04/1.10
3.85/4.09
A/A
5(12)
dB(A)
Outdoor
Indoor
CMM
Outdoor
Exterior dimensions Height x Width x Depth mm
kg
Net weight
Unit+Panel
Panel
Air filter, Q'ty
Remote control(option)
Exterior dimensions Height x Width x Depth mm
Net weight
kg
Type of compressor
Ref.amount precharged
kg(m)
ø
Ref.piping size Liquid/Gas
m
Ref.piping length
m
Vertical height O/U is higher
m
O/U is lower
difference
O/U
Cooling
Operating
temperature range Heating
O/U
Range of Outdoor unit
usage
Indoor unit
Air flow
FDTC60ZIXVD
FDTC60VD
SRC60ZIX-S
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
Power source
*1
Sound Ievel
FDTC50ZIXVD
FDTC50VD
SRC50ZIX-S
5.0
(2.2~5.6)
5.4
(2.5~6.3)
1.56/1.45
3.21/3.72
A/A
5.6
(2.8~6.3)
6.7
(3.1~6.7)
1.99/2.08
2.81/3.22
C/C
5(14)
Cooling : Hi:42 Me:36 Lo:30
Heating : Hi:42 Me:36 Lo:32
47
Cooling : Hi:11.5 Me:9 Lo:7
Heating : Hi:11.5 Me:9 Lo:8
Cooling : Hi:46 Me:39 Lo:30
Heating : Hi:46 Me:39 Lo:32
48
Cooling : Hi:13.5 Me:10 Lo:7
Heating : Hi:13.5 Me:10 Lo:8
40
Unit:248x570x570 Panel:35x700x700
18.5(Unit:15 Panel:3.5)
TC-PSA-25W-E
Pocket Plastic net x1 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-TC-24W-ER
640x800(+71)x290
43
Scroll
1.4(15)
6.35/12.7
30
20
20
-15~43*2
-15~20
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*21 :: IfIndicates
* a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 40/50/60ZIXVD 47dB
Air flow: 40/50/60ZIXVD 13.5CMM
13
[ INDOOR UNIT ]
A
DUCT CONNECTED -High Static pressure-
FDU
Wired
remote control
Fan control kit
(100~200Pa)
Wireless
remote control
RC-E4 RCH-E3
(Option)
R410A
CLASS
(Option)
RCN-KIT3-E
FDU 71/100/125/140VD
FDU 200/250VD
U-FCRA
[For 200/250VD]
(option)
(Option)
1 Enhanced installation workability
Point
High static pressure of 200 Pa (FDU200/250VD)
extends the degree of freedom in the designing
of air conditioners.
Quiet, Lightweight and Compact
With the FDU71, the noise level is
only 37dB (low), weight is only 40kg
and height is only 297mm.
In addition 600mm Drain Pump is
mounted in FDU71/100/125/140VD.
The indoor unit is completely
hidden in the ceiling, so this is
suitable for spaces with classy
interior decoration.
2 Adaptability to higher static pressures
Point
Height
297mm
600mm
This is a real and earnest
model for duct air-conditioning.
A unit external static pressure
of up to 200 Pa
(FDU200/250VD) is possible.
Precise air flow designing is
possible.
Control box
Slide type fan system
Thin type duct connection
opening
Fan motor
High static pressure
silent fan
Outline drawing (Unit:mm)
FDU71VD
FDU100,125,140VD
Installation workability
FDU200,250VD
(FDU200,250VD)
Using piping attachment that
has flared connection and
brazed connection ends, there
is no need conduct brazing
work inside the outdoor unit.
Flared
connection
ø19.05mm
232mm
Brazed
connection
ø22.2mm
14
*Not available in 60Hz
SPECIFICATIONS
Set model name
Indoor name
Outdoor name
*FDU71VNXVD
FDU71VD
*FDU100VNXVD
FDU100VD
*FDU125VNXVD
FDU125VD
*FDU140VNXVD
FDU140VD
FDC71VNX
FDC100VNX
FDC125VNX
FDC140VNX
7.1
(3.2~8.0)
8.0
(3.6~9.0)
10.0
(4.0~11.2)
11.2
(4.0~12.5)
1Phase 220-240V 50Hz
Power source
Range of Outdoor unit Indoor unit
usage
Nominal cooling capacity
kW
ISO-T1(JIS)
(Min~Max)
Nominal heating capacity
kW
ISO-T1(JIS)
(Min~Max)
kW
Power Consumption Cooling/Heating
Cooling/Heating
COP
Cooling/Heating
Energy label
A
Inrush current (Max. running current)
Indoor
1
dB(A)
Sound Ievel*
Outdoor
Indoor
CMM
Air flow
Outdoor
Pa
External static pressure
Exterior dimensions Height x Width x Depth mm
kg
Net weight
Air filter, Q'ty
Remote control(option)
Exterior dimensions Height x Width x Depth mm
kg
Net weight
Type of compressor
kg(m)
Ref.amount precharged
ø
Ref.piping size Liquid/Gas
m
Ref.piping length
m
Vertical height O/U is higher
m
difference
O/U is lower
Cooling
O/U
Operating
temperature range Heating
O/U
2.15/2.15
3.30/3.72
A/A
5(17)
Hi:41 Lo:37
Cooling:51 Heating:48
Hi:20 Lo:17
Cooling:60 Heating:50
297x850x650
40
750x880(+88)x340
60
2.95(30)
50
12.5
(5.0~14.0)
14.0
(4.0~17.0)
2.78/2.90
3.44/3.67
4.20/4.30
3.60/3.86
3.63/3.81
3.33/3.72
A/A
A/A
A/A
5(25)
5(29)
5(30)
Hi:42 Lo:37
Hi:43 Lo:38
Cooling:48 Heating:50
Cooling:49 Heating:52
Hi:42 Lo:33.5
Hi:34 Lo:27
100
Standard:50, Max:130
350x1,370x650
63
Procure locally
Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E
1,300x970x370
105
Rotary
4.5(30)
9.52/15.88
100
30
15
-15~43*2
-20~20
*Not available in 60Hz
SPECIFICATIONS
Set model name
Indoor name
Outdoor name
*FDU100VSXVD
FDU100VD
*FDU125VSXVD
FDU125VD
*FDU140VSXVD
FDU140VD
FDC100VSX
FDC125VSX
FDC140VSX
3Phase 380-415V 50Hz
Power source
Range of Outdoor unit Indoor unit
usage
Nominal cooling capacity
kW
ISO-T1(JIS)
(Min~Max)
Nominal heating capacity
kW
ISO-T1(JIS)
(Min~Max)
kW
Power Consumption Cooling/Heating
Cooling/Heating
COP
Cooling/Heating
Energy label
A
Inrush current (Max. running current)
Indoor
1
dB(A)
Sound Ievel*
Outdoor
Indoor
CMM
Air flow
Outdoor
Pa
External static pressure
Exterior dimensions Height x Width x Depth mm
kg
Net weight
Air filter, Q'ty
Remote control(option)
Exterior dimensions Height x Width x Depth mm
kg
Net weight
Type of compressor
kg(m)
Ref.amount precharged
ø
Ref.piping size Liquid/Gas
m
Ref.piping length
m
Vertical height O/U is higher
m
difference
O/U is lower
Cooling
O/U
Operating
temperature range Heating
O/U
14.0
(5.0~16.0)
16.0
(4.0~18.0)
10.0
(4.0~11.2)
11.2
(4.0~16.0)
12.5
(5.0~14.0)
14.0
(4.0~18.0)
14.0
(5.0~16.0)
16.0
(4.0~20.0)
2.78/2.90
3.60/3.86
A/A
5(16)
Hi:42 Lo:37
Cooling:48 Heating:50
Hi:34 Lo:27
3.44/3.67
3.63/3.81
A/A
5(18)
4.20/4.30
3.33/3.72
A/A
5(19)
Hi:43 Lo:38
Cooling:49 Heating:52
Cooling:48 Heating:50
Hi:42 Lo:33.5
100
Standard:50, Max:130
350x1,370x650
63
Procure locally
Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E
1,300x970x370
105
Rotary
4.5(30)
9.52/15.88
100
30
15
-15~43*2
-20~20
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB. External static pressure
of FDU71/100/125/140 is 60Pa and that of FDU200/250 is 100Pa.
Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*21 :: External
static pressure is changeable to be set by the remote control. Standard external static pressure is factory setting. MAX external static pressure is ''High static
*
pressure'' setting. The values of sound pressure level become 5dB(A) higher at eternal static pressure of 130Pa.
*3 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
15
[ INDOOR UNIT ]
DUCT CONNECTED -Middle Static pressure-
FDUM
Wired
remote control
A
CLASS
Wireless
remote control
Filter kit
UM-FL1E : for 50
UM-FL2E : for 60, 71
UM-FL3E : for 100, 125, 140
RC-E4
RCH-E3
RCN-KIT3-E
(Option)
(Option)
(Option)
(option)
1 Various Adaptability
Point
Selectable static pressure and
Flexible duct design with
selectable air suction (direct
suction /duct suction) can meet
wide pattern of installation.
FDUM 50/60/71/
100/125/140VD
external static pressure loss:5pa
Static pressure Pa
model
50/60/71VD
100VD
125/140VD
Standard
50
60
60
Outline drawing(Unit:mm)
Model FDUM50VD
(50Hz)
Max
85
90
85
2 600mm Drain Pump
Point
Drain can be discharged
upwards by 600mm from
the ceiling surface. It
allows a piping layout
with a high degree of
freedom Depending on
the installation location.
Models FDUM60V,71VD
16
Flexible hose
less than
600mm
Models FDUM100V,125V,140VD
SPECIFICATIONS
Set model name
Indoor name
Outdoor name
FDUM50ZIXVD
FDUM50VD
SRC50ZIX-S
Power source
Range of Outdoor unit Indoor unit
usage
Nominal cooling capacity
ISO-T1(JIS)
kW
(Min~Max)
Nominal heating capacity
ISO-T1(JIS)
kW
(Min~Max)
Power Consumption Cooling/Heating
kW
Cooling/Heating
COP
Cooling/Heating
Energy label
Inrush current (Max. running current)
A
Indoor
Sound Ievel*1
dB(A)
Outdoor
Indoor
Air flow
CMM
Outdoor
50Hz/60Hz
Static pressure
Pa
Exterior dimensions Height x Width x Depth mm
Net weight
kg
Air filter, Q'ty
Remote control(option)
Exterior dimensions Height x Width x Depth mm
Net weight
kg
Type of compressor
Ref.amount precharged
kg(m)
Ref.piping size Liquid/Gas
ø
Ref.piping length
m
Vertical height O/U is higher
m
difference
O/U is lower
m
Cooling
O/U
Operating
temperature range Heating
O/U
FDUM71VNVD
FDUM71VD
FDC71VNX
FDUM60ZIXVD
FDUM60VD
SRC60ZIX-S
FDUM100VNXVD
FDUM100VD
FDC100VNX
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
5.0
(2.2~5.6)
5.6
(2.8~6.3)
7.1
(3.2~8.0)
10.0
(4.0~11.2)
5.4
(2.5~6.3)
6.7
(3.1~7.1)
8.0
(3.6~9.0)
11.2
(4.0~12.5)
2.14/2.16
2.72/2.95
3.32/3.70
3.68/3.80
A/A
A/A
5(17)
5(24)
5(14)
Hi:37 Me:35 Lo:32
Hi:35 Me:32 Lo:29
Hi:34 Me:31 Lo:28
47
Cooling:51 Heating:48
Cooling:48 Heating:50
48
Hi:16 Me:15 Lo:14
Hi:13 Me:12 Lo:11
Hi:20 Me:18 Lo:15
Hi:28 Me:25 Lo:22
40
Cooling:60 Heating:50
100
Standard:50/40, Max:85/90
Standard:50/40, Max:85/100
Standard:60/60, Max:90/100
299x750x635
299x950x635
350x1,370x635
34
40
59
Procure locally
Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E
640x800(+71)x290
1,300x970x370
750x880(+88)x340
43
105
60
Rotary
Scroll
1.4(15)
4.5(30)
2.95(30)
6.35/12.7
9.52/15.88
30
100
50
20
30
20
15
-15~43*2
-20~20
-15~20
1.86/1.96
3.01/3.42
B/B
1.52/1.41
3.29/3.83
A/A
SPECIFICATIONS
Set model name
Indoor name
Outdoor name
Power source
Range of Outdoor unit Indoor unit
usage
Nominal cooling capacity
ISO-T1(JIS)
kW
(Min~Max)
Nominal heating capacity
ISO-T1(JIS)
kW
(Min~Max)
Power Consumption Cooling/Heating
kW
Cooling/Heating
COP
Cooling/Heating
Energy label
Inrush current (Max. running current)
A
Indoor
Sound Ievel*1
dB(A)
Outdoor
Indoor
Air flow
CMM
Outdoor
50Hz/60Hz
Static pressure
Pa
Exterior dimensions Height x Width x Depth mm
Net weight
kg
Air filter, Q'ty
Remote control(option)
Exterior dimensions Height x Width x Depth mm
Net weight
kg
Type of compressor
Ref.amount precharged
kg(m)
Ref.piping size Liquid/Gas
ø
Ref.piping length
m
Vertical height O/U is higher
m
difference
O/U is lower
m
Cooling
O/U
Operating
temperature range Heating
O/U
FDUM125VNXVD
FDUM125VD
FDC125VNX
FDUM140VNXVD
FDUM140VD
FDC140VNX
FDUM100VSXVD
FDUM100VD
FDC100VSX
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
FDUM125VSXVD
FDUM125VD
FDC125VSX
FDUM140VSXVD
FDUM140VD
FDC140VSX
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
12.5
(5.0~14.0)
14.0
(5.0~16.0)
10.0
(4.0~11.2)
12.5
(5.0~14.0)
14.0
(5.0~16.0)
14.0
(4.0~17.0)
16.0
(4.0~18.0)
11.2
(4.0~16.0)
14.0
(4.0~18.0)
16.0
(4.0~20.0)
4.34/4.69
3.62/3.77
3.23/3.41
3.45/3.71
A/B
A/A
5(15)
5(26)
Hi:37 Me:35 Lo:32
Hi:38 Me:36 Lo:33
Hi:38 Me:36 Lo:33
Cooling:48 Heating:50
Cooling:49 Heating:52
Cooling:48 Heating:50 Cooling:49 Heating:52
Hi:28 Me:25 Lo:22
100
Standard:60/55, Max:85/100
Standard:60/55, Max:85/100
Standard:60/60, Max:90/100
350x1,370x635
59
Procure locally
Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E
1,300x970x370
105
Rotary
4.5(30)
9.52/15.88
100
30
15
-15~43*2
-20~20
3.62/3.77
3.45/3.71
A/A
4.34/4.69
3.23/3.41
A/B
2.72/2.95
3.68/3.80
A/A
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB. External static pressure
of indoor units is 60Pa.
the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*21 :: IfIndicates
* a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 50ZIXVD 35dB, 60ZIXVD 38dB, 71VNXVD 38dB, 100/125/140VNXVD 41dB, 100/125/140VSXVD 41dB
Air flow: 50ZIXVD 14CMM, 60ZIXVD 18CMM, 71VNXVD 23CMM, 100/125/140VNXVD 34CMM, 100/125/140VSXVD 34CMM
17
[ INDOOR UNIT ]
CEILING SUSPENDED
A
FDEN
CLASS
FDEN 40/50/60/71/100/125/140VD
Wired remote control
1 Improved installation workability
Wireless remote control
RC-E4
RCH-E3
RCN-E1R
(Option)
(Option)
(Option)
2 Compact and modern design
Point
Point
Increased freedom of a piping layout
Up
Height
210mm
Right
Rear
The refrigerant pipe from the unit can be arranged in three directions,
rear, right and up. The drain pipe can be arranged in two directions, left
and right. This will allow a free layout of piping for various installation
conditions. The unit can only be serviced from the bottom.
All models fit compactly on ceiling. (Height-210mm or 250mm).
Plain, modern design featuring rounded edges gives room a
comfortable atmosphere.
FDEN40VD, 50VD weights 30kg the lightest level in the industry.
Convenient and quick installation.
Outline drawing (Unit:mm)
290(Suspension bolts pitch)
24
b
40
68
52
Liquid piping
100
or more
Gas piping
e
d
173
5
135
Space for installation and service
Holes for suspension bolts
(M8 to M10X 4pcs.Not included)
410
145
40
c
690
Air outlet
195
235
300 or more
a (Suspension bolts pitch)
53
109
24
150
or more
5
or more
Obstacles
Drain hole
connection(1)
(VP20 (I.D.20))
271
Drain hole
connection(1)
(VP20(I.D.20))
76
53
Dimension Table
model
Air inlet grille
Gas piping
Drain hole
connection(1)
(VP20(I.D.20))
18
Note(1) The slope of drain piping
inside the unit is able
to take incline of 10mm.
10
308
Indication board
75 Liquid piping
110
135
a
b
c
d
e
FDEN40,50
1022
990
1070
215
210
FDEN60,71
1272
1240
1320
215
210
FDEN100~140
1572
1540
1620
255
250
SPECIFICATIONS
Set model name
Indoor name
Outdoor name
FDEN50ZIXVD
FDEN50VD
SRC50ZIX-S
FDEN40ZIXVD
FDEN40VD
SRC40ZIX-S
Range of Outdoor unit Indoor unit
usage
FDEN71VNXVD
FDEN71VD
FDC71VNX
FDEN100VNXVD
FDEN100VD
FDC100VNX
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
Power source
Nominal cooling capacity
ISO-T1(JIS)
kW
(Min~Max)
Nominal heating capacity
ISO-T1(JIS)
kW
(Min~Max)
kW
Power Consumption Cooling/Heating
Cooling/Heating
COP
Cooling/Heating
Energy label
A
Inrush current (Max. running current)
Indoor
*
1
Sound Ievel
dB(A)
Outdoor
Indoor
Air flow
CMM
Outdoor
Exterior dimensions Height x Width x Depth mm
Net weight
kg
Air filter, Q'ty
Remote control(option)
Exterior dimensions Height x Width x Depth mm
Net weight
kg
Type of compressor
Ref.amount precharged
kg(m)
ø
Ref.piping size Liquid/Gas
Ref.piping length
m
Vertical height O/U is higher
m
difference
m
O/U is lower
O/U
Cooling
Operating
temperature range Heating
O/U
FDEN60ZIXVD
FDEN60VD
SRC60ZIX-S
7.1
10.0
(3.2~8.0)
(4.0~11.2)
8.0
11.2
(3.6~9.0)
(4.0~12.5)
2.11/2.11
2.80/2.88
3.36/3.79
3.57/3.89
A/A
A/A
5(17)
5(24)
5(14)
Hi:44 Me:41 Lo:39
Hi:41 Me:39 Lo:38
48
Cooling:51 Heating:48
Cooling:48 Heating:50
Hi:18 Me:14 Lo:12
Hi:26 Me:23 Lo:21
Hi:18 Me:14 Lo:12
100
Cooling:60 Heating:50
210x1,320x690
250x1,620x690
37
49
Pocket Plastic net x2 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-E1R
640x800(+71)x290
1,300x970x370
750x880(+88)x340
43
105
60
Scroll
Rotary
1.4(15)
4.5(30)
2.95(30)
6.35/12.7
9.52/15.88
30
50
20
30
20
15
-15~43*2
-15~20
-20~20
4.0
5.0
(1.8~4.7)
(2.2~5.6)
4.5
5.4
(2.0~5.4)
(2.5~6.3)
1.04/1.13
1.59/1.58
3.85/3.98
3.14/3.42
A/A
B/B
5(12)
Hi:39 Me:38 Lo:37
47
Hi:11 Me:9 Lo:7
40
210x1,070x690
28
5.6
(2.8~6.3)
6.7
(3.1~7.1)
1.95/2.12
2.87/3.16
C/D
SPECIFICATIONS
Set model name
Indoor name
Outdoor name
Power source
Range of Outdoor unit Indoor unit
usage
Nominal cooling capacity
ISO-T1(JIS)
kW
(Min~Max)
Nominal heating capacity
ISO-T1(JIS)
kW
(Min~Max)
kW
Power Consumption Cooling/Heating
Cooling/Heating
COP
Cooling/Heating
Energy label
A
Inrush current (Max. running current)
Indoor
Sound Ievel*1
dB(A)
Outdoor
Indoor
Air flow
CMM
Outdoor
Exterior dimensions Height x Width x Depth mm
Net weight
kg
Air filter, Q'ty
Remote control(option)
Exterior dimensions Height x Width x Depth mm
kg
Net weight
Type of compressor
kg(m)
Ref.amount precharged
ø
Ref.piping size Liquid/Gas
m
Ref.piping length
m
Vertical height O/U is higher
m
O/U is lower
difference
O/U
Cooling
Operating
temperature range Heating
O/U
FDEN125VNXVD
FDEN125VD
FDC125VNX
FDEN140VNXVD
FDEN140VD
FDC140VNX
FDEN100VSXVD
FDEN100VD
FDC100VSX
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
12.5
(5.0~14.0)
14.0
(4.0~17.0)
3.86/3.77
3.24/3.71
A/A
14.0
(5.0~16.0)
16.0
(4.0~18.0)
4.98/4.69
2.81/3.41
C/B
10.0
(4.0~11.2)
11.2
(4.0~16.0)
2.80/2.88
3.57/3.89
A/A
FDEN125VSXVD
FDEN125VD
FDC125VSX
FDEN140VSXVD
FDEN140VD
FDC140VSX
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
5(26)
Hi:46 Me:44 Lo:43
Cooling:48 Heating:50 Cooling:49 Heating:52
Hi:29 Me:26 Lo:23
12.5
14.0
(5.0~14.0)
(5.0~16.0)
14.0
16.0
(4.0~18.0)
(4.0~20.0)
3.86/3.77
4.98/4.69
3.24/3.71
2.81/3.41
A/A
C/B
5(15)
Hi:46 Me:44 Lo:43
Cooling:48 Heating:50 Cooling:49 Heating:52
Hi:29 Me:26 Lo:23
100
100
Hi:44 Me:41 Lo:39
Cooling:48 Heating:50
Hi:26 Me:23 Lo:21
100
250x1,620x690
49
Pocket Plastic net x2 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-E1R
1,300x970x370
105
Rotary
4.5(30)
9.52/15.88
50
30
15
-15~43*2
-20~20
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB.
Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*21 :: IfIndicates
* a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 40/50ZIXVD 46dB, 60ZIXVD 50dB, 71VNXVD 50dB, 100VNXVD 46dB, 125/140VNXVD 50dB, 100VSXVD 46dB, 125/140VSXVD 50dB
Air flow: 40/50ZIXVD 13CMM, 60ZIXVD 22CMM, 71VNXVD 22CMM, 100VNXVD 28CMM, 125/140VNXVD 32CMM, 100VSXVD 28CMM, 125/140VSXVD 32CMM
19
Micro Inverter [ INDOOR UNIT ]
A
CEILING CASSETTE -4way-
FDT
CLASS
FDT 100/125/140VD
Wireless remote control
Wired remote control
RC-E4
RCH-E3
RCN-T-36W-E
(Option)
(Option)
(Option)
SPECIFICATIONS
Micro Inverter
Set model name
Indoor name
Outdoor name
FDT100VNVD
FDT100VD
FDC100VN
Power source
*1
Indoor
kW
kW
kW
Indoor
10.0
(4.0~11.2)
11.2
(4.0~12.5)
2.76/2.74
3.62/4.09
A/A
A
dB(A)
Outdoor
CMM
Outdoor
Exterior dimensions Height x Width x Depth mm
kg
Net weight
Unit+Panel
Panel
Air filter, Q'ty
Remote control(option)
Exterior dimensions Height x Width x Depth mm
kg
Net weight
Type of compressor
kg(m)
Ref.amount precharged
ø
Ref.piping size Liquid/Gas
m
Ref.piping length
m
Vertical height O/U is higher
m
difference
O/U is lower
O/U
Cooling
Operating
temperature range Heating
O/U
Hi:40
Me:37 Lo:35
49
Hi:27
Me:24 Lo:20
12.5
(5.0~14.0)
14.0
(4.0~16.0)
4.05/3.77
3.09/3.71
B/A
5(24)
Hi:42
Me:40 Lo:37
Cooling:50 Heating:51
Hi:30
Me:27 Lo:23
Cooling:75 Heating:73
Range of Outdoor unit
usage
FDT100VSVD
FDT100VD
FDC100VS
FDT125VSVD
FDT125VD
FDC125VS
FDT140VSVD
FDT140VD
FDC140VS
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
14.0
(5.0~14.5)
16.0
(4.0~16.5)
4.98/4.57
2.81/3.50
C/B
10.0
(4.0~11.2)
11.2
(4.0~12.5)
2.76/2.74
3.62/4.09
A/A
Hi:43
Me:41 Lo:38
51
Hi:30
Me:27 Lo:23
Hi:40
Me:37 Lo:35
49
Hi:27
Me:24 Lo:20
12.5
(5.0~14.0)
14.0
(4.0~16.0)
4.05/3.77
3.09/3.71
B/A
5(15)
Hi:42
Me:40 Lo:37
Cooling:50 Heating:51
Hi:30
Me:27 Lo:23
Cooling:75 Heating:73
14.0
(5.0~14.5)
16.0
(4.0~16.5)
4.98/4.57
2.81/3.50
C/B
Hi:43
Me:41 Lo:38
51
Hi:30
Me:27 Lo:23
Unit:298x840x840 Panel:35x950x950
32.5(Unit:27 Panel:5.5)
T-PSA-3AW-E
Pocket Plastic net x1 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-T-36W-E
845x970x370
Indoor unit
Air flow
FDT140VNVD
FDT140VD
FDC140VN
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
Nominal cooling capacity
ISO-T1(JIS)
(Min~Max)
Nominal heating capacity
ISO-T1(JIS)
(Min~Max)
Power Consumption Cooling/Heating
Cooling/Heating
COP
Cooling/Heating
Energy label
Inrush current (Max. running current)
Sound Ievel
FDT125VNVD
FDT125VD
FDC125VN
81
83
Rotary
3.8(30)
9.52/15.88
50
30
15
-15~43*2
-20~20
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*21 :: IfIndicates
* a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 100/125/140VNVD 51dB, 100/125/140VSVD 51dB
Air flow: 100/125/140VNVD 37CMM, 100/125/140VSVD 37CMM
20
A
DUCT CONNECTED -High Static pressure-
FDU
CLASS
SPECIFICATIONS
RC-E4
RCH-E3
(Option)
(Option)
FDU 100/125/140VD
Wireless
remote control
RCN-KIT3-E
FDU 200/250VD
(Option)
Fan control kit
(100~200Pa)
U-FCRA
[For 200/250VD]
(option)
*FDU100VNVD
FDU100VD
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
kW
ISO-T1(JIS)
(Min~Max)
Nominal heating capacity
kW
ISO-T1(JIS)
(Min~Max)
Power Consumption Cooling/Heating
kW
COP
Cooling/Heating
Energy label
Cooling/Heating
Inrush current (Max. running current)
A
1
Indoor
*
dB(A)
Sound Ievel
Outdoor
Indoor
Air flow
CMM
Outdoor
External static pressure
Pa
Exterior dimensions Height x Width x Depth mm
kg
Net weight
Air filter, Q'ty
Remote control(option)
Exterior dimensions Height x Width x Depth mm
kg
Net weight
Type of compressor
kg(m)
Ref.amount precharged
ø
Ref.piping size Liquid/Gas
m
Ref.piping length
m
Vertical height O/U is higher
m
difference
O/U is lower
Cooling
O/U
Operating
temperature range Heating
O/U
*FDU125VNVD
FDU125VD
FDC125VN
FDC100VN
1Phase 220-240V 50Hz
10.0
12.5
(4.0~11.2)
(5.0~14.0)
11.2
14.0
(4.0~12.5)
(4.0~16.0)
2.88/2.99
4.04/3.79
3.09/3.69
3.47/3.75
B/A
A/A
5(27)
5(25)
Hi:43 Lo:38
Hi:42 Lo:37
Cooling:50 Heating:51
49
Hi:42 Lo:33.5
Hi:34 Lo:27
Cooling:75 Heating:73
Standard:50, Max:130
350x1,370x650
63
Procure locally
Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E
845x970x370
81
Rotary
3.8(30)
9.52/15.88
50
30
15
-15~43*3
-15~43*2
-20~20
Range of Outdoor unit Indoor unit
usage
Wired
remote control
*
Not available in 60Hz
Micro Inverter
SPECIFICATIONS
*
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
ISO-T1(JIS)
(Min~Max)
Nominal heating capacity
ISO-T1(JIS)
(Min~Max)
Power Consumption Cooling/Heating
COP
kW
kW
kW
Cooling/Heating
Range of Outdoor unit Indoor unit
usage
Cooling/Heating
Energy label
A
Inrush current (Max. running current)
Indoor
1
dB(A)
Sound Ievel*
Outdoor
Indoor
CMM
Air flow
Outdoor
2
Pa
External static pressure *
Exterior dimensions Height x Width x Depth mm
kg
Net weight
Air filter, Q'ty
Remote control(option)
Exterior dimensions Height x Width x Depth mm
kg
Net weight
Type of compressor
kg(m)
Ref.amount precharged
ø
Ref.piping size Liquid/Gas
m
Ref.piping length
m
Vertical height O/U is higher
m
O/U is lower
difference
O/U
Cooling
Operating
temperature range Heating
O/U
FDU140VNVD
FDU140VD
FDC140VN
1Phase
220-240V 50Hz
14.0
(5.0~14.5)
16.0
(4.0~16.5)
*
Micro Inverter
FDU100VSVD
FDU100VD
FDC100VS
*FDU125VSVD
FDU125VD
*FDU140VSVD
FDU140VD
FDC125VS
FDC140VS
12.5
(5.0~14.0)
14.0
(4.0~16.0)
14.0
(5.0~14.5)
16.0
(4.0~16.5)
4.95/4.43
2.88/2.99
4.04/3.79
4.95/4.43
2.83/3.61
3.47/3.75
3.09/3.69
2.83/3.61
81
FDU250VSVD
FDU250VD
FDC250VS
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
3Phase 380-415V 50Hz
10.0
(4.0~11.2)
11.2
(4.0~12.5)
C/A
5(28)
Hi:43 Lo:38
51
Hi:42 Lo:33.5
FDU200VSVD
FDU200VD
FDC200VS
A/A
C/A
B/A
5(16)
5(19)
5(18)
Hi:42 Lo:37
Hi:43 Lo:38
51
Cooling:50 Heating:51
49
Hi:34 Lo:27
Hi:42 Lo:33.5
Cooling:75 Heating:73
Standard:50, Max:130
350x1,370x650
63
Procure locally
Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E
845x970x370
83
Rotary
3.8(30)
9.52/15.88
50
30
15
-15~43 *3
-20~20
20.0
25.0
(7.0~22.4)
(10.0~28.0)
22.4
28.0
(7.6~25.0)
(9.5~31.5)
50Hz:6.59/6.08
50Hz: 9.91/8.50
60Hz:6.58/5.84
60Hz:10.21/8.22
50Hz:3.03/3.68
50Hz:2.52/3.29
60Hz:3.04/3.83
60Hz:2.45/3.41
50Hz:E/C 60Hz:E/B
B/A
5(27)
5(24)
52
51
Cooling:57 Heating:58
57
50Hz:68, 60Hz:80
50Hz:51, 60Hz:60
Cooling:150 Heating:145
Standard:100, Max:200
360x1,570x830
92
1,300x970x370
122
140
Scroll
5.4(30)
9.52/25.4
7.2(30)
12.7/25.4
70
-15~20
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB. External static pressure
of FDU100/125/140 is 60Pa and that of FDU200/250 is 100Pa.
Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*21 :: External
static pressure is changeable to be set by the remote control. Standard external static pressure is factory setting. MAX external static pressure is ''High static
*
pressure'' setting. The values of sound pressure level become 5dB(A) higher at eternal static pressure of 130Pa.
*3 : If a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
21
Micro Inverter [ INDOOR UNIT ]
A
DUCT CONNECTED -Low/Middle Static pressure-
FDUM
CLASS
FDUM 100/125/140VD
Filter kit
UM-FL3E : for 100, 125, 140
(option)
external static pressure loss:5pa
Wired remote control
RC-E4
RCH-E3
(Option)
(Option)
Wireless remote control
RCN-KIT3-E
(Option)
SPECIFICATIONS
Micro Inverter
FDUM140VSVD
FDUM100VSVD
FDUM125VSVD
FDUM100VNVD
FDUM125VNVD
FDUM140VNVD
FDUM140VD
FDUM100VD
FDUM125VD
FDUM100VD
FDUM125VD
FDUM140VD
FDC140VS
FDC100VS
FDC125VS
FDC100VN
FDC125VN
FDC140VN
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
10.0
14.0
12.5
10.0
14.0
12.5
kW
(4.0~11.2)
(5.0~14.5)
(5.0~14.0)
(4.0~11.2)
(5.0~14.5)
(5.0~14.0)
11.2
16.0
14.0
11.2
16.0
14.0
kW
(4.0~12.5)
(4.0~16.5)
(4.0~16.0)
(4.0~12.5)
(4.0~16.5)
(4.0~16.0)
50Hz:2.80/2.77
50Hz:4.95/4.89
50Hz:4.03/3.80
50Hz:2.80/2.77
50Hz:4.95/4.89
50Hz:4.03/3.80
Power Consumption Cooling/Heating
kW
60Hz:2.80/2.80
60Hz:4.95/4.91
60Hz:4.03/3.85
60Hz:2.80/2.80
60Hz:4.95/4.91
60Hz:4.03/3.85
50Hz:3.57/4.04
50Hz:2.83/3.27
50Hz:3.10/3.68
50Hz:3.57/4.04
50Hz:2.83/3.27
50Hz:3.10/3.68
COP
Cooling/Heating
60Hz:3.57/4.00
60Hz:2.83/3.26
60Hz:3.10/3.64
60Hz:3.57/4.00
60Hz:2.83/3.26
60Hz:3.10/3.64
Energy label
A/A
C/C
B/A
A/A
C/C
B/A
Cooling/Heating
5(24)
5(15)
Inrush current (Max. running current)
A
Hi:37 Me:35 Lo:32
Hi:38 Me:36 Lo:33
Hi:38 Me:36 Lo:33
Hi:37 Me:35 Lo:32
1
Indoor
dB(A)
Sound Ievel*
49
Cooling:50 Heating:51
51
49
Cooling:50 Heating:51
51
Outdoor
Hi:28 Me:25 Lo:22
Indoor
Air flow
CMM
Cooling:75 Heating:73
Outdoor
Standard:60, Max:90/100
Standard:60/55, Max:85/100
Standard:60, Max:90/100
Standard:60/55, Max:85/100
Static pressure
Pa
Exterior dimensions Height x Width x Depth mm
350x1,370x635
Net weight
kg
59
Air filter, Q'ty
Procure locally
Remote control(option)
Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E
Exterior dimensions Height x Width x Depth mm
845x970x370
Net weight
kg
81
83
Type of compressor
Rotary
Ref.amount precharged
kg(m)
3.8(30)
ø
Ref.piping size
Liquid/Gas
9.52/15.88
Ref.piping length
m
50
Vertical height O/U is higher
m
30
difference
m
15
O/U is lower
Cooling
O/U
-15~43*2
Operating
temperature range Heating
O/U
-20~20
Range of Outdoor unit Indoor unit
usage
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
ISO-T1(JIS)
(Min~Max)
Nominal heating capacity
ISO-T1(JIS)
(Min~Max)
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB. External static pressure
of indoor units is 60Pa.
the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*21 :: IfIndicates
* a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 100/125/140VNVD 41dB, 100/125/140VSVD 41dB
Air flow: 100/125/140VNVD 34CMM, 100/125/140VSVD 34CMM
22
A
CEILING SUSPENDED
FDEN
CLASS
FDEN 100/125/140VD
Wired remote control
Wireless remote control
RC-E4
RCH-E3
RCN-E1R
(Option)
(Option)
(Option)
SPECIFICATIONS
Micro Inverter
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
ISO-T1(JIS)
(Min~Max)
Nominal heating capacity
ISO-T1(JIS)
(Min~Max)
Power Consumption Cooling/Heating
COP
Cooling/Heating
Energy label
Cooling/Heating
Inrush current (Max. running current)
*1
Sound Ievel
Indoor
kW
kW
kW
A
dB(A)
Outdoor
Air flow
Indoor
Range of Outdoor unit Indoor unit
usage
CMM
Outdoor
Exterior dimensions Height x Width x Depth mm
kg
Net weight
Air filter, Q'ty
Remote control(option)
Exterior dimensions Height x Width x Depth mm
kg
Net weight
Type of compressor
kg(m)
Ref.amount precharged
ø
Ref.piping size Liquid/Gas
m
Ref.piping length
m
Vertical height O/U is higher
m
difference
O/U is lower
O/U
Cooling
Operating
temperature range Heating
O/U
FDEN140VNVD
FDEN125VNVD
FDEN100VNVD
FDEN100VSVD
FDEN125VSVD
FDEN140VSVD
FDEN100VD
FDEN125VD
FDEN140VD
FDEN140VD
FDEN125VD
FDEN100VD
FDC100VS
FDC125VS
FDC140VS
FDC140VN
FDC125VN
FDC100VN
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
12.5
14.0
10.0
10.0
12.5
14.0
(5.0~14.5)
(4.0~11.2)
(4.0~11.2)
(5.0~14.0)
(5.0~14.5)
(5.0~14.0)
16.0
14.0
11.2
11.2
14.0
16.0
(4.0~16.5)
(4.0~16.0)
(4.0~12.5)
(4.0~12.5)
(4.0~16.0)
(4.0~16.5)
5.80/4.92
4.45/4.08
2.85/2.97
2.85/2.97
4.45/4.08
5.80/4.92
3.51/3.77
2.41/3.25
2.80/3.43
3.51/3.77
2.80/3.43
2.41/3.25
A/A
E/C
C/B
A/A
C/B
E/C
5(24)
5(15)
Hi:44
Hi:44
Hi:46 Me:44 Lo:43
Hi:46 Me:44 Lo:43
Me:41 Lo:39
Me:41 Lo:39
49
49
Cooling:50 Heating:51
Cooling:50 Heating:51
51
51
Hi:26
Hi:26
Hi:29 Me:26 Lo:23
Hi:29 Me:26 Lo:23
Me:23 Lo:21
Me:23 Lo:21
Cooling:75 Heating:73
250x1,620x690
49
Pocket Plastic net x2 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-E1R
845x970x370
81
83
Rotary
3.8(30)
9.52/15.88
50
30
15
-15~43*2
-20~20
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB.
Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*21 :: IfIndicates
* a cooling operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 100VNVD 46dB, 125/140VNVD 50dB, 100VSVD 46dB, 125/140VSVD 50dB
Air flow: 100VNVD 28CMM, 125/140VNVD 32CMM, 100VSVD 28CMM, 125/140VSVD 32CMM
23
MULTI SYSTEM
Up to Four indoor units can be connected
to a single outdoor unit and simultaneously
operated with a single remote control.
Twin / Triple / Double Twin Multi System
By referring to the following table for applicable indoor units,
select the same models and capacities.
Applicable indoor units
Capacity
Model
Combination
4way
4way compact (600 x 600mm)
Low/Middle Static pressure
Ceiling Suspended
Wall Mounted
Only used with outdoor units of Multi System
Combination of indoor units
Micro Inverter
NEW
FDC125VNX FDC140VNX FDC100VNV FDC125VNV FDC140VNV
FDC71VNX FDC100VNX
FDC100VSX FDC125VSX FDC140VSX FDC100VSV FDC125VSV FDC140VSV FDC200VSV FDC250VSV
40 + 40
50 + 50
60 + 60
71 + 71
50 + 50
60 + 60
71 + 71
100 + 100
125 + 125
50 + 50 + 50
50 + 50 + 50 71 + 71 + 71
50+50+50+50 60+60+60+60
Decision of piping specification
Twin type
(Example)
Item
Models FDC71VNX, FDC100~140VNV/VSV
[Branch pipe set : DIS-WA1]
3
2
1
Liquid line
3
Gas pipe
Symbol
Liquid pipe
48
ID15.88
11
24
ø12.7Xt 0.8
ø9.52Xt 0.8 ø9.52Xt 0.8 ø15.88Xt1.0
ø15.88Xt1.0
Symbol
Reducer
ID15.88
ID9.52
1
8
2
Symbol
210
ø6.35
flared nut
ID9.52
50
8
ID9.52
105
Notes (1) Symbol 1 to 4 in the drawing shows the symbols of branch piping parts in the chart respectively.
(2) Branch piping should always be arranged to have level or perpendicular position.
24
Gas pipe
Main pipe Branch pipe
Reducer
Symbol
ID9.52
ID15.88
11
Chart of shapes of
branch piping parts
(DIS-WA1)
Liquid pipe
Main pipe Branch pipe
Notes (1) When 40-60 models of indoor units are applied to this combination, the
reducer 3 supplied with the branch piping set should be used in order to
reduce the liquid piping size from ø9.52mm to ø6.35mm at indoor unit side
(flare connection). Accordingly be sure to select the liquid piping size
ø9.52mm from branch to indoor unit.
(2) The reducer 4 is for FDC71 and 100 models only.
4
180
L
Model
FDC71
FDC100
FDC125
FDC140
Indoor unit
Gas line
4
Indoor unit
combinations
40+40
50+50
60+60
71+71
8
Outdoor unit
Diagrams below show the application as samples. For further information, refer to TECHNICAL MANUAL.
3
OD15.88
80
2 piece
ID12.7
10
The branch piping (both gas and liquid lines)
should always be arranged to have a level
or perpendicular position.
2-Way Branch
Floor
Mount
sections
level with the floor.
Floor
Mount
sections
perpendicular to the floor.
3-Way Branch
4
2 piece
Floor
Floor
Ideal for the installation in large area and L-shaped rooms, the V
Multi System has an extensive degree of flexibility in the selection
of indoor units. Specifically, the selection of indoor units with
different capacities in different types can be made.
V Multi System
Different models and capacities
can be selected.
Applicable indoor units
Capacity
Model
4way
Ceiling Suspended
Combination of indoor units
NEW
FDC71VNX
Micro Inverter
FDC100VNX
FDC100VSX
FDC125VNX
FDC125VSX
FDC140VNX
FDC140VSX
FDC100VNV
FDC100VSV
FDC125VNV
FDC125VSV
FDC140VNV
FDC140VSV
FDC200VSV
FDC250VSV
50 + 50
60 + 60
50 + 71
71 + 71
100 + 100
71 + 125
125 + 125
50 + 50 + 50
71 + 71 + 71
60 + 60 + 125
71 + 71 + 100
40 + 40
50+50+50+50 60+60+60+60
Triple type
The indoor_outdoor piping length differences among indoor units are less than 3m.
Model FDC140VNV/VSV
[Branch pipe set : DIS-TA1]
(Example)
Indoor unit
Item
Model
3
ø15.88Xt 1.0
100
80 80
Symbol
ID15.88
Liquid pipe
ID12.7x3
0
10
ø12.7X t0.8
ID9.52
1
Symbol
8
10
300
Reducer
Symbol
ID9.52x3
14°
Chart of shapes of
branch piping parts
(DIS-TA1)
30
Gas pipe
3
10
2
3
Floor
ø9.52Xt 0.8
30
1
L
Liquid line
ø9.52X t0.8
100
Outdoor unit
50+50+50
Notes (1) The reducer 3 supplied with the branch piping set should be used in order to reduce the liquid piping size
from ø9.52mm to ø6.35mm at indoor unit side (flare connection). Accordingly be sure to select the liquid piping
size ø9.52mm from branch to indoor unit.
Gas line
Floor
FDC140
Gas pipe
Main pipe
Branch pipe
Liquid pipe
Main pipe
Branch pipe
Indoor unit
combinations
8
2
ID9.52
8
105
50
ø6.35
flared
nut
3
237
Notes (1) Symbol 1 to 3 in the drawing shows the symbols of branch piping parts in the chart respectively.
(2) Branch piping should always be arranged to have level or perpendicular position.
25
MULTI [ INDOOR UNIT ]
A
CEILING CASSETTE -4way-
FDT
CLASS
SPECIFICATIONS
Set model name
Wireless remote control
RC-E4
RCH-E3
RCN-T-36W-E
(Option)
(Option)
(Option)
SPECIFICATIONS
Set model name
Indoor name
Outdoor name
Power source
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
Nominal cooling capacity
7.1
10.0
kW
ISO-T1(JIS)
(3.2~8.0)
(4.0~11.2)
(Min~Max)
Nominal heating capacity
8.0
11.2
kW
ISO-T1(JIS)
(3.6~9.0)
(4.0~12.5)
(Min~Max)
Power Consumption Cooling/Heating
kW
1.85/1.99
2.56/2.66
COP
Cooling/Heating
3.84/4.02
3.91/4.21
Energy label
Cooling/Heating
A/A
A/A
Inrush current (Max. running current)
A
5(24)
5(17)
Hi:33 Me:31 Lo:30
Indoor*2
Sound Ievel*1
dB(A)
Cooling:51 Heating:48 Cooling:48 Heating:50
Outdoor
2
Hi:18 Me:16 Lo:14
Indoor*
Air flow
CMM
Cooling:60 Heating:50
Outdoor
100
Exterior dimensions Height x Width x Depth mm Unit:246x840x840 Panel:35x950x950
kg
Unit+Panel
Net weight
27.5(Unit:22 Panel:5.5)
Panel
T-PSA-3AW-E
Air filter, Q'ty
Pocket Plastic net x1 (Washable)
Remote control(option)
Wired:RC-E4, RCH-E3 Wireless:RCN-T-36W-E
Exterior dimensions Height x Width x Depth mm 750x880(+88)x340 1,300x970x370
Net weight
kg
105
60
kg(m)
Ref.amount precharged
4.5(30)
2.95(30)
ø
Ref.piping size Liquid/Gas
9.52/15.88
m
Ref.piping length
100
50
m
Vertical height O/U is higher
30
m
difference
O/U is lower
15
Operating
O/U
Cooling
-15~43*3
temperature range Heating
O/U
-20~20
Indoor unit
Wired remote control
FDT100VNXPVD
FDT71VNXPVD
Twin
FDT40VD
FDT50VD
FDC71VNX
FDC100VNX
Range of Outdoor unit
usage
FDT 40/50/60/71/100/125VD
The values are for simultaneous Multi operation.
The values are for simultaneous Multi operation.
FDT125VNXPVD FDT140VNXPVD FDT140VNXTVD FDT100VSXPVD FDT125VSXPVD FDT140VSXPVD FDT140VSXTVD
Twin
Triple
Twin
Triple
FDT50VD
FDT60VD
FDT71VD
FDT50VD
FDT71VD
FDT50VD
FDT60VD
FDC140VNX
FDC125VSX
FDC140VSX
FDC140VSX
FDC140VNX
FDC100VSX
FDC125VNX
Range of Outdoor unit
usage
Indoor unit
Indoor name
Outdoor name
Power source
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
Nominal cooling capacity
14.0
12.5
14.0
10.0
12.5
14.0
14.0
kW
ISO-T1(JIS)
(5.0~16.0)
(5.0~14.0)
(5.0~16.0)
(4.0~11.2)
(5.0~14.0)
(5.0~14.5)
(5.0~14.5)
(Min~Max)
Nominal heating capacity
16.0
14.0
16.0
11.2
14.0
16.0
16.0
kW
ISO-T1(JIS)
(4.0~18.0)
(4.0~17.0)
(4.0~18.0)
(4.0~16.0)
(4.0~18.0)
(4.0~20.0)
(4.0~20.0)
(Min~Max)
Power Consumption Cooling/Heating
kW
3.88/3.70
3.06/3.22
3.88/3.76
2.56/2.66
3.06/3.22
3.88/3.70
3.88/3.76
COP
Cooling/Heating
3.61/4.32
4.08/4.35
3.61/4.26
3.91/4.21
4.08/4.35
3.61/4.32
3.61/4.26
Energy label
Cooling/Heating
A/A
A/A
A/A
A/A
A/A
A/A
A/A
Inrush current (Max. running current)
A
5(26)
5(15)
2
Hi:33 Me:31 Lo:30 Hi:35 Me:33 Lo:31 Hi:33 Me:31 Lo:30
Hi:33 Me:31 Lo:30
Hi:35 Me:33 Lo:31 Hi:33 Me:31 Lo:30
Indoor*
Sound Ievel*1
dB(A)
Cooling:48 Heating:50
Cooling:48 Heating:50
Cooling:49 Heating:52
Cooling:49 Heating:52
Outdoor
Hi:18 Me:16 Lo:14 Hi:21 Me:19 Lo:17 Hi:18 Me:16 Lo:14
Indoor*2
Hi:21 Me:19 Lo:17 Hi:18 Me:16 Lo:14
Hi:18 Me:16 Lo:14
Air flow
CMM
100
Outdoor
Exterior dimensions Height x Width x Depth mm
Unit:246x840x840 Panel:35x950x950
kg
Unit+Panel
Net weight
27.5(Unit:22 Panel:5.5)
29.5(Unit:24 Panel:5.5)
27.5(Unit:22 Panel:5.5)
29.5(Unit:24 Panel:5.5)
Panel
T-PSA-3AW-E
Air filter, Q'ty
Pocket Plastic net x1 (Washable)
Remote control(option)
Wired:RC-E4, RCH-E3 Wireless:RCN-T-36W-E
Exterior dimensions Height x Width x Depth mm
1,300x970x370
Net weight
kg
105
kg(m)
Ref.amount precharged
4.5(30)
ø
Ref.piping size Liquid/Gas
9.52/15.88
m
Ref.piping length
100
m
Vertical height O/U is higher
30
m
difference
O/U is lower
15
Operating
O/U
Cooling
-15~43*3
temperature range Heating
O/U
-20~20
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*21 :: The
values are for one indoor unit operation.
*3 : If a cooling
operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
*
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 71/100VNXPVD 39dB, 100VSXPVD 39dB, 125/140VNXPVD 46dB, 125/140VSXPVD 46dB, 140VNXTVD 39dB,
140VSXTVD 39dB
Air flow: 71/100VNXPVD 20CMM, 100VSXPVD 20CMM, 125/140VNXPVD 28CMM, 125/140VSXPVD 28CMM, 140VNXTVD 20CMM, 140VSXTVD 20CMM
26
SPECIFICATIONS
The values are for simultaneous Multi operation.
Micro Inverter
FDT100VNPVD FDT125VNPVD FDT140VNPVD FDT140VNTVD FDT100VSPVD FDT125VSPVD FDT140VSPVD
Twin
Triple
Twin
Indoor name
FDT50VD
FDT50VD
FDT60VD
FDT71VD
FDT71VD
FDT50VD
FDT60VD
Outdoor name
FDC140VN
FDC125VS
FDC140VS
FDC100VS
FDC140VN
FDC100VN
FDC125VN
Power source
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
Nominal cooling capacity
10.0
14.0
10.0
12.5
14.0
12.5
14.0
kW
ISO-T1(JIS)
(4.0~11.2)
(5.0~14.5)
(4.0~11.2)
(5.0~14.0)
(5.0~14.5)
(5.0~14.0)
(5.0~14.5)
(Min~Max)
Nominal heating capacity
11.2
16.0
11.2
14.0
16.0
14.0
16.0
kW
ISO-T1(JIS)
(4.0~12.5)
(4.0~16.5)
(4.0~12.5)
(4.0~16.0)
(4.0~16.5)
(4.0~16.0)
(4.0~16.5)
(Min~Max)
Power Consumption Cooling/Heating
kW
2.94/3.09
4.65/4.63
2.94/3.09
3.95/3.70
4.51/4.58
3.95/3.70
4.51/4.58
COP
Cooling/Heating
3.40/3.62
3.01/3.46
3.40/3.62
3.16/3.78
3.10/3.49
3.16/3.78
3.10/3.49
Energy label
Cooling/Heating
A/A
B/B
A/A
B/A
B/B
B/A
B/B
5(15)
Inrush current (Max. running current)
A
5(24)
Hi:33
Hi:35
Hi:33
Hi:33
Hi:33
Hi:35
Hi:33
Indoor*2
*1
Sound Ievel
dB(A) Me:31 Lo:30
Me:33 Lo:31
Me:31 Lo:30
Me:31 Lo:30
Me:31 Lo:30
Me:33 Lo:31
Me:31 Lo:30
49
Cooling:50 Heating:51
51
Outdoor
Cooling:50 Heating:51
49
51
Hi:21
Hi:18
Hi:21
*
2
Hi:18
Me:16
Lo:14
Hi:18
Me:16
Lo:14
Indoor
Me:19 Lo:17
Me:16 Lo:14
Air flow
CMM
Me:19 Lo:17
Cooling:75 Heating:73
Outdoor
Exterior dimensions Height x Width x Depth mm
Unit:246x840x840 Panel:35x950x950
29.5(Unit:24 Panel:5.5)
29.5(Unit:24 Panel:5.5)
27.5(Unit:22 Panel:5.5)
kg 27.5(Unit:22 Panel:5.5)
Net weight
Unit+Panel
Panel
T-PSA-3AW-E
Air filter, Q'ty
Pocket Plastic net x1 (Washable)
Remote control(option)
Wired:RC-E4, RCH-E3 Wireless:RCN-T-36W-E
Exterior dimensions
845x970x370
Net weight
kg
81
83
Ref.amount precharged
kg(m)
3.8(30)
Ref.piping size Liquid/Gas
ø
9.52/15.88
m
50
Ref.piping length
m
30
Vertical height O/U is higher
O/U is lower
m
15
difference
Cooling
Operating
O/U
-15~43*3
temperature range Heating
O/U
-20~20
Range of Outdoor unit
usage
Indoor unit
Set model name
Powerful-Hi can be selected. Sound level: 100VNPVD 39dB, 125/140VNPVD 46dB, 140VNTVD 39dB, 100VSPVD 39dB, 125/140VSPVD 46dB
Air flow: 100VNPVD 20CMM, 125/140VNPVD 28CMM, 140VNTVD 20CMM, 100VSPVD 20CMM, 125/140VSPVD 28CMM
SPECIFICATIONS
The values are for simultaneous Multi operation.
Micro Inverter
FDT140VSTVD
FDT200VSTVD
FDT200VSDVD
FDT250VSDVD
Triple
Double Twin
Indoor name
FDT50VD
FDT71VD
FDT50VD
FDT60VD
Outdoor name
FDC140VS
FDC200VS
FDC200VS
FDC250VS
Power source
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
Nominal cooling capacity
25.0
14.0
20.0
20.0
25.0
20.0
kW
ISO-T1(JIS)
(10.0~28.0)
(5.0~14.5)
(7.0~22.4)
(7.0~22.4)
(10.0~28.0)
(7.0~22.4)
(Min~Max)
Nominal heating capacity
28.0
16.0
22.4
22.4
28.0
22.4
kW
ISO-T1(JIS)
(9.5~31.5)
(4.0~16.5)
(7.6~25.0)
(7.6~25.0)
(9.5~31.5)
(7.6~25.0)
(Min~Max)
Power Consumption Cooling/Heating
kW
8.30/7.75
4.65/4.63
6.49/6.12
6.58/6.15
8.28/7.70
6.58/6.02
COP
Cooling/Heating
3.01/3.61
3.01/3.46
3.08/3.66
3.04/3.64
3.02/3.64
3.04/3.72
Energy label
Cooling/Heating
B/A
B/B
B/A
B/A
B/A
B/A
Inrush current (Max. running current)
A
5(22)
5(15)
5(19)
5(19)
5(22)
5(19)
Hi:42
Hi:40
Hi:33
Hi:35
Hi:33
Hi:33
Indoor*2
Sound Ievel*1
Me:40 Lo:37
Me:37 Lo:35
Me:31 Lo:30
Me:33 Lo:31
dB(A)
Me:31 Lo:30
Me:31 Lo:30
51
57
57
Cooling:57 Heating:58
Outdoor
57
Cooling:57 Heating:58
Hi:27
Hi:21
Hi:18
Hi:30
Hi:18
Indoor*2
Me:24 Lo:20
Me:19 Lo:17
Air flow
CMM
Me:16 Lo:14
Me:27 Lo:23
Me:16 Lo:14
Cooling:150 Heating:145
Cooling:75 Heating:73 Cooling:150 Heating:145
Cooling:150 Heating:145
Outdoor
Exterior dimensions Height x Width x Depth mm Unit:298x840x840 Panel:35x950x950
Unit:246x840x840 Panel:35x950x950
27.5(Unit:22 Panel:5.5) 29.5(Unit:24 Panel:5.5) 27.5(Unit:22 Panel:5.5) 29.5(Unit:24 Panel:5.5)
kg
Unit+Panel
Net weight
32.5(Unit:27 Panel:5.5)
Panel
T-PSA-3AW-E
Air filter, Q'ty
Pocket Plastic net x1 (Washable)
Remote control(option)
Wired:RC-E4, RCH-E3 Wireless:RCN-T-36W-E
1,505x970x370
1,300x970x370
1,505x970x370
Exterior dimensions Height x Width x Depth mm
1,300x970x370
845x970x370
kg
140
122
140
Net weight
122
83
kg(m)
7.2(30)
5.4(30)
7.2(30)
Ref.amount precharged
5.4(30)
3.8(30)
ø
12.7/22.22
9.52/22.22
12.7/22.22
Ref.piping size Liquid/Gas
9.52/22.22
9.52/15.88
Ref.piping length
m
70
70
50
Vertical height O/U is higher
m
30
O/U is lower
difference
m
15
O/U
Cooling
Operating
-15~43*3
O/U
temperature range Heating
-15~20
-20~20
-15~20
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*21 :: The
values are for one indoor unit operation.
*3 : If a cooling
operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
*
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
FDT250VSPVD
FDT200VSPVD
Twin
FDT125VD
FDT100VD
FDC250VS
FDC200VS
Range of Outdoor unit
usage
Indoor unit
Set model name
Powerful-Hi can be selected. Sound level: 200/250VSPVD 51dB, 140VSTVD 39dB, 200VSTVD 46dB, 200VSDVD 39dB, 250VSDVD 46dB
Air flow: 200/250VSPVD 37CMM, 140VSTVD 20CMM, 200VSTVD 28CMM, 200VSDVD 20CMM, 250VSDVD 28CMM
27
MULTI [ INDOOR UNIT ]
A
CEILING CASSETTE -4way Compact (600 X 600mm)-
FDTC
CLASS
FDTC 40/50/60VD
Wired remote control
SPECIFICATIONS
*1
Sound Ievel
Indoor*2
kW
kW
kW
A
dB(A)
Outdoor
Air flow
Indoor*2
Indoor unit
CMM
Outdoor
Exterior dimensions Height x Width x Depth mm
kg
Net weight
Unit+Panel
Panel
Air filter, Q'ty
Remote control(option)
Exterior dimensions Height x Width x Depth mm
Net weight
kg
kg(m)
Ref.amount precharged
ø
Ref.piping size Liquid/Gas
m
Ref.piping length
m
Vertical height O/U is higher
m
O/U is lower
difference
Operating
O/U
Cooling
temperature range Heating
O/U
Range of Outdoor unit
usage
RC-E4
RCH-E3
RCN-TC-24W-ER
(Option)
(Option)
(Option)
The values are for simultaneous Multi operation.
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
ISO-T1(JIS)
(Min~Max)
Nominal heating capacity
ISO-T1(JIS)
(Min~Max)
Power Consumption Cooling/Heating
COP
Cooling/Heating
Energy label
Cooling/Heating
Inrush current (Max. running current)
Wireless remote control
FDTC71VNXPVD FDTC100VNXPVD FDTC125VNXPVD FDTC140VNXTVD FDTC100VSXPVD FDTC125VSXPVD FDTC140VSXTVD
Twin
Triple
Twin
Triple
FDTC60VD
FDTC50VD
FDTC50VD
FDTC40VD
FDTC50VD
FDTC60VD
FDTC50VD
FDC125VSX
FDC140VSX
FDC100VSX
FDC71VNX
FDC100VNX
FDC125VNX
FDC140VNX
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
14.0
12.5
7.1
10.0
14.0
10.0
12.5
(5.0~14.0)
(5.0~16.0)
(3.2~8.0)
(4.0~11.2)
(5.0~16.0)
(4.0~11.2)
(5.0~14.0)
14.0
16.0
8.0
11.2
16.0
11.2
14.0
(4.0~18.0)
(4.0~17.0)
(3.6~9.0)
(4.0~12.5)
(4.0~20.0)
(4.0~16.0)
(4.0~18.0)
4.10/4.10
4.34/4.34
1.99/2.18
2.78/3.02
4.34/4.34
2.78/3.02
4.10/4.10
3.05/3.41
3.23/3.69
3.57/3.67
3.60/3.71
3.23/3.69
3.60/3.71
3.05/3.41
A/A
B/B
A/A
A/A
A/A
A/A
B/B
5(17)
5(24)
5(15)
5(26)
Cooling : Hi:42 Me:36 Lo:30
Cooling : Hi:46 Me:39 Lo:30
Cooling : Hi:42 Me:36 Lo:30
Cooling : Hi:46 Me:39 Lo:30 Cooling : Hi:42 Me:36 Lo:30
Heating : Hi:42 Me:36 Lo:32
Heating : Hi:46 Me:39 Lo:32
Heating : Hi:42 Me:36 Lo:32
Heating : Hi:46 Me:39 Lo:32 Heating : Hi:42 Me:36 Lo:32
Cooling:51 Heating:48
Cooling:48 Heating:50
Cooling:49 Heating:52
Cooling:48 Heating:50
Cooling:49 Heating:52
Cooling : Hi:13.5 Me:10 Lo:7
Cooling : Hi:11.5 Me:9 Lo:7
Cooling : Hi:13.5 Me:10 Lo:7 Cooling : Hi:11.5 Me:9 Lo:7
Cooling : Hi:11.5 Me:9 Lo:7
Heating : Hi:13.5 Me:10 Lo:8
Heating : Hi:11.5 Me:9 Lo:8
Heating : Hi:13.5 Me:10 Lo:8 Heating : Hi:11.5 Me:9 Lo:8
Heating : Hi:11.5 Me:9 Lo:8
100
Cooling:60 Heating:50
Unit:248x570x570 Panel:35x700x700
18.5(Unit:15 Panel:3.5)
TC-PSA-25W-E
Pocket Plastic net x1 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-TC-24W-ER
1,300x970x370
750x880(+88)x340
105
60
4.5(30)
2.95(30)
9.52/15.88
100
50
30
15
-15~43*3
-20~20
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*21 :: The
values are for one indoor unit operation.
*3 : If a cooling
operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
*
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
28
Powerful-Hi can be selected. Sound level: 71/100/125VNXPVD 47dB, 100/125VSXPVD 47dB, 140VNXTVD 47dB, 140VSXTVD 47dB
Air flow: 71/100/125VNXPVD 13.5CMM, 100/125VSXPVD 13.5CMM, 140VNXTVD 13.5CMM, 140VSXTVD 13.5CMM
SPECIFICATIONS
The values are for simultaneous Multi operation.
Micro Inverter
Twin
Indoor name
Outdoor name
Power source
Nominal cooling capacity
ISO-T1(JIS)
(Min~Max)
Nominal heating capacity
ISO-T1(JIS)
(Min~Max)
Power Consumption Cooling/Heating
COP
Cooling/Heating
Energy label
Cooling/Heating
Inrush current (Max. running current)
Sound Ievel
*1
Indoor*2
FDTC50VD
FDC100VN
kW
kW
kW
A
dB(A)
Outdoor
Air flow
FDTC125VNPVD
FDTC100VNPVD
Set model name
Indoor*2
Range of Outdoor unit
usage
Indoor unit
CMM
Outdoor
Exterior dimensions Height x Width x Depth mm
kg
Net weight
Unit+Panel
Panel
Air filter, Q'ty
Remote control(option)
Exterior dimensions Height x Width x Depth mm
kg
Net weight
kg(m)
Ref.amount precharged
ø
Ref.piping size Liquid/Gas
m
Ref.piping length
m
Vertical height O/U is higher
O/U is lower
m
difference
O/U
Cooling
Operating
temperature range Heating
O/U
10.0
(4.0~11.2)
11.2
(4.0~12.5)
2.84/3.08
3.52/3.64
A/A
5(24)
Cooling : Hi:42 Me:36 Lo:30
Heating : Hi:42 Me:36 Lo:32
49
Cooling : Hi:11.5 Me:9 Lo:7
Heating : Hi:11.5 Me:9 Lo:8
FDTC60VD
FDC125VN
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
12.5
(5.0~14.0)
14.0
(4.0~16.0)
5.35/4.62
2.34/3.03
F/D
5(27)
Cooling : Hi:46 Me:39 Lo:30
Heating : Hi:46 Me:39 Lo:32
Cooling:50 Heating:51
Cooling : Hi:13.5 Me:10 Lo:7
Heating : Hi:13.5 Me:10 Lo:8
Cooling:75 Heating:73
Unit:248x570x570 Panel:35x700x700
18.5(Unit:15 Panel:3.5)
TC-PSA-25W-E
Pocket Plastic net x1 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-TC-24W-ER
845x970x370
81
3.8(30)
9.52/15.88
50
30
15
-15~43*3
-20~20
FDTC140VNTVD
Triple
FDTC50VD
FDC140VN
14.0
(5.0~14.5)
16.0
(4.0~16.5)
4.64/4.52
3.02/3.54
B/B
5(24)
Cooling : Hi:42 Me:36 Lo:30
Heating : Hi:42 Me:36 Lo:32
51
Cooling : Hi:11.5 Me:9 Lo:7
Heating : Hi:11.5 Me:9 Lo:8
Powerful-Hi can be selected. Sound level: 100/125VNPVD 47dB, 140VNTVD 47dB
Air flow: 100/125VNPVD 13.5CMM, 140VNTVD 13.5CMM
SPECIFICATIONS
The values are for simultaneous Multi operation.
Micro Inverter
FDTC140VSTVD
FDTC200VSDVD
FDTC250VSDVD
Twin
Triple
Double Twin
Indoor name
FDTC60VD
FDTC50VD
FDTC50VD
FDTC60VD
FDTC50VD
Outdoor name
FDC125VS
FDC140VS
FDC200VS
FDC250VS
FDC100VS
Power source
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
20.0
25.0
14.0
Nominal cooling capacity
12.5
10.0
kW
ISO-T1(JIS)
(7.0~22.4)
(10.0~28.0)
(5.0~14.5)
(5.0~14.0)
(4.0~11.2)
(Min~Max)
22.4
28.0
16.0
Nominal heating capacity
14.0
11.2
kW
ISO-T1(JIS)
(7.6~25.0)
(9.5~31.5)
(4.0~16.5)
(4.0~16.0)
(4.0~12.5)
(Min~Max)
7.33/6.98
11.28/10.19
4.64/4.52
Power Consumption Cooling/Heating
kW
5.35/4.62
2.84/3.08
2.73/3.21
2.22/2.75
3.02/3.54
COP
Cooling/Heating
2.34/3.03
3.52/3.64
D/C
F/E
B/B
Energy label
Cooling/Heating
F/D
A/A
5(19)
5(22)
5(15)
Inrush current (Max. running current)
A
5(15)
5(15)
Cooling : Hi:42 Me:36 Lo:30 Cooling : Hi:46 Me:39 Lo:30
Cooling : Hi:42 Me:36 Lo:30
Cooling : Hi:46 Me:39 Lo:30
*1
Indoor*2
Sound Ievel
Heating : Hi:42 Me:36 Lo:32
Heating : Hi:46 Me:39 Lo:32
dB(A) Heating : Hi:42 Me:36 Lo:32 Heating : Hi:46 Me:39 Lo:32
Cooling:57 Heating:58
Cooling:50 Heating:51
Outdoor
51
57
49
Cooling : Hi:11.5 Me:9 Lo:7 Cooling : Hi:13.5 Me:10 Lo:7
Cooling : Hi:13.5 Me:10 Lo:7
Cooling : PHi:11.5 Me:9 Lo:7
Indoor*2
Air flow
Heating : Hi:13.5 Me:10 Lo:8
Heating : Hi:11.5 Me:9 Lo:8
CMM Heating : Hi:11.5 Me:9 Lo:8 Heating : Hi:13.5 Me:10 Lo:8
Cooling:150 Heating:145
Cooling:75 Heating:73
Outdoor
Unit:248x570x570 Panel:35x700x700
Exterior dimensions Height x Width x Depth mm
18.5(Unit:15 Panel:3.5)
Unit+Panel
kg
Net weight
TC-PSA-25W-E
Panel
Pocket Plastic net x1 (Washable)
Air filter, Q'ty
Wired:RC-E4, RCH-E3 Wireless:RCN-TC-24W-ER
Remote control(option)
1,505x970x370
1,300x970x370
845x970x370
Exterior dimensions Height x Width x Depth mm
140
122
83
kg
Net weight
7.2(30)
5.4(30)
3.8(30)
kg(m)
Ref.amount precharged
9.52/22.22
12.7/22.22
9.52/15.88
ø
Ref.piping size Liquid/Gas
50
Ref.piping length
m
70
Vertical height O/U is higher
30
m
15
difference
m
O/U is lower
Operating
-15~43*3
O/U
Cooling
temperature range Heating
-20~20
-15~20
O/U
FDTC100VSPVD
FDTC125VSPVD
Range of Outdoor unit
usage
Indoor unit
Set model name
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*21 :: The
values are for one indoor unit operation.
*3 : If a cooling
operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
*
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 100/125VSPVD 47dB, 140VSTVD 47dB, 200/250VSDVD 47dB
Air flow: 100/125VSPVD 13.5CMM, 140VSTVD 13.5CMM, 200/250VSDVD 13.5CMM
29
MULTI [ INDOOR UNIT ]
A
DUCT CONNECTED -Low/Middle Static pressure-
FDUM
CLASS
SPECIFICATIONS
The values are for simultaneous Multi operation.
Set model name
Filter kit
UM-FL1E : for 50
UM-FL2E : for 60, 71
UM-FL3E : for 100, 125
external static pressure loss:5pa
(option)
Wireless remote control
Wired remote control
RC-E4
(Option)
RCH-E3
RCN-KIT3-E
(Option)
SPECIFICATIONS
(Option)
The values are for simultaneous Multi operation.
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
ISO-T1(JIS)
(Min~Max)
Nominal heating capacity
ISO-T1(JIS)
(Min~Max)
Power Consumption Cooling/Heating
COP
Cooling/Heating
Range of Outdoor unit Indoor unit
usage
FDUM 50/60/71/
100/125VD
Indoor name
Outdoor name
Power source
Nominal cooling capacity
kW
ISO-T1(JIS)
(Min~Max)
Nominal heating capacity
kW
ISO-T1(JIS)
(Min~Max)
Power Consumption Cooling/Heating
kW
COP
Cooling/Heating
Energy label
Cooling/Heating
Inrush current (Max. running current)
A
Indoor*2
Sound Ievel*1
dB(A)
Outdoor
Indoor*2
Air flow
CMM
Outdoor
Exterior dimensions Height x Width x Depth mm
kg
Net weight
Air filter, Q'ty
Remote control(option)
Exterior dimensions Height x Width x Depth mm
Net weight
kg
Ref.amount precharged
kg(m)
ø
Ref.piping size Liquid/Gas
m
Ref.piping length
m
Vertical height O/U is higher
m
O/U is lower
difference
Operating
O/U
Cooling
temperature range Heating
O/U
FDUM100VNXPVD FDUM125VNXPVD
Twin
FDUM50VD
FDUM60VD
FDC100VNX
FDC125VNX
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
10.0
12.5
(4.0~11.2)
(5.0~14.0)
11.2
14.0
(4.0~12.5)
(4.0~17.0)
2.94/2.94
3.86/4.10
3.40/3.81
3.24/3.41
A/A
A/B
5(24)
5(26)
Hi:34 Me:31 Lo:28
Cooling:48 Heating:50
Hi:13 Me:12 Lo:11 Hi:16 Me:15 Lo:14
100
299x750x635
299x950x635
34
40
Procure locally
Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E
1,300x970x370
105
4.5(30)
9.52/15.88
100
30
15
-15~43*3
-20~20
kW
kW
kW
FDUM140VNXPVD FDUM140VNXTVD FDUM100VSXPVD FDUM125VSXPVD FDUM140VSXPVD FDUM140VSXTVD
Twin
Triple
Twin
Triple
FDUM60VD
FDUM71VD
FDUM50VD
FDUM50VD
FDUM71VD
FDUM50VD
FDC125VSX
FDC140VSX
FDC140VSX
FDC140VNX
FDC140VNX
FDC100VSX
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
12.5
10.0
14.0
14.0
14.0
14.0
(5.0~14.0)
(4.0~11.2)
(5.0~16.0)
(5.0~16.0)
(5.0~16.0)
(5.0~16.0)
14.0
11.2
16.0
16.0
16.0
16.0
(4.0~18.0)
(4.0~16.0)
(4.0~20.0)
(4.0~18.0)
(4.0~18.0)
(4.0~20.0)
4.60/4.69
4.60/4.69
2.94/2.94
3.86/4.10
4.60/4.69
4.60/4.69
3.04/3.41
3.04/3.41
3.40/3.81
3.24/3.41
3.04/3.41
3.04/3.41
Range of Outdoor unit Indoor unit
usage
Energy label
Cooling/Heating
B/B
B/B
B/B
A/A
A/B
B/B
Inrush current (Max. running current)
A
5(15)
5(26)
Indoor*2
Hi:35 Me:32 Lo:29
Hi:34 Me:31 Lo:28
Hi:35 Me:32 Lo:29 Hi:34 Me:31 Lo:28
Sound Ievel*1
dB(A)
Cooling:49 Heating:52 Cooling:49 Heating:52
Cooling:48 Heating:50
Cooling:49 Heating:52 Cooling:49 Heating:52
Outdoor
Indoor*2
Hi:20 Me:18 Lo:15 Hi:13 Me:12 Lo:11 Hi:13 Me:12 Lo:11 Hi:16 Me:15 Lo:14 Hi:20 Me:18 Lo:15 Hi:13 Me:12 Lo:11
Air flow
CMM
Outdoor
100
Exterior dimensions Height x Width x Depth mm
299x750x635
299x950x635
299x950x635
299x750x635
kg
Net weight
34
40
40
34
Air filter, Q'ty
Procure locally
Remote control(option)
Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E
Exterior dimensions Height x Width x Depth mm
1,300x970x370
kg
Net weight
105
kg(m)
Ref.amount precharged
4.5(30)
ø
Ref.piping size Liquid/Gas
9.52/15.88
m
100
Ref.piping length
m
30
Vertical height O/U is higher
m
O/U is lower
15
difference
Operating
O/U
Cooling
-15~43*3
temperature range Heating
O/U
-20~20
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*21 :: The
values are for one indoor unit operation.
*3 : If a cooling
operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
*
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 100VNXPVD 35dB, 100VSXPVD 35dB, 125/140VNXPVD 38dB, 125/140VSXPVD 38dB, 140VNXTVD 35dB, 140VSXTVD 35dB
Air flow: 100VNXPVD 14CMM, 100VSXPVD 14CMM, 125/140VNXPVD 18CMM, 125/140VSXPVD 18CMM, 140VNXTVD 14CMM, 140VSXTVD 14CMM
30
SPECIFICATIONS
The values are for simultaneous Multi operation.
Micro Inverter
FDUM100VNPVD
Set model name
Indoor name
Outdoor name
FDUM50VD
FDC100VN
Power source
FDUM140VNPVD
FDUM140VNTVD
Triple
FDUM50VD
FDC140VN
FDUM71VD
FDC140VN
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
Nominal cooling capacity
ISO-T1(JIS)
(Min~Max)
Nominal heating capacity
ISO-T1(JIS)
(Min~Max)
Power Consumption Cooling/Heating
COP
FDUM125VNPVD
Twin
FDUM60VD
FDC125VN
kW
10.0
(4.0~11.2)
11.2
(4.0~12.5)
12.5
(5.0~14.0)
14.0
(4.0~16.0)
kW
3.12/3.27
4.47/4.51
3.21/3.43
2.80/3.10
A/B
C/D
kW
Cooling/Heating
Range of Outdoor unit Indoor unit
usage
Energy label
Cooling/Heating
Inrush current (Max. running current)
A
Indoor*2
Sound Ievel*1
dB(A)
Outdoor
Indoor*2
Air flow
CMM
Outdoor
Exterior dimensions Height x Width x Depth mm
kg
Net weight
Air filter, Q'ty
Remote control(option)
Exterior dimensions Height x Width x Depth mm
kg
Net weight
kg(m)
Ref.amount precharged
ø
Ref.piping size Liquid/Gas
Ref.piping length
m
Vertical height O/U is higher
m
difference
m
O/U is lower
Operating
O/U
Cooling
temperature range Heating
O/U
14.0
(5.0~14.5)
16.0
(4.0~16.5)
50Hz:5.00/4.94
60Hz:5.00/4.80
50Hz:2.80/3.24
60Hz:2.80/3.33
C/C
14.0
(5.0~14.5)
16.0
(4.0~16.5)
50Hz:5.09/5.03
60Hz:5.09/4.89
50Hz:2.75/3.18
60Hz:2.75/3.27
50Hz:D/D 60Hz:D/C
FDUM100VSPVD
Twin
FDUM50VD
FDC100VS
3Phase 380-415V 50Hz,
3Phase 380V 60Hz
10.0
(4.0~11.2)
11.2
(4.0~12.5)
3.12/3.27
3.21/3.43
A/B
5(15)
5(24)
Hi:34 Me:31 Lo:28
49
Hi:13 Me:12 Lo:11
299x750x635
34
Hi:34 Me:31 Lo:28
Cooling:50 Heating:51
Hi:16 Me:15 Lo:14
Hi:34 Me:31 Lo:28
Hi:35 Me:32 Lo:29
51
Hi:20 Me:18 Lo:15
Cooling:75 Heating:73
299x950x635
40
Procure locally
Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E
845x970x370
81
3.8(30)
9.52/15.88
50
30
15
-15~43*3
-20~20
Hi:13 Me:12 Lo:11
34
49
299x750x635
83
Powerful-Hi can be selected. Sound level: 100VNPVD 35dB, 125VNPVD 38dB, 140VNPVD 38dB, 140VNTVD 35dB, 100VSPVD 35dB
Air flow: 100VNPVD 14CMM, 125VNPVD 18CMM, 140VNPVD 23CMM, 140VNTVD 14CMM, 100VSPVD 14CMM
SPECIFICATIONS
The values are for simultaneous Multi operation.
Micro Inverter
FDUM140VSPVD FDUM200VSPVD FDUM250VSPVD FDUM140VSTVD FDUM200VSTVD
Triple
Twin
Indoor name
FDUM125VD
FDUM50VD
FDUM71VD
FDUM60VD
FDUM71VD
FDUM100VD
Outdoor name
FDC250VS
FDC140VS
FDC200VS
FDC125VS
FDC140VS
FDC200VS
Power source
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
Nominal cooling capacity
14.0
25.0
20.0
14.0
20.0
12.5
ISO-T1(JIS)
kW
(5.0~14.5)
(10.0~28.0)
(7.0~22.4)
(5.0~14.5)
(7.0~22.4)
(5.0~14.0)
(Min~Max)
Nominal heating capacity
16.0
28.0
22.4
16.0
22.4
14.0
ISO-T1(JIS)
kW
(4.0~16.5)
(9.5~31.5)
(7.6~25.0)
(4.0~16.5)
(7.6~25.0)
(4.0~16.0)
(Min~Max)
50Hz:5.09/5.03
50Hz:5.00/4.94
Power Consumption Cooling/Heating
kW
6.86/6.72
9.31/8.35
6.88/6.74
4.47/4.51
60Hz:5.09/4.89
60Hz:5.00/4.80
50Hz:2.75/3.18
50Hz:2.80/3.24
COP
Cooling/Heating
2.92/3.33
2.69/3.35
2.91/3.32
2.80/3.10
60Hz:2.75/3.27
60Hz:2.80/3.33
Energy label
Cooling/Heating
C/C
D/C
C/C
50Hz:D/D 60Hz:D/C
C/C
C/D
Inrush current (Max. running current)
5(15)
A
5(22)
5(19)
5(19)
5(15)
Indoor*2
Hi:34 Me:31 Lo:28 Hi:35 Me:32 Lo:29 Hi:37 Me:35 Lo:32 Hi:38 Me:36 Lo:33 Hi:34 Me:31 Lo:28 Hi:35 Me:32 Lo:29
Sound Ievel*1
dB(A)
Cooling:50 Heating:51
Outdoor
57
57
51
Cooling:57 Heating:58
51
Indoor*2
Hi:16 Me:15 Lo:14 Hi:20 Me:18 Lo:15
Hi:13 Me:12 Lo:11 Hi:20 Me:18 Lo:15
Hi:28 Me:25 Lo:22
Air flow
CMM
Cooling:75 Heating:73 Cooling:150 Heating:145
Cooling:150 Heating:145
Cooling:75 Heating:73
Outdoor
350x1,370x635
299x950x635
Exterior dimensions Height x Width x Depth mm
299x750x635
1,300x970x370
59
40
kg
Net weight
34
122
Air filter, Q'ty
Procure locally
Remote control(option)
Wired:RC-E4, RCH-E3 Wireless:RCN-KIT3-E
Exterior dimensions Height x Width x Depth mm
1,505x970x370
1,300x970x370
1,300x970x370
845x970x370
845x970x370
kg
Net weight
140
122
122
83
83
kg(m)
Ref.amount precharged
7.2(30)
5.4(30)
5.4(30)
3.8(30)
3.8(30)
ø
Ref.piping size Liquid/Gas
12.7/22.22
9.52/22.22
9.52/22.22
9.52/15.88
9.52/15.88
m
70
70
50
Ref.piping length
50
m
Vertical height O/U is higher
30
m
O/U is lower
difference
15
Operating
O/U
Cooling
-15~43*3
temperature range Heating
-20~20
-20~20
-15~20
-15~20
O/U
FDUM125VSPVD
Range of Outdoor unit Indoor unit
usage
Set model name
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB. External static pressure
of indoor units is 60Pa.
Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*21 :: The
values are for one indoor unit operation.
*3 : If a cooling
operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
*
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 125/140VSPVD 38dB, 200/250VSPVD 41dB, 140VSTVD 35dB, 200VSTVD 38dB
Air flow: 125VSPVD 18CMM, 140VSPVD 23CMM, 200/250VSPVD 34CMM, 140VSTVD 14CMM, 200VSTVD 23CMM
31
MULTI [ INDOOR UNIT ]
A
CEILING SUSPENDED
FDEN
CLASS
SPECIFICATIONS
The values are for simultaneous Multi operation.
Set model name
Wired remote control
Wireless remote control
RC-E4
RCH-E3
RCN-E1R
(Option)
(Option)
(Option)
SPECIFICATIONS
Range of Outdoor unit Indoor unit
usage
FDEN 40/50/60/71/100/125VD
Indoor name
Outdoor name
Power source
Nominal cooling capacity
ISO-T1(JIS)
kW
(Min~Max)
Nominal heating capacity
ISO-T1(JIS)
kW
(Min~Max)
Power Consumption Cooling/Heating
kW
COP
Cooling/Heating
Energy label
Cooling/Heating
Inrush current (Max. running current)
A
Indoor*2
Sound Ievel*1
dB(A)
Outdoor
Indoor*2
Air flow
CMM
Outdoor
Exterior dimensions Height x Width x Depth mm
kg
Net weight
Air filter, Q'ty
Remote control(option)
Exterior dimensions Height x Width x Depth mm
kg
Net weight
kg(m)
Ref.amount precharged
ø
Ref.piping size Liquid/Gas
m
Ref.piping length
m
Vertical height O/U is higher
m
difference
O/U is lower
Operating
O/U
Cooling
temperature range Heating
O/U
FDEN71VNXPVD FDEN100VNXPVD
Twin
FDEN40VD
FDEN50VD
FDC71VNX
FDC100VNX
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
7.1
10.0
(3.2~8.0)
(4.0~11.2)
8.0
11.2
(3.6~9.0)
(4.0~12.5)
1.98/2.40
3.02/3.18
3.59/3.33
3.31/3.52
A/C
A/B
5(24)
5(17)
Hi:39 Me:38 Lo:37
Cooling:51 Heating:48 Cooling:48 Heating:50
Hi:11 Me:9 Lo:7
Cooling:60 Heating:50
100
210x1,070x690
28
Pocket Plastic net x2 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-E1R
750X880(+88)X340 1,300x970x370
105
60
4.5(30)
2.95(30)
9.52/15.88
50
100
30
15
-15~43*3
-20~20
The values are for simultaneous Multi operation.
FDEN125VNXPVD FDEN140VNXPVD FDEN140VNXTVD FDEN100VSXPVD FDEN125VSXPVD FDEN140VSXPVD FDEN140VSXTVD
Twin
Triple
Twin
Triple
Indoor name
FDEN71VD
FDEN50VD
FDEN50VD
FDEN60VD
FDEN71VD
FDEN50VD
FDEN60VD
Outdoor name
FDC140VNX
FDC140VNX
FDC100VSX
FDC125VSX
FDC140VSX
FDC140VSX
FDC125VNX
Power source
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
Nominal cooling capacity
12.5
14.0
14.0
10.0
12.5
14.0
14.0
ISO-T1(JIS)
kW
(5.0~14.0)
(5.0~16.0)
(5.0~16.0)
(4.0~11.2)
(5.0~14.0)
(5.0~16.0)
(5.0~16.0)
(Min~Max)
Nominal heating capacity
14.0
16.0
16.0
11.2
14.0
16.0
16.0
ISO-T1(JIS)
kW
(4.0~17.0)
(4.0~18.0)
(4.0~18.0)
(4.0~16.0)
(4.0~18.0)
(4.0~20.0)
(4.0~20.0)
(Min~Max)
Power Consumption Cooling/Heating
kW
3.86/3.70
4.78/4.43
4.72/4.38
3.02/3.18
3.86/3.70
4.78/4.43
4.72/4.38
COP
Cooling/Heating
3.24/3.78
2.93/3.61
2.97/3.65
3.31/3.52
3.24/3.78
2.93/3.61
2.97/3.65
Energy label
Cooling/Heating
A/A
C/A
C/A
A/B
A/A
C/A
C/A
Inrush current (Max. running current)
5(26)
A
5(15)
2
Indoor*
Hi:39 Me:38 Lo:37
Hi:39 Me:38 Lo:37
Hi:41 Me:39 Lo:38
Hi:41 Me:39 Lo:38
Sound Ievel*1
dB(A)
Cooling:48 Heating:50 Cooling:49 Heating:52 Cooling:49 Heating:52
Cooling:48 Heating:50 Cooling:49 Heating:52 Cooling:49 Heating:52
49
Outdoor
Indoor*2
Hi:18 Me:14 Lo:12
Hi:11 Me:9 Lo:7
Hi:18 Me:14 Lo:12
Hi:11 Me:9 Lo:7
Air flow
CMM
100
Outdoor
Exterior dimensions Height x Width x Depth mm
210x1,070x690
210x1,070x690
210x1,320x690
210x1,320x690
kg
Net weight
28
28
37
37
Pocket Plastic net x2 (Washable)
Air filter, Q'ty
Wired:RC-E4, RCH-E3 Wireless:RCN-E1R
Remote control(option)
1,300x970x370
Exterior dimensions Height x Width x Depth mm
105
kg
Net weight
4.5(30)
kg(m)
Ref.amount precharged
9.52/15.88
ø
Ref.piping size Liquid/Gas
100
m
Ref.piping length
30
m
Vertical height O/U is higher
15
m
difference
O/U is lower
Operating
-15~43*3
O/U
Cooling
temperature range Heating
-20~20
O/U
Range of Outdoor unit Indoor unit
usage
Set model name
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*21 :: The
values are for one indoor unit operation.
*3 : If a cooling
operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
*
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 71/100VNXPVD 46dB, 100VSXPVD 46dB, 125/140VNXPVD 50dB, 125/140VSXPVD 50dB, 140VNXTVD 46dB, 140VSXTVD 46dB
Air flow: 71/100VNXPVD 13CMM, 100VSXPVD 13CMM, 125/140VNXPVD 22CMM, 125/140VSXPVD 22CMM, 140VNXTVD 13CMM, 140VSXTVD 13CMM
32
SPECIFICATIONS
The values are for simultaneous Multi operation.
Micro Inverter
FDEN100VNPVD
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
ISO-T1(JIS)
(Min~Max)
Nominal heating capacity
ISO-T1(JIS)
(Min~Max)
Power Consumption Cooling/Heating
COP
Cooling/Heating
Energy label
Cooling/Heating
Inrush current (Max. running current)
*1
Sound Ievel
Air flow
Indoor*2
FDEN50VD
FDC100VN
kW
kW
kW
10.0
(4.0~11.2)
11.2
(4.0~12.5)
3.12/3.28
3.21/3.41
A/B
A
dB(A)
Hi:39 Me:38 Lo:37
Outdoor
49
Indoor*2
Hi:11 Me:9 Lo:7
Range of Outdoor unit Indoor unit
usage
CMM
Outdoor
Exterior dimensions Height x Width x Depth mm
kg
Net weight
Air filter, Q'ty
Remote control(option)
Exterior dimensions Height x Width x Depth mm
kg
Net weight
kg(m)
Ref.amount precharged
ø
Ref.piping size Liquid/Gas
m
Ref.piping length
m
Vertical height O/U is higher
O/U is lower
m
difference
Cooling
O/U
Operating
temperature range Heating
O/U
FDEN140VNTVD
FDEN125VNPVD
FDEN140VNPVD
Twin
Triple
FDEN50VD
FDEN71VD
FDEN60VD
FDC140VN
FDC140VN
FDC125VN
1Phase 220-240V 50Hz, 1Phase 220V 60Hz
14.0
12.5
14.0
(5.0~14.5)
(5.0~14.0)
(5.0~14.5)
16.0
14.0
16.0
(4.0~16.5)
(4.0~16.0)
(4.0~16.5)
4.88/4.58
4.23/3.83
4.87/4.59
2.87/3.49
2.96/3.66
2.87/3.49
C/B
C/A
C/B
5(24)
210x1,070x690
28
Hi:41 Me:39 Lo:38
Cooling:50 Heating:51
51
Hi:18 Me:14 Lo:12
FDEN100VSPVD
FDEN125VSPVD
Twin
FDEN50VD
FDEN60VD
FDC100VS
FDC125VS
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
10.0
12.5
(4.0~11.2)
(5.0~14.0)
11.2
14.0
(4.0~12.5)
(4.0~16.0)
3.12/3.28
4.23/3.83
3.21/3.41
2.96/3.66
A/B
C/A
5(15)
Hi:41
Hi:39 Me:38 Lo:37
Me:39 Lo:38
49
Cooling:50 Heating:51
Hi:18
Hi:11 Me:9 Lo:7
Me:14 Lo:12
Cooling:75 Heating:73
210x1,070x690
210x1,320x690
28
37
Pocket Plastic net x2 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-E1R
845x970x370
81
3.8(30)
9.52/15.88
50
30
15
-15~43*3
-20~20
210x1,320x690
37
83
Powerful-Hi can be selected. Sound level: 100VNPVD 46dB, 125/140VNPVD 50dB, 140VNTVD 46dB, 100VSPVD 46dB, 125VSPVD 50dB
Air flow: 100VNPVD 13CMM, 125/140VNPVD 22CMM, 140VNTVD 13CMM, 100VSPVD 13CMM, 125VSPVD 22CMM
SPECIFICATIONS
The values are for simultaneous Multi operation.
Micro Inverter
Set model name
Indoor name
Outdoor name
Power source
Nominal cooling capacity
ISO-T1(JIS)
(Min~Max)
Nominal heating capacity
ISO-T1(JIS)
(Min~Max)
Power Consumption Cooling/Heating
COP
Cooling/Heating
Energy label
Cooling/Heating
Inrush current (Max. running current)
*1
Sound Ievel
Indoor*2
kW
kW
kW
A
dB(A)
Outdoor
Air flow
Indoor*2
Range of Outdoor unit Indoor unit
usage
CMM
Outdoor
Exterior dimensions Height x Width x Depth mm
kg
Net weight
Air filter, Q'ty
Remote control(option)
Exterior dimensions Height x Width x Depth mm
kg
Net weight
kg(m)
Ref.amount precharged
ø
Ref.piping size Liquid/Gas
m
Ref.piping length
m
Vertical height O/U is higher
m
difference
O/U is lower
O/U
Cooling
Operating
O/U
temperature range Heating
FDEN140VSPVD FDEN200VSPVD FDEN250VSPVD FDEN140VSTVD FDEN200VSTVD FDEN200VSDVD FDEN250VSDVD
Triple
Twin
Double Twin
FDEN125VD
FDEN50VD
FDEN71VD
FDEN50VD
FDEN60VD
FDEN100VD
FDEN71VD
FDC250VS
FDC140VS
FDC200VS
FDC200VS
FDC250VS
FDC200VS
FDC140VS
3Phase 380-415V 50Hz, 3Phase 380V 60Hz
25.0
25.0
14.0
20.0
20.0
14.0
20.0
(10.0~28.0)
(10.0~28.0)
(5.0~14.5)
(7.0~22.4)
(7.0~22.4)
(5.0~14.5)
(7.0~22.4)
28.0
28.0
16.0
22.4
22.4
16.0
22.4
(9.5~31.5)
(9.5~31.5)
(7.6~25.0)
(4.0~16.5)
(7.6~25.0)
(4.0~16.5)
(7.6~25.0)
9.01/8.05
9.50/8.69
4.87/4.59
6.47/5.97
4.88/4.58
6.40/5.90
7.43/7.26
2.77/3.48
2.63/3.22
3.09/3.75
2.87/3.49
2.87/3.49
3.13/3.80
2.69/3.09
D/B
D/C
C/B
B/A
C/B
B/A
D/D
5(19)
5(22)
5(22)
5(15)
5(19)
5(15)
Hi:46
Hi:41
Hi:41
Hi:44
Hi:39
Hi:41
Hi:39
Me:44 Lo:43
Me:39 Lo:38
Me:39 Lo:38
Me:41 Lo:39
Me:38 Lo:37
Me:39 Lo:38
Me:38 Lo:37
57
51
57
51
Cooling:57 Heating:58
Cooling:57 Heating:58
Hi:18
Hi:26
Hi:11
Hi:29
Hi:18
Hi:18
Hi:11
Me:14 Lo:12
Me:23 Lo:21
Me:9 Lo:7
Me:26 Lo:23
Me:14 Lo:12
Me:14 Lo:12
Me:9 Lo:7
Cooling:75 Heating:73
Cooling:75 Heating:73
Cooling:150 Heating:145
Cooling:150 Heating:145
210x1,320x690
210x1,070x690 210x1,320x690 210x1,070x690 210x1,320x690
250x1,620x690
37
28
37
49
37
28
Pocket Plastic net x2 (Washable)
Wired:RC-E4, RCH-E3 Wireless:RCN-E1R
1,300x970x370
845x970x370 1,300x970x370 1,505x970x370 845x970x370
1,505x970x370
122
83
140
140
122
83
5.4(30)
3.8(30)
7.2(30)
7.2(30)
5.4(30)
3.8(30)
9.52/22.22
9.52/15.88
12.7/22.2
12.7/22.22
9.52/22.22
9.52/15.88
50
70
70
50
30
15
-15~43*3
-20~20
-15~20
-20~20
-15~20
The data are measured under the following conditions(ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB. Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*21 :: The
values are for one indoor unit operation.
*3 : If a cooling
operation is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
*
wind. If wind blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
Powerful-Hi can be selected. Sound level: 140VSPVD 50dB, 200VSPVD 46dB, 250VSPVD 50dB, 140VSTVD 46dB, 200VSTVD 50dB, 200VSDVD 46dB, 250VSDVD 50dB
Air flow: 140VSPVD 22CMM, 200VSPVD 28CMM, 250VSPVD 32CMM, 140VSTVD 13CMM, 200VSTVD 22CMM, 200VSDVD 13CMM, 250VSDVD 22CMM
33
MULTI [ INDOOR UNIT ]
WALL MOUNTED
A
SRK
CLASS
Only used with outdoor units of TWIN, TRIPLE, MULTI System.
SRK 50/60ZJX-S
Wired remote control
RC-E4
RCH-E3
(Option)
(Option)
1 Jet Air Scroll
Point
We used the same aerodynamic
analysis technology as used in
developing jet engines.
SC-BIKN-E
SC-BIKN-E
RC-E4
Fast
Slow
Colors in the figure show the air speed.
2 Long Reach Air Flow
Point
881.9
21
61.5
60
60
46.5
26
61.5
Powerful airflow is realized by Jet technology.
Good for large living rooms and shops.
Increase your comfort.
Outline drawing (Unit:mm)
46.5
CFD (computational fluid dynamics),
used in blade shape design of jet
engines, has been applied to the design
of air channels in air conditioners to
develop the ideal air channel system (air
circulation). The airflow of the jets
created in this system enable a large
volume of air to be blown with minimum
power consumption, yet the air flow is
uniform, quiet and reaches points a long
distance from the blower.
SRK50/60ZJX-S
(in cooling operation)
220
3
Terminal block
34
122.1
9
3.1
309
(right, left)61.5
890
Piping hole
right
SPECIFICATIONS
The values are for simultaneous Multi operation.
SRK100VNXPZJX
Set model name
Range of Outdoor unit Indoor unit
usage
Indoor name
Outdoor name
Power source
Nominal cooling capacity
ISO-T1(JIS)
kW
(Min~Max)
Nominal heating capacity
ISO-T1(JIS)
kW
(Min~Max)
kW
Power Consumption Cooling/Heating
Cooling/Heating
COP
Cooling/Heating
Energy label
A
Inrush current (Max. running current)
Cooling
Indoor*2
1
Heating dB(A)
Sound Ievel*
Outdoor
Cooling
Indoor*2
Heating CMM
Air flow
Outdoor
Exterior dimensions Height x Width x Depth mm
kg
Net weight
Air filter, Q'ty
Remote control(option)
Exterior dimensions Height x Width x Depth mm
kg
Net weight
kg(m)
Ref.amount precharged
ø
Ref.piping size Liquid/Gas
m
Ref.piping length
m
Vertical height O/U is higher
m
O/U is lower
difference
Cooling
O/U
Operating
temperature range Heating
O/U
SPECIFICATIONS
SRK125VNXPZJX
SRK140VNXTZJX
Twin
SRK100VSXPZJX
Triple
SRK125VSXPZJX
Twin
SRK140VSXTZJX
Triple
SRK60ZJX-S
SRK50ZJX-S
SRK50ZJX-S
SRK50ZJX-S
SRK60ZJX-S
SRK50ZJX-S
FDC125VNX
FDC100VSX
FDC100VNX
FDC140VNX
FDC125VSX
FDC140VSX
1Phase 220-240 50Hz, 1Phase 220V 60Hz
3Phase 380-415 50Hz, 3Phase 380V 60Hz
12.5
10.0
10.0
14.0
12.5
14.0
(5.0~14.0)
(4.0~11.2)
(4.0~11.2)
(5.0~16.0)
(5.0~14.0)
(5.0~16.0)
14.0
11.2
11.2
16.0
14.0
16.0
(4.0~17.0)
(4.0~16.0)
(4.0~12.5)
(4.0~18.0)
(4.0~18.0)
(4.0~20.0)
3.60/3.48
2.66/2.60
2.66/2.60
3.98/3.68
3.60/3.48
3.98/3.68
3.47/4.02
3.76/4.31
3.76/4.31
3.52/4.35
3.47/4.02
3.52/4.35
A/A
A/A
A/A
A/A
A/A
A/A
5 (24)
5 (15)
Hi:45 Me:38 Lo:26 Hi:47 Me:38 Lo:26 Hi:45 Me:38 Lo:26 Hi:45 Me:38 Lo:26 Hi:47 Me:38 Lo:26 Hi:45 Me:38 Lo:26
Hi:45 Me:38 Lo:32 Hi:45 Me:39 Lo:33 Hi:45 Me:38 Lo:32 Hi:45 Me:38 Lo:32 Hi:45 Me:39 Lo:33 Hi:45 Me:38 Lo:32
Cooling:48 Heating:50
Cooling:48 Heating:50
Cooling:49 Heating:52
Cooling:49 Heating:52
Hi:13.5 Me:11 Lo:8 Hi:14.5 Me:12.5 Lo:8.5 Hi:13.5 Me:11 Lo:8 Hi:13.5 Me:11 Lo:8 Hi:14.5 Me:12.5 Lo:8.5 Hi:13.5 Me:11 Lo:8
Hi:16.5 Me:14.5 Lo:10.5 Hi:17 Me:15 Lo:11 Hi:16.5 Me:14.5 Lo:10.5 Hi:16.5 Me:14.5 Lo:10.5 Hi:17 Me:15 Lo:11 Hi:16.5 Me:14.5 Lo:10.5
100
309x890x220
15
Polypropylene net x2 (Washable)
Wired:RC-E4, RCH-E3 & Interface kit:SC-BIKN-E
1,300x970x370
105
4.5(30)
9.52/15.88
100
30
15
-15~43*3
-20~20
The values are for simultaneous Multi operation.
Micro Inverter
Set model name
Range of Outdoor unit Indoor unit
usage
Indoor name
Outdoor name
Power source
Nominal cooling capacity
ISO-T1(JIS)
kW
(Min~Max)
Nominal heating capacity
ISO-T1(JIS)
kW
(Min~Max)
Cooling/Heating
kW
Power Consumption
Cooling/Heating
COP
Cooling/Heating
Energy label
A
Inrush current (Max. running current)
2 Cooling
*
Indoor
Heating dB(A)
Sound Ievel*1
Outdoor
Cooling
Indoor*2
Heating CMM
Air flow
Outdoor
Exterior dimensions Height x Width x Depth mm
kg
Net weight
Air filter, Q'ty
Remote control(option)
Exterior dimensions Height x Width x Depth mm
kg
Net weight
kg(m)
Ref.amount precharged
ø
Ref.piping size Liquid/Gas
Ref.piping length
m
Vertical height O/U is higher
m
difference
O/U is lower
m
Cooling
O/U
Operating
temperature range Heating
O/U
SRK100VNPZJX
SRK125VNPZJX
Twin
SRK140VNTZJX
Triple
SRK100VSPZJX
SRK125VSPZJX
Twin
SRK140VSTZJX
Triple
SRK50ZJX-S
SRK50ZJX-S
SRK60ZJX-S
SRK60ZJX-S
SRK50ZJX-S
SRK50ZJX-S
FDC100VS
FDC140VN
FDC125VN
FDC125VS
FDC140VS
FDC100VN
3Phase 380-415 50Hz, 3Phase 380V 60Hz
1Phase 220-240 50Hz, 1Phase 220V 60Hz
10.0
14.0
12.5
12.5
14.0
10.0
(4.0~11.2)
(5.0~14.5)
(5.0~14.0)
(5.0~14.0)
(5.0~14.5)
(4.0~11.2)
11.2
16.0
14.0
14.0
16.0
11.2
(4.0~12.5)
(4.0~16.5)
(4.0~16.0)
(4.0~16.0)
(4.0~16.5)
(4.0~12.5)
2.72/2.86
4.53/4.05
4.25/4.29
4.25/4.29
4.53/4.05
2.72/2.86
3.62/3.92
3.09/3.95
2.94/3.26
2.94/3.26
3.09/3.95
3.62/3.92
A/A
B/A
C/C
C/C
B/A
A/A
5 (24)
5 (15)
Hi:45 Me:38 Lo:26 Hi:47 Me:38 Lo:26 Hi:45 Me:38 Lo:26 Hi:45 Me:38 Lo:26 Hi:47 Me:38 Lo:26 Hi:45 Me:38 Lo:26
Hi:45 Me:38 Lo:32 Hi:45 Me:39 Lo:33 Hi:45 Me:38 Lo:32 Hi:45 Me:38 Lo:32 Hi:45 Me:39 Lo:33 Hi:45 Me:38 Lo:32
51
51
Cooling:50,Heating:51
Cooling:50,Heating:51
49
49
Hi:13.5 Me:11 Lo:8 Hi:14.5 Me:12.5 Lo:8.5 Hi:13.5 Me:11 Lo:8 Hi:13.5 Me:11 Lo:8 Hi:14.5 Me:12.5 Lo:8.5 Hi:13.5 Me:11 Lo:8
Hi:16.5 Me:14.5 Lo:10.5 Hi:17 Me:15 Lo:11 Hi:16.5 Me:14.5 Lo:10.5 Hi:16.5 Me:14.5 Lo:10.5 Hi:17 Me:15 Lo:11 Hi:16.5 Me:14.5 Lo:10.5
Cooling:75,Heating:73
309x890x220
15
Polypropylene net x2 (Washable)
Wired:RC-E4, RCH-E3 & Interface kit:SC-BIKN-E
845x970x370
81
83
3.8(30)
9.52/15.88
50
30
15
-15~43*3
-20~20
The data are measured under the following conditions (ISO-T1).
Cooling:Indoor temp. of 27˚CDB, 19˚CWB, and outdoor temp. of 35˚CDB.
Heating:Indoor temp. of 20˚CDB, and outdoor temp. of 7˚CDB, 6˚CWB.
Indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient conditions.
*21 :: The
values are for one indoor unit operation.
*3 : If a cooling
is conducted when the outdoor air temperature is –5˚C or lower, the outdoor unit should be installed at a place where it is not influenced by natural
* wind. If windoperation
blows, the low pressure will drop and compressor frequency will increase, this will cause the capacity to drop and may cause the unit to break down.
35
OUTDOOR UNIT (1.5-10.0HP)
NEW
FDC100VNX
FDC100VSX
(4.0HP)
FDC125VNX
FDC125VSX
(5.0HP)
SRC40ZIX-S
SRC50ZIX-S*
SRC60ZIX-S*
(1.5HP~2.5HP)
FDC140VNX
FDC140VSX
(6.0HP)
FDC71VNX
(3.0HP)
is common for both of outdoor units of
*SRC50/60ZIX-S
SRK50/60ZJX-S (Residential Air-conditioners) and 1.5,
2, 2.5HP of Inverter Packaged Air-Conditioners.
Common components make for easy inventory control
and the installation procedure will be the same.
Blue Fin (3~10HP)
Due to application of blue coated fins (KS101)
for the heat exchanger of new outdoor unit,
corrosion resistance has been improved
compared to current models.
Micro Inverter
Base heater kit (option)
FDC100VN FDC100VS
FDC125VN FDC125VS
FDC140VN FDC140VS
(4.0HP~6.0HP)
FDC200VS
(8.0HP)
This kit is recommended to be used in
an area where the lowest temperature
drops below 0˚C.
FDC250VS
(10.0HP)
CW-H-E
applied for
FDC100~250VN,VS
FDC100~140VNX,VSX
Installation workability
Enhanced installation workability thanks to the extended pipe length – longest level
in the industry and pre-charged refrigerant.
1 Piping length – 100m (Hyper Inverter 4~6HP)
Point
Refer to our Technical Manual in detail
Micro Inverter
Height difference
Height difference
(Outdoor higher than Indoor)
(Outdoor higher than Indoor)
Piping
length
Piping
length
Piping
length
Height
difference
1.5~2.5
30m
20m
3
50m
30m
30m
HP
4~6
100m
Piping
length
Height
difference
4~6
50m
30m
8.10
70m
30m
HP
2 Refrigerant precharged piping length extending to 30m
Point
Refrigerant precharged piping length extends up to 30m. (1.5~2.5HP:15m)
This eliminates the need to add refrigerant on site, which sets it free from trouble of excessive or insufficient charging of refrigerant, and allows
carrying out the installation smoothly.
36
Control Systems [Individual control]
Remote Control line up
indoor unit
wired
remote control
RC-E4
all models
RCH-E3
wireless
indoor unit
FDT
FDTC
FDUM, FDU
FDEN
remote control
RCN-T-36W-E
RCN-TC-24W-ER
RCN-KIT3-E
RCN-E1R
Wired remote control with weekly timer (option)
RC-E4
Run hour meters to facilitate maintenance checking
RC-E4 stores operation data when an anomaly occurs and indicates the error
on the LCD. It also displays cumulative operation hours of the air conditioner
and compressor since commissioning.
The RC-E4 controller
enables extensive access to
service and maintenance
technical data combined
with easy to use functions
and a clear LCD display.
Weekly timer function as standard
RC-E4 provides (as a standard feature) a weekly timer, which allows oneweek operation schedules to be registered. A user can specify up to four
times a day to start/stop the air conditioner. (Temperature setting is also
possible with the timer).
Timer operation
Room temperature controlled
by the remote control sensor
The temperature sensor is housed in the top
section of the remote control unit. This
arrangement has improved the sensitivity of the
remote control unit’s sensor, which permits more
finely controlled air conditioning.
Changeable set temperature ranges
RC-E4 allows the upper and lower limits of a set temperature range to be
specified separately.
By adjusting a set temperature range, you can ensure energy saving air
conditioning by avoiding excessive cooling or heating.
Changeable range
Upper limit
20~30°C(effective for heating operation)
Lower limit
18~26°C(effective for non-heating operation)
Simple remote control (option)
RCH-E3 (wired)
Considering specialized usage in hotel
rooms, control buttons are limited only to
minimum required functions such as ON/OFF,
mode, temperature setting and fan speed. It
is really simple and easy to use.
Up to 16 units
It can control up to 16 units individually, with pressing the AIR CON No. button.
AUTO restart
RCH-E3 is not applicable to the Individual flap control
system and the Flap control system.
When RCH-E3 is used, the fan has 3 speed settings (HiMe-Lo) only.
This function allows starting the air conditioner automatically when power
supply is restored after power failure or by turning on the power switch.
Wireless remote control (option)
Thermistor (option)
SC-THB-E3
For wireless control simply insert the infrared
receiver kit on a corner of the panel.
RCN-T-36W-E,
RCN-TC-24W-ER
RCN-KIT3-E
RCN-E1R
In case sensor in the indoor units or the remote
control sensor can not sense the room temperature
correctly, or individual remote control in each room is
not required but only censor is required (as when
center control system is in place), install SC-THB-E3
at proper place in the rooms.
When wireless remote control is used, the fan has 3 speed settings (Hi-Me-Lo) only.
37
Control System
SUPERLINK-
KX6 series
SC-SL1N-E
RAC series
(SRK/SRF-ZJX-S)
SC-BIKN-E
SC-ADNA-E
SC-SL2NA-E
SC-ADNA-E
SC-ADNA-E
Central Control
SC-SL1N-E
Start/stop control of up to 16 indoor units is
possible either individually or collectively. With
simple operations, you can effect centralized
control.
PC windows central control
SC-WGWNA-A/B
(SC-WGWNA-B is with electric power calculation function)
SC-SL2NA-E
SC-SL3N-AE/BE
Centralized control of up to 64 indoor units. It
can allow connection with a weekly timer
without using any interface.
BMS interface unit
SC-BGWN-A/B
(BACnet gateway)
(SC-WGWN-B is with electric power calculation function)
38
Easy operation realized with a large color LCD
and touch panel. Up to 128 indoor units can be
controlled, when three SUPERLINK-2 systems
are connected.
Up to 96 cells (some cells can have two or
more indoor units and total number of indoor
units can be up to 128 units) are controlled
from the Internet Explorer.
Up to 96 cells (some cells can have two or
more indoor units and total number of indoor
units can be up to 128 units) are controlled
centrally from a BMS.
Additional engineering service cost etc. is
required. Please consult your dealer when using
this central control.
Additional engineering service cost etc. is required.
In case of SC-BGWN-B, communication test by
qualified person regarding electric cost calculation
function is required before commissioning. Please
consult your dealer when using this gateway.
SC-LGWN-A
(LonWorks gateway)
Up to 96 indoor units (48 indoor unit x 2) are
linked as an open network! Centrally controlled
through LonWorks!
Additional engineering service cost etc. is
required. Please consult your dealer when using
this gateway.
SUPERLINK E BOARD (SC-ADNA-E)
This board is used when conducting control of the single package (wired remote control unit) 1-type series using a network
option (SC-SL1N-E, SC-SL2NA-E, etc).
(1) Functions
(a) Transmits the settings from the network option to the indoor units.
(b) Returns the priority indoor unit data in response to a data request from the network option.
(c) Inspects the error status of connected indoor units and transmits the inspection codes to the network option.
(d) A maximum of 16 units can be controlled (if in the same operation mode).
(2) Wiring connection diagram
Blue
A
Run
Abnormal
SL E board
A
Blue
B
B
LED3
LED2
Black
X
X
White
Y
Connected to the terminals for
Superlink signal lines
MVVS 0.75 - 1.25mm2
Y
Connected to the remote controller terminals (no
polarity) (the length should be 600 m or shorter)
ON
OFF SW3
SW2
SW1
Network address setting switches
[000]-(127)
Master/Sub
address
Basic Connections
Plural Controls by Multiple Remote Controls. Mixture of Multiple Units
Outdoor unit
Outdoor unit
Internal/external Crossing
Internal/external Crossing
Indoor unit
X Y
SL E Board
X Y
A B
Inside Inside Inside Inside
Remote control
X Y
SL E
Board
Network
options
Network A B
options
R
R
• Transmit the information of plural “Master” units to the network.
• Transmit the abnormalities of the “Slave” units to the network.
Setting the plural “Master/Slave” units with the dip SW of the printed circuit board.
Setting the “Master/Slave” remote controls with the dip SW of the remote control board.
Plural Controls by Multiple Remote Controls. Mixture of Multiple Units
Outdoor unit
Outdoor unit
Internal/external Crossing
R
Inside Inside Inside
SL E
Board
R
Network
options
Without Remote Control
Outdoor unit
Internal/external Crossing
Inside Inside Inside Inside
SL E
Board
0.5 mm2 x 2 cores
0.75 mm2 x 2 cores
1.25 mm2 x 2 cores
2.0 mm2 x 2 cores
200 m or shorter
300 m or shorter
400 m or shorter
600 m or shorter
R
R
Set up “000” to “127” using address switch on the SL E board.
Internal/external Crossing
Inside Inside
SL E
Board
Network
options
Set the SL E board dip SW
to “Master” SW3-1 ON.
The network option SLA-1E, SL1N-E is not allowed
(This will disturb switching
of the operation mode)
Wireless Kit
Outdoor unit
Internal/external Crossing
Inside Inside
SL E
Board
Network
options
Wireless Kit
Wireless
remote control
(3) Metal box dimension
85
35
30
70
90
5
22.5
100
40
2-ø6
39
OUTDOOR UNIT DIMENSIONS
FDC100VNX, 100VSX, 125VNX, 125VSX,
140VNX, 140VSX (unit:mm)
Mark
A
B
C
D
E
B
A
51
46
F
46
Item
Service valve connection of the
attached connecting pipe(gas
ø15.88(5/8")(Flare)
side)
Service valve connection(liquid side) ø9.52(3/8")(Flare)
Pipe/cable draw-out hole
ø20x3places
Drain discharge hole
M10x4places
Anchor bolt hole
ø30x2places(front)
ø45(side)
Cable draw-out hole
ø50(back)
113
Notes:
(1) It must not be surrounded by walls on the four
sides.
(2) The unit must be fixed with anchor bolts. An
anchor bolt must not protrude more than
15mm.
(3) Where the unit is subject to strong winds, lay it
in such a direction that the blower outlet faces
perpendicularly to the dominant wind direction.
(4) Leave 1m or more space above the unit.
(5) A wall in front of the blower outlet must not
exceed the units height.
(6) The model name label is attached on the lower
right corner of the front panel.
(7) Connect the Service valve with local pipe by
using the pipe of the attachment. (Gas side
only)
Terminal block
B
1300
A
15
38
40
20
262
388
50
L3
L2
C
70
160
170
624
155
85
52
50
50
200
60
15
E
C
27
15
50
Dimensions
L4
L1
Service
space
C
D
F
Examples of
installation
Intake
Intake
103
40
580
60
15
55
370
410
20
190
60
55
50
50
10
C
970
F
50
85
35
612
F
Outlet
1
2
3
L1
L2
L3
L4
Open Open 500
300
5 Open
150 300 150
5
5
5
Intake
L3
Minimum installation space
SRC40ZIX-S, 50ZIX-S, 60ZIX-S (unit:mm)
Terminal block
148.4
33.5
640
L2
Check joint
B
93
12.4
201
800
40
E
71.2
14.8
17.9
510
Dimensions
24.3
L1
L2
L3
L4
1
2
3
Open 280 280
100
75 Open
100
80
80
250 Open 250
351.6
290
312.5
43.5
A
83.5
327.3
89
L1
Examples of
installation
50.6
12
327.3
outlet
40°
42.5
40°
D
L4
Service
space
Intake
Mark
A
B
D
E
Item
Refrigerant gas side pipe connection tap
Refrigerant liquid side pipe connection tap
Drain discharge port
Anchor bolt hole
ø12.7(flare)
ø6.35(flare)
ø20.5x5places
M10x4places
Notes:
(1) It must not be surrounded by walls on the four sides.
(2) The unit must be fixed with anchor bolts.An anchor bolt must not protrude more than
15mm.
(3) Where the unit is subject to strong winds, lay it in such a direction that the blower outlet
faces perpendicularly to the dominant wind direction.
(4) Leave a 1m or larger space above the unit.
(5) A wall in front of the blower outlet must not exceed the units height.
(6) The unit name plate is attached on the lower right corner of the front panel.
FDC71VNX (unit:mm)
Mark
Item
Service valve connection
(gas side)
Service valve connection
(liquid side)
Pipe/cable draw-out hole
Drain discharge hole
Anchor bolt hole
A
B
C
D
E
223
ø20x3places
M10x4places
E
60
310
Notes:
(1) It must not be surrounded by walls on the four sides.
(2) The unit must be fixed with anchor bolts. An anchor bolt must
not protrude more the 15mm.
(3) Where the unit is subject to strong winds, lay it in such a
direction that the blower outlet faces perpendicularly to the
dominant wind direction.
(4) Leave 1m or more space above the unit.
(5) A wall in front of the blower outlet must not exceed the units
height.
(6) The model name label is attached on the lower right corner of
the front.
ø15.88(5/8")
(Flare)
ø9.52(3/8")
(Flare)
2-
15
.
R7
L3
47.5
5
Intake
L4
418
380
340
L2
Service
space
27
D
580
150
150
L1
61
19
61
Intake
outlet
32
88
880
Terminal block
Minimum installation space
750
C
B
30
48.5
30
24
Examples of
installation
Dimensions
L1
L2
L3
L4
103.5
A
165.5
25
1
2
3
Open
300
100
250
Open
250
150
250
500
Open
100
250
FDC100VN, 125VN, 140VN
100VS, 125VS, 140VS (unit:mm)
Mark
A
B
B
51
36
40
C
D
E
F
Item
Refrigerant gas side pipe
ø15.88(flare)
connection tap
Refrigerant liquid side pipe
ø9.52(flare)
connection tap
Pipe/cable draw-out port
ø20.3x3places
Drain discharge port
Anchor bolt hole
M10x4places
ø30.3x3places
Cable draw-out port
A
100
Notes:
(1) It must not be surrounded by walls on the four sides.
(2) The unit must be fixed with anchor bolts.An anchor
bolt must not protrude more than 15mm.
(3) Where the unit is subject to strong winds, lay it in such
a direction that the blower outlet faces
perpendicularly to the dominant wind direction.
(4) Leave a 1m or larger space above the unit.
(5) A wall in front of the blower outlet must not exceed the
units height.
(6) The unit name plate is attached on the lower right
corner of the front panel.
Terminal block
B
A
50
150
110
195
279
F
50
50
55
C
242
110
50
10
195
F
70
845
A
52
15
27
970
40
C
C
50
15
50
VIEW A
E
190
580
200
60
15
103
370
40
C
20
L2
L3
262
388
D
Intake
Examples of
installation
L4
Intake
L1
38
410
15
40
60
55
20
60
outlet
Service
space
Dimensions
L1
L2
L3
L4
1
2
3
Open Open 500
300
5 Open
150 300 150
5
5
5
Minimum installation space
41
OUTDOOR UNIT DIMENSIONS
FDC200VS (unit:mm)
FDC250VS (unit:mm)
42
MEMO
43
Before starting use
Heating performance
Refrigerant leakage
The heating performance values (kW) described in catalog are the values
obtained by operating at an outdoor temperature of 7 C and indoor
temperature of 20 C as set forth in the ISO Standards. As the heating
performance decreases as the outdoor temperature drops, if the outdoor
temperature is too low and the heating performance is insufficient, use other
heating appliances as well.
The refrigerant (R410A) used for Air conditioner is non-toxic and
inflammable in its original state.
However, in consideration of a state where the refrigerant leaks into the
room, measures against refrigerant leaks must be taken in small rooms
where the tolerable level could be exceeded. Take measures by installing
ventilation devices, etc.
Indication of sound values
Use in snowy areas
The sound values are the values (A scale) measured in a chamber such as an
anechoic chamber following the ISO Standards. In the actual installation
state, the value is normally larger than the values given in the catalog due to
the effect of surrounding noise and echo. Take this into consideration when
installing.
Take the following measures when installing the outdoor unit in snowy areas.
·Snow prevention
Install a snow-prevention hood so that the snow does not obstruct the air
intake port or enter and freeze in the outdoor unit.
Use in oil atmosphere
·Snow piling
Avoid installing this unit in as atmosphere where oil scatters or builds up,
such as in a kitchen or machine factory.
If the oil adheres to the heat exchanger, the heat exchanging performance
will drop, mist may be generated, and the synthetic resin parts may deform
and break.
In areas with heavy snow fall, the piled snow could block the air intake
port. In this case, a frame that is 50cm or higher than the estimated snow
fall must be installed underneath the outdoor unit.
Use in acidic or alkaline atmosphere
If this unit is used in acidic atmosphere such as hot spring areas having high
level of sulfuric gases or in alkaline atmosphere including ammonia or
calcium chloride, places where the exhaust of the heat exchanger is sucked
in, or at coastal areas where the unit is subject to salt breezes, the outer plate
or heat exchanger, etc., will corrode. Please ask a dealer or specialist when
you use an air conditioner in places differing from a general atmosphere.
Use in places with high ceilings
If the ceiling is high, install a circulator to improve the heat and air flow
distribution when heating.
Automatic defrosting device
If the temperature is low, and the humidity is high, frost will stick to the
heat exchanger of the outdoor unit. If use is continued, the heating
performance will drop.
The "Automatic defrosting device" will function to remove this frost.
After heating for approx, three to ten minutes, it will stop, and the frost will
be removed. After defrosting, hot air will be blown again.
Servicing the air-conditioner
After the air-conditioner is used for several seasons, dirt will build up in
the air-conditioner causing the performance to drop. In addition to regular
servicing, we recommend the maintenance contract (charged for) by a
specialist.
Safety Precautions
Air-conditioner usage target
Installation
The air-conditioner described in this catalog is a dedicated cooling/heating
device for human use.
Do not use it for special applications such as the storage of foodstuffs,
animals or plants, precision devices or valuable art, etc.
This could cause the quality of the items to drop, etc.
Do not use this for cooling vehicles or ships. Water leakage or current leaks
could occur.
Always commission the installation to a dealer or specialist. Improper
installation will lead to water leakage, electric shocks and fires.
Make sure that the outdoor unit is stable in installation. Fix the unit to
stable base.
Before use
,
Always read the "User s Manual" thoroughly before starting use.
Usage place
Do not install in places where combustible gas could leak or where there
are sparks.
Installation in a place where combustible gas could be generated, flow or
accumulate, or places containing carbon fibers could lead to fires.
Japan Head Office:
Mitsubishi Heavy Industries Ltd
16-5 2-Chome Kounan Minato-ku Tokyo
108-8215, Japan
www.mhi.co.jp
Our factories are ISO9001 and ISO14001 certified.
Certified ISO 9001
Certified ISO 14001
Certificate 04104 1998 0813 E5
BIWAJIMA PLANT
Mitsubishi Heavy Industries, Ltd.
Air-conditioning & Refrigeration Systems Headquarters
Certificate number : JQA-0709
HB91-10P01E-A-0
MITSUBISHI HEAVY INDUSTRIESMAHAJAK AIR CONDITIONERS CO., LTD.
Certificate Number : 04100 1998 0813
Mitsubishi Heavy
Industries-Haier (Quingdao)
Air-conditioners Co.,Ltd.
Certificate Number : 5170-1996-AQ-RCG-RvA
February 2010(3B)R
BIWAJIMA PLANT
Mitsubishi Heavy Industries, Ltd.
Air-conditioning & Refrigeration Systems Headquarters
Certificate number : JQA-EM0256
MITSUBISHI HEAVY INDUSTRIESMAHAJAK AIR CONDITIONERS CO.,LTD.
Certificate Number : 04104 1998 0813 E5
Mitsubishi Heavy
Industries-Haier (Quingdao)
Air-conditioners Co.,Ltd.
Certificate number : 01-1998-083
Because of our policy of continuous improvement, we reserve right to make changes in all specifications without notice.
Printed in Japan