Download Mitsubishi Electric MXZ-3C54VA Installation manual
Transcript
Split-type Air-Conditioner MXZ-3C54VA MXZ-4C71VA Installation Manual ForINSTALLER • Thismanualonlydescribestheinstallationofoutdoorunit. Wheninstallingtheindoorunit,refertotheinstallationmanualofindoorunit. JG79A460H02.indd 1 English 2011/03/08 15:21:15 ENGLISH CONTENTS . BEFOREINSTALLATION............................................................ 2. OUTDOORUNITINSTALLATION............................................... 4 3. FLARINGWORKANDPIPECONNECTION............................... 4 4. PURGINGPROCEDURES,LEAKTEST,ANDTESTRUN......... 5 5. RELOCATIONANDMAINTENANCE.......................................... 6 Required Tools for Installation Phillipsscrewdriver FlaretoolforR40A Level GaugemanifoldforR40A Scale VacuumpumpforR40A Utilityknifeorscissors ChargehoseforR40A Torquewrench Pipecutterwithreamer Wrench(orspanner) 4mmhexagonalwrench 1. BEFORE INSTALLATION 1-1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY • Besuretoread“THEFOLLOWINGSHOULDALWAYSBEOBSERVEDFORSAFETY”beforeinstallingtheairconditioner. • Besuretoobservethewarningsandcautionsspecifiedhereastheyincludeimportantitemsrelatedtosafety. • Afterreadingthismanual,besuretokeepittogetherwiththeOPERATINGINSTRUCTIONSforfuturereference. WARNING (Couldleadtodeath,seriousinjury,etc.) n Do not install the unit by yourself (user). Incompleteinstallationcouldcausefireorelectricshock,injuryduetothe unitfalling,orleakageofwater.Consultthedealerfromwhomyoupurchasedtheunitoraqualifiedinstaller. n Perform the installation securely referring to the installation manual. Incompleteinstallationcouldcausefireorelectricshock,injuryduetothe unitfalling,orleakageofwater. n When installing the unit, use appropriate protective equipment and tools for safety. Failuretodosocouldcauseinjury. n Install the unit securely in a place which can bear the weight of the unit. If the installation location cannot bear the weight of the unit, the unit couldfallcausinginjury. n Perform electrical work according to the installation manual and be sure to use an exclusive circuit. Do not connect other electrical appliances to the circuit. If the capacity of the power circuit is insufficient or there is incomplete electricalwork,itcouldresultinafireoranelectricshock. n Do not damage the wires by applying excessive pressure with parts or screws. Damagedwirescouldcausefire. n Be sure to cut off the main power in case of setting up the indoor P.C. board or wiring works. Failuretodosocouldcauseelectricshock. n Usethespecifiedwirestoconnecttheindoorandoutdoorunitssecurelyandattachthewiresfirmlytotheterminalblockconnecting sections so the stress of the wires is not applied to the sections. Incompleteconnectingandsecuringcouldcausefire. n Donotinstalltheunitinaplacewhereinflammablegasmayleak. Ifgasleaksandaccumulatesintheareaaroundtheunit,itcouldcause anexplosion. n Do not use intermediate connection of the power cord or the extension cord and do not connect many devices to one AC outlet. Itcouldcauseafireoranelectricshockduetodefectivecontact,defectiveinsulation,exceedingthepermissiblecurrent,etc. n Besuretousethepartsprovidedorspecifiedpartsfortheinstallation work. Theuseofdefectivepartscouldcauseaninjuryorleakageofwaterdue toafire,anelectricshock,theunitfalling,etc. n When plugging the power supply plug into the outlet, make sure that there is no dust, clogging, or loose parts in both the outlet and the plug. Make sure that the power supply plug is pushed completely into the outlet. Ifthereisdust,clogging,orloosepartsonthepowersupplyplugorthe outlet,itcouldcauseelectricshockorfire.Ifloosepartsarefoundonthe powersupplyplug,replaceit. CAUTION n Attach the electrical cover to the indoor unit and the service panel to the outdoor unit securely. Iftheelectricalcoveroftheindoorunitand/ortheservicepanelofthe outdoor unit are not attached securely, it could result in a fire or an electricshockduetodust,water,etc. n When installing, relocating, or servicing the unit, make sure that no substance other than the specified refrigerant (R410A) enters the refrigerant circuit. Any presence of foreign substance such as air can cause abnormal pressureriseandmayresultinexplosionorinjury.Theuseofanyrefrigerantotherthanthatspecifiedforthesystemwillcausemechanical failure, system malfunction, or unit breakdown. In the worst case, this couldleadtoaseriousimpedimenttosecuringproductsafety. n Do not discharge the refrigerant into the atmosphere. If refrigerant leaks during installation, ventilate the room. Ifrefrigerantcomesincontactwithafire,harmfulgascouldbegenerated. Refrigerantleakagemaycausesuffocation.Ventilatetheroom. n Check that the refrigerant gas does not leak after installation has been completed. Ifrefrigerantgasleaksindoors,andcomesintocontactwiththeflame of a fan heater, space heater, stove, etc., harmful substances will be generated. n Use appropriate tools and piping materials for installation. ThepressureofR40Ais.6timesmorethanR22.Notusingappropriatetoolsormaterialsandincompleteinstallationcouldcausethepipes toburstorinjury. n When pumping down the refrigerant, stop the compressor before disconnecting the refrigerant pipes. If the refrigerant pipes are disconnected while the compressor is runningandthestopvalveisopen,aircouldbedrawninandthepressure in the refrigeration cycle could become abnormally high. This could causethepipestoburstorinjury. n When installing the unit, securely connect the refrigerant pipes before starting the compressor. Ifthecompressorisstartedbeforetherefrigerantpipesareconnected andwhenthestopvalveisopen,aircouldbedrawninandthepressure in the refrigeration cycle could become abnormally high. This couldcausethepipestoburstorinjury. n Fastenaflarenutwithatorquewrenchasspecifiedinthismanual. Iffastenedtootight,aflarenutmaybreakafteralongperiodandcause refrigerantleakage. n The unit shall be installed in accordance with national wiring regulations. n Earth the unit correctly. Donotconnecttheearthtoagaspipe,waterpipe,lightningrodortelephoneearth.Defectiveearthingcouldcauseelectricshock. (Couldleadtoseriousinjuryinparticularenvironmentswhenoperatedincorrectly.) n Install an earth leakage breaker depending on the installation place. Ifanearthleakagebreakerisnotinstalled,itcouldcauseelectricshock. n Perform the drainage/piping work securely according to the installation manual. Ifthereisdefectinthedrainage/pipingwork,watercoulddropfromthe unit,soakinganddamaginghouseholdgoods. n Donottouchtheairinletorthealuminumfinsoftheoutdoorunit. Thiscouldcauseinjury. n Do not install the outdoor unit where small animals may live. If small animals enter and touch the electric parts inside the unit, it could cause a malfunction, smoke emission, or fire. Also, advise user tokeeptheareaaroundtheunitclean. 1-2. SPECIFICATIONS Powersupply* Model MXZ-3C54VA MXZ-4C7VA Wirespecifications*2 Pipelengthandheightdifference*3,*4,*5,*6,*7,*8 Max.no.ofbends Max.pipelength Rated Fre- Breaker RefrigerantadjustIndoor/outdoor Max.height perindoorunit/ Powersupply perindoorunit/ mentA*0 Voltage quency capacity connectingwire difference*9 formultisystem formulti-system 25m/50m 25/50 4-core 230V 50Hz 25A 3-core2.5mm2 5m 20g/m .0/.5mm2 25m/60m 25/60 * Connect to the power switch which has a gap of 3 mm or more when opentointerruptthesourcepowerphase.(Whenthepowerswitchisshut off,itmustinterruptallphases.) *2 Use wires in conformity with design 60245 IEC 57. Use the indoor/outdoorconnectingwireinconformitywiththewirespecificationsspecifiedin theinstallationmanualoftheindoorunit. *3 Neverusepipeswiththicknesslessthanspecified.Thepressureresistancewillbeinsufficient. *4 Useacopperpipeoracopper-alloyseamlesspipe. *5 Becarefulnottocrushorbendthepipeduringpipebending. *6 Refrigerantpipebendingradiusmustbe00mmormore. *7 Insulationmaterial:Heatresistingfoamplastic0.045specificgravity *8 Besuretousetheinsulationofspecifiedthickness.Excessivethickness may cause incorrect installation of the indoor unit and insufficient thicknessmaycausedewdrippage. *9 Iftheoutdoorunitisinstalledhigherthantheindoorunit,max.height differenceisreducedto0m. *0Ifpipelengthexceeds40m,additionalrefrigerant(R40A)chargeisrequired.(Noadditionalchargeisrequiredforpipelengthlessthan40m.) Additionalrefrigerant=A×(pipelength(m)-40) En- JG79A460H02.indd 1 2011/03/08 15:21:16 1-3. SELECTING OPTIONAL DIFFERENT-DIAMETER JOINTS Ifthediameterofconnectionpipedoesnotmatchtheportsizeofoutdoorunit,useoptionaldifferent-diameterjointsaccordingtothefollowingtable. (Unit:mm(inch)) MXZ3C54VA Portsizeofoutdoorunit MXZLiquid/Gas 4C7VA - AUNIT 6.35(/4)/2.7(/2) A-CUNIT B-DUNIT 6.35(/4)/9.52(3/8) Optionaldifferent-diameterjoints(portsizeofoutdoorunit→diameterofconnectionpipe) 6.35(/4)→9.52(3/8):PAC-493PI 9.52(3/8)→2.7(/2):MAC-454JP 9.52(3/8)→5.88(5/8):PAC-SG76RJ 2.7(/2)→9.52(3/8):MAC-A455JP 2.7(/2)→5.88(5/8):MAC-A456JP Refertotheinstallationmanualofindoorunitforthediameterofconnectionpipeofindoorunit. 1-4. SELECTING THE INSTALLATION LOCATION • • • • • Whereitisnotexposedtostrongwind. Whereairflowisgoodanddustless. Whererainordirectsunshinecanbeavoidedasmuchaspossible. Whereneighboursarenotannoyedbyoperationsoundorhotair. Whererigidwallorsupportisavailabletopreventtheincreaseofoperationsoundorvibration. • Wherethereisnoriskofcombustiblegasleakage. • Wheninstallingtheunit,besuretosecuretheunitlegs. • Whereitisatleast3mawayfromtheantennaofTVsetorradio.OperationoftheairconditionermayinterferewithradioorTVreceptionin areaswherereceptionisweak.Anamplifiermayberequiredfortheaffecteddevice. • Installtheunithorizontally. • Please install it in an area not affected by snowfall or blowing snow. Inareaswithheavysnow,pleaseinstallacanopy,apedestaland/or somebaffleboards. Note: It is advisable to make a piping loop near outdoor unit so as to reduce vibrationtransmittedfromthere. FREE SPACE REQUIRED AROUND OUTDOOR UNIT 1. Obstacles above When there is no obstacle in front and on the sides of the unit, it is allowed to install the unit where an obstacle is above the unit only if the 500ormore spaceshowninthefigureisprovided. 00ormore Note: Whenoperatingtheairconditionerinlowoutsidetemperature,besure tofollowtheinstructionsdescribedbelow. • Neverinstalltheoutdoorunitinaplacewhereitsairinlet/outletside maybeexposeddirectlytowind. • Topreventexposuretowind,installtheoutdoorunitwithitsairinlet sidefacingthewall. • Topreventexposuretowind,itisrecommendedtoinstallabaffle boardontheairoutletsideoftheoutdoorunit. Avoidthefollowingplacesforinstallationwhereairconditionertrouble isliabletooccur. • Whereflammablegascouldleak. • Wherethereismuchmachineoil. • Saltyplacessuchastheseaside. • Wheresulfidegasisgeneratedsuchasahotspring. • Wherethereishigh-frequencyorwirelessequipment. • WherethereisemissionofhighlevelsofVOCs,includingphthalate compounds,formaldehyde,etc.,whichmaycausechemicalcracking. 2. Front (blowing) side open As long as space indicated in the figure is provided, it is allowed to install the unit where obstacles are behind and on the sides of the unit. (Noobstacleabovetheunit) 200ormore 350ormore 00ormore 3. Obstacles in front (blowing) only 4. Obstacles in front and behind Whenthereisanobstacleinfrontof theunitasshowninthefigure,open space above, behind, and on the sidesoftheunitisrequired. 500ormore Theunitcanbeusedbyattachinganoptionaloutdoor blowingguide(MAC-856SG) (butbothsidesandtopare open). 00ormore 500ormore Blowingguide(MAC-856SG) 6. Service space 5. Obstacles in front, behind and on side(s) • Wheninstallingtheunitinanareathatisenclosedwithwallssuch asaverandah,besuretohaveenoughspaceasshownbelow. In this case, the air conditioning capacity and power consumption mightdeteriorate. • Whenthereisalackofairfloworthereisapossibilityofbecoming shortcycle,installanoutletguideandmakesurethereisenough spacebehindoftheunit. • Wheninstallingtwoormoreunits,donotinstalltheunitsinfrontor behindeachother. Providespaceforserviceandmaintenanceasshowninthefigure. Servicespace 00ormore 500ormore 200ormore 00ormore 350ormore 00ormore 500ormore Heightoftheobstacleis200orless 500ormore 350ormore 350ormore (Unit:mm) En-2 JG79A460H02.indd 2 2011/03/08 15:21:16 1-5. INSTALLATION DIAGRAM Aftertheleaktest,applyinsulatingmaterialtightlysothatthereis nogap. Whenthepipingistobeattachedtoawallcontainingmetals (tinplated)ormetalnetting,use achemicallytreatedwooden piece20mmorthickerbetween thewallandthepipingorwrap7 to8turnsofinsulationvinyltape aroundthepiping. Touseexistingpiping,perform COOLoperationfor30minutes andpumpdownbeforeremoving theoldairconditioner.Remake flareaccordingtothedimension fornewrefrigerant. Openasarule Morethan500mm ifthefrontandboth sidesareopen Morethan00mm Morethan200mmifthereare obstaclestobothsides Morethan 00mm ACCESSORIES Checkthefollowingpartsbeforeinstallation. () Drainsocket (2) Draincap 2 PARTS TO BE PROVIDED AT YOUR SITE (A) (B) (C) (D) (E) Powersupplycord* Indoor/outdoorunitconnectingwire* Extensionpipe Wallholecover Pipingtape Extensiondrainhose (F) (orsoftPVChose,5mminner diameterorhardPVCpipeVP6) (G) Refrigerationoil (H) (I) (J) (K) Putty Pipefixingband Fixingscrewfor(I) Wallholesleeve SoftPVChose,5mminnerdi(L) ameterorhardPVCpipeVP6for drainsocket() Little amount 2to7 2to7 * Note: Place indoor/outdoor unit connecting wire (B) and power supply cord (A) at least m away from the TVantennawire. Openasarule Morethan500mmiftheback, bothsidesandtopareopen The“Q’ty”for(B)to(K)intheabovetableisquantitytobeusedperindoorunit. Morethan350mm IMPORTANT NOTES TocomplywiththerequirementsofAustralianstandardAS/NZS3000electricalinstallations(wiring rules),theelectricalwiringrequiredbetweentheindoorandoutdoorunitsmustbeinstalledbya licencedelectricalcontractor. Outdoor unit installation Unitsshouldbeinstalledbylicensedcontractor accordingtolocalcoderequirements. 835 396 Airinlet 36 500 Airinlet 330 66 Airoutlet 4-0×2Ovalholes (Unit:mm) 1-6. DRAIN PIPING FOR OUTDOOR UNIT Pleaseperformthedrainpipingworkonlywhendrainingfromoneplace. )Chooseoneholetodischargedrainandinstallthedrainsocket()tothehole. 2)Closetherestoftheholeswiththedraincaps(2). 3)ConnectthesoftPVChose(L)of5mmintheinsidediameteronthemarketwiththedrainsocket()andleaddrain. Note: Installtheunithorizontally. Donotusethedrainsocket()andthedraincaps(2)inthecoldregions.Drainmayfreezeanditmakesthefanstop. Theoutdoorunitproducescondensateduringtheheatingoperation.Selecttheinstallationplacetoensuretopreventtheoutdoorunitand/orthegrounds frombeingwetbydrainwaterordamagedbyfrozendrainwater. En-3 JG79A460H02.indd 3 2011/03/08 15:21:17 2. OUTDOOR UNIT INSTALLATION 2-1. CONNECTING WIRES FOR OUTDOOR UNIT )Removetheservicepanel. 2)Loosenterminalscrew,andconnectindoor/outdoorunitconnectingwire(B)from theindoorunitcorrectlyontheterminalblock.Becarefulnottomakemis-wiring. Fixthewiretotheterminalblocksecurelysothatnopartofitscoreisappeared, andnoexternalforceisconveyedtotheconnectingsectionoftheterminalblock. 3)Firmlytightentheterminalscrewstopreventthemfromloosening.Aftertightening,pullthewireslightlytoconfirmthattheydonotmove. 4)Perform2)and3)foreachindoorunit. 5)Connectpowersupplycord(A). 6)Fixindoor/outdoorunitconnectingwire(B)andpowersupplycord(A)withthe cableclamps. 7)Closetheservicepanelsecurely.Makesurethat3-2.PIPECONNECTIONis completed. • Aftermakingconnectionsbetweenbothpowersupplycord(A)andindoor/outdoorunitconnectingwire(B),besuretofixbothcableandwirewithcable clamps. Terminalblockforpowersupply 4C7VA Servicepanel <OUTDOORUNIT> Indoor/outdoorunit connectingwire Terminalblock Terminalblockfor powersupply Terminalblock 5mm 35mm Leadwire Terminalblock POWERSUPPLY ~/N230V50Hz Terminalblock <INDOORUNIT> • Be sure to attach each screw to its correspondent terminal whensecuringthecordand/orthewiretotheterminalblock. • Makeearthwirealittlelongerthanothers.(Morethan35mm) • Forfutureservicing,giveextralengthtotheconnectingwires. Dunitisfor4C7VAonly 3. FLARING WORK AND PIPE CONNECTION 3-1. FLARING WORK )Cutthecopperpipecorrectlywithpipecutter.(Fig.,2) 2)Completelyremoveallburrsfromthecutcrosssectionofpipe.(Fig.3) • Aimthecopperpipedownwardwhileremovingburrstopreventburrsfrom droppinginthepipe. 3)Remove flare nuts attached to indoor and outdoor units, then put them on pipehavingcompletedburrremoval.(Notpossibletoputthemonafterflaring work.) 4)Flaring work (Fig. 4, 5). Firmly hold copper pipe in the dimension shown in thetable.SelectAmmfromthetableaccordingtothetoolselected. 5)Check • ComparetheflaredworkwithFig.6. • Ifflareisnotedtobedefective,cutofftheflaredsectionanddoflaringwork again. A(mm) Pipediameter Nut Clutch Clutch Wingnut (mm) (mm) typetool typetool typetool forR40A forR22 forR22 ø6.35(/4”) 7 .5to2.0 ø9.52(3/8”) 22 0to0.5 .0to.5 ø2.7(/2”) 26 2.0to2.5 ø5.88(5/8”) 29 TiltedUnevenBurred Fig. 3.7to7.7 34.3to4.2 49.0to56.4 73.5to78.4 Copperpipe Sparereamer Pipecutter Clutchtype Fig.3 kgf•cm 40to80 350to420 500to575 750to800 Fig.2 Flaringtool Burr Tighteningtorque N•m Nogood Good Copper pipe Wingnuttype Fig.4 Smoothall around Insideisshiningwithoutany scratches. Copperpipe Die Evenlength allaround Flarenut 3-2. PIPE CONNECTION Fig.5 Fig.6 1)Applyathincoatofrefrigerationoil(G)totheflaredendsofthepipesand thepipeconnectionsoftheoutdoorunit. 2)Alignthecenterofthepipewiththatofthepipeconnectionsoftheoutdoor unit,thenhandtightentheflarenut3to4turns. WARNING 3)Tightentheflarenutwithatorquewrenchasspecifiedinthetable. •Over-tighteningmaycausedamagetotheflarenut,resultinginrefrigerant When installing the unit, securely leakage. connect the refrigerant pipes before •Besuretowrapinsulationaroundthepiping.Directcontactwiththebare starting the compressor. pipingmayresultinburnsorfrostbite. 3-3. INSULATION AND TAPING )Coverpipingjointswithpipecover. 2)Foroutdoorunitside,surelyinsulateeverypipingincludingvalves. CAUTION 3)Usingpipingtape(E),applytapingstartingfromtheentryofoutdoorunit. • Stoptheendofpipingtape(E)withtape(withadhesiveagentattached). When there are the ports which are • Whenpipinghavetobearrangedthroughaboveceiling,closetorwhere not used, make sure their nuts are thetemperatureandhumidityarehigh,windadditionalcommerciallysold tightened securely. insulationtopreventcondensation. En-4 JG79A460H02.indd 4 2011/03/08 15:21:18 4. PURGING PROCEDURES, LEAK TEST, AND TEST RUN 4-1. PURGING PROCEDURES AND LEAK TEST )Removeserviceportcapofstopvalveonthesideoftheoutdoorunit gaspipe.(Thestopvalvesarefullyclosedandcoveredincapsin theirinitialstate.) 2)Connectgaugemanifoldvalveandvacuumpumptoserviceportof stopvalveonthegaspipesideoftheoutdoorunit. 3)Runthevacuumpump.(Vacuumizeformorethan5minutes.) 4)Checkthevacuumwithgaugemanifoldvalve,thenclosegauge manifoldvalve,andstopthevacuumpump. 5)Leaveasitisforoneortwominutes.Makesurethepointerofgauge manifoldvalveremainsinthesameposition.Confirmthatpressure gaugeshows-0.0MPa[Gauge](-760mmHg). 6)Removegaugemanifoldvalvequicklyfromserviceportofstopvalve. 7)Fullyopenallstopvalvesonthegaspipeandtheliquidpipe.Operatingwithoutfullyopeninglowerstheperformanceandthiscauses trouble. 8)Referto-2.,andchargetheprescribedamountofrefrigerantif needed.Besuretochargeslowlywithliquidrefrigerant.Otherwise, compositionoftherefrigerantinthesystemmaybechangedand affectperformanceoftheairconditioner. 9)Tightencapofserviceporttoobtaintheinitialstatus. 0)Leaktest Stopvalvecap (Torque9.6to 29.4N•m,200 to300kgf•cm) *4to5turns *Close Compoundpressure –0.0MPa gauge(forR40A) (–760mmHg) Pressuregauge (forR40A) *Open Gaugemanifold valve(forR40A) Serviceportcap (Torque3.7to 7.7N•m,40to 80kgf•cm) Stopvalve forGAS Precautionswhenusing thecontrolvalve Close A Open Control valve HandleHigh Handle Low Hexagonalwrench Body Stopvalve forLIQUID Chargehose (forR40A) Vacuumpump (forR40A) Whenattachingthecontrolvalveto theserviceport,valvecoremaydeformorloosenifexcesspressureis applied.Thismaycausegasleak. Serviceport Whenattachingthecontrolvalveto theserviceport,makesurethatthe Chargehose valvecoreisinclosedposition,and then tighten partA. Do not tighten (forR40A) partAorturnthebodywhenvalve coreisinopenposition. 4-2. GAS CHARGE Performgaschargetounit. )Connectgascylindertotheserviceportofstopvalve. 2)Performairpurgeofthepipe(orhose)comingfromrefrigerantgascylinder. 3)Replenish specified amount of the refrigerant, while operating the air conditionerforcooling. Note: Incaseofaddingrefrigerant,complywiththequantityspecifiedfortherefrigeratingcycle. CAUTION: Whenchargingtherefrigerantsystemwithadditionalrefrigerant,besuretouse liquid refrigerant.Adding gas refrigerant may change the composition of the refrigerantinthesystemandaffectnormaloperationoftheairconditioner.Also, chargetheliquidrefrigerantslowly,otherwisethecompressorwillbelocked. To maintain the high pressure of the gas cylinder, warm the gas cylinder with warmwater(under40°C)duringcoldseason.Butneverusenakedfireorsteam. Stopvalve Liquid pipe Union Union Indoor unit Union Union Refrigerantgas cylinder operatingvalve (forR40A) Outdoor unit Stopvalvewith Gas serviceport pipe Gaugemanifold valve(forR40A) *Dunitisfor 4C7VAonly. Chargehose (forR40A) RefrigerantgascylinderforR40Awithsiphon Refrigerant(liquid) Electronicscaleforrefrigerantcharging 4-3. REMOVING THE MAINTENANCE PANEL ThesettingofDipSwitchontheoutdoorcontrollerboardcanbechanged withoutremovingthefrontpanel. Followtheproceduresbelowtoremovethemaintenancepanelandset theDipSwitch. 1)Removescrew(s)whichfixthemaintenancepanel. 2)Removethemaintenancepanel,andperformnecessarysettings. 3)Installthemaintenancepanel. Note: Makesuretofixthemaintenancepanelsecurely.Incompleteinstallation couldcausemalfunction. maintenancepanel En-5 JG79A460H02.indd 5 2011/03/08 15:21:19 4-4. LOCKING THE OPERATION MODE OF THE AIR CONDITIONER (COOL, DRY, HEAT) • Descriptionofthefunction: With this function, once the operation mode is locked to either COOL/DRY modeorHEATmode,theairconditioneroperatesinthatmodeonly. * Changingthesettingisrequiredtoactivatethisfunction.Pleaseexplainabout thisfunctiontoyourcustomersandaskthemwhethertheywanttouseit. [How to lock the operation mode] )Be sure toturnoffthemain power fortheairconditioner beforemaking the setting. 2)Setthe“2”ofSWontheoutdoorcontrollerboardtoONtoenablethisfunction. 3)TolocktheoperationmodeinCOOL/DRYmode,setthe“”ofSWonthe outdoorcontrollerboardtoOFF.TolocktheoperationinHEATmode,setthe sameswitchtoON. 4)Turnonthemainpowerfortheairconditioner. COOL/DRY HEAT 4-5. LOWERING THE OPERATION NOISE OF THE OUTDOOR UNIT • Descriptionofthefunction: Withthisfunction,theoperatingnoiseoftheoutdoorunitcanbeloweredbyreducingtheoperationload,forexample,duringnighttimeinCOOLmode. However,pleasenotethatthecoolingandheatingcapacitymaylowerifthisfunctionisactivated. * Changingthesettingisrequiredtoactivatethisfunction.Pleaseexplainaboutthisfunctiontoyourcustomersandaskthemwhethertheywanttouseit. [How to lower the operating noise] )Be sure toturnoffthemain power fortheairconditioner beforemaking the setting. 2)Setthe“3”ofSWontheoutdoorcontrollerboardtoONtoenablethisfunction. 3)Turnonthemainpowerfortheairconditioner. Lowertheoperatingnoise 4-6. TEST RUN • Testrunsoftheindoorunitsshouldbeperformedindividually.Seetheinstallationmanualcomingwiththeindoorunit,andmakesurealltheunitsoperateproperly. • Ifthetestrunwithalltheunitsisperformedatonce,possibleerroneousconnectionsoftherefrigerantpipesandtheindoor/outdoorunitconnectingwires cannotbedetected.Thus,besuretoperformthetestrunonebyone. Makesurethatthefollowingisdone. • Powerissuppliedtotheunit. • Stopvalvesareopen. About the restart protective mechanism Oncethecompressorstops,therestartpreventivedeviceoperatessothecompressorwillnotoperatefor3minutestoprotecttheairconditioner. 4-7. EXPLANATION TO THE USER • UsingtheOPERATINGINSTRUCTIONS,explaintotheuserhowtousetheairconditioner(howtousetheremotecontroller,howtoremovetheairfilters,howtoremoveorputtheremotecontrollerintheremotecontrollerholder,howtoclean,precautionsforoperation,etc.). • RecommendtheusertoreadtheOPERATINGINSTRUCTIONScarefully. 5. RELOCATION AND MAINTENANCE 5-1. PUMPING DOWN Whenrelocatingordisposingoftheairconditioner,pumpdownthesystemfollowingtheprocedurebelowsothatnorefrigerantisreleasedintotheatmosphere. )Connectthegaugemanifoldvalvetotheserviceportofthestopvalveonthegaspipesideoftheoutdoorunit. 2)Fullyclosethestopvalveontheliquidpipesideoftheoutdoorunit. 3)Closethestopvalveonthegaspipesideoftheoutdoorunitalmostcompletelysothatitcanbeeasilyclosedfullywhenthepressuregaugeshows0 MPa[Gauge](0kgf/cm2). 4)StarttheemergencyCOOLoperationonalltheindoorunits. TostarttheemergencyoperationinCOOLmode,disconnectthepowersupplyplugand/orturnoffthebreaker.After5seconds,connectthepower supplyplugand/orturnonthebreaker,andthenpresstheE.O.SWonce.(TheemergencyCOOLoperationcanbeperformedcontinuouslyforupto30 minutes.) 5)Fullyclosethestopvalveonthegaspipesideoftheoutdoorunitwhenthepressuregaugeshows0.05to0MPa[Gauge](approx.0.5to0kgf/cm2). 6)StoptheemergencyCOOLoperation. PresstheE.O.SWseveraltimesuntilallLEDlampsturnoff.Refertooperatinginstructionsfordetails. WARNING When pumping down the refrigerant, stop the compressor before disconnecting the refrigerant pipes. The compressor may burst if air etc. get into it. En-6 JG79A460H02.indd 6 2011/03/08 15:21:19 HEADOFFICE:TOKYOBLDG.,2-7-3,MARUNOUCHI,CHIYODA-KU,TOKYO00-830,JAPAN JG79A460H02 JG79A460H02.indd 7 2011/03/08 15:21:19