Download Det-Tronics X3300 Specifications

Transcript
Devices
EQ3740IPM Intelligent Protection Module
EQ3740IPM Intelligent Protection Module (Spec Sheet: 90-1184). The IPM is designed
to provide continuous and automated local area fire protection, while monitoring system
operation through continuous supervision of its inputs/outputs (I/O) and Local Operating
Network/Signaling Line Circuit (LON/SLC) connection to the EQP controller. In addition, the
module contains a unique “embedded logic program” that if enabled during configuration,
allows the IPM to perform local area protection in a “back-up mode” without controller
interaction. The IPM utilizes eight pre-configured I/O channels to perform its monitoring,
supervision, and mitigation functions.
•
Provides a pre-packaged single hazard protection solution to the Det-Tronics Eagle Quantum
Premier system
•
•
•
Class 1 Div. 2 locations combined with Zone 2 rated devices Type N
Eight independent, supervised I/O channels
Individual channels have the pre-assigned functions necessary to deliver a single hazard
protection solution
Supports two conventional “two-wire” smoke/heat zones with up to 15 devices per zone, and
the ability to reset latched zones. Does not require the use of “relay bases”
Individual points are supervised in accordance with NFPA requirements for alarm/supervisory/
other input styles, notification/releasing outputs
Panel or DIN rail mounting
Meets the requirements of NFPA 72
•
•
•
•
Manual
Release
DETECTORS
Abort
EQ3740
Intelligent
Protection
Module
Systems C.7
Devices
Release -2
EQ30XX
Controller
ACCESSORIES
KEY:
Zone 2
Smoke and
Heat
LON Communication Loop
Release -1
CONTROLLER
Bell
Zone 1
Smoke and
Heat
Supervisory
Device
Mounting Option
(Panel or DIN
Rail)
= Required
= Option
= Choice Required
52-1002-8.1
8/01/2011