Parameters - XR140C - XR150C continued. Use fold out programming flow chart inside front cover Fdt Drip Time dPO First Defrost after start up Ot Thermostat Probe Calibration OE Evaporator Probe Calibration CF Unit of Measurement COn Probe Fault “ON” Time COF Probe Fault “OFF” Time Sets the period of time following the termination of a defrost during which nothing happens. This allows any residual moisture on the evaporator time to drip down and drain away. Tells the controller whether to do an immediate defrost when the power is switched on or to wait for the normal interval time as set in parameter IdF. Can be used to make sure defrosts are not missed in areas with unreliable power supplies. Probe offset adjustment – thermostat Probe offset adjustment – evaporator Sets the display to read out in Celsius or Fahrenheit If a probe fault is detected the display will flash P1 and the controller will automatically cycle the compressor on and off. This parameter sets the “ON” time period If a probe fault is detected the display will flash P1 and the controller will automatically cycle the compressor on and off. This parameter sets the “OFF” time period - 12 - 0 ÷ 120 mins. 0=immediate 1=After IdF time - 12 ∃ 0 ÷ 12 ∃ 0c - 12 ∃ 0 ÷ 12 ∃ 0c 0=Degrees C 1=Degrees F 0 ÷ 120 mins. 0 ÷ 120 mins. Pr2 0 Pr2 1 Pr2 0 Pr2 0 Pr2 0 Pr2 15 mins. Pr2 30 mins.