Download Data Aire DAMW/G-01 Unit installation
Transcript
Pre-Start Before starting up units perform the following procedures to ensure proper unit operation. To close and reattach the panel, reverse the above procedures. Units with VFD Note: Verify that all wires are in proper position and not rubbing once the panel has been secured. This panel is hinged to allow service access to fan motor and belt drive components that are located behind it. Note: The panel weight rating is 225 lbs. total including factory-installed components. To swing the panel open: WARNING Proper Field Wiring and Grounding Required! All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury. Pre-Start Checklist Complete this checklist after installing unit to verify all recommended installation procedures are complete before start-up.This does not replace the detailed instructions in the appropriate sections of this manual. Always read the entire section carefully to become familiar with the procedures. Supply Fan • Verify the fan and motor shafts are parallel. • Verify the fan and motor sheaves are aligned. • Check the fan belt condition and tension. Adjust the tension if belts are floppy or squeal continually. Replace worn or fraying belts in matched sets. • Ensure the fan rotates freely. • Tighten locking screws, bearing set screws and sheaves. Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. • Ensure bearing locking collars do not wobble when rotated. • Remove fan assembly tie down bolts. On 20 - 38 ton units, do not remove the fan assembly tie down bolts if the fan speed is 750 rpm or less. • Ensure fan rotation is in direction of arrow on fan housing. If incorrect, verify incoming power phasing is correct. Switch wires on the fan contact to properly phase fan if necessary. For additional information regarding the safe discharge of capacitors, see PROD-SVB06A-EN • Ensure trunk ductwork to VAV boxes is complete and secure to prevent leaks. • Verify that all ductwork conforms to NFPA 90A or 90B and all applicable local codes WARNING Hazardous Voltage w/Capacitors! 1. Remove the unit center cover panel to the left of the VFD panel. 2. Verify/remove/discard the sheet metal shipping screws along the top and bottom edges of the VFD panel. Ductwork Water-Cooled Unit Piping • 3. Disconnect the communications cable from the keypad on the VFD door panel. 4. Turn the two slotted-head fasteners on the right edge of the VFD panel fully counterclockwise. Air-Cooled Units Only • Verify leak test was performed after refrigerant piping was installed. • Verify liquid line filter driers installed. 5. Pull on the handle to swing the panel 180°. Note: To secure the panel in the open position during service procedures, attach the chain mounted to the cabinet frame behind the unit center cover panel to the chain retainer notch on the edge of the VFD panel. SCXF-SVX01K-EN Verify condensate drain, water piping drain plugs, economizer header, and condenser vent plug are installed. Units with Hydronic Heat • Verify the entering water temperature sensor is installed upstream of the hydronic coil. 73