Download Daikin BRC4C64 User`s manual

Transcript
Warning
Daikin Industries, Ltd.’s products are manufactured for export to numerous countries throughout the
world. Daikin Industries, Ltd. does not have control over which products are exported to and used in a
particular country. Prior to purchase, please therefore confirm with your local authorised importer,
distributor and/or retailer whether this product conforms to the applicable standards, and is suitable for
use, in the region where the product will be used. This statement does not purport to exclude, restrict
or modify the application of any local legislation.
PCS0316H
Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the User's Manual carefully before using this product. The User's Manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.
AIR CONDITIONING SYSTEM
COOLING ONLY
HE AT PUMP
Cautions on product corrosion
1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install
the outdoor unit close to the sea shore, contact your local distributor.
JMI-0107
JQA-1452
About ISO 9001
ISO 9001 is a plant certification system
defined by the International Organization for
Standardization (ISO) relating to quality
assurance. ISO 9001 certification covers
quality assurance aspects related to the
“ design, development, manufacture,
installation, and supplementary service” of
products manufactured at the plant.
About ISO 14001
ISO 14001 is the standard defined by the
International Organization for Standardization
(ISO) relating to environmental management
systems. Our group has been acknowledged
by an internationally accredited compliance
organisation as having an appropriate
programme of environmental protection
procedures and activities to meet the
requirements of ISO 14001.
Dealer
Head Office:
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:
JR Shinagawa East Bldg., 2-18-1, Konan,
Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com/global_ac/
c All rights reserved
Printed in Japan 05/08/005 SW • HP • SS
Specifications, designs and other content appearing in this brochure are current as of May 2008 but subject to change without notice.
C
r e a t io n o f
C
o m fo r t
[ 50 Hz ]
[ 50 Hz ]
Stores often feature the latest in designed
decor.
This refined beauty attracts people.
Meanwhile, offices have a functional beauty.
This encourages those within to work hard
and apply intelligence and passion to their
tasks.
In either situation, a certain elegance should
fill the space because thinking minds require
high quality air conditioning. SkyAir by D aikin
realise a comfortable indoor environment. All
over the world, stores, offices, and homes
prefer the low operating sound, attractive
1
2
Cooling only
Capacity
HP
The values given for
1 HP is for FDGB type,
1.5 HP–6 HP is for FHYC type,
7 HP is for FDMG type,
8 HP–20 HP is for FD type.
kW
1
1.5
2
2.5
3
4
5
6
7
8
10
15
20
2.6
3.5
5.3
6.4
7.7
10.5
12.8
14.2
16.8
24.0
29.2
47.9
58.4
Btu/h
8,900
11,900
18,100
21,800
26,200
35,700
43,600
48,400
57,500
81,800
99,600
163,500
199,400
kcal/h
2,250
3,010
4,560
5,500
6,600
9,000
11,000
12,200
14,400
20,600
25,100
41,200
50,200
FHC35KVE
FHC50KVE
FHC60KVE
FHYC71KVE
FHYC100KVE
FHYC125KVE
FHYC140KVE
R35GV1
R50GV1
R60GV1
R71LUV1 / Y1
R100LUV1 / Y1
R125LUY1
R140LUY1
FH35BVE
FH50BVE
FH60BVE
FHY71BVE
FHY100BVE
FHY125BVE
R35GV1
R50GV1
R60GV1
R71LUV1 / Y1
R100LUV1 / Y1
R125LUY1
CEILING MOUNTED
CASSETTE TYPE
Page 11– 14
Specifications
Dimensions
Indoor unit
Page 39
Page 60
Outdoor unit
CEILING SUSPENDED TYPE
Page 15– 16
Specifications
Dimensions
Indoor unit
Page 39
Page 60
Outdoor unit
CEILING SUSPENDED
CASSETTE TYPE
Page 17– 18
Specifications
Dimensions
Page 40
Page 61
Indoor unit
FUY71FJV1
FUY100FJV1
FUY125FJV1
Outdoor unit
R71LUV1 / Y1
R100LUV1 / Y1
R125LUY1
CEILING MOUNTED
CASSETTE CORNER TYPE
Page 19– 20
Specifications
Dimensions
Indoor unit
Page 40
Page 61
Outdoor unit
FHK35FV1
FHK45FV1
FHK60FV1
FHYK71FJV1
R35GV1
R50GV1
R60GV1
R71LUV1 / Y1
FHB35FV1
FHB45FV1
FHB60FV1
FHYB71FV1
FHYB100FV1
FHYB125FV1
R35GV1
R50GV1
R60GV1
R71LUV1 / Y1
R100LUV1 / Y1
R125LUY1
CEILING MOUNTED
BUILT-IN TYPE
Page 21– 22
Specifications
Dimensions
Page 41
Page 62
Indoor unit
Outdoor unit
WALL MOUNTED TYPE
Page 23– 24
Specifications
Dimensions
Page 41
Page 62,63
FAY71LVE
FAY100FAVE
R71LUV1 / Y1
R100LUV1 / Y1
Indoor unit
FVY71LAVE
FVY100LAVE
FVY125LAVE
Outdoor unit
R71LUV1 / Y1
R100LUV1 / Y1
R125LUY1
Indoor unit
Outdoor unit
FLOOR STANDING TYPE
Page 25– 26
Specifications
Dimensions
Page 42
Page 63
PACKAGED AIR CONDITIONERS
LOW STATIC
PRESSURE TYPE
Specifications Page 42
Dimensions Page 64
Indoor unit
Outdoor unit
DUCT
CONNECTION
FDBG25AVE
FDBG35AVE
FDBG50AVE
FDBG60AVE
FDBG71AVE
R25JV1
R35JV1
R50GV1
R60GV1
R71FUV1 / Y1
MIDDLE STATIC
PRESSURE TYPE
Specifications Page 43
Dimensions Page 64,65
Page 27– 30
(FDMG)
(FDMG)
(FDYM)
(FDYM)
(FDMG)
(FDMG)
(FDYM)
Indoor unit
FDMG71AV1
FDMG100AV1
FDMG125AV1
FDMG140AV1
FDMG180AV1
Outdoor unit
Indoor unit
RG71AV1 / Y1
R100FUV1 / Y1
R125FUY1
RG140AY1
RG180AY1
FDYM03FAV1
FDYM04FAV1
FDYM05FAV1
FDYM06FAV1
Outdoor unit
R71LUV1 / Y1
R100LUV1 / Y1
R125LUY1
R140LUY1
Indoor unit
FD03KY1
FD04KY1
FD05KY1
FD06KY1
FD08KY1
FD10KY1
FD15KY1
FD20KY1
Outdoor unit
Outdoor unit
R71FUY1
R100FUY1
R125FUY1
RU06KY1
RU08KUY1
RU08KY1
RU10KUY1
RU10KY1
RU08KUY1 × 2
RU08KY1 × 2
RU10KUY1 × 2
RU10KY1 × 2
RU08KUY1
RU08KY1
RU10KUY1
RU10KY1
RU08KUY1 × 2
RU08KY1 × 2
RU10KUY1 × 2
RU10KY1 × 2
HIGH STATIC
PRESSURE TYPE
Specifications Page 44,45
Dimensions Page 65– 67
(Type without factory charged refrigerant)
OUTDOOR UNIT
Page 33– 34
Dimensions Page 68– 74
R25JV1
3
R35GV1
R35JV1
R50GV1
R60GV1
R71LUV1
R71LUY1
R71FUY1
RG71AV1 R100LUV1 R100FUY1
RG71AY1 R100LUY1 R100FUV1
R125LUY1 R125FUY1
R140LUY1
RU06KY1
RG140AY1
RG180AY1
4
Cooling only
Simultaneous operation system
HP
Capacity
The values given on the right
are for the FHYC type.
Page 31– 32
TWIN MULTI OPERATION
3
4
Specifications Page 46– 48
5
6
8
10
kW
7.7
10.5
12.8
14.2
22.2
26.6
Btu/h
26,200
35,700
43,600
48,400
75,800
90,800
kcal/h
6,600
9,000
11,000
12,200
19,100
22,900
FHYC35KVE × 2
FHYC50KVE × 2
FHYC60KVE × 2
FHYC71KVE × 2
FHYC100KVE × 2
FHYC125KVE × 2
R71LUV1 / Y1
R100LUV1 / Y1
R125LUY1
R140LUY1
R200KUY1
R250KUY1
Simultaneously running
2 to 4 units distributes
comfort across wide spaces.
CEILING MOUNTED
CASSETTE TYPE
Indoor unit
Outdoor unit
Simultaneous control with
2 units in spacious space
CEILING SUSPENDED
TYPE
Indoor unit
Outdoor unit
FHY35BVE × 2
FHY50BVE × 2
FHY60BVE × 2
FHY71BVE × 2
FHY100BVE × 2
FHY125BVE × 2
R71LUV1 / Y1
R100LUV1 / Y1
R125LUY1
R140LUY1
R200KUY1
R250KUY1
FDYM04FAV1 × 2
FDYM05FAV1 × 2
R200KUY1
R250KUY1
R200KUY1
R250KUY1
DUCT CONNECTION
MIDDLE STATIC
PRESSURE TYPE
Indoor unit
Outdoor unit
Simultaneous control with
3 units for irregularly
shaped space
OUTDOOR UNIT
Page 33– 34
R71LUV1
R71LUY1
Simultaneous operation system
Capacity
The values given on the right
are for the FHYC type.
R100LUV1
R100LUY1
R125LUY1
R140LUY1
Page 31– 32
TRIPLE MULTI OPERATION
Specifications Page 46– 48
Simultaneous
operation system
DOUBLE TWIN MULTI
OPERATION
Page 31– 32
Specifications Page 46– 48
HP
6
8
8
10
kW
14.2
22.2
22.2
26.6
Btu/h
48,400
75,800
75,800
90,800
kcal/h
12,200
19,100
19,100
22,900
FHYC50KVE × 3
FHYC71KVE × 3
FHYC50KVE × 4
FHYC60KVE × 4
R140LUY1
R200KUY1
R200KUY1
R250KUY1
FHY50BVE × 3
FHY71BVE × 3
FHY50BVE × 4
FHY60BVE × 4
R140LUY1
R200KUY1
R200KUY1
R250KUY1
R200KUY1
R250KUY1
Simultaneous control with
4 units for large space
CEILING MOUNTED
CASSETTE TYPE
Indoor unit
Outdoor unit
CEILING SUSPENDED
TYPE
Indoor unit
Outdoor unit
DUCT CONNECTION
MIDDLE STATIC
PRESSURE TYPE
FDYM03FAV1 × 3
Indoor unit
Outdoor unit
R200KUY1
OUTDOOR UNIT
Page 33– 34
R140LUY1
5
R200KUY1
6
Heat pump
1.5
3.75
2
5.2
2.5
6.15
3
7.7
4
10.4
5
12.8
6
14.2
8
22.2
10
27.1
15
43.5
20
53.0
Btu/h
12,800
17,800
21,000
26,200
35,300
43,600
48,400
75,700
92,500
148,000
181,000
kcal/h
3,230
4,470
5,290
6,600
8,900
11,000
12,220
19,100
23,300
37,400
45,600
kW
4.22
5.8
7.0
7.9
11.2
14.2
16.3
23.2
29.5
44.8
56.8
Btu/h
14,400
19,800
23,900
27,000
38,100
48,400
56,000
79,200
100,700
153,000
194,000
kcal/h
3,630
4,990
6,020
6,800
9,600
12,200
14,000
20,000
25,400
38,500
48,800
Indoor unit
HP
Capacity
kW
Cooling
The values given on the right are
for the FHYC type. Values for other
Heating
types may differ slightly.
The values given for 8HP to 20HP are for
the FDY type.
CEILING MOUNTED
CASSETTE TYPE
Page 11– 14
Specifications Page 49
Dimensions
Page 60
FHYC35KVE
FHYC50KVE
FHYC60KVE
FHYC71KVE
FHYC100KVE
FHYC125KVE
FHYC140KVE
Outdoor unit
RY35FV1A
RY50GAV1A
RY60GAV1A
RY71LUV1 / Y1
RY100LUV1 / Y1
RY125LUY1
RY140LUY1
Indoor unit
FHY35BVE
FHY50BVE
FHY60BVE
FHY71BVE
FHY100BVE
FHY125BVE
Outdoor unit
RY35FV1A
RY50GAV1A
RY60GAV1A
RY71LUV1 / Y1
RY100LUV1 / Y1
RY125LUY1
FUY71FJV1
FUY100FJV1
FUY125FJV1
RY71LUV1 / Y1
RY100LUV1 / Y1
RY125LUY1
CEILING SUSPENDED TYPE
Page 15– 16
Specifications Page 49
Dimensions
Page 60
CEILING SUSPENDED
CASSETTE TYPE
Page 17– 18
Specifications Page 50
Dimensions
Page 61
Indoor unit
Outdoor unit
CEILING MOUNTED
CASSETTE CORNER TYPE
Page 19– 20
Specifications Page 50
Dimensions
Page 61
Indoor unit
Outdoor unit
FHYK35FJV1
FHYK45FJV1
FHYK60FJV1
FHYK71FJV1
RY35FV1A
RY50GAV1A
RY60GAV1A
RY71LUV1 / Y1
FHYB35FV1
FHYB45FV1
FHYB60FV1
FHYB71FV1
FHYB100FV1
FHYB125FV1
RY35FV1A
RY50GAV1A
RY60GAV1A
RY71LUV1 / Y1
RY100LUV1 / Y1
RY125LUY1
CEILING MOUNTED
BUILT-IN TYPE
Page 21– 22
Specifications Page 51
Dimensions
Page 62
Indoor unit
Outdoor unit
WALL MOUNTED TYPE
Page 23– 24
Specifications Page 51
Dimensions
Page 62,63
Indoor unit
Outdoor unit
FAY71LVE
FAY100FAVE
RY71LUV1 / Y1
RY100LUV1 / Y1
FLOOR STANDING TYPE
Page 25– 26
Specifications Page 52
Dimensions
Page 63
Indoor unit
Outdoor unit
FVY71LAVE
FVY100LAVE
FVY125LAVE
RY71LUV1 / Y1
RY100LUV1 / Y1
RY125LUY1
PACKAGED AIR CONDITIONERS
DUCT
CONNECTION
LOW STATIC
PRESSURE TYPE
Specifications Page 52
Dimensions
Page 64
Indoor unit
Outdoor unit
FDYB35KAVE
FDYB50KAVE
FDYB60KAVE
FDYB71KAVE
RY35FV1A
RY50GAV1A
RY60GAV1A
RY71LUV1 / Y1
MIDDLE STATIC
PRESSURE TYPE
Specifications Page 53
Dimensions
Page 64,65
Indoor unit
FDYM03FAV1
FDYM04FAV1
FDYM05FAV1
FDYM06FAV1
Outdoor unit
RY71LUV1 / Y1
RY100LUV1 / Y1
RY125LUY1
RY140LUY1
HIGH STATIC
PRESSURE TYPE
Specifications Page 54
Dimensions
Page 65– 67
Page 27– 30
Indoor unit
FDY06KAY1
FDY08KAY1
FDY10KAY1
FDY15KAY1
FDY20KAY1
Outdoor unit
RY140LUY1
RY200KUY1
RY250KUY1
RY200KUY1 × 2
RY250KUY1 × 2
RY140LUY1
RY200KUY1
RY250KUY1
RY200KUY1 × 2
RY250KUY1 × 2
OUTDOOR UNIT
Page 33– 34
7
Dimensions
Page 68– 74
RY35FV1A
RY50GAV1A
RY60GAV1A
RY71LUV1
RY71LUY1
RY100LUV1
RY100LUY1
RY125LUY1
8
Heat pump
Simultaneous operation system
HP
Capacity
Cooling / Heating
The values given on the right
are for the FHYC type.
Page 31– 32
TWIN MULTI OPERATION
3
4
Specifications Page 54– 56
5
6
8
Simultaneously running
2 to 4 units distributes
comfort across wide spaces.
10
kW
7.7/7.9
10.4/11.2
12.8/14.2
14.2/16.3
22.2/22.7
26.6/28.4
Btu/h
26,200/27,000
35,300/38,100
43,600/48,400
48,400/56,000
75,800/77,500
90,800/97,000
kcal/h
6,600/6,800
8,900/9,600
11,000/12,200
12,200/14,000
19,100/19,500
22,900/24,400
FHYC35KVE × 2
FHYC50KVE × 2
FHYC60KVE × 2
FHYC71KVE × 2
FHYC100KVE × 2
FHYC125KVE × 2
RY71LUV1 / Y1
RY100LUV1 / Y1
RY125LUY1
RY140LUY1
RY200KUY1
RY250KUY1
CEILING MOUNTED
CASSETTE TYPE
Indoor unit
Outdoor unit
Simultaneous control with
2 units in spacious space
CEILING SUSPENDED
TYPE
Indoor unit
FHY35BVE × 2
FHY50BVE × 2
FHY60BVE × 2
FHY71BVE × 2
FHY100BVE × 2
FHY125BVE × 2
Outdoor unit
RY71LUV1 / Y1
RY100LUV1 / Y1
RY125LUY1
RY140LUY1
RY200KUY1
RY250KUY1
FDYM04FAV1 × 2
FDYM05FAV1 × 2
RY200KUY1
RY250KUY1
RY200KUY1
RY250KUY1
DUCT CONNECTION
MIDDLE STATIC
PRESSURE TYPE
Indoor unit
Outdoor unit
Simultaneous control with
3 units for irregularly
shaped space
OUTDOOR UNIT
Page 33– 34
RY71LUV1
RY71LUY1
Simultaneous operation system
HP
Capacity
Cooling / Heating
The values given on the right
are for the FHYC type.
RY100LUV1
RY100LUY1
RY125LUY1
RY140LUY1
Page 31– 32
TRIPLE MULTI OPERATION
6
Specifications Page 54– 56
8
Simultaneous
operation system
Page 31– 32
DOUBLE TWIN MULTI
OPERATION
8
Specifications Page 54– 56
10
kW
14.2/16.3
22.2/22.7
22.2/22.7
26.6/28.4
Btu/h
48,400/56,000
75,800/77,500
75,800/77,500
90,800/97,000
kcal/h
12,200/14,000
19,100/19,500
19,100/19,500
22,900/24,400
FHYC50KVE × 3
FHYC71KVE × 3
FHYC50KVE × 4
FHYC60KVE × 4
RY140LUY1
RY200KUY1
RY200KUY1
RY250KUY1
FHY50BVE × 3
FHY71BVE × 3
FHY50BVE X 4
FHY60BVE × 4
RY140LUY1
RY200KUY1
RY200KUY1
RY250KUY1
FDYB71KAVE × 3
FDYB50KAVE × 4
FDYB60KAVE × 4
RY200KUY1
RY200KUY1
RY250KUY1
RY200KUY1
RY250KUY1
CEILING MOUNTED
CASSETTE TYPE
Indoor unit
Outdoor unit
Simultaneous control with
4 units for large space
CEILING SUSPENDED
TYPE
Indoor unit
Outdoor unit
DUCT CONNECTION
LOW STATIC
PRESSURE TYPE
Indoor unit
Outdoor unit
DUCT CONNECTION
MIDDLE STATIC
PRESSURE TYPE
FDYM03FAV1 × 3
Indoor unit
Outdoor unit
RY200KUY1
OUTDOOR UNIT
Page 33– 34
RY140LUY1
9
RY200KUY1
10
CEILING MOUNTED CASSETTE TYPE
Sound level
35/ 30
CEILING MOUNTED
CASSETTE TYPE
High
Low
Unified square panels
dB(A)
All models from the 35K to 140K use
the same size panel. Multiple unit
installations maintain a physical
uniformity that is aesthetically
pleasing and make it easier to plan
ceiling lighting systems and to design
interiors.
FHYC71K
FH( Y) C
950 mm
Cooling only FH(Y)C35KVE–140KVE
Heat pump FHYC35KVE–140KVE
Quiet, decor-blending form
and easy installation in
new or old buildings.
Optimal comfort and convenience assured by 3 air discharge modes
Same for
all models
Air direction
Desired
situation
Draft prevention setting
When drafts are unwanted
Auto-swing
5-levels
air direction
setting
Wireless LCD remote controller
A s ignal rec eiver mus t be
added to the indoor unit.
950 mm
Compact body and quiet operation
BRC1C61
Note: R emote c ontroller c able not
inc luded. C ables must be
proc ured loc ally.
Signal receiver unit
(Installed type)
Cooling only
BRC7C613W
Heat pump
BRC7C612W
Indoor units use an
aerodynamically designed
Diffuser Turbo Fan
Wireles s remote
c ontroller and
s ignal rec eiver unit
are s old as a s et.
Diffus er
For gentle drafts
(Ceiling is soiled.)
Auto-s wing between
30° and 65°
Settable to 5 different
levels between 10° and 40°
Settable to 5 different
levels between 10° and 65°
Settable to 5 different
levels between 30° and 65°
Draft prevention
(In heating mode)
At heating s tartup and thermo
OFF*, air direc tion is automatic ally s et to a near horizontal 10˚ to
prevent direc t expos ure to c ool
Auto air
direction control
The air direc tion is s et automatic ally to the memoris ed
pos ition of the previous air direc tion. (Initial s etting is 65˚ for
heating and 30˚ for c ooling.)
Multi-Flow System
4-way flow
1 pattern
4 pattern
dB(A)
Indoor unit
High
Low
35K
33
33
35
35
39
42
44
29
29
30
30
34
36
37
100K
125K
140K
Wide air distribution
A newly shaped air discharge opening
increases flow without increasing
wind speed, hence discharged air
reaches farther than before.
Air discharge distribution comparison
•125K
Draft resistance has been reduced by
incorporating, into a single unit, an
impeller and a diffuser to control air
flow inside the unit. The Diffuser
Turbo Fan is both quiet during
operation and compact.
71K
At heating startup and thermo OFF*, air discharge is automatically set to 30˚ to prevent
both direct exposure to cool air drafts and con-
Note: Air direc tion is s et to the s tandard pos ition when the unit is s hipped from the fac tory.
The pos ition c an be c hanged from the remote c ontroller.
*When the thermos tat turns off.
B lade
60K
When ceilings must
be kept spotless
Auto-s wing between
10° and 65°
3-way flow
50K
Setting to prevent soiling of ceiling
Auto-s wing between
10° and 40°
Accessory required for indoor unit (option)
Wired LCD remote controller
Standard setting
2-way flow
2.5 m/sec
2
2.0 m/sec
1.5 m/sec
1.0 m/sec 1
0.5 m/sec
0.5 m/sec
3 pattern
4 (m)
3
2
1
0
1
2
" " denotes piping direction. "
" denotes sealing
member for air discharge outlet (option) .
Air discharge temperature comparison
Note: For 3-way or 2-way flow ins tallation, the
s ealing member for air dis c harge outlet
(option) mus t be us ed to c los e off the
unus ed outlet(s ).
(m) Conventional model
2.7
33˚C
30˚C
2
27˚C
Air direction can be selected
according to installation.
Note: Operation s ound
inc reas es when
us ing 2-way
or 3-way
•125K
3
4 (m)
(In heating)
(m)
3.2
3
Super Cassette
1
3
33˚C
30˚C
27˚C
2
1
2
1
25˚C
25˚C
22˚C
4 (m)
(m)
3.2
3
Super Cassette
(m) Conventional model
2.7
2.5 m/sec
2.0 m/sec
2
1.5 m/sec
1.0 m/sec
1
22˚C
0
1
2
3
4 (m)
Suitable for high ceilings
Criteria for ceiling height and number of
air discharge outlets
Number of air discharge outlets used
35K–71K
4-way
flow
Standard
Ceiling
High ceiling
height
High ceiling
Note : Anec hoic c hamber c onvers ion value,
meas ured ac c ording to J IS parameters and
3-way
flow
2-way
flow
100K–140K
4-way
flow
3-way
flow
2-way
flow
2.7 m 3.0 m 3.5 m 3.2 m 3.6 m 4.2 m
3.0 m 3.3 m 3.8 m 3.6 m 4.0 m 4.2 m
3.5 m 3.5 m 4.2 m 4.2 m -
Note: Initial s ettings are for s tandard c eiling
height and 4-way flow. High c eiling s ettings
1 and 2 are s et from the remote
Programme "Dry"
Two selectable temperature-sensors
Both indoor unit and wired remote
controller (option) contain temperaturesensors. Temperature sensing can be
set at the unit or, to further improve
comfort level, closer to the target area
at the wired remote control.
11
Guide Line up
P. 3–10
Outdoor units
P. 33–34
Remote controllers
P. 35–36
Standard specifications
P. 39, 46, 49, 54
Options
P. 57
Outer dimension drawings
P. 60
*Temperature-s ens or on indoor unit mus t be us ed
when the air c onditioner is c ontrolled from another
room.
**Wireles s remote c ontroller does not have a
Dehumidification is microprocessor
controlled to prevent abrupt and
uncomfortable changes in air
temperature.
Switchable fan speed: High/Low
12
CEILING MOUNTED CASSETTE TYPE
Easier to maintain
Dust can be kept from blowing onto
ceilings by directly setting flaps by
hand or by remote control.
The new long-life filter is 20% more
efficient than the previous one. This has
enabled further reductions in running
costs by extending the heat-exchanger
cleaning interval by once every two
years to once every three years.
Conventional
Super Cassette
*1 298 mm high with 100K – 140K
*2 303 mm high with 100K – 140K
U lt r a lo n g -life filt e r
P a n e l s pa c e r
Even in smoky environments where
the air conditioning is on most of the
time, the ultra long-life filter only
has to be changed once a year.
Use when only minimal space is available between drop ceilings
and ceiling slabs.
Smoky atmosphere: annual filter change
*For dust concentration of 0.3 mg/m3 (Requires separately sold Air Cleaner.)
1 year (Approx. 5,000 hr) 15 hr/day x 28 day/month x 12 month/year
S e a lin g m e m be r fo r a ir d is c h a r g e o u t le t
3 years
Conventional
Super Cassette
H ig h -e ffic ie n c y filt e r
B r a n c h d u c t c h a m be r
Available in two types: 65% and 90% colorimetry.
This chamber lets you connect a round flexible duct to the air
discharge opening at any time after the original installation.
F r e s h a ir in t a k e k it
Less cleaning work
thanks to "Non-dew Flaps"
with non-flocking
The use of non-flocking flaps minimises adnerring dart, so less cleaning
work is needed.
Installable in any direction
Self-diagnosis function
Using this kit, a duct can be
fitted to increase the intake of
outdoor air.
Outside Note: *C onnec ting duc ts , ins ec t nets , fire dampers , air filters , and other
parts s hould, as required, be proc ured loc ally.
**Outs ide Air fan interloc ked with air c onditioning unit is nec es s ary.
Optional PC B (K R P1C 63)is required for interloc king.
***It is rec ommended that the volume of outdoor air introduc ed through
the kit is limited to 10% of the maximum airflow rate of the indoor
unit. Introduc ing higher quantities will inc reas e the operating nois e
and may als o influenc e temperature s ending.
Low gas pressure detection
Insufficient gas charging is normally
hard to detect. During post-installation
trials and regular inspection procedures,
the refrigerant level is monitored by
microprocessor to maintain proper gas
pressure.
The units can be installed in the following different ways.
Chamber type (without T-joint pipe and fan)
Kit name: KDDP55D160
Since the orientation
of the intake grill can
be adjusted after installing, the direction
of the intake grill
lines can be unified
when multiple units
are installed.
Chamber type (with T-joint pipe and without fan)
Kit name: KDDP55D160K
Flexible duct
(procured locally)
Flexible duct
T-joint pipe
(procured locally)
T-joint pipe
Direct installation type
Kit name: KDDJ55X160
Suction
chamber
Connection
chamber
Figure 1)
Signal receiver
unit
Notes : R equires an ins pec tion port for maintenanc e ac c es s .
For dual intake duc t ins tallation only. If only a s ingle intake duc t c an be c onnec ted
bec aus e of an obs truc tion, etc .,
K DDP55D160 s hould be us ed ins tead.
It is not pos s ible to us e this kit s imultaneous ly with the wireles s remote c ontroller.
Refrigerant piping
Notes: R equires an inspection port for maintenance
access.
If intake ducts cannot be connected to both
connection chambers due, for example, to an
obstruction, single intake duct installation is
possible.
Figure 1 shows what the installation will look like
750 mm
Note: Us e of options will inc reas e operating s ound.
Cooling only
Heat pump
DoubleTwin Multi Operation
*1Applic able
*2Applic able
*3Applic able
*4Applic able
*1
*2
*4
*4
*1
*3
*4
*4
Option
Others
PE fin
Auto-res tart
Control features
S elf-diagnos is func tion
E mergenc y operation
Low gas pres s ure
detec tion
C eiling s oiling prevention
Filter s ign
Long-life filter
Pre c harged for
up to 30 m
Work & Servicing
Drain pump mec hanis m
Mould res is tant treatment
for filter
Year-round c ooling
applic able
Hot s tart
Two s elec table
temperature-s ens ors
S witc hable fan s peed
Draft prevention func tion
Model
S wing pattern s elec tion
Auto s wing
The high-performance filter and other
options are easily clipped into place.
There is no need for a screwdriver.
Supports simultaneous running of the twin,
triple, and double twin multi operation.
Mould
prevention
Comfort
High c eiling applic ation
Easy installation for options
(Features are explained on P. 37–38.)
Feature
Programme "Dry"
Features
Triple Multi Operation
Intake duct
(procured locally)
Intake duct
Connection (procured locally)
chamber
(duct length: 4 m max.)
Intake duct
(procured locally)
(duct length: 4 m max.)
Drain pump is equipped
as standard accessory with
750 mm lift.
Duct flange
(with insulation
material)
Suction
chamber
Twin / triple / double twin
multi operation
All models suspended
without lift
2 years
High-effic ienc y filter
Note: If the wireless remote c ontrol option is installed, a
light rec eptor unit is housed
in one of the adjuster poc k-
Move to 0°
1
Move to des ired angle
Sealing members block air discharge openings not used in 2-way
or 3-way blow.
Fres h air intake kit
Each corner of the unit has an Adjuster Pocket that lets you
easily adjust the unit's
suspended height.
1
2
*For dust concentration of 0.15 mg/m3
4 years (Approx. 10,000 hr) 8 hr/day x 25 day/month x 4 years
Ultra long-life filter
Easy height adjustment
less ce
ilin
dirt tha g
Move flaps
n
before
direc tly to
des ired angle
Heat-exchanger cleaning interval
258 mm
40 mm
Ordinary store or office: filter change every 4 years
30%—40%
Twin Multi Operation
Note: S ome c eiling c ons truc tions may hinder ins tallation.
40 mm
C ontac t your DaiPanel spacer
Panel spacer
kin Dealer before
ins talling your unit.
For 35K–71K indoor units For 100K–140K indoor units
200 mm
Interloc k c ontrol
245 mm *2
Heat exchanger cleaning
required only once every 3 years
Timer s elec tor
240 mm *1
Stepping motor controls flaps
to prevent soiled ceilings
C entral remote c ontrol
Just 240 mm high.
Installable in tight ceiling
spaces (35K–71K)
Options required for specific operating environments
Auto-c ooling/heating
c hange-over
C ontrol by 2 remote
c ontrollers
C ontrol by 1 remote
c ontroller
E xternal c ommand
c ontrol
Quick and easy to install
when wired remote c ontroller is us ed
to R 71LU– R 140LU outdoor units (for temp. down to – 15°C ) (An option is required.)
to R Y71LU– R Y140LU outdoor units (for temp. down to – 5°C ) and R Y200LU– R Y250LU outdoor units (for temp. down to – 0°C )
to R (Y)71LU– 140LU outdoor units
See pages 31–32 for details of the Multi Series.
13
14
CEILING SUSPENDED TYPE
Sound level
CEILING SUSPENDED
TYPE
39/ 35
High
Low
Spreads comfortable air throughout the room
dB(A)
Auto-swing for comfort in
all directions
FHY71B
Both indoor unit and wired remote controller
(option) contain temperature-sensors. Temperature sensing can be set at the unit or, to
further improve comfort level, closer to the
target area at the wired remote control.
dB(A)
Accessory required for indoor unit (option)
Wired LCD remote controller
A s ignal rec eiver mus t be
added to the indoor unit.
BRC1C61
Note: R emote c ontroller c able not
inc luded. C ables must be
proc ured loc ally.
Cooling only
BRC7EA66
Heat pump
BRC7E63W
Wireles s remote
c ontroller and
s ignal rec eiver unit
are s old as a s et.
37
38
38
39
42
44
32
33
33
35
37
39
125B
Note : Anec hoic c hamber c onvers ion value,
meas ured ac c ording to J IS parameters and
Uses quiet stream fan
and other quiet
technologies.
Sound damper
Installation flexibility for freedom of design
Drain pump kit (option) can be
easily incorporated
Uniform height and depth. Compact
design for small-capacity models to
meet tighter dimensional constraints.
Signal receiver unit
(Installed type)
35B
71B
Switchable fan speed: High/Low
Wireless LCD remote controller
Low
100B
Dehumidification is microprocessor controlled to prevent abrupt and uncomfortable changes in air temperature.
Installable
on ceilings
3.5 m high
High
60B
Programme "Dry"
100°
Indoor unit
50B
*Temperature-sensor on indoor unit must be used when
the air c onditioner is c ontrolled from another room.
**Wireless remote controller does not have a temperaturesensor.
Cooling only FH(Y)35BVE–125BVE
Heat pump FHY35BVE–125BVE
Upgrade to a quiet and
compact system.
Sound operation has been reduced on the
exposed ceiling suspended type unit.
Two selectable temperature-sensors
Wide air discharge openings
produce a spreading 100° airflow
FH( Y)
Quiet operation
Drain pipe connection can be done
inside the unit. Refrigerant and drain
pipe outlets are at the same opening.
(mm)
Indoor unit 35B/50B 60B/71B 100B
Height
Width
Depth
125B
195
960
1,160
1,400
Two time settings (2500 hrs and 1250 hrs) are available
to match the installation environment. Maintenance time
warning is displayed on the remote controller (filter sign).
Non-dew flap without bristles
All wiring and internal servicing
done from below the unit
The unit fits more snugly into tight
spaces.
Absence of bristles minimises clinging
dirt and simplifies
cleaning.
Pipes more easily rigged, too
For 71B indoor unit
Non-dew flap
Plastic panels are used to conceal
piping holes. Holes can be easily
punched out without requiring special
tools.
Dimens ions in brac kets are for previous model.
1,160 mm (1,300 mm)
1,220 mm (1,420 mm)
* For dust concentration of 0.15 mg/m3
Drain pump kit (built inside main unit)
Reduced edge space,
more flexible installation
(60 mm)
Long-life filter lasts about 1 year *
Maintenance not required
600 mm
Weight of all models reduc ed (down 10%
c ompared with previous models ). Trans fer and
ins tallation work is les s arduous .
30 mm
Easy-clean, flat surfaces
It is easy to wipe dirt off the flat
side and lower surfaces of the unit.
For all maintenance tasks,
access is from bottom
surface.
(60 mm)
Low gas pressure detection
*Water used in the test-run can now be drained from the air
discharge opening rather than from the side as was formerly
the case.
Quiet
stream fan
Easier to maintain
1,590
680
30 mm
Turbulent flow Straightening
is produced
vane
Improved-oil resistant grille
Supports simultaneous running of the twin,
triple and double twin multi operation.
Twin Multi Operation
Triple Multi Operation
Oil-resistant plastic is used for the air
discharge grille. This improves
durability in restaurants and other
similar environments.
DoubleTwin Multi Operation
Note: Intended for use in salons, dining rooms, and
ordinary sales floors, this specification is not
suitable for kitchens or other harsh environments.
See pages 31–32 for details of the Multi Series.
(Features are explained on P. 37–38.)
15
Guide Line up
P. 3–10
Outdoor units
P. 33–34
Remote controllers
P. 35–36
Standard specifications
P. 39, 47, 49, 55
Options
P. 57
Outer dimension drawings
P. 60
*1Ins tallable on max. 3.5 m high c eiling
*4Applic able to R Y71LU– R Y140LU outdoor units (for temp. down to – 5°C )
*2Applic able when wired remote c ontroller is us ed
and R Y200LU– R Y250LU outdoor units (for temp. down to – 0°C )
*3Applic able to R 71LU– R 140LU outdoor units (for temp. down to – 15°C
*5Optional
)
available
6
* Applic able to R (Y)71LU– 140LU outdoor units
(An option is required.)
PE fin
Twin / triple / double twin
multi operation
Others
Interloc k c ontrol
C entral remote c ontrol
E xternal c ommand
c ontrol
C ontrol by 1 remote
c ontroller
C ontrol by 2 remote
c ontrollers
Auto-c ooling/heating
c hange-over
Auto-res tart
Control features
S elf-diagnos is func tion
E mergenc y operation
Low gas pres s ure
detec tion
Filter s ign
*6
Long-life filter
*6
*6
Mould-proofing
drain pan
Pre c harged for
up to 30 m
Mould res is tant treatment
for filter
*6
*5
Timer s elec tor
*5
*4
Year-round c ooling
applic able
*3
*2
Hot s tart
*2
Two s elec table
temperature-s ens ors
High c eiling
applic ation *1
S witc hable fan s peed
Draft prevention func tion
Work & Servicing
Drain pump mec hanis m
Cooling only
Heat pump
Auto s wing
Model
Mould
prevention
Comfort
Feature
Programme "Dry"
Features
16
CEILING SUSPENDED CASSETTE TYPE
Sound level
High
Low
The auto-swing function increases comfort level
dB(A)
Ultra-thin with quiet operation
Auto-swing
5-levels air direction setting
Auto-air direction control
Auto-swing between 0° and
60°
Settable to 5 different levels
between 0° and 60°
The air direction is set automatically to
the memorised position of the previous
air direction. (Initial setting is 60° for
heating and 30° for cooling.)
Thinner usually means noisier, but
Daikin's exclusive technology has
solved this.
FUY71FJ
Heat exchanger
Ultra-thin, quiet design made possible by new Flat Turbo Fan.
At heating startup and thermo OFF*, air direction is automatically set to
horizontal
Draft prevention (in heating)
Through use of a high-static-pressure
vane and a thorough reduction in flow
loss in the path between internal fan
suction and air output, we have achieved a thinner fan unit and quiet operation while maintaining airflow.
*When the thermos tat turns off.
Air direction can be selected according to installation
Selection patterns for air direction and fan speed ratio
Note: Applicable only to the flow configurations shown below.
Wireless LCD remote controller
*R equires sealing member for air disc harge
outlet (optional ac c essory) for opposing 2-
Moderate (approx. 70%)
dB(A)
2-way
flow
BRC1C61
Note: R emote c ontroller c able not
inc luded. C ables must be
proc ured loc ally.
Cooling only
BRC7C529W
Heat pump
BRC7C528W
Wireles s remote
c ontroller and
s ignal rec eiver unit
are s old as a s et.
Suitable for high ceilings
Two selectable temperature-sensors
Criteria for ceiling height and number of
air discharge outlets
Both indoor unit and wired remote controller (option) contain temperaturesensors. Temperature sensing can be
set at the unit or, to further improve
comfort level, closer to the target area
at the wired remote control.
Standard
3.5 m
3.8 m
—
Ceiling
High ceiling 1
height
High ceiling 2
3-Way
3-wayAirflow
Flow 4-Way
4-wayAirflow
Flow
3.0 m
3.3 m
3.5 m
2.7 m
3.0 m
3.5 m
Note: Initial s ettings are for s tandard c eiling
height and 4-way flow. High c eiling s ettings
1 and 2 are s et from the remote
Simply lock the body
in place with suspension bolts to install.
Adjustment is
smooth and simple,
too.
Dehumidification is microprocessor controlled to prevent abrupt and uncomfortable changes in air temperature.
Since the orientation of the intake grill can
be adjusted after installing, the direction of
the intake grill lines
can be unified when
multiple units are installed.
Accessible from below for easy
maintenance
(Features are explained on P. 37–38.)
Cooling only
Heat pump
17
Outer dimension drawings
P. 61
*1
*2
*4
*4
*1
*3
*4
*4
Control features
S elf-diagnos is func tion
E mergenc y operation
Low gas pres s ure
detec tion
Filter s ign
Long-life filter
Pre c harged for
up to 30 m
Work & Servicing
Drain pump mec hanis m
Mould-proofing
drain pan
Timer s elec tor
Year-round c ooling
applic able
Hot s tart
Two s elec table
temperature-s ens ors
High c eiling applic ation
S witc hable fan s peed
Draft prevention func tion
S wing pattern s elec tion
Auto-s wing
Mould res is tant treatment
for filter
Mould
prevention
Comfort
Feature
Model
Note: The panel cannot be
turned when the wireless
remote controller is in
use.
Low gas pressure detection
Programme "Dry"
Features
T-type hexagon wrench
Installable in any direction
Easier to maintain
* For dust concentration of 0.15 mg/m3
Hook
500 mm
Switchable fan speed: High/Low
Long-life filter lasts about 1 year *
Maintenance not required
Suspension bolt
Drain pump is equipped as
standard accessory with
500 mm lift.
*Temperature-sensor on indoor unit must be used
when the air c onditioner is c ontrolled from another
room.
**Wireless remote controller does not have a
Programme "Dry"
Options
P. 57
35
38
39
Simple installation procedure
Number of air discharge outlets used
Standard specifications
P. 40 and 50
40
43
44
Quick and easy to install
2-way flow
Remote controllers
P. 35–36
71FJ
Note : Anec hoic c hamber c onvers ion value,
meas ured ac c ording to J IS parameters and
Note: When 2- or 3-way flow configurations are selected, the unused flow outlets must be blocked off with the optional sealing
material. Sound during operation will rise by about 2 dB.
Outdoor units
P. 33–34
Low
125FJ
3-way
flow
4-way
flow
Guide Line up
P. 3–4, 7–8
High
100FJ
Piping
position
Signal receiver unit
(Installed type)
Indoor unit
*1Applic able when wired remote c ontroller is us ed
*3Applic able to R Y71LU– 125LU outdoor units (for temp. down to – 5°C )
*2Applic able to R 71LU– 125LU outdoor units (for temp. down to – 15°C*4)Applic able to R (Y)71LU– 125LU outdoor units
(An option is required.)
E xternal c ommand
c ontrol
C entral remote
c ontrol
A s ignal rec eiver mus t be
added to the indoor unit.
Standard (100%)
C ontrol by 1 remote
c ontroller
Wired LCD remote controller
C ontrol by 2 remote
c ontrollers
Flexibility in installation location.
Installation is also simple.
Accessory required for indoor unit (option)
Auto-c ooling/heating
c hange-over
Cooling only FUY71FJV1–125FJV1
Heat pump FUY71FJV1–125FJV1
Auto-res tart
FUY
Sliding shutter
Closes to moderate airflow (70%)
Others
PE fin
40/ 35
Interloc k c ontrol
CEILING
SUSPENDED CASSETTE
TYPE
18
CEILING MOUNTED CASSETTE CORNER TYPE
Sound level
41/ 36dB(A)
CEILING MOUNTED
CASSETTE CORNER
TYPE
High
Multiple airflow variations
for stepped or 3.8 m high ceilings
Low
1 Downward flow
FHYK71FJ
FHYK71FJ
Quiet operation
dB(A)
2 Downward flow + Forward flow
Indoor unit
High
Low
35F(J)
39
39
41
41
33
34
36
36
3 Forward flow
45F(J)
Airflow
variation
FH( Y) K
60F(J)
71F(J)
Note : Anec hoic c hamber c onvers ion value,
meas ured ac c ording to J IS parameters and
Auto-swing
Cooling only FH(Y)K35FV1–71F(J)V1
Heat pump FHYK35FJV1–71FJV1
Easier to install and service
High ceiling
installation
R equires ceiling tap cutting.
R equires ceiling tap cutting.
Air dis c harge grille, flexible duc t
Required options
Fits in ceiling corners.
Equipped for versatile
airflow control.
Accessory required for indoor unit
(option)
Wired LCD remote controller
Panel spacers (option) can be installed with all three airflow variations.
Decoration panels (option) to hide the downward air discharge opening can be installed with variation 3 above.
500 mm
E x a m ple in s t a lla t io n s
In the corner of a room
(downward flow)
Comfortable cooling from
ceiling to floor
(downward flow)
Wind speed profile
Heating (65° downward flow ... Standard installation)
BRC1C61
Note: R emote c ontroller c able not
inc luded. C ables must be proc ured
loc ally.
Drain pump is equipped as
standard accessory with
500 mm lift.
Not s uited for high c eilings
because air currents do not
(m)
3.8
3
2.0 m/s
1.5 m/s
1.0 m/s
0.5 m/s
0.3 m/s
1
1
2
3
4
* For dust concentration of 0.15 mg/m3
Low gas pressure detection
Fresh air intake possible
Air c onditioner
2.0 m/s
1.5 m/s
1.0 m/s
0.5 m/s
0.3 m/s
2
1
5
Long-life filter lasts about 1 year *
Maintenance not required
Wind speed profile
On stepped ceilings, downward flow
Heating (65° downward flow from high ceiling) can be blocked and outward flow alone
can be used to cool or heat the space.
3
2
On stepped ceiling
(Outward
(outward
+
downward flow)
6
(m)
1
2
3
4
5
(Site installation required)
A duct can be connected to the rear of the
indoor unit to draw in outdoor air.
C over here with
dec orative panel.
Dec orative panel
(s old s eparately)
Decorative panels (option) can be installed on the downward air discharge
opening to close gaps without stepped
room interiors.
6
K eep duc t no more than 5 m long.
Optimal comfort and convenience assured by three air discharge modes
Draft prevention setting
Air direction
When drafts are unwanted
Desired
situation
Auto-swing
5-levels
air direction
setting
Standard setting
Note: The maximum duc t length for c onnec tion to
the fres h air intake kit is 5 m. C onnec ting
duc ts , ins ec t nets , fire dampers , air filters ,
and other parts s hould, as required, be
Setting to prevent soiling of ceiling
For gentle drafts
(Ceiling is soiled.)
When ceilings must
be kept spotless
P a n e l s pa c e r ( o pt io n )
Auto-s wing between
0° and 65°
Auto-s wing between
0° and 65°
Auto-s wing between
0° and 65°
Settable to 5 different
levels between 0° and 65°
Settable to 5 different
levels between 30° and 65°
Settable to 5 different
levels between 40° and 65°
Use when only minimal space is
available between drop ceilings and
ceiling slabs.
20mm
C eiling
Panel s pac er
Draft prevention
(In heating)
model
At heating s tartup and thermo OFF*,
air dis c harge is automatic ally s et to
a near horizontal 10˚ to prevent direc t expos ure to c ool air drafts .
Upgrade options for easy
installation on stepped ceilings
Air dis c harge grille
The air direc tion is s et automatic ally to the memoris ed pos ition of the previous air direc tion. (Initial s etting is 65° for
heating and 30° for c ooling.)
Auto air
direction control
Flexible duc t
Note: Air direc tion is s et to the s tandard pos ition when the unit is s hipped from
the fac tory. The pos ition c an be c hanged from the remote c ontroller.
*When the thermos tat turns off.
Programme "Dry"
Dehumidification is microprocessor controlled to prevent
abrupt and uncomfortable changes in air temperature.
Cooling only
Heat pump
19
Guide Line up
P. 3–4, 7–8
Outdoor units
P. 33–34
Remote controllers
P. 35–36
Standard specifications
P. 40 and 50
Options
P. 58
Outer dimension drawings
P. 61
*1
*3
*3
*2
*3
*3
*1Applic able to R 71LU outdoor units (for temp. down to – 15°C ) (An option is required.)
*2Applic able to R Y71LU outdoor units (for temp. down to – 5°C )
*3Applic able to R (Y)71LU outdoor units
PE fin
Others
Interloc k c ontrol
C entral remote c ontrol
E xternal c ommand
c ontrol
C ontrol by 1 remote
c ontroller
Auto-c ooling/heating
c hange-over
C ontrol by 2 remote
c ontrollers
Auto-res tart
S elf-diagnos is func tion
Control features
E mergenc y operation
Low gas pres s ure
detec tion
C eiling s oiling prevention
Filter s ign
Long-life filter
Pre c harged for
up to 30 m
Work & Servicing
Drain pump mec hanis m
Timer s elec tor
Year-round c ooling
applic able
Hot s tart
High c eiling applic ation
Programme "Dry"
Draft prevention func tion
S wing pattern s elec tion
Mould res is tant
treatment for filter
Mould
prevention
Comfort
Auto s wing
Model
For outward blow, detach the punch-out
panel from the duct-connection port on
the front of the unit.
(Features are explained on P. 37–38.)
Feature
S witc hable fan s peed
Features
Switchable fan speed:
High/Low
20
CEILING MOUNTED BUILT-IN TYPE
Sound level
CEILING MOUNTED
BUILT-IN TYPE
41/ 35
High
Low
Flexibly adapts to shop interiors
dB(A)
Meets diverse of installation needs
To cope with the challenges of Lshaped or U-shaped spaces, it is possible to install the air discharge unit
away from the main unit. At the same
time, different types of architectural
space can be kept comfortable.
FHYB71F
FH( Y) B
The indoor unit can be installed in rooms with as little as 350 mm between the drop
ceiling and ceiling slab. It also works with both flexible and ordinary ducts.
S t a n d a r d in s t a lla t io n e x a m ple s
In crawl space
6
With canvas bellows and air intake panel (sold separately)
2 Air conditioner
4
2 Air conditioner
350 mm or more
4
6
5
1
Air blow
Cooling only FH(Y)B35FV1–125FV1
Heat pump FHYB35FV1–125FV1
425 mm or more
Long-life filter
Air intake Long-life filter
5
W it h h ig h -e ffic ie n c y filt e r
C e ilin g r e t u r n
2 Air conditioner
2 Air conditioner
Accessory required for indoor unit
(option)
Wired LCD remote controller
U-shaped space
Long space
4
13
6
540 mm or more
7
5
1
Air intake
Air blow
Air blow
C e iling re turn w ith high-e ffic ie nc y filte r
2 Air conditioner
6
4
9
11
7
W it h o r d in a r y d u c t s
Ordinary duct
(procured locally)
540 mm or more
Air intake
8
5
Options
1
dB(A)
Low
35F
38
39
41
41
41
44
32
34
35
35
35
38
60F
71F
100F
125F
2
4
3
Decorative panel
Air discharge opening adapter
Canvas bellows and air intake panel
Air intake
Air blow
5
High
6
7
8
Flexible duct
Air discharge grille
Air discharge chamber
High-performance filter
Inspection panel
Drain pump is equipped as
standard accessory with
250 mm lift.
250 mm
9
10
11
12
13
External static pressure can be
set depending on duct length,
presence of high-efficiency filter,
and other installation conditions.
Indoor unit
High
Standard
Low
35F–71F
78
98
39
39
20
100F and 125F
Fresh air intake possible
Easier to maintain
Note: The maximum duct length for connection to the fresh air
intake kit is 5 m. C onnecting ducts, insect nets, fire
dampers, air filters, and other parts should, as required,
Low gas pressure detection
Insufficient gas charging is normally
hard to detect. During post-installation
trials and regular inspection procedures,
the refrigerant level is monitored by
microprocessor to maintain proper gas
pressure.
Remote controllers
P. 35–36
Standard specifications
P. 41, 51
Options
P. 58
Outer dimension drawings
P. 62
H ig h -e ffic ie n c y filt e r ( o pt io n )
Available in two types: 65% and 90% colorimetry. This filter easily meets dust collection efficiency regulations specified in building codes.
Options have also been upgraded to make
installation even easier.
Air discharge opening adapter
Air
discharge
chamber
Air
Flexible duct
Flexible duct discharge
(dia. 200 mm)
(dia. 150 mm) grille
Canvas bellows Decorative panel
Branch duct
and air Intake panel
(Features are explained on P. 37–38.)
*1
*3
*3
*2
*3
*3
*1Applic able to R 71LU– R 125LU outdoor units (for temp. down to – 15°C ) (An option is required.)
*2Applic able to R Y71LU– R Y125LU outdoor units (for temp. down to – 5°C )
*3Applic able to R (Y)71LU– 125LU outdoor units
High-effic ienc y filter
Option Others
Interloc k c ontrol
E xternal c ommand
c ontrol
C entral remote
c ontrol
C ontrol by 1 remote
c ontroller
Auto-c ooling/heating
c hange-over
C ontrol by 2 remote
c ontrollers
Auto-res tart
Control features
S elf-diagnos is func tion
E mergenc y operation
Low gas pres s ure
detec tion
Filter s ign
Long-life filter
Pre c harged for
up to 30 m
Work & Servicing
Drain pump mec hanis m
Timer s elec tor
Year-round c ooling
applic able
Hot s tart
Programme "Dry"
S witc hable fan s peed
Mould res is tant
treatment for filter
Mould
prevention
Comfort
Feature
Outdoor units
P. 33–34
External static pressure is set to standard when the unit is shipped from the factory.
A duct can be connected to the rear of
the indoor unit to draw in outdoor air.
* For dust concentration of 0.15 mg/m3
Cooling only
Heat pump
(Pa)
(Custom installation required with locally
procured materials)
Long-life filter lasts about 1 year *
Maintenance not required
Model
Rear intake blocking pad
Air discharge opening flange
Rear intake filter chamber
Branch duct
Low-draft filter chamber
External static pressure pattern
Note : Anec hoic c hamber c onvers ion value,
meas ured ac c ording to J IS parameters and
Features
460 mm or more
9
8
Quiet operation
Indoor unit
Ordinary duct
(procured locally)
Air conditioner
10
Air blow
45F
8
5
Programme "Dry"
Switchable fan speed: High/Low
Note: R emote c ontroller c able not
inc luded. C ables must be proc ured
loc ally.
Air intake
Long-life filter
3
Dehumidification is microprocessor controlled to prevent abrupt and uncomfortable changes in air temperature.
BRC1C61
450 mm or more
4
6
PE fin
Clever and compact
mini ducted unit provides
comfort and flexibility.
Guide Line up
P. 3–4, 7–8
1
Air intake
Air blow
45 mm
L-shaped space
21
3
22
WALL MOUNTED TYPE
Sound level
43/ 37dB(A)
WALL MOUNTED
TYPE
High
Drastic size reduction
Low
FAY71L
FAY
Sound level
45/ 41
High
Low
Auto-swing
Reduced size (by 22% in volume,
32% in installation area)makes
installation possible in a very limited
Conventional model
space.
FAY71LVE
Cooling only FAY71LVE / FAY100FAVE
Heat pump FAY71LVE / FAY100FAVE
Improved airflow modes realise comfortable air distribution across the entire room
Below features only apply to FAY71L.
5-level air direction setting
10°
10°
10°
(FAY71FAVE)
Auto-s wing
from 10° to 70°
-70 mm
dB(A)
-200 mm
S ettable to 5
different levels
between 10° to 70°
70°
290 mm
FAY100FA
Auto-air direction control
70°
The air direction is set automatically
to the memorised position of the
previous air direction.
(Initial setting is 10° for cooling 70°
and 70° for heating.)
Comfort even on the far side of the room
To carry air to the far side of long rooms, extrahigh airflow adds 10% more fan speed the "high"
setting. Air discharge strength is selected from the
remote controller.
1,050 mm
Made more compact,
stylish, and quieter
Sophisticated extension design
FAY100FAVE
Accessory required for indoor unit (option)
Wired LCD remote controller
Wireless LCD remote controller
A s ignal rec eiver mus t be
added to the indoor unit.
Signal receiver unit
(Installed type)
Compact and stylish design that does
not detract from the decor of the room.
Two selectable temperature-sensors
Flap is closed when not operating
Easier to install and service
Cooling only
Light weight
BRC7E619
Heat pump
BRC7EA618
BRC1C61
FAY71L
Cooling only
BRC7C611W
Heat pump
Note: R emote c ontroller c able not
inc luded. C ables must be
proc ured loc ally.
BRC7C610W
FAY100F
Wireles s remote c ontroller and s ignal
rec eiver unit are s old as a s et.
Reduced weight by 8kg greatly
facilitates installation.
Conventional
New model
(FAY71FAVE)
(FAY71LVE)
21 Kg
13 Kg
Easier to install and service
Both indoor unit and wired remote
controller (option) contain temperaturesensors. Temperature sensing can be
set at the unit or, to further improve
comfort level, closer to the target area
at the wired remote control.
Maintenance possible from
the front of the unit
All maintenance tasks can be carried
out via front access. During service
work, attachment and detachment of
parts is easier.
*Temperature-sensor on indoor unit must be used
when the air c onditioner is c ontrolled from another
room.
**Wireles s remote c ontroller does not have a
Low gas pressure detection
Insufficient gas charging is normally
hard to detect. During post-installation
trials and regular inspection procedures,
the refrigerant level is monitored by
microprocessor to maintain proper gas
pressure.
Programme "Dry"
Drain pump kit is available as option.
Dehumidification is microprocessor
controlled to prevent abrupt and
uncomfortable changes in air temperature.
Installs onto side of unit.
Height of drain up
Switchable fan speed: High/Low
1,000 mm
Indoor unit
Drain-pump kit
(Available to be installed onto right side.)
Drain enclosure can
be used on either
left and right side.
Drain pan and air filter can be kept
clean by mould-proof polystyrene
Removable and washable grille
DIII-NET connection is standard
specification. Adapter is not required.
(Features are explained on P. 37–38.)
Cooling only
Heat pump
23
Guide Line up
P. 3–4, 7–8
Outdoor units
P. 33–34
Remote controllers
P. 35–36
Standard specifications
P. 41, 51
Options
P. 58
Outer dimension drawings
P. 62, 63
*1Applic able
*2Applic able
*3Applic able
*4Applic able
*1
*2
*4
*4
*1
*3
*4
*4
PE fin
Others
Interloc k c ontrol
C entral remote c ontrol
E xternal c ommand
c ontrol
C ontrol by 2 remote
c ontrollers
C ontrol by 1 remote
c ontroller
Auto-c ooling/heating
c hange-over
Auto-res tart
Control features
S elf-diagnos is func tion
E mergenc y operation
Low gas pres s ure
detec tion
Filter s ign
Pre c harged for
up to 30 m
Work & Servicing
Drain pump mec hanis m
Mould-proofing
drain pan
Mould res is tant
treatment for filter
Timer s elec tor
Year-round c ooling
applic able
Hot s tart
Upward
Two s elec table
temperature-s ens ors
Programme "Dry"
S witc hable fan s peed
Draft prevention func tion
Auto s wing
Model
Mould
prevention
Comfort
Feature
High fan s peed mode
Features
when wired remote c ontroller is us ed
to R 71LU/R 100LU outdoor units (for temp. down to – 15°C ) (An option is required.)
to R Y71LU/R Y100LU outdoor units (for temp. down to – 5°C )
to R (Y)71LU/100LU outdoor units
24
FLOOR STANDING TYPE
Sound level
FLOOR STANDING
TYPE
41/ 35
High
Low
Quiet operation
dB(A)
Easier to install and service
dB(A)
FVY71LA
FVY
Indoor unit
High
Low
71LA
41
46
49
35
40
43
100LA
125LA
Lightweight
The unit can be easily transported and
installed.
Note : Anec hoic c hamber c onvers ion value,
meas ured ac c ording to J IS parameters and
Weight
Auto-swing delivers comfort to every corner of the room
Cooling only FVY71LAVE–125LAVE
Heat pump FVY71LAVE–125LAVE
The floor-standing
configuration means
the FVY is easy to install
and maintain.
It can also be installed
under high ceilings.
Conventional
FVY-F
New model
71 class
45 kg
63 kg
67 kg
39 kg
46 kg
47 kg
100 class
FVY units have swinging louver spreads comfortable airflow. Any uncomfortable
sensation of sudden change is avoided by a slow cycle of 2 to 3 full swings per
minute.
125 class
Manual setting of vertical airflow louvers
Auto-swing
Indoor unit
Long-life filter lasts about 1 year *
Maintenance not required
*For dust concentration of 0.15 mg/m3
LCD control panel is standard
Filter exchange interval
Vertical airflow adjustment is possible when
(changing between cooling and heating or) to
match interior spaces and partitions.
Note: This remote controller has a temperaturesensor.
A good choice for spaces with
ceilings so high that heating by
ceiling-mounted units is inefficient.
Annual
Long-life filter
Low gas pressure detection
Insufficient gas charging is normally
hard to detect. During post-installation
trials and regular inspection procedures,
the refrigerant level is monitored by
microprocessor to maintain proper gas
pressure.
Programme "Dry"
Dehumidification is microprocessor controlled to prevent abrupt and uncomfortable changes in air temperature.
Note: For optimal installation, space factors should be
accurately calculated.
2 weeks
Conventional
filter
Switchable fan speed: High/Low
Easy-to-operate, handy LCD control panel
The LCD displays text, numbers and graphics to indicate the temperature setting,
timer setting, auto-swing, fan speed, and more. Furthermore, the LCD panel can
be detached and used as a remote controller, so air conditioning can be controlled
from another room or from the cash register.
(Remote controller cable not included. Cables must be procured locally.)
Two selectable temperature-sensors
Temperature-sensors on both indoor unit and wired remote controller.
Temperature sensing can be set closer to the target area to further improve
comfort level.
*Temperature-sensor on indoor unit must be used when the air c onditioner is c ontrolled from another room.
**Wireles s remote c ontroller does not have a temperature-s ens or.
(Features are explained on P. 37–38.)
Cooling only
Heat pump
25
Guide Existing
Line up models:
P.33–4,
P.
~ 4 7–8
Outdoor units
units:
P.25
P.
33–34
~ 26
Remote controllers
controllers:
P.27
P.
35–36
~ 28
Standard specifications
specifications:
P.34
P.
42, 52
Options Outer dimension drawings
Options:
drawings:
P.36
P.
58~ 37 P.
P.38
63~ 45
*1
*3
*3
*2
*3
*3
*1Applic able to R 71LU– R 125LU outdoor units (for temp. down to – 15°C ) (An option is required.)
*2Applic able to R Y71LU– R Y125LU outdoor units (for temp. down to – 5°C )
*3Applic able to R (Y)71LU– 125LU outdoor units
PE fin
Others
Interloc k c ontrol
C entral remote c ontrol
E xternal c ommand
c ontrol
C ontrol by 1 remote
c ontroller
C ontrol by 2 remote
c ontrollers
Auto-c ooling/heating
c hange-over
Auto-res tart
Control features
S elf-diagnos is func tion
E mergenc y operation
Low gas pres s ure
detec tion
Filter s ign
Long-life filter
Work & Servicing
Pre c harged for
up to 30 m
Mould res is tant
treatment for filter
Timer s elec tor
Two s elec table
temperature-s ens ors
Year-round c ooling
applic able
Hot s tart
S witc hable fan s peed
Auto s wing
Model
Mould
prevention
Comfort
Feature
Programme "Dry"
Features
26
DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE
Sound level
DUCT CONNECTION
MIDDLE STATIC PRESSURE TYPE
39dB(A)
Freedom of layout
(220V)
High
LOW
FDMG71A
42
44
45
46
47
38
36
37
36
37
FDMG125A
FDMG140A
Duct connection is simpler with standard rear intake chambers
FDMG180A
FDYM03FA
FDYM03FAV1–06FAV1
FDYM03FAV1–06FAV1
FDYM04FA
Compact, 295 mm high design makes installation possible where the
ceiling space is limited (For FDYM)
FDYM05FA
FDYM06FA
FDYM03FA
Unit can be mounted
in the ceiling and air can be
delivered freely by duct.
Indoor unit
FDMG100A
Middle static pressure type is available in a larger than standard space
FDMG100A
Cooling only FDMG71AV1–180AV1
Heat pump
dB(A) (220V)
The duct system allows the efficient location of discharge outlets
in accordance with the room layout
High
FDYM03FA
FDMG/FDYM
Quiet operation
Note : Anec hoic c hamber c onvers ion value,
meas ured ac c ording to J IS parameters and
Air conditioner
295 mm
Ordinary duct
(procured locally)
Ordinary duct
(procured locally)
Accessory required for indoor unit (option)
For FDYM
Wired LCD remote controller
Wireless LCD remote controller
Switchable fan speed: High/Low
305 mm or more
Air intake
Air blow
39
39
44
46
Programme "Dry"
Dehumidification is microprocessor
controlled to prevent abrupt and uncomfortable changes in air temperature.
BRC1C61
Note: R emote c ontroller c able not
inc luded. C ables must be
proc ured loc ally.
Signal receiver unit
(Separate type)
Cooling only
BRC4C64
Heat pump
BRC4C62
For FDMG
Digital remote controller
Wireles s remote
c ontroller and
s ignal rec eiver unit
are s old as a s et.
Remote controller
KRC47-2A
KRC47-4A
Low gas pressure detection
Insufficient gas charging is normally
hard to detect. During post-installation
trials and regular inspection procedures,
the refrigerant level is monitored by
microprocessor to maintain proper gas
pressure.
Supports simultaneous running of the twin and
triple multi operations.
Twin Multi Operation
Triple Multi Operation
KRC47-1A
See pages 31–32 for details of the Multi Series.
Simultaneous air conditioning of two rooms and ventilation grille (ventilation opening)
When air conditioning two rooms
simultaneously, the air discharged into each
room must be circulated back to the air
conditioner. To achieve this, a ventilation
duct should be installed for each room or one
of the indicated ventilation grilles should be
installed on the partitioning wall or under the
door between the rooms.
27
Guide Line up
P. 3–10
Outdoor units
P. 33–34
Remote controllers
P. 35–36
Standard specifications
P. 43, 48, 53, 56
Options
P. 59
Outer dimension drawings
P. 64, 65
Under-door cutout
Ventilates air through
the partitioning wall.
(S ee right)
Partitioning wall
Ventilation grille
Ventilation grille
Under-door c utout
Note: The under-door cutout method should be used only when there is a small volume of airflow.
Adjus table external
s tatic pres s ure
PE fin
Twin and triple multi
operation
Others
Interloc k c ontrol
E xternal c ommand
c ontrol
C entral remote
c ontrol
G roup c ontrol by 1 remote
c ontroller
C ontrol by 2 remote
c ontrollers
*3
Control features
Auto-res tart
*3
*3
S elf-diagnos is func tion
*3
*2
E mergenc y operation
*1
Timer s elec tor
Low gas pres s ure
detec tion
Year-round c ooling
applic able
Work & Servicing
Pre c harged for
up to 30 m
Heat pump
FDMG
FDYM
Programme "Dry"
S witc hable fan s peed
Model
Automatic c ool/heat
c hange -over
Comfort
Feature
Cooling
only
Wall-installed
ventilation grille
(Features are explained on P. 37–38.)
Hot s tart
Features
Door-installed
ventilation grille
*1Applic able to R 71LU– R 140LU outdoor units (for temp. down to – 15°C ) (An option is required.)
*2Applic able to R Y71LU– R Y140LU outdoor units (for temp. down to – 5°C ) and R Y200LU– R Y250LU outdoor units (for temp. down to – 0°C )
*3Applic able to R (Y)71LU– 140LU outdoor units
28
Sound level
Sound level
DUCT CONNECTION
LOW STATIC PRESSURE TYPE
DUCT CONNECTION
HIGH STATIC PRESSURE TYPE
38
dB(A)
LOW
FDBG/FDYB
FD( Y)
FDYB50KA
(220V)
FDYB50KA
Cooling only FDBG25AVE–71AVE
Heat pump FDYB35KAVE–71KAVE
Accessory required for indoor unit (option)
51
dB(A)
High
FDY06KA
FDY06KA
Cooling only FD03KY1–20KY1
Heat pump FDY06KAY1–20KAY1
Accessory required for indoor unit (option)
Cooling only
Cooling only
Digital remote controller
Remote controller
Remote controller
KRC47-2A
KRC47-4A
KRC47-1A
KRC47-3A
Heat pump
Heat pump
Wired LCD remote controller
Wired LCD remote controller
Signal receiver unit
(Separate type)
BRC1C61
Note: R emote c ontroller c able not
inc luded. C ables must be
proc ured loc ally.
BRC4C62
Note : Anechoic chamber conversion value,
measured according to J IS parameters and criteria.
Highly durable outdoor unit has PE fins for improved
resistance to salt corrosion and atmospheric pollution.
Durable
S uc tion c hamber
29
Adjus table external
s tatic pres s ure
PE fin
Triple and double twin
multi operation
*2
* Applic able to R Y71LU outdoor units (for temp. down to – 5°C )
and R Y200LU– R Y250LU outdoor units (for temp. down to – 0°C )
*2Applic able to R Y71LU outdoor units
Guide Line up
P. 3–10
*2
Outdoor units
P. 33–34
Remote controllers
P. 35–36
Adjus table external
s tatic pres s ure
PE fin
Simultaneous air conditioning of two rooms and ventilation grille (ventilation opening)
1
*1
Others
*2Applic able to R (Y)140LU outdoor units
*3R equired to c hange the pulley
*4FDY06-10 only
Others
Interloc k c ontrol
C entral remote
c ontrol
G roup c ontrol by 1 remote
c ontroller
E xternal c ommand
c ontrol
C ontrol by 2 remote
c ontrollers
Control features
Auto-res tart
S elf-diagnos is func tion
E mergenc y operation
Low gas pres s ure
detec tion
Pre c harged for
up to 30 m
Timer s elec tor
Work & Servicing
Year-round c ooling
applic able
Automatic c ool/heat
c hange -over
Programme "Dry"
S witc hable fan s peed
Hot s tart
Comfort
Control features
Interloc k c ontrol
Hot s tart
(Features are explained on P. 37–38.)
Feature
Cooling only
Heat pump
See pages 31–32 for details of the Multi Series.
Work & Servicing
C entral remote
c ontrol
Double twin Multi Operation
Guide
Line up
P. 3–4, 7–8
Outdoor units
P. 33–34
Remote controllers
P. 35–36
Standard specifications
P. 44, 45, 53
Model
Options
*3
Cooling only
P. 59
*4
*1
*2
*2
*4
*3
Heat pump
Outer dimension drawings
*1Applic able to R Y140LU outdoor units (for temp. down to – 5°C ) and R Y200LU– R Y250LU outdoor units (for temp. downP.
to 65–67
– 0°C )
Comfort
Feature
G roup c ontrol by 1 remote
c ontroller
E xternal c ommand
c ontrol
Triple Multi Operation
(Features are explained on P. 37–38.)
C ontrol by 2 remote
c ontrollers
To prevent increased operation sound, avoid installing the air suction grille
directly below the suction chamber.
Auto-res tart
[Duc t c onnec tion]
Supports
simultaneous
running of the
triple and double
twin multi
operations.
Model
Features
Air filter
S elf-diagnos is func tion
To achieve increased durability by improved resistance
to salt corrosion and atmospheric pollution, coated PE
fins (with special acryl pretreatment) are used for the
heat exchanger of the outdoor unit.
Features
Many options are available for use with large-scale and
advanced-function centrally controlled systems
Durable
E mergenc y operation
39
BRC4C62
Wireles s remote
c ontroller and
s ignal rec eiver unit
are s old as a s et.
Central control
Low gas pres s ure
detec tion
42
Quiet operation
Pre c harged for
up to 30 m
FDBG60AVE
Small, lightweight, and easy-to-install outdoor unit.
Timer s elec tor
Low
Year-round c ooling
applic able
High
Automatic c ool/heat
c hange -over
Indoor unit
Note: R emote c ontroller c able not
inc luded. C ables must be
proc ured loc ally.
Recommended for spacious and large-volume areas because of its flexible installation
Suitable for large stores, factories, and other large areas, and for use with housing
ducts in homes
Compact
dB(A)
Signal receiver unit
(Separate type)
BRC1C61
Wireles s remote
c ontroller and
s ignal rec eiver unit
are s old as a s et.
Ideal for quiet, beautiful living spaces
Suitable for condominiums and apartments, houses and hotels
Quiet operation
Wireless LCD remote controller
Wireless LCD remote controller
Standard specifications
P. 42, 52, 56
Options
P. 59
Outer dimension drawings
P. 64
When air conditioning two rooms
simultaneously, the air discharged into each
room must be circulated back to the air
conditioner. To achieve this, a ventilation
duct should be installed for each room or one
of the indicate ventilation grilles should be
installed on the partitioning wall or under the
door between the rooms.
Door-installed
ventilation grille
Partitioning wall
Wall-installed
ventilation grille
Under-door cutout
Ventilates air through
the partitioning wall.
(S ee right)
Ventilation grille
Ventilation grille
Under-door c utout
Note: The under-door cutout method should be used only when there is a small volume of airflow.
30
Simultaneous operation system
MULTI SERIES
Simultaneous operation system
Remote controllers for the Multi Series
MULTI SERIES
INDOOR UNIT
Wired LCD remote controller
Wireless LCD remote controller
(Option)
(Option)
Twin, Triple, and Double Twin Multi-Operation
CEILING MOUNTED
CASSETTE TYPE
Heat pump
BRC7EA66
BRC7E63W
Heat pump
BRC4C62
Cooling only
BRC4C64
BRC4C62
Cooling only
BRC1C61
DUCT CONNECTION
LOW STATIC PRESSURE TYPE
DUCT CONNECTION
MIDDLE STATIC PRESSURE TYPE
In a single-floor restaurant, for example, positioning 4 units at
strategic locations realises comfortable airflow that reaches
every inch of the room.
In large interior spaces a single indoor unit
may not be able to provide uniform comfort.
Installation of 2 to 4 units, can provide an
effective solution.
Heat pump
CEILING SUSPENDED TYPE
Simultaneously operates
2 to 4 indoor units using
a single outdoor unit.
BRC7C613W
BRC7C612W
Cooling only
Heat pump
A single remote controller
controls simultaneous
operation of multiple indoor units.
Connect the wired remote controller
to turn an indoor unit into the master
unit.
Install the signal receiver unit (part
of the optional wireless remote
controller) to turn an indoor unit into
the master unit.
Supports Two selectable
temperature-sensor functions.
Wired remote controller has a
temperature-sensor. Depending on
the installation conditions, select
and set the temperature-sensor of a
selected indoor unit or the temperaturesensor of the remote controller.
Because the wireless remote
controller does not have a
temperature-sensor, select the
temperature-sensor of the indoor
master unit.
Note: This type of system does not allow individual control or independent operation of indoor
units. It is not the best choice for large rooms with partitions.
Installing multiple units is economical and realises comfort
Lower cost of installation than for individual pair type
Reduced installation space for outdoor units
Enhanced comfort from distributed indoor units
Note: Selectable temperature sensing is available
with ceiling-mounted cassette and ceilingsuspended models, but not with middle staticpressure models.
Note: An indoor unit's temperature-sensor must
be used when the air conditioners
are controlled from another room.
Indoor units include ceiling mounted cassette type, ceiling suspended type, and duct connection middle and low static pressure type.
Double Twin Multi operation
4 indoor units can be run simultaneously
with a single outdoor unit.
Improved comfort level and space-saving
for outdoor unit installation
New
5 HP x 2 units
10 HP double twin multi operation
Twin Multi Operation
Triple Multi Operation
Sub
unit
Dead zone
Dead zone
Before
Piping Guideline
Branch
piping kit
L1
Branch piping kit
Branch piping kit
Required about 40% less installation space
for outdoor unit
Before
Sub
unit
L2
Branch
piping kit
Sub
unit
Main
unit
L3
L3
Outdoor unit
L4
Sub
unit
L5
L1
Branch
piping kit
Remote
controller
Main pipe
L
Sub
unit
L6
L2
Remote
controller
Main pipe
L
Outdoor unit
Outdoor unit
300 mm
R(Y)200KU or R(Y)250KU x 1 unit
500 mm
Simultaneous operation system
Max. piping length
Max. branch piping length
300 mm
1000 mm
Max. branch pipe length difference
Twin Multi Operation
L
Max. (L1, L2)
Max. (L1, L2)*1
Max. (L1, L2)
50 m
20 m
Min. (L1, L2)*2
Triple Multi Operation
Double Twin Multi Operation
L
L
Max. (L1, L2, L3)
Max. (L1, L2 , L3)
10 m
Max. (L1, L2, L3)
50 m
20 m
Min. (L1, L2, L3)
10 m
Max. (L1, L2)
Max. (L3, L4, L5, L6)
Max. (L1, L2)
Max. (L3, L4, L5, L6)
(L2 L6)
(L1 L3) 10 m
L2 L1 10 m
L4 L3 10 m
L6 L5 10 m
In case of L1
Triple Multi operation
Main
unit
New
R(Y)125KU x 2 units
4 indoor units distribute comfortable airflow
throughout the room.
Simultaneous operation of four indoor units
can be controlled from a single remote controller.
Requires a single refrigerant piping system.
L1
Remote
controller
Main pipe
L
Branch piping kit
Sub
unit
Main
unit
L2
Double Twin Multi Operation
Twin Multi operation
L2, L3
Max. level difference between outdoor unit and indoor units
30 m
30 m
30 m
Max. level difference between indoor units
0.5 m
0.5 m
0.5 m
L4, L5
50 m
20 m
L6
*1 Max. (L1, L2) means maximum length out of L1 and L2.
*2 Min. (L1, L2) means minimum length out of L1 and L2.
Refrigerant piping uses terminal branching to facilitate installation.
(Branch piping kits are sold separately. Please use the model indicated on page 59)
Branch piping kit
Branch piping kit
31
Guide Line up
P. 5–6, 9–10
Outdoor units
P. 33–34
Remote controllers
P. 35–36
Standard specifications
P. 46–48, 54–56
Options Outer dimension drawings
P. 57–59 P. 60–74
(For Twin Multi)
(For Triple Multi)
(For Double Twin Multi)
32
OUTDOOR UNIT
OUTDOOR UNIT
Compact unit provides
quiet operation.
P o w e r fu l
Ins ta lla tion a nd ma intena nc e
Uses "Receiver"
to enhance refrigerant control
Pre charged for up to 30 metres
(Applies to R(Y)71LU–140LU)
Instead of the using an accumulator to absorb excess refrigerant, Daikin outdoor
units have a receiver in the piping located
away from the compressor. By preventing
the return of liquid to the compressor, the
receiver enhances reliability.
Defrost control delivers powerful
heating in extremely cold climates
(Applies to RY71LU–140LU) (Heat pump only)
R(Y)125LU
R(Y)140LU
Q u ie t O pe r a t io n
Fitted with wide inlet fan
Fitted with Super Aero Grille
(Applies to R(Y)71LU–140LU)
(Applies to R(Y)71LU–140LU)
Fully shaped aerodynamic propellers
are designed to push air with a large
wing surface, providing both high
blow volume and quiet operation with
turbulence.
To suppress turbulence and achieve
quiet operation, the curved ribs of the
grille are optimised to meet the
outflow of air.
Equipped with scroll compressor
for quiet operation
(Applies to R(Y)125LU and 140LU)
Smooth running, minimal vibration,
low operating sound.
Integral heating capacity and temperature difference
(actual measurement when outdoor temperature is -1.5°C)
25
°C
Defrost begins
in this area
Integral heating
capacity
20
15
10
5
Max. point of
integral capacity
R(Y)100LU
Defrost and hot start
R(Y)71LU
To optimise heating performance, by
monitoring the difference in air temperature
in the indoor/outdoor heat exchanger and
the intake air temperature, the system
accurately adjusts to provide the best
operating parameters.
This enables defrost mode to be initiated
and so minimise indoor declines in
temperature caused by frost. For example, if
the outdoor airtemperature falls to -1.5°C,
the integrated heating capacity is raised
about 20%.
0
0
10
20
30
Difference between
indoor heat exchange
temperature and intake
air temperature ( T)
40
50
60
70
80
Elapses operation time (min.)
Defrost operation complete Defrost monitoring start
(heating operation restart) (monitors to maximum point)
Suited for year-round cooling
applications
Wide inlet fan
Operation sound
(Applies to R(Y)71LU–140LU)
dB(A)
Heat pump
Outdoor unit
Sound level (cool/heating)
RY71LU
48/49
Slim and low-profile design outdoor units
RY100LU
49/52
(Applies to R(Y)71LU–140LU)
RY125LU
49/52
RY140LU
54/56
Cooling only
Outdoor unit
Sound level
R71LU
48
(Applies to R(Y)71LU-125LU)
R100LU
49
The light weight makes delivery and
installation easier.
R125LU
49
R140LU
54
C o m pa c t
Compactly designed outdoor unit
with interior layout optimised for the
smooth airflow.
Reduced weight
conventional
New
108 kg
89 kg
RY100KUV1
RY100LUV1
The design curved Super Aero
Grille restricts the spread of
exhaust gas and fits in the same
space as conventional outdoor
units.
50
500
(mm)
33
Note : Anec hoic c hamber c onvers ion value,
meas ured ac c ording to J IS parameters and
Cooling is efficient even in winter when
indoor temperatures are higher than those
outside, such as in underground public spaces
or offices with many computers.
If refrigerant piping length does not
exceed 30 m, there is no need for onsite gas charging.
(Applies to R(Y)71LU–140LU)
Flexible design
for large room
or multi-use
Allowed refrigerant pipe length and
level difference
Pre charged
*1
Max. length
Max. level
difference
R25J
10 m
25 m
15 m
RY35F
10 m
20 m
15 m
R35J
RY50GA
R50G
RY60GA
R60G
RY71LU
R71LU
RY100LU
R100LU
RY125LU
R125LU
RY140LU
R140LU
RG71A
RA140A
RG180A
R100FU
R125FU
10 m
25 m
15 m
10 m
30 m
15 m
5m
30 m
15 m
30 m
50 m
30 m
50 m
30 m
50 m
30 m
50 m
30 m
50 m
30 m
50 m
30 m
30 m
30 m
(Equivalent length 70 m)
(Equivalent length 70 m)
(Equivalent length 70 m)
30 m
(Equivalent length 70 m)
5m
(Equivalent length 70 m)
5m
(Equivalent length 70 m)
Piping can be drawn out from three
directions - front, left side, or below.
200 and 250 class models can
be combined for centralised,
horizontal-series installation
1
Note: Additional refrigerant charging is required if the
refrigerant pipe is longer than the length.
Common width and depth make
series installation easy.
4-direction piping offers
greater layout freedom
R(Y)200KU R(Y)200KU R(Y)250KU
(Applies to R(Y)71LU–140LU)
Piping can be run from the front,
bottom, right or rear surface
according to how the unit is installed.
690 mm
1280 mm
1280 mm
1280 mm
Allowed refrigerant pipe length and
level difference
Facilitates pump down
(Refrigerant recovery function)
A pump-down switch is provided to
make it easier to collect refrigerant if
the unit is to be moved or layout
modified.
Pre charged
*1
Max. length
Max. level
difference
5m
50 m
30 m
50 m
30 m
R(Y)200KU
R(Y)250KU
5m
(Equivalent length 70 m)
(Equivalent length 70 m)
Note: 1Additional refrigerant charging is required if the
refrigerant pipe is longer than the length.
Also adapts to year-round cooling
Low gas level detection function
(Applies to R(Y)71LU–140LU)
Effective gas monitoring reduces the
labor required for operation,
maintenance, and repairs.
RY200K U and250KU can adapt up to 0°C.
(Heat pump only)
RU08/10K models are available
in two type depending on
installation conditions
• Heat pump/RY71–140LU: possible up to -5°C
• Cooling only/R71–140LU: possible up to -15°C
• The year-round cooling kit is required as option.
RU08/10KU models are factory
shipped with refrigerant charged for
5 m of piping.
RU08/10K models are factory
shipped with no refrigerant charged.
D u r a bilit y
Heat exchange fins provided with anti-corrosion treatment
To achieve increased durability by
improved resistance to salt corrosion
and atmospheric pollution, coated PE
fins (with special acryl pretreatment)
are used for the heat exchanger of the
outdoor unit.
(Applies to all outdoor units)
Construction
Non-treated fin
Aluminium
PE fin
Hydrophilic film
Aluminium
C orrosion resistant
ac rylic resin
34
LCD REMOTE CONTROLLER
Easy-to-read LCD remote
controller allows various system
control configurations and can
control multiple indoor units.
LCD REMOTE
CONTROLLERS
Necessary optional accessory
Remote controller options are shown on the page introducing each indoor unit model.
Wired LCD remote controller
W ir e d r e m o t e c o n t r o lle r h a s bu ilt -in
t e m pe r a t u r e -s e n s o r (Applies to wired remote controllers)
Easier to read because LCD screen is larger.
For easier operation, louver switches, which are frequently
used, have been made larger.
Oil-resistant plastic casing.
Only 17 mm thick. Can be installed either recessed or
exposed.
Indoor units applicable for the remote controller
CEILING MOUNTED CASSETTE TYPE
CEILING SUSPENDED TYPE
CEILING SUSPENDED CASSETTE TYPE
CEILING MOUNTED CASSETTE CORNER TYPE
WALL MOUNTED TYPE
CEILING MOUNTED BUILT-IN TYPE*1
DUCT CONNECTION LOW STATIC PRESSURE TYPE *2
DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE
DUCT CONNECTION HIGH STATIC PRESSURE TYPE *2
BRC1C61
BRC1C61
*1. When the auto-swing function is not available, the message,
THIS FUNCTION IS NOT AVAILABLE is displayed when
the wind direction adjustment button is pressed.
*2. Applicable to only heat pump type.
Wired LCD remote controller with weekly schedule timer
Remote control is equipped with weekly timer function.
24-hour clock function (1-hour backup for power failures)
Programming function for each day of week.
Scheduling possible of start/stop and temperature limit (5
settings/day)
Programming can be enabled or disabled.
Copy function for programmed schedules.
Indoor units applicable for the remote controller
CEILING MOUNTED CASSETTE TYPE
CEILING SUSPENDED TYPE
CEILING SUSPENDED CASSETTE TYPE
CEILING MOUNTED CASSETTE CORNER TYPE
WALL MOUNTED TYPE
CEILING MOUNTED BUILT-IN TYPE*1
DUCT CONNECTION LOW STATIC PRESSURE TYPE *2
DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE
DUCT CONNECTION HIGH STATIC PRESSURE TYPE *2
BRC1D61
BRC1D61
*1. When the auto-swing function is not available, the message,
THIS FUNCTION IS NOT AVAILABLE is displayed when
the wind direction adjustment button is pressed.
*2. Applicable to only heat pump type.
•Standard remote controller (BRC1C61) is not required.
•If the BRC1D61 is connected to the centralised remote controller,
the schedule function is not available.
Wireless LCD remote controller
signal receiver mounted type
The wireless remote controller is supplied in a set
with a signal receiver.
Shape of signal receiver unit differs according to
the indoor unit.
Note: The signal rec eiver unit shown in the
photograph is for mounting inside the
dec oration panel of the c eiling mounted
assette
type.
Indoor cunits
applicable
for the remote controller
Signal receiver unit
(For ceiling mounted
cassette type)
Wireless remote controller
35
Enables temperature sensing closer to target
area for improved comfort. (When using remote
control from another room, temperature-sensor
in indoor unit's air inlet must be selected.)
Note: The indoor unit’s temperature-sensor is specified at the time of
shipment. Temperature sensing with the wired remote controller is not
available with the ceiling mounted cassette corner, ceiling-mounted
built-in, and duct connection type.
L C D pa n e l s h o w s o pe r a t in g s t a t u s in le t t e r s , n u m be r s , a n d m o t io n .
Airflow / swing display
(Not available for ceiling mounted built-in type and duct connection type )
Preset temperature / operation mode display
Programming time display
Self-diagnosis function
Setting contents: High ceiling use, air direction, filter type,
address for centralised control (group control address is
set automatically).
Control by 1
remote controller
Wired remote controller
Wireless remote controller
(Basic system)
Non-polar, double-c ore
(max. wiring length 500 m)
Control by 2
remote controllers
Group control
S ignal rec eiver unit ins talled
on indoor unit
C ontrol by 1 wireles s remote
c ontroller and 1 wired remote
c ontroller (S ee note 1)
For control from 2
locations such as in
room and control room,
exits, etc.
S ignal rec eiver unit ins talled
on indoor unit
C onnec ts 2 wired
remote c ontrollers
For simultaneous
control of up to 16
indoor units.
Automatic addres s s etting func tion
Automatic addres s s etting func tion
S ignal rec eiver unit ins talled
on 1 indoor unit
Control by
external command
Operation and surveillance is
carried out using the contact
signal from the operation
control box in the building
surveillance (security) room.
(C ommand from outs ide)
(C ommand from outs ide)
Optional wiring adaptor for
elec tric al appendic es is nec es s ary
Optional wiring adaptor for
elec tric al appendic es is nec es s ary
C entral remote c ontroller (option)
Centralised remote
control
Remote controller is equipped with model name
and failure display functions. This facilitates
service in the unlikely event of a malfunction.
S k y A ir s h a r e s c o m m o n c o n t r o l w it h
H R V (h e a t r e c la im v e n t ila t io n ) a n d
t h e o t h e r D a ik in a ir -c o n dit io n in g
u n it s , t h u s s im plify in g in t e r lo c k in g
o pe r a t io n s .
Operation start and stop time can be set for individual timers up to 72 hours. The liquid crystal display also shows
when it is time to clean the filter, when changeover is under centralised control, and ventilation/cleaning.
Monitors operating status within the system covering 40 items, and displays a message to indicate as soon as a malfunction occurs.
Control pattern
F a c ilit a t e s m a in t e n a n c e a n d r e pa ir
All initial settings can be set from the remote
controller. After interior construction is
complete, ceiling mounted units can be
remotely set without having to use stepladder
access for manual setting.
Displays preset room temperature and operating status (fan, dry, cool).
S im ple s y s t e m pr o v id e s a d iv e r s e a s s o r t m e n t o f c o n t r o l m o d e s .
N o n -po la r , do u ble -c o r e c o n n e c t io n
s pe c ific a t io n s s im plify w ir in g
Non-polar, double-core remote controller
wire prevents wiring mistakes. signal
receiver unit (or decoration panel) of
wireless type is also easy to connect.
Displays auto-swing operating status and setting position of air discharge angle.
C entral remote c ontroller (option)
Centralised control of
up to 64 indoor groups
from remote location
up to 1 kilometer away.
Optional S kyAir s eries interfac e
adaptor required. *1
Optional S kyAir s eries interfac e
adaptor required. *1
HR V
Link by remote
controller group control.
HR V
C an be operated s imultaneous ly
or independently by remote c ontroller
(s et by ventilation mode)
Interlock control
with HRV
C an be operated s imultaneous ly
by remote c ontroller
(s et by ventilation mode)
C entral remote c ontroller (option)
C entral remote c ontroller (option)
Easily adaptable to large-scale, highfunction, centralised remote control systems.
Zone link control by
centralised control.
Installing and connecting control wiring between
SkyAir and other Daikin air-conditioning
equipment is easy.
HR V
HR V
HR V for indoor units within a zone are operated by interlocking
C an also be operated independently by remote controller.
Optional interface adaptor for S kyAir series
is necessary *1
Optional adaptor for external commands or
remote control of external equipment has
been standardised to one type.
HR V for indoor units within a zone are operated
by interloc king
Optional interfac e adaptor for S kyAir s eries
is nec es s ary *1
Note: When a wireless remote c ontroller is used, remote c ontrol by two remote c ontrollers is not possible.
*1. DIII-net adaptor function is standard equipment for the FAY71L.
Easily adaptable to large-scale, high-function, centralised remote control system.
C e ntr a l r e m o te c o ntr o lle r
DCS302CA61 (Option)
U n ifie d o n /o ff c o n t r o lle r
DCS301BA61 (Option)
S c h e d u le t im e r
DST301BA61 (Option)
DCS601C51 (Option)
Signal receiver unit is contained inside decoration panel or indoor unit
Heat pump
Cooling only
CEILING MOUNTED
CASSETTE TYPE
BRC7C612W BRC7C613W
CEILING SUSPENDED TYPE
BRC7E63W
CEILING SUSPENDED
CASSETTE TYPE
FAY71L
WALL MOUNTED TYPE
FAY100FA
DUCT CONNECTION
LOW STATIC PRESSURE TYPE
DUCT CONNECTION
MIDDLE STATIC PRESSURE TYPE
DUCT CONNECTION
HIGH STATIC PRESSURE TYPE
BRC7EA66
BRC7C528W BRC7C529W
BRC7EA618 BRC7E619
BRC7C610W BRC7C611W
BRC4C62
Centralised control of on/off by
group or all at once for up to 256
indoor units.
Unified control of weekly schedule
for up to 1,024 indoor units.
Schedule timer sets on/off time in 1 minute units
to be executed twice a day for a week at a time.
With its high functionality, the full
color “all-in-one” graphic controller
facilitates management of Skyair
System in a variety of ways.
*Please refer to the page 59 for the details.
BRC4C62
BRC4C62
Centralised control, with setting as
simple as it is with a standard
remote controller, of up to 64 groups
(1,024 indoor units) is possible.
BRC4C64
Interface adaptor
for SkyAir series
Enables centralised control via connection to
a high-speed, DIII-NET communication
system, adopted for the Daikin VRV system.
Necessary for interface adaptor for SkyAir series with the
central remote control units shown at above.
Note : DIII-net adaptor function is standard equipment for the FAY71L.
DTA102A52 (Option)
Central control adaptor kit *2
DTA107A55 (Option) (for FD series)
*2.The central control adaptor kit for FDB series
can be made to order.
36
Abundance of functions that provide comfortable
air-conditioning in stores and offices.
Note: Some features only available on selected models. See model pages for full list of features applicable to each unit.
C omfort
A u t o -s w in g
H ig h fa n s pe e d m o d e
Delivers comfortable air-conditioning to all areas,
near to and far from the air-conditioner.
You can increase fan speed approximately 10%
higher than the "high" setting.
Applicable for wall mounted type
H ig h -c e ilin g a pplic a t io n
Air discharge direction angle can be set (fixed setting)
S w in g pa t t e r n s e le c t io n
Delivers air-conditioning comfort all the way down to
the floor in air-conditioning zones with high ceilings.
W ork a nd S e rvic ing
L o w g a s pr e s s u r e d e t e c t io n
D r a in pu m p m e c h a n is m
Steeper gradient realises more
efficient condensate drainage.
High-lift is especially useful for
long lengths of drain piping.
P r e c h a r g e d fo r u p t o 3 0 m e t r e s
If refrigerant piping length does not exceed 30 m,
there is no need for on-site gas charging.
If there is a malfunction elsewhere in the system, the fan
or compressor can still be operated.
L o n g -life filt e r
Maintenance is not required for one year (two years
when a ceiling mounted cassette type is used).
C e ilin g s o ilin g pr e v e n t io n fu n c t io n
Applicable for ceiling mounted cassette type and ceiling mounted
cassette corner type.
Note:When units are installed on high ceilings, depending on the model, various restrictions
concerning maximum height, air discharge direction, and choice of options may apply.
(1) Air direction in
standard position
T w o s e le c t a ble t e m pe r a t u r e -s e n s o r s
(2) Air direction in draft
prevention position
Temperature-sensors are included in the indoor unit and optional wired remote controller.
Temperature sensing closer to
target area is possible to further
(3) Air direction in ceiling
soiling prevention position
D r a ft pr e v e n t io n fu n c t io n
Daikin's innovative air discharge mechanism keeps
airflow away from the ceiling. Ceiling cleaning is
less frequently required.
F ilt e r s ig n
To prevent cold air drafts, automatically adjusts airflow
to horizontal vector when heating initially starts or
when the thermostat turns off.
(Horizontal air dis c harge)
Note: Wireless remote controllers have no
temperature-sensor.
H ot s ta rt
(after defrost)
Uncomfortable cold air draft is not discharged when
heating operation starts or when switching to heat
after defrosting.
Y e a r -r o u n d c o o lin g a pplic a ble
S w it c h a ble fa n s pe e d
High setting provides maximum reach while low
setting minimises drafts.
P rogra m m e " Dry"
Dehumidification is microprocessor controlled to
prevent uncomfortable changes in air temperature.
Useful for reducing uncomfortable humidity without
uncomfortable cooling.
Efficient cooling even in winter when indoor temperatures
are higher than those outside, such as in underground public spaces or offices with many computers.
• Heat pump/RY71—140LU: possible up to -5°C
• Cooling only/R71—140LU: possible up to -15°C
• The year-round cooling kit is required as option.
T im e r s e le c t o r
Operation starts when the preset time of the ON
timer elapses and stops when the preset time of the
OFF timer elapses.
S e lf d ia g n o s is fu n c t io n
The operating parameters of indoor and outdoor units,
and sensor data at critical locations throughout the
system, are constantly monitored using a microcomputer.
To facilitate quick response in the event of a
malfunction, a message appears on the LCD of the
remote controller and an LED on the unit illuminates.
The filter sign warns you when it is time to clean the filter.
*When using a wired remote controller the sign is displayed in the LCD. When using a
wireless remote controller the filter sign lamp illuminates on the signal receiver unit.
C ontrol features
Use the temperature-sensor in the
indoor unit when controlling air
conditioning from another room.
(heating)
E m e r g e n c y o pe r a t io n
(Applies to R(Y)71LU–140LU)
(draft prevention, standard, ceiling soiling prevention)
You can freely set 3 air discharge positions by
remote controller.
Insufficient gas charging is normally hard to detect.
During post-installation trials and regular inspection
procedures, the refrigerant level is monitored by
microprocessor to maintain proper gas
pressure.Reliability is assured and maintenance and
inspection can be carried out more quickly.
A u t o -r e s t a r t
C o n t r o l by 1 r e m o t e c o n t r o lle r
If there is a power outage while the equipment is operating, operations will restart in the same mode as
before the power cut when electricity is restored.
A u t o c o o l/h e a t c h a n g e -o v e r
(Heat pump only)
Detects difference in preset temperature and actual
room temperature and automatically switches to
cooling or heating accordingly.
C o n t r o l by 2 r e m o t e c o n t r o lle r s
You can turn up to 16 indoor units on/off with a
single remote controller. (When using connected
indoor units, the settings must all be the same and
on/off will be simultaneous.)
E x te rna l c om m a nd c ontrol
Operation and surveillance is carried out using the
contact signal from the operation control box in the
building surveillance (security) room.
C e ntra l re m ote c ontrol
Using 2 remote controllers you can operate the
equipment locally or from a remote location.
Note: When a wireless remote controller is used, remote control by
two remote controllers is not possible.
Optional central remote controller enables
centralised control of up to 1024 indoor units (64
groups) from up to 1 kilometer away.
I n t e r lo c k c o n t r o l
Enables interlocking control with external
equipment such as heat reclaim ventilation (HRV).
Mould prevention
M o u ld -r e s is t a n t t r e a t m e n t fo r filt e r
M o u ld -pr o o fin g d r a in pa n
Sanitary filter has mould-resistant treatment.
Mould-proofing maintains hygiene by preventing
growth in highly humid conditions.
Others
T w in / tr iple / do u ble tw in m u lti o pe r a tio n
Simultaneously operates 2–4 indoor units
with a single outdoor unit.
37
P E fin
To achieve increased durability by improved resistance to salt corrosion and atmospheric pollution, coated PE fins (with special acryl pretreatment) are used for the heat exchanger of the outdoor unit.
In high corrosive areas, regular maintenance needs to be carried out.
Options
H ig h -e ffic ie n c y filt e r u n it
F r e s h -a ir in t a k e k it
Two types are available: 65% and 90% colorimetry.
U lt r a lo n g -life filt e r
Requires no maintenance for about 4 years* (10,000 h) in stores
and offices. * For dust concentration of 0.15 mg/m
3
You can provide air-conditioning with fresh air from
outside. Convenient for places where a ventilation
fan cannot be installed.
Note: *Connecting ducts, insect nets, fire dampers, air filters, and other parts should, as
required, be procured locally.
**Outside Air fan interlocked with air conditioning unit is necessary. Optional
PCB(KRP1C63)is required for interlocking.
***It is recommended that the volume of outdoor air introduced through the kit is limited
to 10% of the maximum airflow rate of the indoor unit. Introducing higher quantities
will increase the operating noise and may also influence temperature sending.
38
CEILING MOUNTED CASSETTE TYPE
Indoor unit
Model
Name
Outdoor unit
Power supply
Cooling capacity 1a/1b
kW
Btu/h
kcal/h
kW
Power consumption 1a/1b
Indoor
unit
Outdoor
unit
35
FHC35KVE
Colour
Unit
Decoration panel
m3/min
Airflow rate (H)
cfm
dB(A)
Sound level (H/L) 2
mm
Dimensions Unit
(HX WX D)
mm
Decoration panel
kg
Unit
Machine weight
kg
Decoration panel
°CWB
Certified operation range
Colour
Compressor Type
Motor output
kW
Refrigerant charge (R-22)
Sound level 2
Dimensions (HX WX D)
Machine weight
Certified operation range
Liquid (Flare)
Piping
connections
Gas (Flare)
Drain
Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation
kg
CEILING SUSPENDED CASSETTE TYPE
50
FHC50KVE
60
FHC60KVE
71
100
125
140
FHYC71KVE FHYC100KVE FHYC125KVE FHYC140KVE
R71LUV1
R100LUV1
R35GV1
R50GV1
R60GV1
R125LUY1
R140LUY1
R71LUY1
R100LUY1
VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
3.54/3.5
5.34/5.3
6.44/6.4
7.8/7.7
10.6/10.5
13.0/12.8
14.5/14.2
12,100/11,900 18,200/18,100 22,000/21,800 26,600/26,200 36,100/35,700 44,500/43,600 49,400/48,400
3,040/3,010
4,590/4,560
5,540/5,500
6,700/6,600
9,100/9,000
11,200/11,000 12,500/12,200
3.07/3.07 (V1) 4.01/4.01 (V1)
1.20/1.20
2.02/2.01
2.45/2.44
4.96/4.96
5.02/5.02
3.05/3.05 (Y1) 3.96/3.96 (Y1)
---------White
14
15
19
19
28
33
35
494
529
670
670
988
1,164
1,235
33/29
33/29
35/30
35/30
39/34
42/36
44/37
230X 840X 840 230X 840X 840 230X 840X 840 230X 840X 840 288X 840X 840 288X 840X 840 288X 840X 840
40X 950X 950
40X 950X 950
40X 950X 950
40X 950X 950
40X 950X 950
40X 950X 950
40X 950X 950
24
24
24
24
28
28
28
5
5
5
5
5
5
5
14 to 23
14 to 25
Ivory white
Hermetically sealed rotary type
Hermetically sealed scroll type
1.1
1.7
2.2
2.24
3.00
3.75
4.50
1.10
1.20
1.50
2.8
3.7
3.7
4.1
(Charged for 10 m) (Charged for 10 m) (Charged for 5 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m)
dB(A)
48
49
54
48
49
49
54
mm
540X 750X 270 540X 750X 270 685X 800X 300 770X 900X 320 1,170X 900X 320 1,170X 900X 320 1,345X 900X 320
kg
37
42
61
72 (V1), 71 (Y1) 87 (V1), 84 (Y1)
98
109
°CDB
19.4 to 46
19.4 to 54
19.4 to 46
21 to 46, -15 to 46 3 (Option installed)
mm
o/ 6.4
o/ 6.4
o/ 6.4
o/ 9.5
o/ 9.5
o/ 9.5
o/ 9.5
mm
o/ 12.7
o/ 15.9
o/ 15.9
o/ 15.9
o/ 19.1
o/ 19.1
o/ 19.1
mm I.Do/ 25X O.Do/ 32 I.Do/ 25X O.Do/ 32 I.Do/ 25X O.Do/ 32 I.Do/ 25X O.Do/ 32 I.Do/ 25X O.Do/ 32 I.Do/ 25X O.Do/ 32 I.Do/ 25X O.Do/ 32
mm
o/ 18.0 (Hole)
o/ 18.0 (Hole)
o/ 18.0 (Hole)
o/ 26.0 (Hole)
o/ 26.0 (Hole)
o/ 26.0 (Hole)
o/ 26.0 (Hole)
25
30
50 (equivalent length 70 m)
m
15
30
m
Both liquid and gas piping
Indoor unit
Outdoor unit
Power supply
Cooling capacity 1a/1b
Power consumption 1a/1b
Indoor
unit
Outdoor
unit
Colour
Airflow rate (H)
Sound level (H/L) 2
Dimensions (HX WX D)
Machine weight
Certified operation range
Colour
Compressor Type
Motor output
Refrigerant charge (R-22)
Sound level 2
Dimensions (HX WX D)
Machine weight
Certified operation range
Piping
Liquid (Flare)
connections
Gas (Flare)
Drain
Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation
35
FH35BVE
71
100
125
FHY71BVE
FHY100BVE
FHY125BVE
R71LUV1
R100LUV1
R35GV1
R50GV1
R60GV1
R125LUY1
R71LUY1
R100LUY1
VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
kW
3.54/3.4
5.19/5.1
6.6/6.5
7.8/7.7
10.6/10.5
13.0/12.8
Btu/h
12,100/11,600
17,700/17,500
22,760/22,200
26,600/26,200
36,100/35,700
44,500/43,600
kcal/h
3,040/2,930
4,460/4,400
5,690/5,600
6,700/6,600
9,100/9,000
11,200/11,000
3.10/3.10 (V1)
3.90/3.90 (V1)
1.51/1.50
2.16/2.15
2.80/2.78
4.92/4.92
kW
3.08/3.08 (Y1)
3.85/3.85 (Y1)
White
30
m3/min
13
13
16
17
24
1,059
cfm
458
458
564
600
847
44/39
dB(A)
37/32
38/33
38/33
39/35
42/37
mm
195X 960X 680
195X 960X 680
195X 1,160X 680
195X 1,160X 680
195X 1,400X 680
195X 1,590X 680
35
kg
23
24
26
27
32
°CWB
14 to 25
14 to 23
Ivory white
Hermetically sealed rotary type
Hermetically sealed scroll type
3.75
kW
1.1
1.7
2.2
2.24
3.00
3.7
1.10
1.20
1.50
2.8
3.7
kg
(Charged for 10 m) (Charged for 10 m) (Charged for 5 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m)
dB(A)
mm
kg
°CDB
mm
mm
mm
mm
m
m
48
540X 750X 270
37
19.4 to 46
o/ 6.4
o/ 12.7
I.D o/ 20X O.D o/ 26
o/ 18.0 (Hole)
25
50
FH50BVE
60
FH60BVE
49
540X 750X 270
42
19.4 to 54
o/ 6.4
o/ 15.9
I.D o/ 20X O.D o/ 26
o/ 18.0 (Hole)
30
15
49
48
49
770X 900X 320
1,170X 900X 320
1,170X 900X 320
98
72 (V1), 71 (Y1)
87 (V1), 84 (Y1)
21 to 46, -15 to 46 3 (Option installed)
o/ 9.5
o/ 9.5
o/ 9.5
o/ 19.1
o/ 15.9
o/ 19.1
I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26 I.D o/ 20X O.D o/ 26
o/ 26.0 (Hole)
o/ 26.0 (Hole)
o/ 26.0 (Hole)
50 (equivalent length 70 m)
30
Both liquid and gas piping
54
685X 800X 300
61
19.4 to 46
o/ 6.4
o/ 15.9
I.D o/ 20X O.D o/ 26
o/ 18.0 (Hole)
Note :
1
Rated cooling capacities are based on the following conditions:
1a
Indoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
1b
Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (R71LU-R140LU is 7.5 m.)
2
Anechoic chamber conversion value, measured according to JIS parameters and criteria.
During operation these values are somewhat higher owing to ambient conditions.
3
This value is for when year-round cooling kit (option) is installed.
39
kW
Btu/h
kcal/h
kW
Power consumption 1a/1b
Colour
Airflow rate (H)
Sound level (H/L) 2
Dimensions (HX WX D)
Machine weight
Certified operation range
Colour
Outdoor
Compressor Type
unit
Motor output
Refrigerant charge (R-22)
Sound level 2
Dimensions (HX WX D)
Machine weight
Certified operation range
Piping
Liquid (Flare)
connections
Gas (Flare)
Drain
Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation
m3/min
cfm
dB(A)
mm
kg
°CWB
kW
kg
dB(A)
mm
kg
°CDB
mm
mm
mm
mm
m
m
100
125
FUY100FJV1
FUY125FJV1
R100LUV1
R125LUY1
R100LUY1
V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
7.8/7.7
10.6/10.5
13.0/12.8
26,600/26,200
36,100/35,700
44,500/43,600
6,700/6,600
9,100/9,000
11,200/11,000
3.08/3.08 (V1)
4.07/4.07 (V1)
4.97/4.97
3.06/3.06 (Y1)
4.02/4.02 (Y1)
White
19
29
32
670
1,023
1,129
40/35
43/38
44/39
165X 895X 895
230X 895X 895
230X 895X 895
25
31
31
14 to 25
Ivory white
Hermetically sealed scroll type
2.24
3.00
3.75
2.8 (Charged for 30 m)
3.7 (Charged for 30 m)
3.7 (Charged for 30 m)
48
49
49
770X 900X 320
1,170X 900X 320
1,170X 900X 320
72 (V1), 71 (Y1)
87 (V1), 84 (Y1)
98
21 to 46, -15 to 46 3 (Option installed)
o/ 9.5
o/ 9.5
o/ 9.5
o/ 15.9
o/ 19.1
o/ 19.1
I.D o/ 20X O.D o/ 26
I.D o/ 20X O.D o/ 26
I.D o/ 20X O.D o/ 26
o/ 26.0 (Hole)
o/ 26.0 (Hole)
o/ 26.0 (Hole)
50 (equivalent length 70 m)
30
Both liquid and gas piping
CEILING MOUNTED CASSETTE CORNER TYPE
Indoor unit
Model
Name
CEILING SUSPENDED TYPE
Model
Name
Outdoor unit
Power supply
Cooling capacity 1a/1b
Indoor
unit
71
FUY71FJV1
R71LUV1
R71LUY1
Indoor unit
Model
Name
Outdoor unit
Power supply
Cooling capacity 1a/1b
Power consumption 1a/1b
Indoor
unit
Outdoor
unit
45
FHK45FV1
60
FHK60FV1
R35GV1
R50GV1
R60GV1
kW
Btu/h
kcal/h
3.54/3.4
12,100/11,600
3,040/2,930
kW
1.41/1.40
Unit
Decoration panel
m3/min
Airflow rate (H)
cfm
dB(A)
Sound level (H/L) 2
mm
Dimensions Unit
(HX WX D)
mm
Decoration panel
kg
Unit
Machine weight
kg
Decoration panel
°CWB
Certified operation range
Colour
Compressor Type
Motor output
kW
kg
Refrigerant charge (R-22)
dB(A)
Sound level 2
mm
Dimensions (HX WX D)
kg
Machine weight
Liquid (Flare)
Gas (Flare)
Drain
Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation
71
FHYK71FJV1
R71LUV1
R71LUY1
V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
5.19/5.1
6.6/6.5
17,700/17,500
22,760/22,200
4,460/4,400
5,690/5,600
2.25/2.24
2.76/2.74
7.8/7.7
26,600/26,200
6,700/6,600
3.07/3.07 (V1)
3.05/3.05 (Y1)
---------White
Colour
Certified operation range
Piping
connections
35
FHK35FV1
12
423
39/33
215X 1,110X 710
70X 1,240X 800
30
8.5
12
423
39/34
215X 1,110X 710
70X 1,240X 800
31
8.5
14 to 23
17
600
41/36
215X 1,310X 710
70X 1,440X 800
33
9.5
Ivory white
Hermetically sealed rotary type
1.1
1.7
2.2
1.10 (Charged for 10 m)
1.20 (Charged for 10 m)
1.50 (Charged for 5 m)
48
49
54
540X 750X 270
540X 750X 270
685X 800X 300
37
42
61
°CDB
19.4 to 46
19.4 to 54
19.4 to 46
mm
mm
mm
mm
m
m
o/ 6.4
o/ 12.7
I.D o/ 25X O.D o/ 32
o/ 18.0 (Hole)
25
o/ 6.4
o/ 15.9
I.D o/ 25X O.D o/ 32
o/ 18.0 (Hole)
o/ 6.4
o/ 15.9
I.D o/ 25X O.D o/ 32
o/ 18.0 (Hole)
30
15
17
600
41/36
215X 1,310X 710
70X 1,440X 800
33
9.5
14 to 25
Hermetically sealed scroll type
2.24
2.8 (Charged for 30 m)
48
770X 900X 320
72 (V1), 71 (Y1)
21 to 46
-15 to 46 3 (Option installed)
o/ 9.5
o/ 15.9
I.D o/ 25X O.D o/ 32
o/ 26.0 (Hole)
50 (equivalent length 70 m)
30
Both liquid and gas piping
Note :
1
Rated cooling capacities are based on the following conditions:
1a
Indoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
1b
Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (R71LU-R125LU is 7.5 m.)
2
Anechoic chamber conversion value, measured according to JIS parameters and criteria.
During operation these values are somewhat higher owing to ambient conditions.
3
This value is for when year-round cooling kit (option) is installed.
40
CEILING MOUNTED BUILT-IN TYPE
Indoor unit
Model
Name
Outdoor unit
Power supply
Cooling capacity 1a/1b
kW
Btu/h
kcal/h
kW
Power consumption 1a/1b
Indoor
unit
Outdoor
unit
35
FHB35FV1
Colour
Unit
Decoration panel
m3/min
Airflow rate (H)
cfm
dB(A)
Sound level (H/L) 2
mm
Dimensions Unit
(HX WX D)
mm
Decoration panel
kg
Unit
Machine weight
kg
Decoration panel
°CWB
Certified operation range
Colour
Compressor Type
Motor output
kW
Refrigerant charge (R-22)
Sound level 2
Dimensions (HX WX D)
Machine weight
Certified operation range
Liquid (Flare)
Piping
connections
Gas (Flare)
Drain
Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation
kg
dB(A)
mm
kg
°CDB
mm
mm
mm
mm
m
m
FLOOR STANDING TYPE
45
FHB45FV1
60
FHB60FV1
71
100
125
FHYB71FV1
FHYB100FV1
FHYB125FV1
R71LUV1
R100LUV1
R35GV1
R50GV1
R60GV1
R125LUY1
R71LUY1
R100LUY1
V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
3.54/3.4
5.19/5.1
6.6/6.5
7.8/7.7
10.6/10.5
13.0/12.8
12,100/11,600
17,700/17,500
22,760/22,200
26,600/26,200
36,100/35,700
44,500/43,600
3,040/2,930
4,460/4,400
5,690/5,600
6,700/6,600
9,100/9,000
11,200/11,000
3.13/3.13 (V1)
4.00/4.00 (V1)
1.47/1.46
2.33/2.32
2.78/2.76
4.74/4.74
3.11/3.11 (Y1)
3.95/3.95 (Y1)
---------White
11.5
14
17
19
27
35
405
494
600
670
953
1,235
38/32
39/34
41/35
41/35
41/35
44/38
300X 700X 800
300X 700X 800
300X 1,000X 800
300X 1,000X 800
300X 1,400X 800
300X 1,400X 800
55X 880X 500
55X 880X 500
55X 1,100X 500
55X 1,100X 500
55X 1,500X 500
55X 1,500X 500
30
31
41
41
51
52
3.5
3.5
4.5
4.5
6.5
6.5
14 to 23
14 to 25
Ivory white
Hermetically sealed rotary type
Hermetically sealed scroll type
1.1
1.7
2.2
2.24
3.00
3.75
1.10
1.20
1.50
2.8
3.7
3.7
(Charged for 10 m) (Charged for 10 m) (Charged for 5 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m)
48
49
54
48
49
49
540X 750X 270
540X 750X 270
685X 800X 300
770X 900X 320
1,170X 900X 320
1,170X 900X 320
37
42
61
72 (V1), 71 (Y1)
87 (V1), 84 (Y1)
98
19.4 to 46
19.4 to 54
19.4 to 46
21 to 46, -15 to 46 3 (Option installed)
o/ 6.4
o/ 6.4
o/ 6.4
o/ 9.5
o/ 9.5
o/ 9.5
o/ 12.7
o/ 15.9
o/ 15.9
o/ 15.9
o/ 19.1
o/ 19.1
I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32 I.D o/ 25X O.D o/ 32
o/ 18.0 (Hole)
o/ 18.0 (Hole)
o/ 18.0 (Hole)
o/ 26.0 (Hole)
o/ 26.0 (Hole)
o/ 26.0 (Hole)
25
30
50 (equivalent length 70 m)
15
30
Both liquid and gas piping
Indoor unit
Outdoor unit
Power supply
Cooling capacity 1a/1b
Power consumption 1a/1b
Indoor
unit
Colour
Airflow rate (H)
Sound level (H/L) 2
Dimensions (HX WX D)
Machine weight
Certified operation range
Colour
Outdoor
Compressor Type
unit
Motor output
Refrigerant charge (R-22)
Sound level 2
Dimensions (HX WX D)
Machine weight
Certified operation range
Piping
Liquid (Flare)
connections
Gas (Flare)
Drain
Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation
kW
Btu/h
kcal/h
kW
m3/min
cfm
dB(A)
mm
kg
°CWB
kW
kg
dB(A)
mm
kg
°CDB
mm
mm
mm
mm
m
m
71
100
FAY71LVE
FAY100FAVE
R71LUV1
R100LUV1
R71LUY1
R100LUY1
VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
7.8/7.7
10.6/10.5
26,600/26,200
36,100/35,700
6,700/6,600
9,100/9,000
2.98/ 2.98(V1)
3.90/3.90 (V1)
3.85/3.85 (Y1)
2.96/2.96(Y1)
White
19
23
670
811
43/37
45/41
290X 1,050X 230
360X 1,570X 200
13
26
14 to 25
Ivory white
Hermetically sealed scroll type
2.24
3.00
2.8 (Charged for 30 m)
3.7 (Charged for 30 m)
48
49
770X 900X 320
1,170X 900X 320
72 (V1), 71 (Y1)
87 (V1), 84 (Y1)
21 to 46, -15 to 46 3 (Option installed)
o/ 9.5
o/ 9.5
o/ 15.9
o/ 19.1
I.D o/ 13X O.D o/ 18
I.D o/ 20X O.D o/ 26
o/ 26.0 (Hole)
o/ 26.0 (Hole)
50 (equivalent length 70 m)
30
Both liquid and gas piping
Note :
1
Rated cooling capacities are based on the following conditions:
(FHB) 1aSuction temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
1b
Suction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (R71LU-R125LU is 7.5 m.)
(FAY) 1aIndoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
1b
Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (R71LU-R100LU is 7.5 m.)
2
Anechoic chamber conversion value, measured according to JIS parameters and criteria.
During operation these values are somewhat higher owing to ambient conditions.
3
This value is for when year-round cooling kit (option) is installed.
41
Outdoor unit
Power supply
Cooling capacity 1a/1b
kW
Btu/h
kcal/h
kW
Power consumption 1a/1b
Indoor
unit
Colour
Airflow rate (H)
Sound level (H/L) 2
Dimensions (HX WX D)
Machine weight
Certified operation range
Colour
Outdoor
Compressor Type
unit
Motor output
Refrigerant charge (R-22)
Sound level 2
Dimensions (HX WX D)
Machine weight
Certified operation range
Piping
Liquid (Flare)
connections
Gas (Flare)
Drain
Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation
m3/min
cfm
dB(A)
mm
kg
°CWB
kW
kg
dB(A)
mm
kg
°CDB
mm
mm
mm
mm
m
m
71
100
125
FVY71LAVE
FVY100LAVE
FVY125LAVE
R71LUV1
R100LUV1
R125LUY1
R71LUY1
R100LUY1
VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
7.8/7.7
10.6/10.5
13.0/12.8
26,600/26,200
36,100/35,700
44,500/43,600
6,700/6,600
9,100/9,000
11,200/11,000
3.18/3.18 (V1)
4.03/4.03 (V1)
5.06/5.06
3.16/3.16 (Y1)
3.98/3.98 (Y1)
White
18
28
32
635
988
1,129
41/35
46/40
49/43
1,850X 600X 270
1,850X 600X 350
1,850X 600X 350
39
46
47
14 to 25
Ivory white
Hermetically sealed scroll type
2.24
3.00
3.75
2.8 (Charged for 30 m)
3.7 (Charged for 30 m)
3.7 (Charged for 30 m)
48
49
49
770X 900X 320
1,170X 900X 320
1,170X 900X 320
72 (V1), 71 (Y1)
87 (V1), 84 (Y1)
98
21 to 46, -15 to 46 3 (Option installed)
o/ 9.5
o/ 9.5
o/ 9.5
o/ 15.9
o/ 19.1
o/ 19.1
I.D o/ 20X O.D o/ 26
I.D o/ 20X O.D o/ 26
I.D o/ 20X O.D o/ 26
o/ 26.0 (Hole)
o/ 26.0 (Hole)
o/ 26.0 (Hole)
50 (equivalent length 70 m)
30
Both liquid and gas piping
DUCT CONNECTION LOW STATIC PRESSURE TYPE
Outdoor unit
Power supply
Cooling capacity 1a/1b, 4
Power consumption 1a/1b
Colour
Airflow rate (H)
Indoor
unit
Outdoor
unit
25
FDBG25AVE
Indoor unit
Model
Name
WALL MOUNTED TYPE
Model
Name
Indoor unit
Model
Name
Fan Driving system
Sound level (H/L) 2
Dimensions (HX WX D)
Machine weight
Certified operation range
Colour
Compressor Type
Motor output
Refrigerant charge (R-22)
Sound level 2
Dimensions (HX WX D)
Machine weight
Certified operation range
Piping
Liquid (Flare)
connections
Gas (Flare)
Drain
Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation
kW
Btu/h
kcal/h
kW
m3/min
cfm
dB(A)
mm
kg
°CWB
kW
kg
dB(A)
mm
kg
°CDB
mm
mm
mm
mm
m
m
35
FDBG35AVE
50
FDBG50AVE
60
FDBG60AVE
71
FDBG71AVE
R71FUV1
R25JV1
R35JV1
R50GV1
R60GV1
R71FUY1
VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
2.64/2.60
3.54/3.50
5.34/5.30
7.03/6.97
7.80/7.70
9,000/8,900
12,100/11,900
18,200/18,100
24,000/23,800
26,600/26,200
2,270/2,250
3,040/3,010
4,590/4,560
6,050/6,000
6,700/6,600
0.88/0.87
1.25/1.24
2.06/2.05
2.76/2.75
2.82/2.80
---------13
13
13
18
18
458
458
458
635
635
Direct drive (2 speed)
41/38
41/38
41/38
42/39
42/39
260X 900X 580
260X 900X 580
260X 900X 580
260X 1,300X 580
260X 1,300X 580
22
22
23
31
31
14 to 23
14 to 25
Ivory white
Hermetically sealed rotary type
Hermetically sealed type
0.7
1.1
1.7
2.2
2.2
0.8
1.0
1.20
1.50
2.10
(Charged for 10 m)
(Charged for 10 m)
(Charged for 10 m)
(Charged for 5 m)
(Charged for 5 m)
46
48
49
54
52
560X 695X 265
560X 695X 265
540X 750X 270
685X 800X 300
816X 880X 370
27
33
42
61
87 (V1), 84 (Y1)
19.4 to 54
19.4 to 46
21 to 52
19.4 to 46
o/ 6.4
o/ 6.4
o/ 6.4
o/ 6.4
o/ 9.5
o/ 9.5
o/ 12.7
o/ 15.9
o/ 15.9
o/ 15.9
3/4B
3/4B
3/4B
3/4B
3/4B
o/ 18.0 (Hole)
o/ 18.0 (Hole)
o/ 18.0 (Hole)
o/ 18.0 (Hole)
o/ 26.0 (Hole)
25
30
50 (equivalent length 70 m)
15
30
Both liquid and gas piping
Note :
1
Rated cooling capacities are based on the following conditions:
(FVY) 1aIndoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
1b
Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (R71LU-R125LU is 7.5 m.)
(FDBG) 1aSuction temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
1b
Suction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
2
Anechoic chamber conversion value, measured according to JIS parameters and criteria.
During operation these values are somewhat higher owing to ambient conditions.
3
This value is for when year-round cooling kit (option) is installed.
4
Capacities are gross, with no deduction made for evaporator fan motor heat.
42
DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE
Indoor unit
Model
Name
Outdoor unit
Power supply
Cooling capacity 1a/1b
Power consumption 1a/1b
Colour
Indoor
Fan Airflow rate (H)
unit
Sound level (H) 2
Dimensions (HX WX D)
Machine weight
Certified operation range
Colour
Outdoor
Compressor Type
unit
Motor output
Refrigerant charge (R-22)
Sound level 2
Dimensions (HX WX D)
Machine weight
Certified operation range
Piping
Liquid (Flare)
connections
Gas (Flare)
Drain
Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation
kW
Btu/h
kcal/h
kW
m3/min
cfm
dB(A)
mm
kg
°CWB
kW
kg
dB(A)
mm
kg
°CDB
mm
mm
mm
mm
m
m
Outdoor unit
Power supply
Cooling capacity 1a/1b
Power consumption 1a/1b
Colour
Fan Airflow rate (H)
External static pressure
Sound level (H) 2
Dimensions (HX WX D)
Machine weight
Certified operation range
Colour
Outdoor
Compressor Type
unit
Motor output
Refrigerant charge (R-22)
Sound level 2
Dimensions (HX WX D)
Machine weight
Certified operation range
Piping
Liquid (Flare)
connections
Gas (Flare)
Drain
Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation
100
125
140
180
FDMG100AV1
FDMG125AV1
FDMG140AV1
FDMG180AV1
R100FUV1
R125FUY1
RG140AY1
RG180AY1
R100FUY1
V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
8.8/8.7
10.6/10.5
13.1/12.9
14.5/14.2
17.2/16.8
30,000/29,600
36,100/35,700
44,500/43,600
49,400/48,400
58,700/57,500
7,600/7,500
9,100/9,000
11,200/11,000
12,500/12,200
14,700/14,400
3.15/3.13
4.08/4.04
4.89/4.85
5.25/5.25
6.45/6.45
---------23
34
37
42
42
811
1,200
1,306
1,412
1,482
42
44
45
46
47
305X 1,350X 680
305X 1,550X 680
305X 1,550X 680
305X 1,550X 680
305X 1,900X 680
43
51
52
52
58
14 to 25
Ivory white
Hermetically sealed type
Hermetically sealed scroll type
2.20
3.00
3.75
4.50
4.50
2.4 (Charged for 5 m) 2.4 (Charged for 5 m) 2.8 (Charged for 5 m) 2.9 (Charged for 5 m) 2.8 (Charged for 5 m)
52
56
57
55
56
816X 880X 370
1,215X 880X 370
1,215X 880X 370
1,345X 880X 370
1,345X 880X 370
87 (V1), 84 (Y1)
117 (V1), 109 (Y1)
110
113
114
21 to 52
21 to 50
o/ 9.5
o/ 9.5
o/ 9.5
o/ 9.5
o/ 9.5
o/ 15.9
o/ 19.1
o/ 19.1
o/ 19.1
o/ 19.1
3/4B
3/4B
3/4B
3/4B
3/4B
o/ 26.0 (Hole)
o/ 26.0 (Hole)
o/ 26.0 (Hole)
o/ 26.0 (Hole)
o/ 26.0 (Hole)
50 (equivalent length 70 m)
30
Both liquid and gas piping
71
FDYM03FAV1
R71LUV1
R71LUY1
Indoor unit
Model
Name
Indoor
unit
71
FDMG71AV1
RG71AV1
RG71AY1
kW
Btu/h
kcal/h
kW
m3/min
cfm
Pa(mmH2O)
dB(A)
mm
kg
°CWB
kW
kg
dB(A)
mm
kg
°CDB
mm
mm
mm
mm
m
m
100
125
140
FDYM04FAV1
FDYM05FAV1
FDYM06FAV1
R100LUV1
R125LUY1
R140LUY1
R100LUY1
V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
7.8/7.7
10.6/10.5
13.0/12.8
14.5/14.2
26,600/26,200
36,100/35,700
44,500/43,600
49,400/48,400
6,700/6,600
9,100/9,000
11,200/11,000
12,500/12,200
3.25/3.25 (V1)
4.08/4.08 (V1)
5.06/5.06
5.18/5.18
3.23/3.23 (Y1)
4.03/4.03 (Y1)
---------20
26
35
37
706
917
1,235
1,306
98(10)
98(10)
98(10)
98(10)
39
39
44
46
295X 1,100X 680
295X 1,500X 680
295X 1,500X 680
295X 1,500X 680
42
56
57
57
14 to 25
Ivory white
Hermetically sealed scroll type
2.24
3.00
3.75
4.50
2.8 (Charged for 30 m)
3.7 (Charged for 30 m)
3.7 (Charged for 30 m)
4.1 (Charged for 30 m)
48
49
49
54
770X 900X 320
1,170X 900X 320
1,170X 900X 320
1,345X 900X 320
72 (V1), 71 (Y1)
87 (V1), 84 (Y1)
98
109
21 to 46, -15 to 46 3 (Option installed)
o/ 9.5
o/ 9.5
o/ 9.5
o/ 9.5
o/ 15.9
o/ 19.1
o/ 19.1
o/ 19.1
I.D o/ 25X O.D o/ 32
I.D o/ 25X O.D o/ 32
I.D o/ 25X O.D o/ 32
I.D o/ 25X O.D o/ 32
o/ 26.0 (Hole)
o/ 26.0 (Hole)
o/ 26.0 (Hole)
o/ 26.0 (Hole)
50 (equivalent length 70 m)
30
Both liquid and gas piping
Note :
1
Rated cooling capacities are based on the following conditions:
1a
Suction temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
1b
Suction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (R71LU-R140LU is 7.5 m.)
2
Anechoic chamber conversion value, measured according to JIS parameters and criteria.
During operation these values are somewhat higher owing to ambient conditions.
3
This value is for when year-round cooling kit (option) is installed.
43
DUCT CONNECTION HIGH STATIC PRESSURE TYPE
Model
Name
Power supply
Cooling capacity 1a/1b
Power consumption 1a/1b
Colour
Indoor
Airflow rate (H)
unit
Fan
Outdoor
unit
External static pressure
Driving system
Sound level (H) 2
Dimensions (HX WX D)
Machine weight
Certified operation range
Colour
Compressor Type
Motor output
Refrigerant charge (R-22)
Sound level
Dimensions (HX WX D)
Machine weight
Certified operation range
Piping
Liquid (Flare)
connections
Gas (Flare)
Drain
Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation
2
Model
Name
Power supply
Cooling capacity 1a/1b
kW
Btu/h
kcal/h
kW
8.1/ 7.9
27,800/ 27,000
7,000/6,800
2.50/2.48
m3/min
cfm
Pa(mmH2O)
26
917
69 (7)
dB(A)
mm
kg
°CWB
46
450X 650X 850
51
kW
3.0
2.1
(Charged for 5 m)
kg
dB(A)
mm
kg
°CDB
mm
mm
mm
mm
m
m
Power consumption 1a/1b
Colour
Airflow rate (H)
Fan
External static pressure
Driving system
Sound level (H) 2
Dimensions (HX WX D)
Machine weight
Certified operation range
Colour
Compressor Type
Motor output
Refrigerant charge (R-22)
Sound level 2
Dimensions (HX WX D)
Machine weight
Certified operation range
Piping
Liquid (Flare)
connections
Gas (Brazing)
Drain
Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation
100
125
FD04KY1
FD05KY1
R100FUY1
R125FUY1
Y1: 3 phase, 380–415 V, 50 Hz
11.0/10.8
14.0/13.8
37,700/36,900
47,600/46,800
9,500/9,300
12,000/11,800
3.52/3.48
4.19/4.15
---------30
46
1,059
1,623
88 (9)
Belt drive
49
450X 900X 850
59
72
14 to 25
Ivory white
Hermetically sealed type
3.8
4.5
2.4
2.8
(Charged for 5 m)
(Charged for 5 m)
52
816X 880X 370
84
56
140
FD06KY1
RU06KY1
17.4/17.2
59,500/58,800
15,000/14,800
5.7/5.7
52
1,835
51
450X 1,130X 850
79
Hermetically sealed scroll type
4.5
3.0
(Charged for 5 m)
57
110
59
1,345X 880X 320
112
o/ 9.5
o/ 19.1
o/ 9.5
o/ 19.1
1,215X 880X 370
109
21 to 52
o/ 9.5
o/ 15.9
o/ 9.5
o/ 19.1
3/4B
o/ 26.0 (Hole)
o/ 26.0 (Hole)
50 (equivalent length 70 m)
30
Both liquid and gas piping
o/ 26.0 (Hole)
200
FD08KY1
RU08KUY1
Indoor unit
Outdoor unit
Indoor
unit
Outdoor
unit
71
FD03KY1
R71FUY1
Indoor unit
Outdoor unit
kW
Btu/h
kcal/h
kW
24.3/24.0
83,000/81,800
20,900/20,600
7.5/7.4
m3/min
cfm
Pa(mmH2O)
68
2,400
----------
250
400
FD10KY1
FD15KY1
RU10KUY1
RU08KUY1X 2
Y1: 3 phase, 380–415 V, 50 Hz
29.7/29.2
48.6/47.9
101,200/ 99,600
166,000/163,500
25,500/25,100
41,800/41,200
9.9/9.8
15.0/14.8
---------83
136
2,929
4,800
98 (10)
500
FD20KY1
RU10KUY1X 2
59.3/58.4
202,400/199,400
51,000/ 50,200
19.8/19.6
166
5,859
147 (15)
Belt drive
dB(A)
mm
kg
°CWB
51
500X 1,130X 850
93
kW
7.5
5.0
(Charged for 5 m)
60
1,220X 1,280X 690
185
kg
dB(A)
mm
kg
°CDB
mm
mm
mm
mm
m
m
53
500X 1,330X 850
104
58
625X 1,620X 850
161
60
625X 1,980X 850
187
14 to 25
Ivory white
Hermetically sealed scroll type
9.0
7.5 X 2
6.1
5.0
(Charged for 5 m)
(Charged for 5 m)X 2
61
60 3
(1,220X 1,280X 690) X 2
1,440X 1,280X 690
200
185X 2
21 to 52
o/ 15.9
o/ 12.7 X 2
o/ 31.8
o/ 25.4 X 2
o/ 12.7
o/ 25.4
3/4B
9.0X 2
6.1
(Charged for 5 m)X 2
61 3
(1,440X 1,280X 690) X 2
200X 2
o/ 15.9 X 2
o/ 31.8 X 2
1B
---------50 (equivalent length 70 m)
30
Both liquid and gas piping
Note :
Models RU08K(U)Y1 and RU10K(U)Y1 are recommended for commercial facilities.
1
Rated cooling capacities are based on the following conditions:
1a
Suction temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
1b
Suction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
2
Anechoic chamber conversion value, measured according to JIS parameters and criteria.
During operation these values are somewhat higher owing to ambient conditions.
3
Specification for outdoor unit is for a single unit only.
44
Simultaneous operation system
DUCT CONNECTION HIGH STATIC PRESSURE TYPE
Model
Name
Power supply
Cooling capacity 1a/1b
Indoor unit
Outdoor unit
Power consumption
Colour
Airflow rate (H)
1a/1b
Indoor
unit
Fan
Outdoor
unit
200
FD08KY1
RU08KY1
External static pressure
Driving system
Sound level (H) 2
Dimensions (HX WX D)
Machine weight
Certified operation range
Colour
Compressor Type
Motor output
Refrigerant charge (R-22)
Sound level 2
Dimensions (HX WX D)
Machine weight
Certified operation range
Piping
Liquid (Brazing)
connections
Gas (Brazing)
Drain
Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation
kW
Btu/h
kcal/h
kW
24.3/24.0
83,000/81,800
20,900/20,600
7.5/7.4
m3/min
cfm
Pa(mmH2O)
68
2,400
CEILING MOUNTED CASSETTE TYPE
250
400
FD10KY1
FD15KY1
RU10KY1
RU08KY1X 2
Y1: 3 phase, 380–415 V, 50 Hz
29.7/29.2
48.6/47.9
101,200/ 99,600
166,000/163,500
25,500/25,100
41,800/41,200
9.9/9.8
15.0/14.8
---------83
136
2,929
4,800
98 (10)
500
FD20KY1
RU10KY1X 2
59.3/58.4
202,400/199,400
51,000/ 50,200
19.8/19.6
166
5,859
kW
kg
dB(A)
mm
kg
°CDB
mm
mm
mm
mm
m
m
51
500X 1,130X 850
93
7.5
5.0
53
500X 1,330X 850
104
(Field charge required for 5 m) 4
58
625X 1,620X 850
161
(Field charge required for 5 m) 4
60
1,220X 1,280X 690
177
61
1,440X 1,280X 690
190
o/ 12.7
o/ 25.4
o/ 15.9
o/ 31.8
3/4B
Note :
Models RU08K(U)Y1 and RU10K(U)Y1 are recommended for commercial facilities.
1
Rated cooling capacities are based on the following conditions:
1a
Suction temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
1b
Suction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
2
Anechoic chamber conversion value, measured according to JIS parameters and criteria.
During operation these values are somewhat higher owing to ambient conditions.
3
Specification for outdoor unit is for a single unit only.
4
This is the amount of refrigerant required for piping of five meters or less.
Since the unit does not contain refrigerant when shipped from the factory, it must be added at the installation site.
For details, please refer to the installation manual.
61 3
(1,440X 1,280X 690) X 2
190 X 2
o/ 15.9 X 2
o/ 31.8 X 2
1B
---------50 (equivalent length 70 m)
30
Both liquid and gas piping
kW
Colour
Unit
Decoration panel
m3/min
Airflow rate (H)
cfm
Sound level (H/L) 2
dB(A)
mm
Dimensions Unit
(HX WX D)
Decoration
mm
panel
Machine weight
(Field charge required for 5 m) 4 X 2
60 3
(1,220X 1,280X 690) X 2
177 X 2
21 to 52
o/ 12.7 X 2
o/ 25.4 X 2
kW
Btu/h
kcal/h
Power consumption 1a/1b
9.0X 2
6.1
(Field charge required for 5 m) 4 X 2
Outdoor unit
Power supply
Cooling capacity 1a/1b
60
625X 1,980X 850
187
14 to 25
Ivory white
Hermetically sealed scroll type
9.0
7.5 X 2
6.1
5.0
Indoor unit
Model
Name
Indoor
unit 3
147 (15)
Belt drive
dB(A)
mm
kg
°CWB
TWIN & TRIPLE & DOUBLE TWIN MULTI
Outdoor
unit
Unit
Decoration
panel
Certified operation range
Colour
Compressor Type
Motor output
Refrigerant charge (R-22)
40X 950X 950
40X 950X 950
40X 950X 950
40X 950X 950
40X 950X 950
40X 950X 950
kg
24
24
24
24
28
28
kg
5
5
5
5
5
5
°CWB
kW
kg
Sound level 2
dB(A)
mm
Dimensions (HX WX D)
kg
Machine weight
Certified operation range °CDB
mm
Piping
Liquid (Flare)
connections Gas
mm
mm
Drain Indoor unit
Outdoor unit mm
m
Max. interunit piping length
m
Max. installation level difference
Heat insulation
Indoor unit
Model
Name
Outdoor unit
Power supply
Cooling capacity 1a/1b
Machine weight
2.24
2.8
(Charged for 30 m)
48
770X 900X 320
72 (V1), 71 (Y1)
o/ 9.5
o/ 15.9 (Flare)
I.D o/ 25X O.D o/ 32
o/ 26.0 (Hole)
14 to 25
Ivory white
Hermetically sealed scroll type
3.00
3.75
4.50
3.7
3.7
4.1
(Charged for 30 m) (Charged for 30 m) (Charged for 30 m)
49
49
54
1,170X 900X 320
1,170X 900X 320
1,345X 900X 320
87 (V1), 84 (Y1)
98
109
21 to 46, -15 to 46 4 (Option installed)
o/ 9.5
o/ 9.5
o/ 9.5
o/ 19.1 (Flare)
o/ 19.1 (Flare)
o/ 19.1 (Flare)
I.D o/ 25X O.D o/ 32
I.D o/ 25X O.D o/ 32
I.D o/ 25X O.D o/ 32
o/ 26.0 (Hole)
o/ 26.0 (Hole)
o/ 26.0 (Hole)
50 (equivalent length 70 m)
30
Both liquid and gas piping
140
FHYC50KVEX 3
R140LUY1
kW
Btu/h
kcal/h
kW
Power consumption 1a/1b
Colour
Unit
Indoor
Decoration panel
unit 3
m3/min
Airflow rate (H)
cfm
Sound level (H/L) 2
dB(A)
mm
Dimensions Unit
(HX WX D)
Decoration
mm
panel
Unit
Decoration
panel
71
100
125
140
200
250
FHYC35KVEX 2
FHYC50KVEX 2
FHYC60KVEX 2
FHYC71KVEX 2
FHYC100KVEX 2
FHYC125KVEX 2
R71LUV1
R100LUV1
R125LUY1
R140LUY1
R200KUY1
R250KUY1
R71LUY1
R100LUY1
VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
7.8/7.7
10.6/10.5
13.0/12.8
14.5/14.2
22.5/22.2
27.1/26.6
26,600/26,200
36,100/35,700
44,500/43,600
49,400/48,400
76,800/75,800
92,500/90,800
6,700/6,600
9,100/9,000
11,200/11,000
12,500/12,200
19,400/19,100
23,300/22,900
3.17/3.17 (V1)
4.06/4.06 (V1)
5.01/5.01
5.02/5.02
7.7/7.6
9.7/9.7
3.15/3.15 (Y1)
4.01/4.01 (Y1)
------------White
14
15
19
19
28
33
494
529
670
670
988
1,164
33/29
33/29
35/30
35/30
39/34
42/36
230X 840X 840
230X 840X 840
230X 840X 840
230X 840X 840
288X 840X 840
288X 840X 840
14.5/14.2
49,400/48,400
12,500/12,200
5.02/5.02
15
529
33/29
230X 840X 840
5.5
9.0
5.3
5.7
(Charged for 5 m)
(Charged for 5 m)
60
61
1,220X 1,280X 690
1,440X 1,280X 690
178
202
-5 to 52
o/ 12.7
o/ 15.9
o/ 25.4 (Flange)
o/ 28.6 (Flange)
I.D o/ 25X O.D o/ 32
I.D o/ 25X O.D o/ 32
-----------------
200
200
FHYC71KVEX 3
FHYC50KVEX 4
R200KUY1
R200KUY1
VE: 1 Phase, 220–240/220 V, 50/60 Hz Y1: 3 Phase, 380–415 V, 50 Hz
22.5/22.2
22.5/22.2
76,800/75,800
76,800/75,800
19,400/19,100
19,400/19,100
7.7/7.6
7.7/7.6
------------White
19
15
670
529
33/29
35/30
33/29
230X 840X 840
230X 840X 840
250
FHYC60KVEX 4
R250KUY1
27.1/26.6
92,500/90,800
23,300/22,900
9.7/9.7
19
670
35/30
230X 840X 840
40X 950X 950
40X 950X 950
40X 950X 950
40X 950X 950
kg
24
24
24
24
kg
5
5
5
5
Certified operation range °CWB
Colour
Outdoor
Compressor Type
unit
kW
4.50
Motor output
kg
4.1 (Charged for 30 m)
Refrigerant charge (R-22)
54
Sound level 2
dB(A)
1,345X 900X 320
mm
Dimensions (HX WX D)
109
kg
Machine weight
Certified operation range °CDB 21 to 46, -15 to 46 4 (Option installed)
mm
Piping
Liquid (Flare)
o/ 9.5
connections Gas
mm
o/ 19.1 (Flare)
mm
Drain Indoor unit
I.D o/ 25X O.D o/ 32
Outdoor unit mm
o/ 26.0 (Hole)
m
Max. interunit piping length
m
Max. installation level difference
Heat insulation
14 to 25
Ivory white
Hermetically sealed scroll type
5.5
5.5
5.3 (Charged for 5 m)
5.3 (Charged for 5 m)
60
60
1,220X 1,280X 690
1,220X 1,280X 690
178
178
-5 to 52
o/ 12.7
o/ 12.7
o/ 25.4 (Flange)
o/ 25.4 (Flange)
I.D o/ 25X O.D o/ 32
I.D o/ 25X O.D o/ 32
----------------50 (equivalent length 70 m)
30
Both liquid and gas piping
9.0
5.7 (Charged for 5 m)
61
1,440X 1,280X 690
202
o/ 15.9
o/ 28.6 (Flange)
I.D o/ 25X O.D o/ 32
---------
Note :
Models R200KU and R250KU are recommended for commercial facilities.
1
Rated cooling capacities are based on the following conditions:
1a
Indoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
1b
Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (R71LU-R140LU is 7.5 m.)
2
Anechoic chamber conversion value, measured according to JIS parameters and criteria.
During operation these values are somewhat higher owing to ambient conditions.
3
Values shown are for a single unit only.
4
This value is for when year-round cooling kit (option) is installed.
45
46
Simultaneous operation system
TWIN & TRIPLE & DOUBLE TWIN MULTI
CEILING SUSPENDED TYPE
Indoor unit
Model
Name
Outdoor unit
Power supply
Cooling capacity 1a/1b
kW
Btu/h
kcal/h
Power consumption 1a/1b
Indoor
unit 3
Outdoor
unit
kW
Colour
Airflow rate (H)
m3/min
cfm
dB(A)
Sound level (H/L) 2
mm
Dimensions (HX WX D)
kg
Machine weight
°
Certified operation range CWB
Colour
Compressor Type
kW
Motor output
Refrigerant charge (R-22)
kg
dB(A)
Sound level
mm
Dimensions (HX WX D)
kg
Machine weight
Certified operation range °CDB
mm
Piping
Liquid (Flare)
connections Gas
mm
mm
Drain Indoor unit
Outdoor unit mm
m
Max. interunit piping length
m
Max. installation level difference
Heat insulation
2
DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE
71
100
125
140
200
250
FHY35BVE × 2
FHY50BVE × 2
FHY60BVE × 2
FHY71BVE × 2
FHY100BVE × 2
FHY125BVE × 2
R71LUV1
R100LUV1
R125LUY1
R140LUY1
R200KUY1
R250KUY1
R71LUY1
R100LUY1
VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
7.8/7.7
10.6/10.5
13.0/12.8
14.5/14.2
22.5/22.2
27.1/26.6
26,600/26,200
36,100/35,700
44,500/43,600
49,400/48,400
76,800/75,800
92,500/90,800
6,700/6,600
9,100/9,000
11,200/11,000
12,500/12,200
19,400/19,100
23,300/22,900
3.20/3.20 (V1)
3.95/3.95 (V1)
4.98/4.98
5.17/5.17
7.7/7.6
9.7/9.7
3.18/3.18 (Y1)
3.90/3.90 (Y1)
White
13
13
16
17
24
30
458
458
564
600
847
1,059
37/32
38/33
38/33
39/35
42/37
44/39
195X 960X 680
195X 960X 680
195X 1,160X 680
195X 1,160X 680
195X 1,400X 680
195X 1,590X 680
23
24
26
27
32
35
14 to 25
Ivory white
Hermetically sealed scroll type
2.24
3.00
3.75
4.50
5.5
9.0
2.8
3.7
3.7
4.1
5.3
5.7
(Charged for 30 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m)
(Charged for 5 m)
(Charged for 5 m)
48
49
49
54
60
61
770X 900X 320
1,170X 900X 320
1,170X 900X 320
1,345X 900X 320
1,220X 1,280X 690
1,440X 1,280X 690
72 (V1), 71 (Y1)
87 (V1), 84 (Y1)
98
109
178
202
21 to 46, -15 to 46 4 (Option installed)
-5 to 52
o/ 9.5
o/ 9.5
o/ 9.5
o/ 9.5
o/ 12.7
o/ 15.9
o/ 15.9 (Flare)
o/ 19.1 (Flare)
o/ 19.1 (Flare)
o/ 19.1 (Flare)
o/ 25.4 (Flange)
o/ 28.6 (Flange)
I.D o/ 20X O.D o/ 26
I.D o/ 20X O.D o/ 26
I.D o/ 20X O.D o/ 26
I.D o/ 20X O.D o/ 26
I.D o/ 20X O.D o/ 26
I.D o/ 20X O.D o/ 26
----------------o/ 26.0 (Hole)
o/ 26.0 (Hole)
o/ 26.0 (Hole)
o/ 26.0 (Hole)
50 (equivalent length 70 m)
30
Both liquid and gas piping
140
200
200
FHY50BVE × 3
FHY71BVE × 3
FHY50BVE × 4
R140LUY1
R200KUY1
R200KUY1
VE: 1 Phase, 220–240/220 V, 50/60 Hz Y1: 3 Phase, 380–415 V,50 Hz
kW
14.5/14.2
22.5/22.2
22.5/22.2
Btu/h
49,600/48,400
76,800/75,800
76,800/75,800
kcal/h
12,500/12,200
19,400/19,100
19,400/19,100
kW
5.17/5.17
7.7/7.6
7.7/7.6
Power consumption 1a/1b
White
Colour
Indoor
m3/min
13
17
13
Airflow rate (H)
unit 3
cfm
458
600
458
dB(A)
38/33
39/35
38/33
Sound level (H/L) 2
mm
195X 960X 680
195X 1,160X 680
195X 960X 680
Dimensions (HX WX D)
kg
24
27
24
Machine weight
14 to 25
Certified operation range °CWB
Ivory white
Colour
Outdoor
Hermetically sealed scroll type
Compressor Type
unit
4.50
5.5
5.5
kW
Motor output
4.1 (Charged for 30 m)
5.3 (Charged for 5 m)
5.3 (Charged for 5 m)
kg
Refrigerant charge (R-22)
60
60
dB(A)
54
Sound level 2
mm
1,345X 900X 320
1,220X 1,280X 690
1,220X 1,280X 690
Dimensions (HX WX D)
kg
109
178
178
Machine weight
-5 to 52
Certified operation range °CDB 21 to 46, -15 to 46 4 (Option installed)
mm
Piping
Liquid (Flare)
o/ 9.5
o/ 12.7
o/ 12.7
connections Gas
mm
o/ 25.4 (Flange)
o/ 25.4 (Flange)
o/ 19.1 (Flare)
mm
Drain Indoor unit
I.D o/ 20X O.D o/ 26
I.D o/ 20X O.D o/ 26
I.D o/ 20X O.D o/ 26
----------------Outdoor unit mm
o/ 26.0 (Hole)
m
50 (equivalent length 70 m)
Max. interunit piping length
30
m
Max. installation level difference
Both liquid and gas piping
Heat insulation
Indoor unit
Model
Name
Outdoor unit
Power supply
Cooling capacity 1a/1b
250
FHY60BVE × 4
R250KUY1
Model
Name
Power supply
Cooling capacity 1a/1b
Indoor unit
Outdoor unit
Power consumption 1a/1b
Colour
Fan Airflow rate (H)
Indoor
unit 3
External static pressure
Sound level (H) 2
Dimensions (HX WX D)
Machine weight
Certified operation range
Colour
Outdoor
Compressor Type
unit
Motor output
Refrigerant charge (R-22)
Sound level 2
Dimensions (HX WX D)
Machine weight
Certified operation range
Piping
Liquid (Flare)
connections
Gas (Flange)
Drain
Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation
kW
Btu/h
kcal/h
kW
m3/min
cfm
Pa(mmH2O)
dB(A)
mm
kg
°CWB
kW
kg
dB(A)
mm
kg
°CDB
mm
mm
mm
mm
m
m
200
250
200
FDYM04FAV1 × 2
FDYM05FAV1 × 2
FDYM03FAV1 × 3
R200KUY1
R250KUY1
R200KUY1
V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
22.5/22.2
27.1/26.6
22.5/22.2
76,800/75,800
92,500/90,800
76,800/75,800
19,400/19,100
23,300/22,900
19,400/19,100
7.7/7.6
9.9/9.9
8.0/7.9
---------26
35
20
917
1,235
706
98(10)
98(10)
98(10)
39
44
39
295X 1,500X 680
295X 1,500X 680
295X 1,100X 680
56
57
42
14 to 25
Ivory white
Hermetically sealed scroll type
5.5
9.0
5.5
5.3 (Charged for 5 m)
5.7 (Charged for 5 m)
5.3 (Charged for 5 m)
60
61
60
1,220X 1,280X 690
1,440X 1,280X 690
1,220X 1,280X 690
178
202
178
-5 to 52
o/ 12.7
o/ 15.9
o/ 12.7
o/ 25.4
o/ 28.6
o/ 25.4
o/ 25I.D.,o/ 32O.D.
o/ 25I.D.,o/ 32O.D.
o/ 25I.D.,o/ 32O.D.
------------------------50 (equivalent length 70 m)
30
Both liquid and gas piping
Note :
Models R200KU and R250KU are recommended for commercial facilities.
1
Rated cooling capacities are based on the following conditions:
1a
Suction temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
1b
Suction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
2
Anechoic chamber conversion value, measured according to JIS parameters and criteria.
During operation these values are somewhat higher owing to ambient conditions.
3
Values shown are for a single unit only.
27.1/26.6
92,500/90,800
23,300/22,900
9.7/9.7
16
564
38/33
195X 1,160X 680
26
9.0
5.7 (Charged for 5 m)
61
1,440X 1,280X 690
202
o/ 15.9
o/ 28.6 (Flange)
I.D o/ 20X O.D o/ 26
---------
Note :
Models R200KU and R250KU are recommended for commercial facilities.
1
Rated cooling capacities are based on the following conditions:
1a
Indoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
1b
Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (R71LU-R140LU is 7.5 m.)
2
Anechoic chamber conversion value, measured according to JIS parameters and criteria.
During operation these values are somewhat higher owing to ambient conditions.
3
Values shown are for a single unit only.
4
This value is for when year-round cooling kit (option) is installed.
47
48
CEILING MOUNTED CASSETTE TYPE
Outdoor unit
Power supply
Cooling capacity 1a/1b
kW
Btu/h
kcal/h
kW
Btu/h
kcal/h
kW
kW
Heating capacity 2
Cooling 1a/1b
Heating 2
Colour
Unit
Decoration panel
m3/min
Airflow rate (H)
cfm
dB(A)
Sound level (H/L) 3
mm
Dimensions Unit
(H×W×D)
mm
Decoration panel
kg
Machine weight Unit
kg
Decoration panel
°CWB
Cooling
Certified
operation range Heating
°CDB
Colour
Compressor Type
Motor output
kW
Power consumption
Indoor
unit
Outdoor
unit
35
FHYC35KVE
Indoor unit
Model
Name
Refrigerant charge (R-22)
Sound level (Cooling/Heating) 3
Dimensions (H×W×D)
Machine weight
Cooling
Certified
operation range Heating
Piping
Liquid (Flare)
connections
Gas (Flare)
Drain
Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation
kg
71
100
125
140
FHYC71KVE
FHYC100KVE FHYC125KVE FHYC140KVE
RY100LUV1
RY71LUV1
RY35FV1A
RY50GAV1A
RY60GAV1A
RY125LUY1
RY140LUY1
RY71LUY1
RY100LUY1
VE: 1 Phase 220–240/220 V, 50/60 Hz V1: 1 Phase 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
3.79/3.75
5.27/5.2
6.24/6.15
7.8/7.7
10.5/10.4
13.0/12.8
14.5/14.2
12,900/12,800 18,000/17,800 21,300/21,000 26,600/26,200 35,700/35,300 44,500/43,600 49,400/48,400
3,260/3,230
4,530/4,470
5,370/5,290
6,700/6,600
9,000/8,900
11,200/11,000 12,500/12,200
4.22
5.8
7.0
7.9
11.2
14.2
16.3
14,400
19,800
23,900
27,000
38,100
48,400
56,000
3,630
4,990
6,020
6,800
9,600
12,200
14,000
1.51/1.50
1.92/1.91
2.35/2.33
3.01 /3.01 (V1), 2.99/2.99 (Y1) 3.93 /3.93 (V1), 3.88/3.88 (Y1)
4.89/4.89
4.95/4.95
1.37
1.68
2.26
2.84 (V1), 2.82 (Y1) 3.64 (V1), 3.60 (Y1)
4.68
4.84
---------White
14
15
19
19
28
33
35
494
529
670
670
988
1,164
1,235
33/29
33/29
35/30
35/30
39/34
42/36
44/37
230×840×840
230×840×840
230×840×840
230×840×840
288×840×840
288×840×840
288×840×840
40×950×950
40×950×950
40×950×950
40×950×950
40×950×950
40×950×950
40×950×950
24
24
24
24
28
28
28
5
5
5
5
5
5
5
14 to 23
12 to 25
15 to 28
15 to 27
Ivory white
Hermetically sealed rotary type
Hermetically sealed scroll type
1.3
1.7
2.2
2.24
3.00
3.75
4.50
1.12
1.55
1.75
2.8
3.7
3.7
4.1
(Charged for 10 m) (Charged for 10 m) (Charged for 5 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m)
47/48
dB(A)
540×750×270
mm
41
kg
°CDB
°CWB
o/ 6.4
mm
o/ 12.7
mm
mm I.Do/ 25×O.Do/ 32
o/ 18.0 (Hole)
mm
20
m
m
50
FHYC50KVE
49/51
685×800×300
51
19.4 to 46
-10 to 15.5
o/ 6.4
o/ 15.9
I.Do/ 25×O.Do/ 32
o/ 18.0 (Hole)
15
60
FHYC60KVE
54/54
685×880×350
75
48/49
49/52
49/52
54/56
770×900×320 1,170×900×320 1,170×900×320 1,345×900×320
73 (V1), 72 (Y1) 89 (V1), 86 (Y1)
101
112
-5 to 46
-10 to 15
o/ 6.4
o/ 9.5
o/ 9.5
o/ 9.5
o/ 9.5
o/ 15.9
o/ 15.9
o/ 19.1
o/ 19.1
o/ 19.1
I.Do/ 25×O.Do/ 32 I.Do/ 25×O.Do/ 32 I.Do/ 25×O.Do/ 32 I.Do/ 25×O.Do/ 32 I.Do/ 25×O.Do/ 32
o/ 18.0 (Hole)
o/ 26.0 (Hole)
o/ 26.0 (Hole)
o/ 26.0 (Hole)
o/ 26.0 (Hole)
30
50 (equivalent length 70 m)
30
Both liquid and gas piping
CEILING SUSPENDED TYPE
Indoor unit
Model
Name
Outdoor unit
Power supply
Cooling capacity 1a/1b
Heating capacity 2
Power consumption
Indoor
unit
Outdoor
unit
Cooling 1a/1b
Heating 2
Colour
Airflow rate (H)
Sound level (H/L) 3
Dimensions (HX WX D)
Machine weight
Cooling
Certified
operation range Heating
Colour
Compressor Type
Motor output
Refrigerant charge (R-22)
Sound level (Cooling/Heating) 3
Dimensions (HX WX D)
Machine weight
Cooling
Certified
operation range Heating
Piping
Liquid (Flare)
connections
Gas (Flare)
Drain
Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation
35
FHY35BVE
71
100
125
FHY71BVE
FHY100BVE
FHY125BVE
RY71LUV1
RY100LUV1
RY35FV1A
RY50GAV1A
RY60GAV1A
RY125LUY1
RY71LUY1
RY100LUY1
VE: 1 Phase 220–240/220 V, 50/60 Hz V1: 1 Phase 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
kW
3.5/3.5
5.0/4.85
6.3/6.15
7.8/7.7
10.5/10.4
13.0/12.8
12,100/11,900
16,900/16,600
21,400/21,000
26,600/26,200
35,700/35,300
44,500/43,600
Btu/h
3,040/3,000
4,260/4,200
5,390/5,300
6,700/6,600
9,000/8,900
11,200/11,000
kcal/h
4.1
5.5
7.1
7.9
11.2
14.2
kW
14,000
18,800
24,200
27,000
38,100
48,400
Btu/h
3,520
4,750
6,100
6,800
9,600
12,200
kcal/h
2.17/2.16
3.14/3.12
kW
1.58/1.57
3.04/3.04 (V1), 3.02/3.02 (Y1) 3.82/3.82 (V1), 3.77/3.77 (Y1)
4.85/4.85
kW
1.37
1.96
2.94
2.98 (V1), 2.95 (Y1) 3.69 (V1), 3.64 (Y1)
4.77
White
m3/min
13
13
16
17
24
30
cfm
458
458
564
600
847
1,059
dB(A)
37/32
38/33
38/33
39/35
42/37
44/39
mm
195X 960X 680
195X 960X 680
195X 1,160X 680
195X 1,160X 680
195X 1,400X 680
195X 1,590X 680
kg
23
24
26
27
32
35
°CWB
14 to 23
12 to 25
°CDB
15 to 28
15 to 27
Ivory white
Hermetically sealed rotary type
Hermetically sealed scroll type
kW
1.3
1.7
2.2
2.24
3.00
3.75
1.12
1.55
1.75
2.8
3.7
3.7
kg
(Charged for 10 m) (Charged for 10 m) (Charged for 5 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m)
dB(A)
mm
kg
°CDB
°CWB
mm
mm
mm
mm
m
m
47/48
540X 750X 270
41
o/ 6.4
o/ 12.7
I.D o/ 20X O.D o/ 26
o/ 18.0 (Hole)
20
50
FHY50BVE
49/51
685X 800X 300
51
19.4 to 46
-10 to 15.5
o/ 6.4
o/ 15.9
I.D o/ 20X O.D o/ 26
o/ 18.0 (Hole)
15
60
FHY60BVE
54/54
685X 880X 350
75
49/52
49/52
1,170X 900X 320
1,170X 900X 320
89 (V1), 86 (Y1)
101
-5 to 46
-10 to 15
o/ 6.4
o/ 9.5
o/ 9.5
o/ 9.5
o/ 15.9
o/ 15.9
o/ 19.1
o/ 19.1
I.D o/ 20X O.D o/ 26
I.D o/ 20X O.D o/ 26
I.D o/ 20X O.D o/ 26
I.D o/ 20X O.D o/ 26
o/ 18.0 (Hole)
o/ 26.0 (Hole)
o/ 26.0 (Hole)
o/ 26.0 (Hole)
30
50 (equivalent length 70 m)
30
Both liquid and gas piping
Note :
1
Rated cooling capacities are based on the following conditions:
1a
Indoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
1b
Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY140LU is 7.5 m.)
2
Rated heating capacities are based on the following conditions:
Indoor temp., 20°CDB; outdoor temp., 7°CDB, 6°CWB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY140LU is 7.5 m.)
3
Anechoic chamber conversion value, measured according to JIS parameters and criteria.
During operation these values are somewhat higher owing to ambient conditions.
49
48/49
770X 900X 320
73 (V1), 72 (Y1)
CEILING SUSPENDED CASSETTE TYPE
Model
Name
Outdoor unit
Power supply
Cooling capacity 1a/1b
Heating capacity 2
Power consumption
Indoor
unit
71
FUY71FJV1
RY71LUV1
RY71LUY1
Indoor unit
Cooling 1a/1b
Heating 2
Colour
Airflow rate (H)
Sound level (H/L) 3
Dimensions (HX WX D)
Machine weight
Cooling
Certified
operation range Heating
Colour
Outdoor
Compressor Type
unit
Motor output
Refrigerant charge (R-22)
Sound level (Cooling/Heating) 3
Dimensions (HX WX D)
Machine weight
Cooling
Certified
operation range Heating
Piping
Liquid (Flare)
connections
Gas (Flare)
Drain
Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation
kW
Btu/h
kcal/h
kW
Btu/h
kcal/h
kW
kW
m3/min
cfm
dB(A)
mm
kg
°CWB
°CDB
kW
kg
dB(A)
mm
kg
°CDB
°CWB
mm
mm
mm
mm
m
m
100
125
FUY100FJV1
FUY125FJV1
RY100LUV1
RY125LUY1
RY100LUY1
V1: 1 Phase 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
7.8/7.7
13.0/12.8
10.5/10.4
26,600/26,200
44,500/43,600
35,700/35,300
6,700/6,600
11,200/11,000
9,000/8,900
7.9
11.2
14.2
27,000
38,100
48,400
6,800
12,200
9,600
4.90/4.90
3.02/3.02 (V1), 3.00/3.00 (Y1)
3.99/3.99 (V1), 3.94/3.94 (Y1)
4.61
2.87 (V1), 2.84 (Y1)
3.66 (V1), 3.62 (Y1)
White
19
29
32
670
1,023
1,129
40/35
43/38
44/39
165X 895X 895
230X 895X 895
230X 895X 895
25
31
31
12 to 25
15 to 27
Ivory white
Hermetically sealed scroll type
2.24
3.00
3.75
2.8 (Charged for 30 m)
3.7 (Charged for 30 m)
3.7 (Charged for 30 m)
48/49
49/52
49/52
770X 900X 320
1,170X 900X 320
1,170X 900X 320
73 (V1), 72 (Y1)
89 (V1), 86 (Y1)
101
-5 to 46
-10 to 15
o/ 9.5
o/ 9.5
o/ 9.5
o/ 15.9
o/ 19.1
o/ 19.1
I.D o/ 20X O.D o/ 26
o/ 26.0 (Hole)
o/ 26.0 (Hole)
o/ 26.0 (Hole)
50 (equivalent length 70 m)
30
Both liquid and gas piping
CEILING MOUNTED CASSETTE CORNER TYPE
Model
Name
Power supply
Cooling capacity 1a/1b
Heating capacity 2
Indoor unit
Outdoor unit
kW
Btu/h
kcal/h
kW
Btu/h
kcal/h
kW
kW
Cooling 1a/1b
Heating 2
Colour
Unit
Indoor
Decoration panel
unit
m3/min
Airflow rate (H)
cfm
dB(A)
Sound level (H/L) 3
mm
Dimensions Unit
(HX WX D)
mm
Decoration panel
kg
Machine weight Unit
kg
Decoration panel
°CWB
Cooling
Certified
°CDB
operation range Heating
Colour
Outdoor
Compressor Type
unit
Motor output
kW
kg
Refrigerant charge (R-22)
dB(A)
Sound level (Cooling/Heating) 3
mm
Dimensions (HX WX D)
kg
Machine weight
°CDB
Cooling
Certified
°CWB
operation range Heating
mm
Piping
Liquid (Flare)
connections
mm
Gas (Flare)
mm
Drain
Indoor unit
mm
Outdoor unit
m
Max. interunit piping length
m
Max. installation level difference
Heat insulation
Power consumption
35
FHYK35FJV1
45
FHYK45FJV1
60
FHYK60FJV1
RY35FV1A
RY50GAV1A
RY60GAV1A
71
FHYK71FJV1
RY71LUV1
RY71LUY1
V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
3.5/3.5
5.0/4.85
6.3/6.15
7.8/7.7
12,100/11,900
16,900/16,600
21,400/21,000
26,600/26,200
3,040/3,000
4,260/4,200
5,390/5,300
6,700/6,600
4.1
5.5
7.1
7.9
14,000
18,800
24,000
27,000
3,520
4,740
6,080
6,800
1.47/1.46
1.95/1.94
2.87/2.85
3.01/3.01 (V1), 2.99/2.99 (Y1)
1,25
1.72
2.65
2.91 (V1), 2.88 (Y1)
---------White
12
12
17
17
423
423
600
600
39/33
39/34
41/36
41/36
215X 1,110X 710
215X 1,110X 710
215X 1,310X 710
215X 1,310X 710
70X 1,240X 800
70X 1,240X 800
70X 1,440X 800
70X 1,440X 800
30
31
33
33
8.5
8.5
9.5
9.5
14 to 23
12 to 25
15 to 27
15 to 28
Ivory white
Hermetically sealed rotary type
Hermetically sealed scroll type
1.3
1.7
2.2
2.24
1.12 (Charged for 10 m)
1.55 (Charged for 10 m)
1.75 (Charged for 5 m)
2.8 (Charged for 30 m)
47/48
49/51
54/54
48/49
540×750×270
685×800×300
685×880×350
770×900×320
41
51
75
73 (V1), 72 (Y1)
19.4 to 46
-5 to 46
-10 to 15.5
-10 to 15
o/ 6.4
o/ 6.4
o/ 6.4
o/ 9.5
o/ 12.7
o/ 15.9
o/ 15.9
o/ 15.9
I.D o/ 25×O.D o/ 32
I.D o/ 25×O.D o/ 32
I.D o/ 25×O.D o/ 32
I.D o/ 25×O.D o/ 32
o/ 18.0 (Hole)
o/ 18.0 (Hole)
o/ 18.0 (Hole)
o/ 26.0 (Hole)
20
30
50 (equivalent length 70 m)
15
30
Both liquid and gas piping
Note :
1
Rated cooling capacities are based on the following conditions:
1a
Indoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
1b
Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY125LU is 7.5 m.)
2
Rated heating capacities are based on the following conditions:
Indoor temp., 20°CDB; outdoor temp., 7°CDB, 6°CWB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY125LU is 7.5 m.)
3
Anechoic chamber conversion value, measured according to JIS parameters and criteria.
During operation these values are somewhat higher owing to ambient conditions.
50
FLOOR STANDING TYPE
CEILING MOUNTED BUILT-IN TYPE
35
FHYB35FV1
Indoor unit
Model
Name
Outdoor unit
Power supply
Cooling capacity 1a/1b
kW
Btu/h
kcal/h
kW
Btu/h
kcal/h
kW
kW
Heating capacity 2
Cooling 1a/1b
Heating 2
Colour
Unit
Decoration panel
m3/min
Airflow rate (H)
cfm
dB(A)
Sound level (H/L) 3
mm
Dimensions Unit
(HX WX D)
mm
Decoration panel
kg
Machine weight Unit
kg
Decoration panel
°CWB
Cooling
Certified
operation range Heating
°CDB
Colour
Compressor Type
Motor output
kW
Power consumption
Indoor
unit
Outdoor
unit
kg
Refrigerant charge (R-22)
Sound level (Cooling/Heating)
Dimensions (HX WX D)
Machine weight
Cooling
Certified
operation range Heating
Piping
Liquid (Flare)
connections
Gas (Flare)
Drain
Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation
3
dB(A)
mm
kg
°CDB
°CWB
mm
mm
mm
mm
m
m
71
100
125
FHYB71FV1
FHYB100FV1
FHYB125FV1
RY71LUV1
RY100LUV1
RY35FV1A
RY50GAV1A
RY60GAV1A
RY125LUY1
RY71LUY1
RY100LUY1
V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
3.5/3.5
5.0/4.85
6.3/6.15
7.8/7.7
10.5/10.4
13.0/12.8
12,100/11,900
16,900/16,600
21,400/21,000
26,600/26,200
35,700/35,300
44,500/43,600
3,040/3,000
4,260/4,200
5,390/5,300
6,700/6,600
9,000/8,900
11,200/11,000
4.1
5.5
7.1
7.9
11.2
14.2
14,000
18,800
24,200
27,000
38,100
48,400
3,520
4,750
6,100
6,800
9,600
12,200
3.07/3.07 (V1), 3.05/3.05 (Y1) 3.92/3.92 (V1), 3.87/3.87 (Y1)
1.53/1.52
1.97/1.96
2.91/2.89
4.67/4.67
1.34
1.92
2.71
3.06 (V1), 3.03 (Y1) 3.75 (V1), 3.70 (Y1)
4.63
---------White
11.5
14
17
19
27
35
405
494
600
670
953
1,235
38/32
39/34
41/35
41/35
41/35
44/38
300X 700X 800
300X 700X 800
300X 1,000X 800
300X 1,000X 800
300X 1,400X 800
300X 1,400X 800
55X 880X 500
55X 880X 500
55X 1,100X 500
55X 1,100X 500
55X 1,500X 500
55X 1,500X 500
30
31
41
41
51
52
3.5
3.5
4.5
4.5
6.5
6.5
14 to 23
12 to 25
15 to 28
15 to 27
Ivory white
Hermetically sealed rotary type
Hermetically sealed scroll type
1.3
1.7
2.2
2.24
3.00
3.75
1.12
1.55
1.75
2.8
3.7
3.7
(Charged for 10 m) (Charged for 10 m) (Charged for 5 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m)
47/48
540X 750X 270
41
o/ 6.4
o/ 12.7
I.D o/ 25X O.D o/ 32
o/ 18.0 (Hole)
20
45
FHYB45FV1
49/51
685X 800X 300
51
19.4 to 46
-10 to 15.5
o/ 6.4
o/ 15.9
I.D o/ 25X O.D o/ 32
o/ 18.0 (Hole)
15
60
FHYB60FV1
54/54
685X 880X 350
75
48/49
770X 900X 320
73 (V1), 72 (Y1)
49/52
49/52
1,170X 900X 320
1,170X 900X 320
89 (V1), 86 (Y1)
101
-5 to 46
-10 to 15
o/ 6.4
o/ 9.5
o/ 9.5
o/ 9.5
o/ 15.9
o/ 15.9
o/ 19.1
o/ 19.1
I.D o/ 25X O.D o/ 32
I.D o/ 25X O.D o/ 32
I.D o/ 25X O.D o/ 32
I.D o/ 25X O.D o/ 32
o/ 18.0 (Hole)
o/ 26.0 (Hole)
o/ 26.0 (Hole)
o/ 26.0 (Hole)
30
50 (equivalent length 70 m)
30
Both liquid and gas piping
Indoor unit
Outdoor unit
Power Supply
Cooling capacity 1a/1b
Heating capacity 2
Power consumption
Indoor
unit
Cooling 1a/1b
Heating 2
Colour
Airflow rate (H)
Sound level (H/L) 3
Dimensions (HX WX D)
Machine weight
Cooling
Certified
operation range Heating
Colour
Outdoor
Compressor Type
unit
Motor output
Refrigerant charge (R-22)
Sound level (Cooling/Heating) 3
Dimensions (HX WX D)
Machine weight
Cooling
Certified
operation range Heating
Piping
Liquid (Flare)
connections
Gas (Flare)
Drain
Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation
51
Outdoor unit
Cooling capacity 1a/1b
kW
Btu/h
kcal/h
kW
Btu/h
kcal/h
kW
kW
71
FAY71LVE
RY71LUV1
RY71LUY1
VE: 1 Phase, 220–240/220 V, 50/60 Hz
7.8/7.7
26,600/26,200
6,700/6,600
7.9
27,000
6,800
2.92/2.92 (V1), 2.90/2.90 (Y1)
2.85 (V1), 2.82 (Y1)
m3/min
cfm
dB(A)
mm
kg
°CWB
°CDB
19
670
43/37
290X 1,050X 230
13
kW
kg
dB(A)
mm
kg
°CDB
°CWB
mm
mm
mm
mm
m
m
2.24
2.8 (Charged for 30 m)
48/49
770X 900X 320
73 (V1), 72 (Y1)
o/ 9.5
o/ 15.9
I.D o/ 13X O.D o/ 18
o/ 26.0 (Hole)
100
FAY100FAVE
RY100LUV1
RY100LUY1
V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
10.5/10.4
35,700/35,300
9,000/8,900
11.2
38,100
9,600
3.82/ 3.82 (V1), 3.77/ 3.77 (Y1)
3.66 (V1), 3.61 (Y1)
White
23
811
45/41
360X 1,570X 200
26
12 to 25
15 to 27
Ivory white
Hermetically sealed scroll type
3.00
3.7 (Charged for 30 m)
49/52
1,170X 900X 320
89 (V1), 86 (Y1)
-5 to 46
-10 to 15
o/ 9.5
o/ 19.1
I.D o/ 20X O.D o/ 26
o/ 26.0 (Hole)
50 (equivalent length 70 m)
30
Both liquid and gas piping
Note :
1
Rated cooling capacities are based on the following conditions:
(FHYB) 1aSuction temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
1b
Suction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY125LU is 7.5 m.)
(FAY) 1aIndoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
1b
Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 7.5 m (horizontal).
2
Rated heating capacities are based on the following conditions:
(FHYB) Suction temp., 20°CDB; outdoor temp., 7°CDB, 6°CWB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY125LU is 7.5 m.)
(FAY) Indoor temp., 20°CDB; outdoor temp., 7°CDB, 6°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).
3
Anechoic chamber conversion value, measured according to JIS parameters and criteria.
During operation these values are somewhat higher owing to ambient conditions.
kW
Btu/h
kcal/h
kW
Btu/h
kcal/h
kW
kW
Heating capacity 2
Power consumption
Indoor
unit
Cooling 1a/1b
Heating 2
Colour
Airflow rate (H)
Sound level (H/L) 3
Dimensions (HX WX D)
Machine weight
Cooling
Certified
operation range Heating
Colour
Outdoor
Compressor Type
unit
Motor output
Refrigerant charge (R-22)
Sound level (Cooling/Heating) 3
Dimensions (HX WX D)
Machine weight
Cooling
Certified
operation range Heating
Liquid (Flare)
Piping
connections
Gas (Flare)
Drain
Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation
m3/min
cfm
dB(A)
mm
kg
°CWB
°CDB
kW
kg
dB(A)
mm
kg
°CDB
°CWB
mm
mm
mm
mm
m
m
71
100
FVY71LAVE
FVY100LAVE
RY71LUV1
RY100LUV1
RY71LUY1
RY100LUY1
VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz
7.8/7.7
10.5/10.4
26,600/26,200
35,700/35,300
6,700/6,600
9,000/8,900
7.9
11.2
27,000
38,100
6,800
9,600
3.12/3.12 (V1), 3.10/3.10 (Y1)
3.95/3.95 (V1), 3.90/3.90 (Y1)
3.00 (V1), 2.97 (Y1)
3.75 (V1), 3.70 (Y1)
White
18
28
635
988
41/35
46/40
1,850X 600X 270
1,850X 600X 350
39
46
12 to 25
15 to 27
Ivory white
Hermetically sealed scroll type
2.24
3.00
2.8 (Charged for 30 m)
3.7 (Charged for 30 m)
48/49
49/52
770X 900X 320
1,170X 900X 320
73 (V1), 72 (Y1)
89 (V1), 86 (Y1)
-5 to 46
-10 to 15
o/ 9.5
o/ 9.5
o/ 15.9
o/ 19.1
I.D o/ 20X O.D o/ 26
I.D o/ 20X O.D o/ 26
o/ 26.0 (Hole)
o/ 26.0 (Hole)
50 (equivalent length 70 m)
30
Both liquid and gas piping
125
FVY125LAVE
RY125LUY1
Y1: 3 Phase, 380–415 V, 50 Hz
13.0/12.8
44,500/43,600
11,200/11,000
14.2
48,400
12,200
4.99/4.99
4.73
32
1,129
49/43
1,850X 600X 350
47
3.75
3.7 (Charged for 30 m)
49/52
1,170X 900X 320
101
o/ 9.5
o/ 19.1
I.D o/ 20X O.D o/ 26
o/ 26.0 (Hole)
DUCT CONNECTION LOW STATIC PRESSURE TYPE
Indoor unit
Model
Name
WALL MOUNTED TYPE
Model
Name
Indoor unit
Model
Name
Outdoor unit
Power supply
Cooling capacity 1a/1b
kW
Btu/h
kcal/h
kW
Btu/h
kcal/h
kW
kW
Heating capacity 2
Power consumption
Indoor
unit
Cooling 1a/1b
Heating 2
Colour
Airflow rate (H)
Fan
Outdoor
unit
External static pressure
Driving system
Sound level (H/L) 3
Dimensions(HX WX D)
Machine weight
Cooling
Certified
operation range Heating
Colour
Compressor Type
Motor output
dB(A)
mm
kg
°CWB
°CDB
kW
kg
Refrigerant charge (R-22)
Sound level (Cooling/Heating)
Dimensions (HX WX D)
Machine weight
Cooling
Certified
operation range Heating
Piping
Liquid (Flare)
connections
Gas (Flare)
Drain
Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation
m3/min
cfm
Pa(mmH2O)
3
dB(A)
mm
kg
°CDB
°CWB
mm
mm
mm
mm
m
m
35
FDYB35KAVE
50
FDYB50KAVE
60
FDYB60KAVE
71
FDYB71KAVE
RY71LUV1
RY35FV1A
RY50GAV1A
RY60GAV1A
RY71LUY1
VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
3.79/3.75
5.27/5.20
6.24/6.15
7.8/7.7
12,900/12,800
18,000/17,800
21,300/21,000
26,600/26,200
3,260/3,230
4,530/4,470
5,370/5,290
6,700/6,600
4.22
5.80
7.0
7.9
14,400
23,900
27,000
19,800
3,630
4,990
6,020
6,800
1.51/1.50
2.01/2.00
2.38/2.36
3.08/3.08 (V1), 3.06/3.06 (Y1)
1.33
1.78
2.29
2.91 (V1), 2.88 (Y1)
---------13
18
460
635
20 (2)
Direct drive (2 speed)
41/ 38
43/ 40
260X 900X 580
260X 1,300X 580
22
23
31
14 to 23
12 to 25
15 to 28
15 to 27
Ivory white
Hermetically sealed rotary type
Hermetically sealed scroll type
1.3
1.7
2.2
2.24
1.12
1.55
1.75
2.8
(Charged for 10 m)
(Charged for 10 m)
(Charged for 5 m)
(Charged for 30 m)
47/48
540X 750X 270
41
49/51
685X 800X 300
51
19.4 to 46
-10 to 15.5
o/ 6.4
o/ 15.9
54/54
685X 880X 350
75
o/ 6.4
o/ 12.7
o/ 6.4
o/ 15.9
48/49
770X 900X 320
73 (V1), 72 (Y1)
-5 to 46
-10 to 15
o/ 9.5
o/ 15.9
3/4B
o/ 18.0 (Hole)
20
o/ 18.0 (Hole)
Note :
1
Rated cooling capacities are based on the following conditions:
(FVY) 1aIndoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
1b
Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 7.5 m (horizontal).
(FDYB) 1aSuction temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
1b
Suction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
2
Rated heating capacities are based on the following conditions:
(FVY) Indoor temp., 20°CDB; outdoor temp., 7°CDB, 6°CWB. Equiv. refrigeration piping, 7.5 m (horizontal).
(FDYB) Suction temp., 20°CDB; outdoor temp., 7°CDB, 6°CWB. Equiv. refrigeration piping, 5 m (horizontal).
3
Anechoic chamber conversion value, measured according to JIS parameters and criteria.
During operation these values are somewhat higher owing to ambient conditions.
o/ 18.0 (Hole)
30
15
o/ 26.0 (Hole)
50 (equivalent length 70 m)
30
Both liquid and gas piping
52
Simultaneous operation system
TWIN & TRIPLE & DOUBLE TWIN MULTI
DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE
Model
Name
Outdoor unit
Power supply
Cooling capacity 1a/1b
kW
Btu/h
kcal/h
kW
Btu/h
kcal/h
kW
kW
Heating capacity 2
Power consumption
Indoor
unit
71
FDYM03FAV1
RY71LUV1
RY71LUY1
Indoor unit
Cooling 1a/1b
Heating 2
Colour
Fan Airflow rate (H)
m3/min
cfm
External static pressure Pa(mmH2O)
dB(A)
Sound level (H) 3
mm
Dimensions (HX WX D)
kg
Machine weight
°CWB
Cooling
Certified
operation range Heating
°CDB
Colour
Outdoor
Compressor Type
unit
Motor output
kW
kg
Refrigerant charge (R-22)
dB(A)
Sound level (Cooling/Heating) 3
mm
Dimensions (HX WX D)
kg
Machine weight
°CDB
Cooling
Certified
operation range Heating
°CWB
mm
Piping
Liquid (Flare)
connections
mm
Gas (Flare)
mm
Drain
Indoor unit
mm
Outdoor unit
m
Max. interunit piping length
m
Max. installation level difference
Heat insulation
100
125
140
FDYM04FAV1
FDYM05FAV1
FDYM06FAV1
RY100LUV1
RY125LUY1
RY140LUY1
RY100LUY1
V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
7.8/7.7
10.5/10.4
13.0/12.8
14.5/14.2
26,600/26,200
35,700/35,300
44,500/43,600
49,400/48,400
6,700/6,600
9,000/8,900
11,200/11,000
12,500/12,200
7.9
11.2
14.2
16.3
27,000
38,100
48,400
56,000
6,800
9,600
12,200
14,000
3.19/3.19 (V1), 3.17/3.17 (Y1) 4.00/4.00 (V1), 3.95/3.95 (Y1)
4.99/4.99
5.10/5.10
2.95 (V1), 2.92 (Y1)
3.91 (V1), 3.86 (Y1)
4.75
4.96
---------20
26
35
37
706
917
1,235
1,306
98 (10)
98 (10)
98 (10)
98 (10)
39
39
44
46
295X 1,100X 680
295X 1,500X 680
295X 1,500X 680
295X 1,500X 680
42
56
57
57
12 to 25
15 to 27
Ivory white
Hermetically sealed scroll type
2.24
3.00
3.75
4.50
2.8 (Charged for 30 m)
3.7 (Charged for 30 m)
3.7 (Charged for 30 m)
4.1 (Charged for 30 m)
48/49
49/52
49/52
54/56
770X 900X 320
1,170X 900X 320
1,170X 900X 320
1,345X 900X 320
73 (V1), 72 (Y1)
89 (V1), 86 (Y1)
101
112
-5 to 46
-10 to 15
o/ 9.5
o/ 9.5
o/ 9.5
o/ 9.5
o/ 15.9
o/ 19.1
o/ 19.1
o/ 19.1
I.Do/ 25X O.Do/ 32
I.Do/ 25X O.Do/ 32
I.Do/ 25X O.Do/ 32
oI.Do/ 25X O.Do/ 32
o/ 26.0 (Hole)
o/ 26.0 (Hole)
o/ 26.0 (Hole)
o/ 26.0 (Hole)
50 (equivalent length 70 m)
30
Both liquid and gas piping
DUCT CONNECTION HIGH STATIC PRESSURE TYPE
Model
Name
Power supply
Cooling capacity 1a/1b
kW
Btu/h
kcal/h
kW
Btu/h
kcal/h
kW
kW
Heating capacity 2
Power consumption
Indoor
unit
Cooling 1a/1b
Heating 2
Colour
Airflow rate (H)
Fan
Outdoor
unit
140
FDY06KAY1
RY140LUY1
Indoor unit
Outdoor unit
External static pressure
Driving system
Sound level (H) 3
Dimensions(HX WX D) 5
Machine weight
Cooling
Certified
operation range Heating
Colour
Compressor Type
Motor output
dB(A)
mm
kg
°CWB
°CDB
kW
kg
Refrigerant charge (R-22)
Sound level (Cooling/Heating)
Dimensions (HX WX D)
Machine weight
Cooling
Certified
operation range Heating
Piping
Liquid (Flare)
connections
Gas
Drain
Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation
m3/min
cfm
Pa(mmH2O)
3
dB(A)
mm
kg
°CDB
°CWB
mm
mm
mm
mm
m
m
200
250
400
500
FDY08KAY1
FDY10KAY1
FDY15KAY1
FDY20KAY1
RY200KUY1
RY250KUY1
RY200KUY1X 2
RY250KUY1X 2
Y1: 3 phase, 380–415 V (4 wires), 50 Hz
14.5/14.2
22.5/22.2
27.6/27.1
44.0/43.5
53.9/53.0
49,500/48,500
76,800/75,700
94,200/92,500
150,000/148,000
184,000/181,000
12,500/12,220
19,300/19,100
23,700/23,300
37,800/37,400
46,400/45,600
15.3
23.2
29.5
44.8
56.8
52,200
100,700
153,000
194,000
79,200
13,200
20,000
25,400
38,500
48,800
5.14/5.14
7.2/7.1
9.3/9.2
14.4/14.2
18.5/18.3
4.54
6.1
8.8
12.2
17.6
--------52
68
83
136
166
1,835
2,400
2,929
4,800
5,859
118 (12)
147 (15)
108 (11)
Belt drive
51
53
58
60
450X 1,130X 850
500X 1,130X 850
500X 1,330X 850
625X 1,620X 850
625X 1,980X 850
80
94
105
161
187
12 to 25
14 to 25
15 to 27
Ivory white
Hermetically sealed scroll type
4.5
5.5
9.0
5.5 X 2
9.0 X 2
4.1
4.0
5.5
4.0
5.5
(Charged for 5 m) X 2
(Charged for 5 m) X 2
(Charged for 30 m)
(Charged for 5 m)
(Charged for 5 m)
54/56
60/62
61/63
60/62 4
61/63 4
1,345X 900X 320
1,220X 1,280X 690
1,440X 1,280X 690
(1,220X 1,280X 690) X 2 (1,440X 1,280X 690) X 2
112
180
206
180 X 2
206 X 2
-5 to 46
0 to 50
0 to 50
-10 to 15
-10 to 15
-10 to 15
o/ 15.9 X 2
o/ 12.7 X 2
o/ 12.7
o/ 15.9
o/ 9.5
o/ 28.6 X 2 (Flange)
o/ 25.4 X 2 (Flange)
o/ 25.4 (Flange)
o/ 28.6 (Flange)
o/ 19.1 (Flare)
1B
3/4B
--------o/ 26.0 (Hole)
50 (equivalent length 70 m)
30
Both liquid and gas piping
Note :
Models RY200KU and RY250KU are recommended for commercial facilities.
1
Rated cooling capacities are based on the following conditions:
1a
Suction temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
1b
Suction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY140LU is 7.5 m.)
2
Rated heating capacities are based on the following conditions:
Suction temp., 20°CDB; outdoor temp., 7°CDB, 6°CWB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY140LU is 7.5 m.)
3
Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.
4
Specification for outdoor unit is for a single unit only.
5
Without control box.
53
CEILING MOUNTED CASSETTE TYPE
Indoor unit
Model
Name
Outdoor unit
Power supply
Cooling capacity 1a/1b
Heating capacity 2
kW
Btu/h
kcal/h
kW
Btu/h
kcal/h
kW
kW
Cooling 1a/1b
Power
consumption
Heating 2
Colour
Unit
Indoor
Decoration panel
unit 3
m3/min
Airflow rate (H)
cfm
dB(A)
Sound level (H/L) 4
mm
Dimensions Unit
(HX WX D)
Decoration panel mm
kg
Machine
Unit
weight
Decoration panel kg
°CWB
Cooling
Certified
operation range Heating
°CDB
Colour
Outdoor
Compressor Type
unit
Motor output kW
Refrigerant charge (R-22)
kg
Sound level (Cooling/Heating) 4 dB(A)
mm
Dimensions (HX WX D)
kg
Machine weight
°CDB
Cooling
Certified
operation range Heating
°CWB
mm
Piping
Liquid (Flare)
connections Gas
mm
mm
Drain Indoor unit
Outdoor unit mm
m
Max. interunit piping length
m
Max. installation level difference
Heat insulation
Indoor unit
Model
Name
Outdoor unit
Power supply
Cooling capacity 1a/1b
Heating capacity 2
71
100
125
140
200
250
FHYC35KVEX 2
FHYC50KVEX 2
FHYC60KVEX 2
FHYC71KVEX 2
FHYC100KVEX 2
FHYC125KVEX 2
RY71LUV1
RY100LUV1
RY125LUY1
RY140LUY1
RY200KUY1
RY250KUY1
RY71LUY1
RY100LUY1
VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
7.8/7.7
10.5/10.4
13.0/12.8
14.5/14.2
22.5/22.2
27.1/26.6
26,600/26,200
35,700/35,300
44,500/43,600
49,400/48,400
76,800/75,800
92,500/90,800
6,700/6,600
9,000/8,900
11,200/11,000
12,500/12,200
19,400/19,100
23,300/22,900
7.9
11.2
14.2
16.3
22.7
28.4
27,000
38,100
48,400
56,000
77,500
97,000
6,800
9,600
12,200
14,000
19,500
24,400
4.94/4.94
4.95/4.95
7.7/7.6
9.7/9.7
3.11/3.11 (V1), 3.09/3.09 (Y1) 3.98/3.98 (V1), 3.93/3.93 (Y1)
2.94 (V1), 2.92 (Y1) 3.69 (V1), 3.65 (Y1)
4.73
4.84
6.5
9.2
------------White
14
15
19
19
28
33
494
529
670
670
988
1,164
33/29
33/29
35/30
35/30
39/34
42/36
230X 840X 840
230X 840X 840
230X 840X 840
230X 840X 840
288X 840X 840
288X 840X 840
40X 950X 950
40X 950X 950
40X 950X 950
40X 950X 950
40X 950X 950
40X 950X 950
24
24
24
24
28
28
5
5
5
5
5
5
12 to 25
14 to 25
15 to 27
15 to 27
Ivory white
Hermetically sealed scroll type
2.24
3.00
3.75
4.50
5.5
9.0
2.8
3.7
3.7
4.1
4.0
5.5
(Charged for 30 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m)
(Charged for 5 m)
(Charged for 5 m)
48/49
770X 900X 320
73 (V1), 72 (Y1)
o/ 9.5
o/ 15.9 (Flare)
I.D o/ 25X O.D o/ 32
o/ 26.0 (Hole)
49/52
49/52
54/56
1,170X 900X 320
1,170X 900X 320
1,345X 900X 320
89 (V1), 86 (Y1)
101
112
-5 to 46
-10 to 15
o/ 9.5
o/ 9.5
o/ 9.5
o/ 19.1 (Flare)
o/ 19.1 (Flare)
o/ 19.1 (Flare)
I.D o/ 25X O.D o/ 32
I.D o/ 25X O.D o/ 32
I.D o/ 25X O.D o/ 32
o/ 26.0 (Hole)
o/ 26.0 (Hole)
o/ 26.0 (Hole)
50 (equivalent length 70 m)
30
Both liquid and gas piping
60/62
61/63
1,220X 1,280X 690
1,440X 1,280X 690
180
206
0 to 50
-10 to 15
o/ 12.7
o/ 15.9
o/ 25.4 (Flange)
o/ 28.6 (Flange)
I.D o/ 25X O.D o/ 32
I.D o/ 25X O.D o/ 32
-----------------
140
FHYC50KVEX 3
RY140LUY1
kW
Btu/h
kcal/h
kW
Btu/h
kcal/h
kW
kW
Cooling 1a/1b
Power
consumption
Heating 2
Colour
Unit
Indoor
Decoration panel
unit 3
m3/min
Airflow rate (H)
cfm
dB(A)
Sound level (H/L) 4
mm
Dimensions Unit
(HX WX D)
Decoration panel mm
kg
Machine
Unit
weight
Decoration panel kg
°CWB
Cooling
Certified
operation range Heating
°CDB
Colour
Outdoor
Compressor Type
unit
Motor output kW
Refrigerant charge (R-22) kg
Sound level (Cooling/Heating) 4 dB(A)
mm
Dimensions (HX WX D)
kg
Machine weight
°CDB
Cooling
Certified
operation range Heating
°CWB
mm
Piping
Liquid (Flare)
connections Gas
mm
mm
Drain Indoor unit
Outdoor unit mm
m
Max. interunit piping length
m
Max. installation level difference
Heat insulation
200
200
250
FHYC71KVEX 3
FHYC50KVEX 4
FHYC60KVEX 4
RY200KUY1
RY200KUY1
RY250KUY1
VE: 1 Phase, 220–240/220 V, 50/60 Hz Y1: 3 Phase, 380–415 V, 50 Hz
14.5/14.2
22.5/22.2
22.5/22.2
27.1/26.6
49,400/48,400
76,800/75,800
76,800/75,800
92,500/90,800
12,500/12,200
19,400/19,100
19,400/19,100
23,300/22,900
16.3
22.7
22.7
28.4
56,000
77,500
77,500
97,000
14,000
19,500
19,500
24,400
4.95/4.95
7.7/7.6
7.7/7.6
9.7/9.7
4.84
6.5
6.5
9.2
------------White
15
19
15
19
529
670
529
670
33/29
35/30
33/29
35/30
230X 840X 840
230X 840X 840
230X 840X 840
230X 840X 840
40X 950X 950
40X 950X 950
40X 950X 950
40X 950X 950
24
24
24
24
5
5
5
5
12 to 25
14 to 25
15 to 27
15 to 27
Ivory white
Hermetically sealed scroll type
4.50
5.5
5.5
9.0
4.1 (Charged for 30 m)
4.0 (Charged for 5 m)
4.0 (Charged for 5 m)
5.5 (Charged for 5 m)
54/56
60/62
60/62
61/63
1,345X 900X 320
1,220X 1,280X 690
1,220X 1,280X 690
1,440X 1,280X 690
112
180
180
206
-5 to 46
0 to 50
-10 to 15
-10 to 15
o/ 12.7
o/ 12.7
o/ 15.9
o/ 9.5
o/ 25.4 (Flange)
o/ 25.4 (Flange)
o/ 28.6 (Flange)
o/ 19.1 (Flare)
I.D o/ 25X O.D o/ 32
I.D o/ 25X O.D o/ 32
I.D o/ 25X O.D o/ 32
I.D o/ 25X O.D o/ 32
------------------------o/ 26.0 (Hole)
50 (equivalent length 70 m)
30
Both liquid and gas piping
Note :
Models RY200KU and RY250KU are recommended for commercial facilities.
1
Rated cooling capacities are based on the following conditions:
1a
Indoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
1b
Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY140LU is 7.5 m.)
2
Rated heating capacities are based on the following conditions:
Indoor temp., 20°CDB; outdoor temp., 7°CDB, 6°CWB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY140LU is 7.5 m.)
3
Values shown are for a single unit only.
4
Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.
54
Simultaneous operation system
TWIN & TRIPLE & DOUBLE TWIN MULTI
CEILING SUSPENDED TYPE
DUCT CONNECTION LOW STATIC PRESSURE TYPE
71
100
125
140
200
250
Indoor unit
FHY35BVE × 2
FHY50BVE × 2
FHY60BVE × 2
FHY71BVE × 2
FHY100BVE × 2
FHY125BVE × 2
Model
RY71LUV1
RY100LUV1
Name
Outdoor unit
RY125LUY1
RY140LUY1
RY200KUY1
RY250KUY1
RY71LUY1
RY100LUY1
Power supply
VE: 1 Phase, 220–240/220 V, 50/60 Hz V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
Cooling capacity 1a/1b
kW
7.8/7.7
10.5/10.4
13.0/12.8
14.5/14.2
22.5/22.2
27.1/26.6
Btu/h
26,600/26,200
35,700/35,300
44,500/43,600
49,400/48,400
76,800/75,800
92,500/90,800
kcal/h
6,700/6,600
9,000/8,900
11,200/11,000
12,500/12,200
19,400/19,100
23,300/22,900
Heating capacity 2
kW
7.9
11.2
14.2
16.3
22.7
28.4
27,000
38,100
48,400
56,000
77,500
97,000
Btu/h
kcal/h
6,800
9,600
12,200
14,000
19,500
24,400
3.14/3.14 (V1)
3.87/3.87 (V1)
Power
1a/1b
9.7/9.7
4.91/4.91
5.10/5.10
7.7/7.6
kW
Cooling
consumption
3.12/3.12 (Y1)
3.82/3.82 (Y1)
9.2
3.08 (V1), 3.05 (Y1) 3.74 (V1),3.69 (Y1)
4.83
4.99
kW
6.5
Heating 2
White
Colour
Indoor
13
13
16
17
24
30
m3/min
Airflow rate (H)
unit 3
458
458
564
600
847
1,059
cfm
37/32
38/33
38/33
39/35
42/37
44/39
dB(A)
Sound level (H/L) 4
195X 960X 680
195X 960X 680
195X 1,160X 680
195X 1,160X 680
195X 1,400X 680
195X 1,590X 680
mm
Dimensions (HX WX D)
23
24
26
27
32
35
kg
Machine weight
°CWB
12 to 25
14 to 25
Cooling
Certified
operation range Heating
°CDB
15 to 27
15 to 27
Ivory white
Colour
Outdoor
Hermetically sealed scroll type
Compressor Type
unit
2.24
3.00
3.75
4.50
5.5
9.0
Motor output kW
2.8
3.7
3.7
4.1
4.0
5.5
Refrigerant charge (R-22) kg
(Charged for 30 m) (Charged for 30 m) (Charged for 30 m) (Charged for 30 m)
(Charged for 5 m)
(Charged for 5 m)
Sound level (Cooling/Heating) 4 dB(A)
mm
Dimensions (HX WX D)
kg
Machine weight
°CDB
Cooling
Certified
operation range Heating
°CWB
mm
Piping
Liquid (Flare)
connections Gas
mm
mm
Drain Indoor unit
Outdoor unit mm
m
Max. interunit piping length
m
Max. installation level difference
Heat insulation
48/49
770X 900X 320
73 (V1), 72 (Y1)
o/ 9.5
o/ 15.9 (Flare)
I.D o/ 20X O.D o/ 26
o/ 26.0 (Hole)
49/52
49/52
54/56
1,170X 900X 320
1,170X 900X 320
1,345X 900X 320
89 (V1), 86 (Y1)
101
112
-5 to 46
-10 to 15
o/ 9.5
o/ 9.5
o/ 9.5
o/ 19.1 (Flare)
o/ 19.1 (Flare)
o/ 19.1 (Flare)
I.D o/ 20X O.D o/ 26
I.D o/ 20X O.D o/ 26
I.D o/ 20X O.D o/ 26
o/ 26.0 (Hole)
o/ 26.0 (Hole)
o/ 26.0 (Hole)
50 (equivalent length 70 m)
30
Both liquid and gas piping
60/62
61/63
1,220X 1,280X 690
1,440X 1,280X 690
180
206
0 to 50
-10 to 15
o/ 12.7
o/ 15.9
o/ 25.4 (Flange)
o/ 28.6 (Flange)
I.D o/ 20X O.D o/ 26
I.D o/ 20X O.D o/ 26
-----------------
Model
Name
Power supply
Cooling capacity 1a/1b
Indoor unit
Outdoor unit
Heating capacity 2
Power consumption
Indoor
unit 3
Cooling 1a/1b
Heating 2
Colour
Airflow rate (H)
Fan External static pressure
Sound level (H) 4
Dimensions (HX WX D)
Machine weight
Cooling
Certified
operation range Heating
Colour
Outdoor
Compressor Type
unit
Motor output
Refrigerant charge (R-22)
Sound level (Cooling/Heating) 4
Dimensions (HX WX D)
Machine weight
Cooling
Certified
operation range Heating
Piping
Liquid
connections
Gas
Drain
Indoor unit
Outdoor unit
Max. interunit piping length
Max. installation level difference
Heat insulation
kW
Btu/h
kcal/h
kW
Btu/h
kcal/h
kW
kW
m3/min
cfm
Pa(mmH2O)
dB(A)
mm
kg
°CWB
°CDB
kW
kg
dB(A)
mm
kg
°CDB
°CWB
mm
mm
mm
mm
m
m
200
200
250
FDYB50KAVE × 4
FDYB71KAVE × 3
FDYB60KAVE × 4
RY200KUY1
RY200KUY1
RY250KUY1
VE: 1 Phase, 220–240/220 V, 50/60 Hz Y1: 3 Phase, 380–415 V, 50 Hz
22.5/22.2
22.5/22.2
27.1/26.6
76,800/75,800
76,800/75,800
92,500/90,800
19,400/19,100
19,400/19,100
23,300/22,900
22.7
22.7
28.4
77,500
77,500
97,000
19,500
19,500
24,400
7.7/7.6
9.7/9.7
7.7/7.6
6.5
9.2
6.5
–––
13
18
18
458
635
635
20 (2)
41
43
43
260X 900X 580
260X 1,300X 580
260X 1,300X 580
23
31
31
14 to 25
14 to 25
14 to 25
15 to 27
15 to 27
15 to 27
Ivory white
Hermetically sealed scroll type
5.5
5.5
9.0
4.0 (Charged for 5 m)
4.0 (Charged for 5 m)
5.5 (Charged for 5 m)
60/62
60/62
61/63
1,220X 1,280X 690
1,220X 1,280X 690
1,440X 1,280X 690
180
206
180
0 to 50
-10 to 15
12.7 (Flare)
12.7 (Flare)
15.9 (Flare)
25.4 (Flange)
25.4 (Flange)
28.6 (Flange)
3/4B
–––
50 (equivalent length 70 m)
30
Both liquid and gas piping
DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE
Model
Indoor unit
Name
Outdoor unit
Power supply
Cooling capacity 1a/1b
Heating capacity 2
Cooling 1a/1b
Power
consumption
Heating 2
Colour
Indoor
Airflow rate (H)
unit 3
140
FHY50BVE × 3
RY140LUY1
kW
Btu/h
kcal/h
kW
Btu/h
kcal/h
kW
kW
m3/min
cfm
dB(A)
mm
kg
°CWB
°CDB
Sound level (H/L) 4
Dimensions (HX WX D)
Machine weight
Cooling
Certified
operation range Heating
Colour
Outdoor
Compressor Type
unit
Motor output kW
Refrigerant charge (R-22) kg
Sound level (Cooling/Heating) 4 dB(A)
mm
Dimensions (HX WX D)
kg
Machine weight
°CDB
Cooling
Certified
operation range Heating
°CWB
mm
Piping
Liquid (Flare)
connections Gas
mm
mm
Drain Indoor unit
Outdoor unit mm
m
Max. interunit piping length
m
Max. installation level difference
Heat insulation
200
200
250
FHY71BVE × 3
FHY50BVE × 4
FHY60BVE × 4
RY200KUY1
RY200KUY1
RY250KUY1
VE: 1 Phase, 220–240/220 V, 50/60 Hz Y1: 3 Phase, 380–415 V, 50 Hz
14.5/14.2
22.5/22.2
22.5/22.2
27.1/26.6
49,400/48,400
76,800/75,800
76,800/75,800
92,500/90,800
12,500/12,200
19,400/19,100
19,400/19,100
23,300/22,900
22.7
22.7
28.4
16.3
77,500
77,500
97,000
56,000
19,500
19,500
24,400
14,000
7.7/7.6
7.7/7.6
9.7/9.7
5.10/5.10
6.5
6.5
9.2
4.99
White
17
16
13
13
600
564
458
458
39/35
38/33
38/33
38/33
195X 1,160X 680
195X 1,160X 680
195X 960X 680
195X 960X 680
27
26
24
24
12 to 25
14 to 25
15 to 27
15 to 27
Ivory white
Hermetically sealed scroll type
4.50
5.5
5.5
9.0
4.1 (Charged for 30 m)
4.0 (Charged for 5 m)
4.0 (Charged for 5 m)
5.5 (Charged for 5 m)
54/56
60/62
60/62
61/63
1,345X 900X 320
1,220X 1,280X 690
1,220X 1,280X 690
1,440X 1,280X 690
112
180
180
206
-5 to 46
0 to 50
-10 to 15
-10 to 15
o/ 12.7
o/ 12.7
o/ 15.9
o/ 9.5
o/ 25.4 (Flange)
o/ 25.4 (Flange)
o/ 28.6 (Flange)
o/ 19.1 (Flare)
I.D o/ 20X O.D o/ 26
I.D o/ 20X O.D o/ 26
I.D o/ 20X O.D o/ 26
I.D o/ 20X O.D o/ 26
------------------------o/ 26.0 (Hole)
50 (equivalent length 70 m)
30
Both liquid and gas piping
Note :
Models RY200KU and RY250KU are recommended for commercial facilities.
1
Rated cooling capacities are based on the following conditions:
1a
Indoor temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
1b
Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY140LU is 7.5 m.)
2
Rated heating capacities are based on the following conditions:
Indoor temp., 20°CDB; outdoor temp., 7°CDB, 6°CWB. Equiv. refrigeration piping, 5 m (horizontal). (RY71LU-RY140LU is 7.5 m.)
3
Values shown are for a single unit only.
4
Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.
55
Model
Indoor unit
Name
Outdoor unit
Power supply
Cooling capacity 1a/1b
Heating capacity 2
Power
consumption
Indoor
unit 3
Cooling 1a/1b
Heating 2
Colour
Fan Airflow rate (H)
kW
Btu/h
kcal/h
kW
Btu/h
kcal/h
kW
kW
m3/min
cfm
External static pressure Pa(mmH2O)
dB(A)
Sound level (H) 4
mm
Dimensions (HX WX D)
kg
Machine weight
°CWB
Cooling
Certified
operation range Heating
°CDB
Colour
Outdoor
Compressor Type
unit
kW
Motor output
kg
Refrigerant charge (R-22)
dB(A)
Sound level (Cooling/Heating) 4
mm
Dimensions (HX WX D)
kg
Machine weight
°CDB
Cooling
Certified
operation range Heating
°CWB
mm
Piping
Liquid (Flare)
connections
mm
Gas
mm
Drain Indoor unit
mm
Outdoor unit
m
Max. interunit piping length
m
Max. installation level difference
Heat insulation
200
250
200
FDYM04FAV1 × 2
FDYM05FAV1 × 2
FDYM03FAV1 × 3
RY200KUY1
RY250KUY1
RY200KUY1
V1: 1 Phase, 220–240 V, 50 Hz Y1: 3 Phase, 380–415 V, 50 Hz
22.5/22.2
27.1/26.6
22.5/22.2
76,800/75,800
92,500/90,800
76,800/75,800
19,400/19,100
23,300/22,900
19,400/19,100
22.7
28.4
22.7
77,500
97,000
77,500
19,500
24,400
19,500
7.7/7.6
9.9/9.9
8.0/7.9
6.5
9.2
6.8
---------26
35
20
917
1,235
706
98 (10)
98 (10)
98 (10)
39
44
39
295X 1,500X 680
295X 1,500X 680
295X 1,100X 680
56
57
42
14 to 25
15 to 27
Ivory white
Hermetically sealed scroll type
5.5
9.0
5.5
4.0 (Charged for 5 m)
5.5 (Charged for 5 m)
4.0 (Charged for 5 m)
60/62
61/63
60/62
1,220X 1,280X 690
1,440X 1,280X 690
1,220X 1,280X 690
180
206
180
0 to 50
-10 to 15
o/ 12.7
o/ 15.9
o/ 12.7
o/ 25.4 (Flange)
o/ 28.6 (Flange)
o/ 25.4 (Flange)
I.D o/ 25X O.D o/ 32
I.D o/ 25X O.D o/ 32
I.D o/ 25X O.D o/ 32
------------------------50 (equivalent length 70 m)
30
Both liquid and gas piping
Note :
Models RY200KU and RY250KU are recommended for commercial facilities.
1
Rated cooling capacities are based on the following conditions:
1a
Suction temp., 27°CDB, 19.5°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal).
1b
Suction temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB. Equiv. refrigeration piping, 5 m (horizontal)
2
Rated heating capacities are based on the following conditions:
Suction temp., 20°CDB; outdoor temp., 7°CDB, 6°CWB. Equiv. refrigeration piping, 5 m (horizontal)
3
Values shown are for a single unit only.
4
Anechoic chamber conversion value, measured according to JIS parameters and criteria.
During operation these values are somewhat higher owing to ambient conditions.
56
CEILING MOUNTED CASSETTE CORNER TYPE
Indoor unit
Kit name
Name of option
CEILING MOUNTED CASSETTE TYPE
Name of option
Remark
Decoration panel
Sealing member for air discharge outlet
Panel spacer
Fresh air intake kit1 Chamber Without the T-joint pipe and fan
type
With the T-joint pipe,without fan
Direct installation type
Chamber connection kit2
High-efficiency filter
(Colorimetric method 65%)
(Colorimetric method 90%)
Replacement
(Colorimetric method 65%)
high-efficiency filter
(Colorimetric method 90%)
High-efficiency filter chamber
Replacement long-life filter
Ultra long-life filter
Replacement ultra long-life filter
Branch duct chamber
Remote controller
Wired type3
Wireless type
Wired LCD remote controller with weekly schedule timer
Central remote controller4
Unified ON/OFF controller4
Schedule timer4
intelligent Touch Controller4
Adaptor for wiring5
Wiring adaptor for electrical appendices5
Interface adaptor for SkyAir series
Installation box for adaptor PCB
Kit name
Heat pump
Cooling only
FHC35K/50K/60K
FHYC35K/50K/60K/71K
FHYC100K/125K/140K
FHYC100K/125K/140K
FHYC35K/50K/60K/71K
BYC125K-W1
KDBHJ55K160
KDBP55H160WA
KDDP55D160
KDDP55D160K
KDDJ55X160
KKSJ55K160
KAFP556D80
KAFP556D160
KAFP557D80
KAFP557D160
KAFP552H80
KAFP552H160
KAFP553H80
KAFP553H160
KDDFP55D160
KAFJ551K160
KAFP55D160
KAFJ55K160H
KDJ55K80
KDJ55K160
BRC1C61
BRC7C612W
BRC1D61
DCS302CA61
DCS301BA61
DST301BA61
DCS601C51
KRP1BA57
KRP4AA53
DTA102A52
KRP1B98
BYC125K-W1
KDBHJ55K160
KDBP55H160WA
KDDP55D160
KDDP55D160K
KDDJ55X160
KKSJ55K160
KAFP556D80
KAFP556D160
KAFP557D80
KAFP557D160
KAFP552H80
KAFP552H160
KAFP553H80
KAFP553H160
KDDFP55D160
KAFJ551K160
KAFP55D160
KAFJ55K160H
KDJ55K80
KDJ55K160
BRC1C61
BRC7C613W
BRC1D61
DCS302CA61
DCS301BA61
DST301BA61
DCS601C51
KRP1BA57
KRP4AA53
DTA102A52
KRP1B98
Note:
1
Refer to page 14 for the details.
2
Required for installing high-efficiency or ultra long-life filter.
3
Wiring for wired remote controller to be procured locally.
4
This optional accessory requires DTA102A52.
5
Installation box for adaptor PCB (KRP1B98) is necessary.
CEILING SUSPENDED TYPE
Kit name
Heat pump
Cooling only
FH(Y)35B FH(Y)50B FH(Y)60B FHY71B FHY100B FHY125B FHY35B FHY50B FHY60B FHY71B FHY100B FHY125B
Replacement long-life filter Resin net
KAFJ501D56
KAFJ501D80
KAFJ501D112 KAFJ501D160
KAFJ501D56
KAFJ501D80
KAFJ501D112 KAFJ501D160
Drain-up kit
KDU50B50VE
KDU50B71VE
KDU50B125VE
KDU50B125VE
KDU50B50VE
KDU50B71VE
L-type piping kit (for upward direction)
KHFJ5F50
KHFJ5F60
KHFJ5F80
KHFJ5F160
KHFJ5F50
KHFJ5F60
KHFJ5F80
KHFJ5F160
Remote controller
Wired type1
BRC1C61
BRC1C61
BRC7E63W
Wireless type
BRC7EA66
Wired LCD remote controller with weekly schedule timer
BRC1D61
BRC1D61
Central remote controller2
DCS302CA61
DCS302CA61
2
Unified ON/OFF controller
DCS301BA61
DCS301BA61
Schedule timer2
DST301BA61
DST301BA61
intelligent Touch Controller2
DCS601C51
DCS601C51
Adaptor for wiring
KRP1BA54
KRP1BA54
Wiring adaptor for electrical appendices3
KRP4AA52
KRP4AA52
Interface adaptor for SkyAir series
DTA102A52
DTA102A52
KRP1CA93
KRP1CA93
Installation box for adaptor PCB
Name of option
Remark
Note:
1
Wiring for wired remote controller to be procured locally.
2
This optional accessory requires DTA102A52.
3
Installation box for adaptor PCB (KRP1CA93) is necessary.
Kit name
Remark
Replacement long-life filter
Sealing member for air discharge outlet1
Decoration panel for air discharge
Vertical flap kit
L-connection piping kit
Remote controller
Wired type2
Wireless type
Wired LCD remote controller with weekly schedule timer
Central remote controller3
Unified ON/OFF controller3
Schedule timer3
intelligent Touch Controller3
Wiring adaptor for electrical appendices4
Interface adaptor for SkyAir series
Installation box for adaptor PCB
Note:
1
Required at time of installation for setting two-way opposing air flow.
2
Wiring for wired remote controller to be procured locally.
3
This optional accessory requires DTA102A52.
4
Installation box for adaptor PCB (KRP1B97) is necessary.
57
Decoration panel
Panel spacer
Air discharge blind panel
Replacement long-life filter Resin net
Discharge grille
Flexible duct with shutter
Remote controller
Wired type1
Wired LCD remote controller with weekly schedule timer
Central remote controller2
Unified ON/OFF controller2
Schedule timer2
intelligent Touch Controller2
Adaptor for wiring (interlock for fresh air intake fan)
Wiring adaptor for electrical appendices
Interface adaptor for SkyAir series
Cooling only
FUY71FJ
FUY100FJ/125FJ
KAFJ495F140
KDBHJ49F80
KDBHJ49F140
KDBTJ49F80
KDBTJ49F140
KDGJ49F80
KDGJ49F140
KHFJ49F80
KHFJ49F140
BRC1C61
BRC7C529W
BRC1D61
DCS302CA61
DCS301BA61
DST301BA61
DCS601C51
KRP4AA53
DTA102A52
KRP1B97
Heat pump
FUY100FJ/125FJ
KAFJ495F140
KDBHJ49F80
KDBHJ49F140
KDBTJ49F80
KDBTJ49F140
KDGJ49F80
KDGJ49F140
KHFJ49F80
KHFJ49F140
BRC1C61
BRC7C528W
BRC1D61
DCS302CA61
DCS301BA61
DST301BA61
DCS601C51
KRP4AA53
DTA102A52
KRP1B97
FUY71FJ
FHK35F/45F
BYK45FJW1
KPBJ52F56W
KDBJ52F56W
KAFJ521F56
K-HV7AW
KFDJ52F56
Heat pump
FHYK60FJ/71FJ
BYK71FJW1
KPBJ52F80W
KDBJ52F80W
KAFJ521F80
K-HV9AW
KFDJ52F80
BRC1C61
BRC1D61
DCS302CA61
DCS301BA61
DST301BA61
DCS601C51
KRP1B51
KRP4AA51
DTA102A52
Cooling only
FHK60F/FHYK71F
BYK71FJW1
KPBJ52F80W
KDBJ52F80W
KAFJ521F80
K-HV9AW
KFDJ52F80
BRC1C61
BRC1D61
DCS302CA61
DCS301BA61
DST301BA61
DCS601C51
KRP1B51
KRP4AA51
DTA102A52
FHYK35FJ/45FJ
BYK45FJW1
KPBJ52F56W
KDBJ52F56W
KAFJ521F56
K-HV7AW
KFDJ52F56
Note: 1Wiring for wired remote controller to be procured locally.
2
This optional accessory requires DTA102A52.
CEILING MOUNTED BUILT-IN TYPE
Kit name
Heat pump
Cooling only
FHB35F/45F FHB60F/FHYB71F FHYB100F FHYB125F FHYB35F/45F FHYB60F/71F FHYB100F FHYB125F
BYBS125DJW1
BYBS125DJW1
Decoration panel
BYBS45DJW1 BYBS71DJW1
BYBS45DJW1 BYBS71DJW1
KTBJ25K160W
KTBJ25K160W
Service access panel
KTBJ25K56W KTBJ25K80W
KTBJ25K56W KTBJ25K80W
KAFJ252L160
KAFJ252L160
(Colorimetric method 65%)
KAFJ252L56 KAFJ252L80
KAFJ252L56 KAFJ252L80
High-efficiency filter
KAFJ253L160
KAFJ253L160
(Colorimetric method 90%)
KAFJ253L56 KAFJ253L80
KAFJ253L56 KAFJ253L80
KAFJ251K160
KAFJ251K160
Replacement long-life filter Resin net
KAFJ251K56 KAFJ251K80
KAFJ251K56 KAFJ251K80
KAJ25L160D
KAJ25L160D
Filter chamber for bottom suction
KAJ25L56D KAJ25L80D
KAJ25L56D KAJ25L80D
KAJ25L160B
KAJ25L160B
Filter chamber for rear suction
KAJ25L56B KAJ25L80B
KAJ25L56B KAJ25L80B
KSA-25K160
KSA-25K160
Canvas duct
KSA-25K56 KSA-25K80
KSA-25K56 KSA-25K80
(o/ 150)
K-DG4DW
K-DG5DW
K-DG4DW
K-DG5DW
K-DG4DW
K-DG5DW
K-DG4DW
K-DG5DW
Discharge grille
(o/ 200)
K-DG7DW
K-DG9DW
K-DG7DW
K-DG9DW
K-DG7DW
K-DG9DW
K-DG7DW
K-DG9DW
K-DGC5D
K-DGC4D
K-DGC5D
(o/ 150)
K-DGC4D
K-DGC4D
K-DGC5D
K-DGC4D
K-DGC5D
Discharge chamber
(o/ 200)
K-DGC7D
K-DGC9D
K-DGC7D
K-DGC9D
K-DGC7D
K-DGC9D
K-DGC7D
K-DGC9D
K-DDV20A
K-DDV20A
Branch duct
o/ 200 o/ 150
(o/ 150)
K-FDS151D (1 m)
K-FDS152D (2 m)
K-FDS153D (3 m)
K-FDS151D (1 m)
K-FDS152D (2 m)
K-FDS153D (3 m)
Flexible duct
K-FDS154D (4 m)
K-FDS155D (5 m)
K-FDS156D (6 m)
K-FDS154D (4 m)
K-FDS155D (5 m)
K-FDS156D (6 m)
(o/ 200)
K-FDS201D (1 m)
K-FDS202D (2 m)
K-FDS203D (3 m)
K-FDS201D (1 m)
K-FDS202D (2 m)
K-FDS203D (3 m)
K-FDS204D (4 m)
K-FDS205D (5 m)
K-FDS206D (6 m)
K-FDS204D (4 m)
K-FDS205D (5 m)
K-FDS206D (6 m)
KBBJ25K160
KBBJ25K160
Blind board
KBBJ25K56 KBBJ25K80
KBBJ25K56 KBBJ25K80
KDAJ25K140
KDAJ25K140
Adaptor for discharge
KDAJ25K56 KDAJ25K71
KDAJ25K56 KDAJ25K71
KDJ2507K160
KDJ2507K160
Flange for suction
KDJ2507K56 KDJ2507K80
KDJ2507K56 KDJ2507K80
Remote controller
Wired type1
BRC1C61
BRC1C61
Wired LCD remote controller with weekly schedule timer
BRC1D61
BRC1D61
Central remote controller2
DCS302CA61
DCS302CA61
2
Unified ON/OFF controller
DCS301BA61
DCS301BA61
Schedule timer2
DST301BA61
DST301BA61
intelligent Touch Controller2
DCS601C51
DCS601C51
Adaptor for wiring (interlock for fresh air intake fan)
KRP1BA54
KRP1BA54
Wiring adaptor for electrical appendices3
KRP4AA51
KRP4AA51
Interface adaptor for SkyAir series
DTA102A52
DTA102A52
Name of option
Remark
Note: 1Wiring for wired remote controller to be procured locally. 2This optional accessory requires DTA102A52.
3
Installation box for adaptor PCB (KRP1B97) is necessary.
WALL MOUNTED TYPE
Kit name
Name of option
FAY71L
K-KDU572CVE
Wired type1
Wireless type
Wired LCD remote controller with weekly schedule timer
Central remote controller
Unified ON/OFF controller
Schedule timer
intelligent Touch Controller
Wiring adaptor for electrical appendices (2)
Interface adaptor for SkyAir series3
Installation box for adaptor PCB
1
3
Heat pump
Cooling only
Remark
Drain-up kit
Remote controller
CEILING SUSPENDED CASSETTE TYPE
Name of option
Remark
FAY100FA
FAY71L
K-KDU572CVE
BRC7C611W
BRC7EA618
BRC1C61
BRC7E619
BRC1C61
BRC7C610W
BRC1D61
BRC1D61
DCS302CA61
DCS301BA61
DST301BA61
DCS601C51
KRP4AA51 3
FAY100FA
DCS302CA61 2
DCS301BA61 2
DST301BA61 2
DCS601C51 2
KRP4AA51
DTA102A52
DCS302CA61
DCS301BA61
DST301BA61
DCS601C51
KRP4AA51 3
KRP4AA93
DCS302CA61 2
DCS301BA61 2
DST301BA61 2
DCS601C51 2
KRP4A51
DTA102A52
KRP4AA93
Wiring for wired remote controller to be procured locally. 2This optional accessory requires DTA102A52.
Installation box for adaptor PCB (KRP4AA93) is necessary.
FLOOR STANDING TYPE
Kit name
Name of option
Remark
Replacement long-life filter
Wired LCD remote controller with weekly schedule timer
Central remote controller1
Unified ON/OFF controller1
Schedule timer1
intelligent Touch Controller2
Remote controller for 2 remote control system
Adaptor for wiring2
Group control adaptor2
Interface adaptor for SkyAir series
Installation box for adaptor PCB
Note: 1This optional accessory requires DTA102A52.
2
Installation box for adaptor PCB (KRP4A95) is necessary.
Cooling only
FVY71LA/100LA/125LA
KAFJ95L160
BRC1D61
DCS302CA61
DCS301BA61
DST301BA61
DCS601C51
BRC1C61
KRP1BA57
KRP4AA52
DTA102A52
KRP4A95
Heat pump
FVY71LA/100LA/125LA
KAFJ95L160
BRC1D61
DCS302CA61
DCS301BA61
DST301BA61
DCS601C51
BRC1C61
KRP1BA57
KRP4AA52
DTA102A52
KRP4A95
58
DIME N S ION S
(Unit: mm)
Indoor unit
CEILING MOUNTED CASSETTE TYPE
Support for centralised control from else
where., using a PC with a Web browser (Optional)
Special
Function 3
Sending of e-mail alerts to a specified
address when malfunctions occur (Optional)
Special
Function 4
Built-in Ethernet port for connecting to
the Internet or an intranet
55
840
55
295
240
Suspension
bolt
4-M8 M10
5
8
260
270
315
840
80 2 100=200 85
4
1
40
350
2
Special
Function 5
Simple interlock function
Unification
adapter for
computerised
control
[DCS302A52]
Special
Function 4
Unified ON/OFF
and status
monitoring from
the central
monitoring panel
1500mm or more
Required space
1500mm
or more
1500mm
or more
1500mm or more
When the discharge grill is closeout,the required space is
200mm or more.
A
C
FHYC100KVE-140KVE 288 298 195
14-M4 Hole
(prepared hole)
40
50
155
165
40
350
B
230 240 165
55
Branch duct
connection
A
1 Liquid pipe connection
2 Gas pipe connection
3 Drain pipe connection
4 Power supply connection
195
150
Notes:
1
Location of unit's Name Plate
For Main body: Switch Box Cover inside surface of suction grille.
For decoration panel: Panel frame inside surface of suction grille.
2
When installing an optional accessory, refer to the
installation drawings.
For fresh air intake kit
Inspection port is necessary.
For high efficiency filter unit
Inspection port is not necessary.
3
In case of using wireless remote controller, this position will
be a signal receiver. Refer to the drawing of wireless remote
controller in detail.
5 Remote control code and control wiring connection
6 Air discharge grille
7 Air suction grille
8 Port for water supply
9 Corner decoration cover
10 Drain hose
CEILING SUSPENDED TYPE
Special
Function 3
1120 1160
FHY100BVE
1360 1400
FHY125BVE
1550 1590
KIS95
RG71A
RG140A
RG180A
R71LU
R100LU
R125LU
R140LU
KIS95
-------
------KKPJ5F180
-------------
------KPW937A4
KKP937A4 1
-------
KHR58C21
KHD58C21A
-------------
RY35F
RY50G(A)
R60G(A)
KHD58D33
KRK5F80V1 KRK5F140V1 KRK5F160V1
-------
RY71LU
RY100LU
RY125LU
RY140LU
------KKPJ5F180
------------KHR58C21
KHD58C21A
------KHD58D33
-------
Note: 1One set includes 5 pieces for 5units.
A
(Hanging position)
Hanging bolt
4-M8~M10
1
Position : Hole of wall for taking out in piping back
(View from the front)
6
90
155
300 or more
55
(Required space)
13
Kit name
Cooling only
For twin multi
For triple multi
For double twin multi
R200KU
KHD58C23A
KHR58P322H
KHRJ5F224F
R250KU
KHD58C24A
------KHRJ5F280F
Heat pump
RY250KU
RY200KU
KHD58C23A
KHD58C24A
KHR58P322H
------KHRJ5F224F
KHRJ5F280F
80
11
40
5
195
680
B
30 or more
(Service space)
30 or more
(Service space)
4 o/ 45
55
14
The Front
Obstacle
Floor side
Brand name plate
(Note.2)
Drain pipe connection VP20
(For left piping)
6
80
3
Remark
105
15
225
275
-------
R71FU
R100FU
R125FU
10
300
275
Heat pump
For height installaion
Kit name
R35G
R50G
R60G
65
60
8
Necessary for optional interface adaptor for SkyAir series (DTA112BA51) with the Intelligent Touch Controller.
Cooling only
50
Position slit hole for taking out in piping back
(View from the front)
127
HRV
5
(Required space)
D -NET Plus Adapter Indoor Unit
(option) [DCS601A52]
145 60
115 60
FHY71BVE
9
12
85
102
160
185
192 36
FH(Y)60BVE 1120 1160
Number of indoor unit expanded from 64 to 128.
R25J
R35J
170
105
90
18 17 16 142 58
65
960
135
920
40
FH(Y)50BVE
From the floor side 2500 or more 155
Trouble
reports
Outdoor unit
Drain piping kit
Central drain plug
Air direction adjustment grille
Drain plug
Refrigerant branch piping For twin multi
For triple multi
Year-round cooling kit
960
Special
Function 1
Mobile Phone
* Limitations apply to some models and functions.
For details please contact your local sales office.
Remark
B
920
5
135 (Required space)
D -NET
A
FH(Y)35BVE
210
• Connection to power consumption metre
when using power proportional
distribution function. (Optional)
Forced OFF
command from
fire alarm
monitoring panel
260
Pi Port
Trouble reports
Colour LCD Touch panel Icon display
Multilingual (English, French, German,
Spanish, Italian, or Chinese)
59
Branch duct
connection
840
80 2 100=200 85
(Hanging
position)
Forced OFF
contact input
Special
Function 3
Labor saving Overall energy savings
Simplified BMS
Refrigerant branch piping
12-M4 Hole
(prepared hole)
Remote monitoring and control
RS-232C
Name of option
55
[FHYC100KVE-140KVE]
DCS601C51
Yearly schedule
Power proportional distribution* (option)
Auto cool/heat change-over
Temperature Limitation
Name of option
For fresh air intake kit
connection
(direct installation type)
B view
Required space
[FH(Y)C35KVE-71KVE]
55
FH(Y)C35KVE-71KVE
PCMCIA
Flash
Memory
Special
Function 2
80
B
1000 or more
Required space
Special
Function 2
60
160
420
A
New communication functions in the user-friendly icon based
multilingual controller simplity centralised control of the system
• CSV output of
power proportional distribution
results (Optional)
C view
4-4M4 Hole
(prepared hole)
75
3
55
Doubling of number of connectable indoor
unit by adding a D -NET PLUS adapter (Optional)
Branch duct
connection
7
A view
Note:
1
This optional accessory requires DTA102A52.
2
This optional accessory requires DTA107A55.
3
This optional accessory requires KRP1B100.
4
Installation plate for adaptor PCB (KRP4A95) is necessary.
5
In case of using KRC17-2B or field supplied remote controller, 3-Minutes Timer (field supplied) is required.
Special
Function 1
C
165
155
6
40
350
80
BRC1C61
------------BRC4C62
DCS302CA611
DCS301BA611
DST301BA611
DCS601C511
------------KRP1BA573
KRP4AA533
------DTA102A52
KRP1B100
-------------
780 Suspension position
860~890 Ceiling opening
10
95
110
BRC1C61
------------BRC4C62
DCS302CA611
DCS301BA611
DST301BA611
DCS601C511
------------------KRP4AA514
------DTA102A52
-------------------
9
BRC1D61
-------
80 2 100=200 85
150
BRC1C61
------------BRC4C64
DCS302CA611
DCS301BA611
DST301BA611
DCS601C511
------------------KRP4AA514
------DTA102A52
-------------------
300 or less
950
------KRC47-2A
KRC47-4A
-------------------------------------------------------------------------------------
------KRC47-3A KRC47-3A/
KRC17-2B 5
------KRC47-5
------------DCS302CA612
DCS301BA612
DST301BA612
DCS601C512
KRCS01-1B
DTA107A55
-------------------------------------------
BRC1D61
-------
950
860~890 Ceiling opening
680 Suspension position
420
125
150
B
------BRC1C61
------KRC47-2A
------KRC47-4A
------BRC4C62
------DCS302CA611
------DCS301BA611
------DST301BA611
DCS601C511
------------------------------------KRP1BA54
------KRP4AA52 3
------KRP1B100
------DTA102A52
------------KDGF19A45 KDGF19A71 KDGF19A45 KDGF19A71
KKD19A1
KKD19A1
BRC1D61
-------
750
Wired LCD remote controller
Digital remote controller
Digital remote controller for duct heater use
Wireless remote controller
Central remote controller
Unified ON/OFF controller
Schedule timer
intelligent Touch Controller
Remote sensor (for indoor temperature)
Central control adaptor kit
Adaptor for wiring
Wiring adaptor for electrical appendices
Switch box for adaptor kit
Interface adaptor for SkyAir series
Installation box for adaptor PCB
Suction grille
Drain pan cover
------KRC47-1A
BRC1D61
-------
Note3.
06K/08K/
10K
Adjustable(0~550)
------KRC47-1A
Wired LCD remote controller with weekly schedule timer
Remote controller
C
200
Remark
40 A
30 10
Name of option
High static pressure type
Heat pump
Cooling only
FD03K/
FD15K/ FDY06KA/08KA/
04K/05K/
20K
10KA/15KA/20KA
Middle static pressure type
Heat pump
Cooling only
FDMG71A/
FDYM03FA/
FDYM03FA/
100A/125A/
04FA/05FA/
04FA/05FA/
140A/180A
06FA
06FA
Low static pressure type
Heat pump
Cooling only
FDBG25A/ FDBG60A/ FDYB35KA/ FDYB60KA/
35A/50A
71A
50KA
71KA
1000 or more
Required space 165
DUCT CONNECTION TYPE
2
Notes:
1
Location of unit's Name Plate: Bottom of fan housing inside the suction grille.
2
In case of using wireless remote controller, this position will be a signal
3
The remote control code is the standard <about 3 m outside the machine> attached.
(0.5 mm2 2 wicks O.D. 5.4)
(It is attached to VRV.)
7
5
80
105
170
4
1 Air discharge grille
2 Air suction grille
3 Air filter
4 Gas pipe connection
5 Liquid pipe connection
6 Drain pipe conneciton
7 Earth terminal (inside the electric components box) (M4)
8 Suspension bracket
9 Backward piping and wiring connection opening lid
10 Upward piping and wiring connection opening lid
11 Right side pipe connection
12 Left back drain pipe connection
13 Left side drain pipe connection
14 Right side drain pipe connection
15 Hole of wall for taking out in piping back
16 Upward drain pipe connection
17 Upward gas pipe connection
18 Upward liquid pipe connection
60
DIME N S ION S
(Unit: mm)
CEILING MOUNTED BUILT-IN TYPE
1500mm
or more
Suspension
bolt
65
895
1500mm
or more
When closing the discharge grill,the required space is
30mm or more.(Note3)
790 Susension position
A
300 or more
52
1
F
G
H
58
40
165
FUY100FJV1/125FJV1
51
147 177 177 147 125 107 230
6
52
1 Liquid pipe connection
2 Gas pipe connection
3 Drain pipe connection
4 Air outlet
132
1000mm or more
(Required space)
Notes:
1
Location for manufacture's label: on bell mouth.
2
This is where the signal of wireless remote controller is received.
Refer to the drawing of wireless remote controller in detail.
3
When closing the discharge grille (2 or 3 way discharge), direction of
pipe connection will be limited, please refer to Installation manual.
5 Air suction grille
6 Corner decoration cover
7 Right pipe/wiring connection
140
170
200mm
or more
1500mm
or more
8
9
7
65
800
710
290
Dimensions for
full open
front panel
60
80
230
75
30 or more
(Required space)
45
80
3
2
Piping direction
1
Name plate Note)2
50 or more
61
215
50 or more
B
C
D
E
F
G
FH(Y)K35.45F(J)V1
1150 1200 1110
FH(Y)K60.71F(J)V1
1350 1400 1310 2 230=460 720 1440 6-M4 hole
260
Note. 2:
Location of unit's Name plate
For main body: Bottom part of fan housing inside of Air
suction grille.
For decoration panel: Service lid face inside of Air
suction grille.
When installing an optional accessory, refer to the
installation drawings.
For discharge grille
For frexible duct
For panel spacer
For air discharge blind panel
Inspection port is not necessary
520 1240 4-M4 hole
(Requred space)
104
894
2500 or more
For installation
in high spaces
52
Outside line
Notes:
Location of unit's of NAME Plate:
Right side surface of casing
2
In case of using wireless remote
controller, this position will be a
signal receiver. Refer to the
drawing of wireless remote
controller in detail.
80 hole
1
1 Liquid pipe connection
2 Gas pipe connection
3 Drain pipe connection
4 Wire intake
5 Wire intake for remote control cord
6 Grounding terminal (M4 in switch box)
7 Air discharge grille
8 Air suction grille
9 Long life air filter
10 Suspension bracket
105
170
10000 or more
E
Front discharge duct
connection position
(Note.2)
Suspension bolt
4-M8~M10
Required space
120
100
20
140
D
A
65
14.5
10
B (Ceiling opening)
G
7
120 or less
1050
44
5
Piping
direction
(Requred space)
45
20
8
4-M4 hole
9
C
150
250
300
160
230
Fresh air intake position
280
125
100
Approx.400
232
F
190
350
(Suspension position)
500
Piping direction
200mm
or more
20mm
or more
250
65
Liquid pipe connection
Gas pipe connection
Drain pipe connection
Wire intake for remote control cord
Wire intake
Drain hole
Air filter
[FAY71LVE]
Required space
4
20
1
2
3
4
5
6
7
C View
H (Suspension position)
215
A (Suspension position)
Notes:
1
Location of unit's Name Plate:
Fan housing surface inside of filter.
2
When installing an optional accessory, refer to the
installation drawings.
3
Refer to the separate drawing when installing the duct.
WALL MOUNTED TYPE
3
6
20
Fresh air intake position
7
10 Accessory drain elbow
67
5
600
125
(Knockout hole)
A View
148
760 (Ceiling opening)
160 P.C.D
FH(Y)B35FV1/45FV1
FH(Y)B60FV1/71FV1
44
2
1
B View
6-M5 hole
(Circumference)
8 Rear pipe/wiring connection
9 Pipe through cover
CEILING MOUNTED CASSETTE CORNER TYPE
5
L
J
K
H
G
6 65=390 750 650 628 4 150=600
11 65=715 1050 950 927 6 150=900
FHYB100FV1/125FV1 16 65=1040 1450 1328 1328 9 150=1350
18-M5 hole
50 or more
(Required space)
E
80
20
D
G
80
F
B
16
E
A
FUY71FJV1
Height of suspension bracket
4
A
B
C
D
E
F
FH(Y)B35FV1/45FV1 700 485 460 3 150=450 760 800
FH(Y)B60FV1/71FV1 1000 785 760 5 150=750 1060 1100
FHYB100FV1/125FV1 1400 1185 1160 7 150=1050 1460 1500
A
G
Suspension bolt
Sustion air intake position
when installing the duct
(Note.3)
L
(Ceiling opening)
630 (Suspension position) 145
3
H
145
185
D
C
(Ceiling opening)
80
8
110 110
462
30
180
F
C
4
J
K
E
7
5
6
83
109
9
46
2
Service
space
895
790 Susension position
2
5
B
45
57
10
Drain pipe can be raised up to 350mm from the top surface of the product.
Brand name plate (Note)2)
45
115~255
B
A
C
1500mm
or more
2 65=130
10
117
3
1
67
150
200
10
300
245
215
150
135
163
1500mm
or more
33
83
83
Required space
The required ceiling depth varies according to
configration of specific system
195
Drain connection
location for
rear piping
800
595 (Air suction parelcenter)
440
315
25
228
Drain connection
location for
upper piping
60
50
465 or more
Required
installation
space
A
B
C
D
135 120
CEILING SUSPENDED CASSETTE TYPE
6
60
5
4
Approx.345
Approx.390
Approx.475
Mounting location
98
80 hole
Piping and
Wiring intake
1
2
3
4
5
6
7
8
9
Front panel
Front grille
Air outlet
Gas pipe
Liquid pipe
Drain hose
Grounding terminal
Right side pipe connection hole
Left side pipe connection hole
62
DIME N S ION S
(Unit: mm)
WALL MOUNTED TYPE
DUCT CONNECTION LOW STATIC PRESSURE TYPE
Piping direction
A
580
A
A
A
A
A
4
5
45
142
A
53
A
2
110
170
228
360
A
684
664
D
Direction for air filter draw out
50
123
Service space
126
164
134
107
120
120
C
(Suspension bolt pinch)
260
210
(Required space)
120
50
or more
180
100
10
10
50 40
40
50 35
50 30 40 40
Approx. 450
Approx. 580
Approx. 600
6
15
40
50
70
120
1235
120
Ceiling surface
15
60
40
6 6
2
8-5x20 Oval Hole (For wood screw)
5-6x20 Oval Hole (For wood screw)
8
5
13- 5 Hole (For wood screw)
2- 12 Hole (For bolt)
4
60
E
K
(All around)
80 Hole
Piping and wiring
intake
6
29
150
219
236
250 or more
Service space
for air filter
7
127
1
Mounting location
Detail A (Mounting hole for installation plate)
1
2
3
4
5
6
7
8
9
Notes:
1
Location of general rated name plate Right side plate outside surface
2
In case of using wireless remote controller,
this position will be a signal receiver. Refer to the drawing of wireless remote controller in detail.
Front grille
Air filter
Discharge outlet
Gas piping connection
Gas piping connection
Drain piping connection
Earth terminal (M4) (inside cover)
Slit hole for right side piping connection
Slit hole for left side piping connection
FLOOR STANDING TYPE
1
2
3
4
5
6
7
8
Liquid pipe connection
Gas pipe connection
Drain pipe connection
Ground terminal
Switch box
Control wiring intake (for outdoor unit)
Control wiring intake (for remote controller)
Suspension bracket
Note: 1Location of unit's Name Plate: Chamber cap
F
G
H
I
J
16
10
151
L
(All around)
52
16
10
Brand name plate
Note 2.
3
55
8
200
74
317
7
360
9
10 or more
3
1
300 or more
260
1570
3
271
50 or more
(Required space)
137
167
50 or more
(Required space)
595
500
(Suspension bolt pinch)
B
[FAY100FAVE]
A
B
C
D
E
F
G
H
I
J
FDBG25AVE/35AVE/50AVE
900
704
755
3XP150=450
500
3XP150=450
674
688
704
900
K
L
FDYB25KVE/35KAVE/50KAVE
FDBG60AVE/71AVE
900 704 755 3XP150=450
1300 1104 1155 6XP150=900
500
700
3XP150=450 674 688 704 900
6XP150=900 1074 1088 1104 1300
10-M4 12-M4
FDYB60KAVE/71KAVE
1300 1104 1155 6XP150=900
700
6XP150=900 1074 1088 1104 1300
16-M4 18-M4
10-M4 12-M4
Holes
Holes
Holes
Holes
16-M4 18-M4
Holes
Holes
Holes
Holes
DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE
A
3
18
330
A
DETAIL OF CONTROL PANEL
1850
OR
50
1
RE
6
50
95
75
F
G
H
REQUIRED SPACE
3 THROUGH HOLE FOR SIDE PIPING
4 THROUGH HOLE FOR SIDE PIPING
5 THROUGH HOLE FOR SIDE WIRING
6 THROUGH HOLE FOR REAR PIPING/WIRING
7 THROUGH HOLE FOR BOTTOM PIPING/WIRING
8 LIQUID PIPE CONNECTION
5
4
R
0O
R
MO
1 SUCTION GRILL
2 AIR FILTER
D
100
95
63
6
6
541
616
825
34
598
MO
0
15
3
E
2
184
184
9 GAS PIPE CONNECTION
10 DRAIN PIPE CONNECTION
NOTES: 1STICKING LOCATION FOR MANUFACTURE'S LABEL
: ON THE SURFACE OF COVER OF SWITCH BOX
INSIDE THE SUCTION GRILL.
151
8
16
4
51
1350
1153
1137
1121
7XP150=1050
5
305
H
29
6
1
7
20-M4 Holes
(All around)
OR
E
APPROX. 36
200
223
253
D
E
F
G
(All around)
MO
RE
FULL OPEN
POSITION
OF SUCTION
B
GRILL
C
[FDMG71AV1]
305
206
175
123
740 OR MORE
TAKE OUT DIMENSION
OF AIR-FILTER
2
9
126
(Suspension bolt pinch)
2-7X15 OBLONG HOLE
(FOR WOOD SCREW)
50
Service space
1
2
3
4
5
6
7
8
[FDMG100AV1/125AV1/140AV1/180AV1]
Liquid pipe connection
Gas pipe connection
Drain pipe connection
Ground terminal
Switch box
Control wiring intake (for remote controller)
Control wiring intake (for outdoor unit)
Suspension bracket
I
151
8
16
J
K
L
51
M
305
314
677
FIXTURE
(ACCESSARY)
10
C
IN CASE OF FIXING IT AT THE REAR
NORMAL INSTALLATION
TAKE OUT DIRECTION
OF AIR-FILTER
8
8
150
263
280
IN CASE VIBRATION RESISTANCE
IS REQUIRED, FIX IT AT BOTH
THE BOTTOM AND THE REAR.
7
4- 14HOLE
(FOR BOLT)
68
3
300 or more
74
16
10
126
THIS MODEL TO BE FIXED
WITH FIXTURE AS SHOWN BELOW.
IN CASE OF FIXING IT AT THE BOTTOM
150
263
280
215
130
J
130
K
FVY100LAVE/125LAVE 350 44 49 130 190 260 266 322 79 202 229
VIEW
Note: 1Location of unit's Name Plate: Chamber cap
N
A
G
H
1350 1153 1203 1134 1114 7XP150=1050
18-M4
727
FDMG100AV1/125AV1/140AV1 1550 1353 1403 1334 1314 7XP150=1050
FDMG180AV1
1900 1703 1753 1684 1664 9XP150=1350
18-M4
827
827
FDMG71AV1
B
C
D
E
F
Holes
Holes
22-M4
Holes
74
16
10
270 45 50 50 110 180 186 242 57 144 149
600
151
260
381
B
L
146
K
116
J
600
H
(Suspension bolt pinch)
G
55
F
152
212
274
E
427
D
50
C
L
FVY71LAVE
B
680
A
(All around)
I
J
K
L
M
FDMG100AV1/125AV1/140AV1 1550 1353 1337 1321 7XP150=1050
FDMG180AV1
1900 1703 1687 1671 9XP150=1350
N
20-M4
Holes
24-M4
Holes
64
DIME N S ION S
(Unit: mm)
DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE
DUCT CONNECTION HIGH STATIC PRESSURE TYPE
236
220
(OPENING)
680
9
[FD08KY1]
[FD10KY1]
1200 or more
P
72
287
3
7
FDYM03FA
FDYM04FA-06FA
N
P
5xP150=750 16- 7 HOLE
8xP150=1200 22- 7 HOLE
5
J
850
1250
K
14- 7 HOLE
20- 7 HOLE
L
1079
1479
M
1064
1464
DUCT CONNECTION HIGH STATIC PRESSURE TYPE
Q
T
46
V U
3
FD06KY1
FD08KY1
FD10KY1
A
B
756
732
732
35
39
39
C
D
E
F
G
967 5XP.180=900 1130 1180 1230
876 4XP.180=720 1130 1180 1230
1076 5XP.180=900 1330 1380 1430
2-M4 Burring holes
(Both sides)
1
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
6-M4
Burring holes
5-M4
Burring holes
6-M4
Burring holes
9
10
10
50
58
58
58
67
67
266
294
294
150
160
160
261
311
311
75
100
100
148
155
155
58
67
67
418
468
468
450
500
500
9
10
10
90
79
79
85
47
47
DUCT CONNECTION HIGH STATIC PRESSURE TYPE
B
35
3
756
3
3
3
9
Service
Space
C
9
9
B
10
850
A
300 or more
850
9
35
6
D
E
E
D
F
G
Air
inlet
9
FD03KY1
FD04KY1
FD05KY1
735
4XP150=600
C
650
900
900
D
E
700 750
950 1000
950 1000
58
9
800 or more
196
[FDY08KAY1]
Service Space
325
[FDY10KAY1]
1200 or more
2-M4 Burring holes
(Both sides)
4 9
2
4
50
50
58
75
85
O
L
K
J
K
L
M
N
450
418
J
90
266
150
9
46
B
2XP120=240
3XP150=450
58
9
[FDY06KAY1]
261
9
3
A
302
552
10
4
58
266
150
2-M4 Burring holes
(Both sides)
3
3
63
148
5
50
2
9
3
1200 or more
9
2-M4 Burring holes
(Both sides)
Arrow View
1
1
2
3
4
5
6
Liquid pipe connection
Gas pipe connection
Drain pipe connection
Earth terminal
Power supply
Suspension bracket
I
50
[FD05KY1]
50
3
63
[FD04KY1]
50
800 or more
[FD03KY1]
Service Space
S
(Both sides)
S
(Both sides)
9
9
D
E
B
A
C
B
A
Air
outlet
H
118
FDYM03FA
FDYM04FA-06FA
H
834
1234
T
Liquid pipe connection
Gas pipe connection
Drain pipe connection
Earth terminal
Power supply
Suspension bracket
130
130
295
130
SUCTION SIDE
(NOTE.1)
2-M4 Burring holes
(Both sides)
R
S
E
F
G
38- 4.7 HOLE 30- 4.7 HOLE 4xP150=600
50- 4.7 HOLE 44- 4.7 HOLE 7xP150=1050
L
M
FDYM03FA
FDYM04FA-06FA
4
(SERVICE SPACE)
1
2
3
4
5
6
4
50
5
2
J
9
[FD06KY1]
3
Service Space
N
A
B
C
D
1100 11xP65=715 15xP65=975 1140
1500 18xP65=1170 21xP65=1365 1540
G
D
C
E
F
I
L
M
FDYM03FA
FDYM04FA-06FA
INSPECTION HOLE 450 OR MORE
1
31
I
K
136
H
(Both sides)
63
E
(ALL ROUND)
145
95
DISCHARGE SIDE
3
H
(Both sides)
NOTES:
1
MOUNT THE AIR FILTER AT THE SUCTION SIDE.
SELECT ITS COLORIMETHOD (GRAVITY METHOD)
50% OR MORE.
58
750 OR MORE
(SERVICE SPACE)
25
680 OR MORE
2
B
O
P
(ALL ROUND)
K
(ALL ROUND)
125
6
850
A
C
D
1 LIQUID PIPE CONNECTION
[ 9.5(FLARE CONNECTION)]
2 GAS PIPE CONNECTION
[03F: 15.9(FLARE CONNECTION)]
[04~06F: 19.1(FLARE CONNECTION)]
3 DRAIN PIPE CONNECTION[VP25]
4 EARTH TERMINAL
(INSIDE SWITCH BOX)
5 POWER SUPPLY
6 SUSPENSION BRACKET
[FOR M10 or M8 BOLT]
7 MANUFACTURER'S LABEL
N
M
L
D
(SUSPENSION POSITION)
C
B
100
6
B
A
H
G
115
100
J
F
(ALL ROUND)
800 or more
600
(SUSPENSION POSITION)
50
210
194
(OPENING)
I
46
P Q
2-M4 Burring holes
(Both sides)
A
FDY06KAY1 756
FDY08KAY1 732
B
35
39
C
9
10
D
967
876
E
F
G
H
5XP180=900 1130 1180 1230
4XP180=720 1130 1180 1230
I
9
10
J
58
67
K
150
160
L
266
294
M
418
468
N
450
500
O
261
311
P
90
79
Q
85
47
FDY10KAY1 732
39
10
1076 5XP180=900 1330 1380 1430
10
67
160
294
468
500
311
79
47
8
1 6 5 7
1
2
3
4
5
6
7
8
9
10
11
Liquid pipe connection
Gas pipe connection
Drain pipe connection
Earth terminal
Hole for power supply
Hole for motor wiring
Hole for wiring from outdoor unit
Hole for remote controller wiring
Control box
Auxiliary pipe
Suspension bracket
Note: 1Location of unit's Name Plate: Lid of control box.
65
66
DIME N S ION S
(Unit: mm)
DUCT CONNECTION HIGH STATIC PRESSURE TYPE
OUTDOOR UNIT // R25JV1, R35JV1
50 or more
12
33
7
Service Space
10
NAME PLATE
19
265
7
4
3
6
5
10
100
50
Service Space
12
190
*1
7- o/ 3.1 holes
(Upward and
downward)
Air
inlet
306
290
95
48
237
60
170
213
*1
10- o/ 3.1 holes
(Upward and downward)
Air
outlet
B
520
DRAIN OUTLETS
10
1045
700
HOLES FOR ANCHOR BOLTS
(M8 OR M10)
5
B
C
D
E
F
G
100 or more
50
Supprting plate
(Commercially available)
800 or more
100 or more
50
OUTDOOR UNIT // R35GV1, RY35FV1A, R50GV1
DUCT CONNECTION HIGH STATIC PRESSURE TYPE
(Commercially available)
150
Evaporator air outlet connection
Evaporator air inlet connection
Liquid pipe connection (No.1)
Gas pipe connection (No.1)
Liquid pipe connection (No.2)
Gas pipe connection (No.2)
Drain pipe connection
Earth terminal
Power supply intake
The holes for anchor bolts
300
544
625
3XP150=450
45
61
763
805
Notes: 1Prepared holes for M4 tapping screw.
38
349
22.5 2XP150=300
257
1
2
3
4
5
6
7
8
9
10
1
10
72
100
530
+4
0
+4
A
B
C
D
E
F
G
500 9XP150=1350 1042 1620 1710 1750 1770
800
or more 11XP150=1650 1762 1980 2070 2110 2220
H
24
54
10
27
SERVICE PORT
MINIMUM SPACE FOR AIR PASSAGE
50
50
100
763
805
Liquid pipe connection (No.1)
Gas pipe connection (No.1)
Liquid pipe connection (No.2)
Gas pipe connection (No.2)
Drain pipe connection
Earth terminal
Hole for power supply
Hole for motor wiring
Hole for wiring from outdoor unit (No.1)
Hole for wiring from outdoor unit (No.2)
Hole for remote controller wiring
Control box
The holes for anchor bolts
58
150
8
38
7
Arrow view (detail)
1
2
3
4
5
6
7
8
9
10
11
12
13
105
300
6
LIQUID STOP VALVE
34
150
*1
4- o/ 3.1 holes
(Both sides)
12
GAS STOP VALVE
35
100
600
850
3XP150=450
2XP150=300 22.5
257
349
FDY15KAY1
FDY20KAY1
11
10
POWER INTAKE
NAME
PLATE
544
625
100
10
Arrow view
3
500 or more
35
*1
3- o/ 3.1 holes
(Both sides)
4
5
[FDY20KAY1]
9
1
540
2
Service Space
14
[FDY15KAY1]
0
EARTH
TERMINAL
(M4)
A
485
12580 80 80
270
H
172
20
45
61
12580 80 80
+4
15
0
71.5
55
193
55
477.5
6
72.5
200 168
750
6
21
LIQUID STOP VALVE
(o/ 6.4CuT)
WALL HEIGHT ON AIR OUTLET SIDE
=LESS THAN 1200
*1
4- o/ 3.1 holes
(Both sides)
2
Supprting plate
12.7
178
GAS STOP VALVE
(o/ A CuT)
MINIMUM SPACE FOR AIR PASSAGE
35
*1
3- o/ 3.1 holes
(Both sides)
50 or more
R35JV1
150
600
850
100
100
35
H
24
54
118
SERVICE PORT
500 or more
50 or more
TERMINAL STRIP
WITH EARTH TERMINAL
78
Service Space
[FD20KY1]
A
B
C
D
E
F
G
FD15KY1 10- o/ 3.1 holes 9XP.150=1350 1042 1620 1710 1750 1770
FD20KY1 12- o/ 3.1 holes 11XP.150=1650 1762 1980 2070 2110 2220
WIRING INLET
50
[FD15KY1]
8
74
800 or more
55
55
125 80 80 80
70
10
10
125 80 80 80
695
9.5
B
C
D
E
F
G
*1
7- o/ 3.1 holes
(Upward and
downward)
R25JV1
50
9
115
560
9
470
H
172
1045
8
A
*1
A
(Upward and downward)
477.5
72.5
8
6XP.150=900
288
100 or more
800 or more
Supprting plate
(Commercially available)
4 –HOLES FOR ANCHOR BOLTS
(M8 OR M10)
420
304
DRAIN OUTLET
(I. D o/ 15.9 HOSE FOR CONNECTION)
100 or more
50 or more
20
Supprting plate
(Commercially available)
50
Notes: 1Prepared holes for M4 tapping screw.
67
68
(Unit: mm)
OUTDOOR UNIT // R71FUY1, RG71AV1/AY1
OUTDOOR UNIT // RY50GAV1A, R60GV1
269
2-DRAIN OUTLET
Hole for anchor
bolt 4-M12
98
37
370
84
44
396
330
350
31
HOLES FOR ANCHOR BOLTS
(M8 OR M10)
30
DIME N S ION S
130
146
800
OUTDOOR
AIR THERMOSTAT
300
15
584
30
540
150
880
30
4
EARTH TERMINAL
(M4)
3
2
POWER INTAKE
816
6
5
5
60
LIQUID PIPE
100
GAS PIPE
84
95
14
49
90
95
195
221
75
49
24
GAS
STOP VALVE
84
95
70
60
SERVICE PORT
UNIT NAME PLATE
7
6
1
UNIT NAME PLATE
LIQUID
STOP VALVE
645
685
7
137
14
Name plate
67
115
102
11
61 11
40
A
Knock hole for lower piping
1 Gas pipe connection
2 Liquid pipe connection
100
50
150
H
275
MINIMUM SPACE FOR AIR PASSAGE
A
50
3 Service port (in the unit)
4 Grounding terminal
50
H
H
H
1000
1000
A
300
600
391
5 Refrigerant piping intake
6 Power supply wiring intake
8
7 Control wiring intake
8 Drain outlet
OUTDOOR UNIT // R(Y)71LUV1/Y1
OUTDOOR UNIT // RY60GAV1A
HOLES FOR ANCHOR BOLTS
(M8 OR M10)
177
120
500
40
TERMINAL COVER
190
OUTDOOR
AIR THERMOSTAT
3-DRAIN OUTLET
881
55
15
140
96
140
620
900
30
3
4
2
1
7
9
6
5
350
EARTH TERMINAL
(M4)
686
770
POWER INTAKE
7
6
5
SERVICE PORT
71
8
100
70 102
A
352
19
80
52
145
13
67
16
58
110
117
120
30
223
53 95
143
54 95
19
16
40
MINIMUM SPACE FOR AIR PASSAGE
100
89
142
UNIT NAME PLATE
100
89
28
145
60
GAS STOP VALVE
329
55
55
LIQUID STOP VALVE
54 95
84 55
40
30
48
55
320
350
(345~355)
410
128
40
370
90
30
Hole for anchor
bolt 4-M12
5
45
376
191
100
69
100
A
1000
350
H
1000
600
H
A
H
1
2
3
4
5
6
7
8
9
Gas pipe connection
Liquid pipe connection
Service port
Grounding terminal
Refrigerant piping outlet
Power supply wiring outlet
Control wiring outlet
Drain outlet
Supplied piping
Note: In some circumstances, with certain machine types,
it may not be possible to attach the supplied piping.
70
DIME N S ION S
(Unit: mm)
OUTDOOR UNIT // R100FUV1/Y1, 125FUY1
30
OUTDOOR UNIT // R(Y)125LUY1, 140LUY1
Hole for anchor
bolt 4-M12
B
C
D
R(Y)125LUY1 1170
A
54
113
579
R(Y)140LUY1 1345
55
—
—
30
Hole for anchor
bolt 4-M12
584
30
48
61
320
350
(345~355)
370
150
41
880
140
96
140
620
900
30
4
30
146
30
35
396
84
38
3
3
2
4
1
7
1
6
2
7
5
6
14
89
24
14
67
115
C
89 19
D
102
8
71
223
80
52
145
13
5 Refrigerant piping intake
6 Power supply wiring intake
OUTDOOR UNIT // R(Y)100LUV1/Y1
3 Service port (in the unit)
4 Grounding terminal M5 (in switch box)
5 Refrigerant piping intake
5
45
7 Control wiring intake
8 Drain outlet
8
1 Gas pipe connection
2 Liquid pipe connection
58
3 Service port(in the unit)
4 Grounding terminal
376
67
16
16
1 Gas pipe connection
2 Liquid pipe connection
Knock hole for lower piping
391
19
142
70 102 117
11
61 11
137
275
40
90
148
95
54
55
410
435
95
54
60
60
95
49
84
95
49
84
24
Name plate
5
B
5
5
568
538
6
60
7
6
A
7
84
1215
5
6 Power supply wiring intake
7 Control wiring intake
191
8 Drain pipe connection
OUTDOOR UNIT // RU06KY1
620
880
140
320
30
3
900
30
36
30
41
620
320
345
80
34
96
140
130
30
130
30
Hole for anchor
bolt 4-M12
320
61
48
350
(345~355)
30
Hole for anchor
bolt 4-M12
4
4
2
3
1
2
7
7
5
54
5
71
376
191
55
406
84
95
95
51
28
53
15
67
15
36
145
58
100
200
Gas pipe connection
Liquid pipe connection
Service port
Grounding terminal
Refrigerant piping outlet
Power supply wiring outlet
Control wiring outlet
Drain outlet
Supplied piping
285
1
2
3
4
5
6
7
8
9
12
12
54
58
117
70 102
45
Note: In some circumstances, with certain machine types,
it may not be possible to attach the supplied piping.
14
137
67
16
5
89
53
name plate
88
13
28
52
145
16
71
376
60
223
80
70.5
8
5
54
95
84 55
6
19
19
142
6
7
435
410
95
157.5
60
89
24
89
5
6
120
6
5
7
7
55
6
1345
7
5
1
148
1170
6
223
9
Knock hole for lower pipng
41
377
8
644
1 Gas pipe connection
2 Liquid pipe connection
3 Service port (in the unit)
4 Grounding terminal M5 (in switch box)
5 Refrigerant piping intake
6 Power supply wiring intake
7 Control wiring intake
8 Drain pipe connection
72
DIME N S ION S
(Unit: mm)
OUTDOOR UNIT // RU08KY1/10KY1
A
30
Hole for anchor
bolt 4-M12
1000
RU08KY1 1220
4- 15 Holls
For anchor bolts
370
RU10KY1 1440
584
30
146
700
35
395
84
38
( Pitch of anchor bolts )
150
880
30
726
( Pitch of anchor bolts )
OUTDOOR UNIT // RG140AY1/180AY1
1290
4
3
2
1
7
1345
6
5
3
A
7
6
4
76
61 11
1440
( for side-roted pipes )
95
A
4- 15mm-dia.holes
( Foundation bolt holes )
220
1000
B
R(Y)200KUY1
228 1220
R(Y)250KUY1
224 1440
( Pitch of anchor bolts )
Notes:
1. The dimensions marked by an asterisk( ) are
those with the installation of the provided pipes.
2.Refer to the installation instructions when the pipes
are routed through the bottom of the unit.
4- 15 Holls
For anchor bolts
1290
95
726
229
1 Liquid pipe conn.
2 Gas pipe conn.
3 Earth terminal
(M5) (in the el.compo. box assy)
4 Wiring intake ( side )
5 Refrigerant piping conn. ( side )
6 Refrigerant piping conn. ( Bottom )
( Pitch of anchor bolts )
71
97
700
RU10KUY1
1000
( Pitch of foundation bolt holes )
( Pitch of foundation bolt holes )
C
1220
80
750
OUTDOOR UNIT // R(Y)200KUY1/250KUY1
700
B
225
54
8 Drain outlet
726
A
76
6 32
name plate
110
6 Power supply wiring intake
7 Control wiring intake
OUTDOOR UNIT // RU08KUY1/10KUY1
RU08KUY1
1280
3 Service port(in the unit)
4 Grounding terminal M5(in switch box)
5 Refrigerant piping intake
8
80
20
5
1 Gas pipe connection
2 Liquid pipe connection
5
391
202
32
690
275
40
137
165
90
165
14
90
14 67
115
2
156
144
60
49
14
102 11
70
1
52 177
90
84
95
49
84
24
name plate
4
5
95
60
538
568
70
5
Notes
The dimension ( with marked )
are attached accessory pipe.
1290
( In case of side conn. )
3
C
3
70
1280
6
750
name plate
(Knock-out hole)
5
110
65
55
13
73
62
97
165
80
90
80
220
155
265
A
(for frontroted pipes)
70
150 80
2
750
1280
690
1 Liquid pipe connection port.
2 Gas pipe connection port.
3 Earth terminal
(M5) (inside of control box)
4 Power cord routing hole ( side )
5 Pipe routing hole ( side )
6 Pipe routing hole ( Bottom )
265
1
34
54
690
1
2
110
A
135
170
(Knock-out hole)
70
4
60
123
150
230
29
32
165
150
90
B
52 177
220
156
70
5
76
4
4
4
B
70
13
97
6
name plate
( In case of front conn. )
1 Liquid pipe conn.
2 Gas pipe conn.
3 Earth terminal
(M5) (in the el.compo. box assy)
4 Wiring intake ( side )
5 Refrigerant piping conn. ( side )
6 Refrigerant piping conn. ( Bottom )
74
DIME N S ION S
(Unit: mm)
[Space required for outdoor unit installation] (Unit: mm)
REMOTE CONTROLLER
Dimensions inside brackets [ ] indicate case where air direction adjustment guide is adjusted downward.
The values represent the case for the R(Y)71 type through R(Y)140 type.
The dimensions in ( ) are for the R(Y)100 and R(Y)140 type (The unit values is mm. )
For R(Y)71LU-140LU
RECEIVER
When there is an obstruction
in the overhead space
When the overhead space is open
157
1. For single unit installation
• RECEIVER
DETAIL
When there is an
obs truc tion on the
inlet s ide
REFRIGERANT
PIPING SIDE
REMOTE CONTROLLER HOLDER
INSTALLATION PROCEDURE
<INSTALLATION TO WALL SURFACE>
When there are
obs truc tions on
both s ides
•
•RECEIVER INSTALLATION PROCEDURE
RECEIVER
FAY100FA
DECORATION PANEL
1. For single unit
installation
s
r les
o
An obs truc tion
in the overhead s pac e
re
mo
or )
50 (100
100
When there are obs truc tions
on the inlet s ide and
ss
or le
both lateral s ides
500
• RECEIVER DETAIL
LIQUID CRYSTAL
REMOTE CONTROLLER
(WIRELESS)
100
or m
ore
100
RECEIVER DETAIL
2-5x9 Slot
18
re
150
or
150
mo
re
When there are obs truc tions
on the inlet s ide and
both lateral
s ides
rm
ore
100
ore
rm
0o )
20 (300
or m
ore
49
1. For single unit
installation
s
ore
An obs truc tion
in the overhead s pac e
500
2. For series installation
(more than two units)
rm
ore
or m
50 (100)
H
ore
rm
0o
or m
ore
or m
200 (300)
100
ss
or le
500
An obs truc tion
in the overhead s pac e
ore
200
• RECEIVER
DETAIL
(Ceiling opening)
or m
2. For series installation
(more than two units)
or le
L
An obs truc tion
in the overhead s pac e
100
0o
Switch box
ore
or m
500
ore
ss
500
H
ore
r les
o
500
0o
70
rm
0o
100
When there is an obstruction
in the overhead space
mo
1. For single unit installation
L
2. For series installation (more than two units)
200
0.5
35
or
L
2. For series installation
(more than two units)
When there are
obs truc tions on
both s ides
RECEIVER
(Ceiling opening)
120
72
83.5
106
The Front
or
500
re
mo
ore
or m
1000 or more
•
• RECEIVER
DETAIL
CEILING SUSPENDED TYPE
•RECEIVER INSTALLATION PROCEDURE
150
1
ore
REMOTE CONTROLLER
HOLDER
When the overhead space is open
2. For series installation
(more than two units)
An obs truc tion
in the overhead s pac e
ore
rm
o
00
or m
When the obstruction on the outlet side is higher than
the unit itself (There is no limit to the height of the
obstruction on the outlet side.)
H
17.5
500
Pattern 1
When the overhead space is open
1. For single unit installation
When there is an
obs truc tion only
on the inlet s ide
When there are obstructions on both
the inlet and outlet sides
H
DRAIN PIPING
SIDE
62
When there is an obstruction
on the outlet side
When there is an obstruction on the inlet side
L
TRANSMITTING PART
WALL MOUNTED TYPE
•RECEIVER INSTALLATION PROCEDURE
FAY71L
RECEIVER
1000 or more
CEILING MOUNTED CASSETTE TYPE
•RECEIVER INSTALLATION PROCEDURE
1000 or more
REMOTE CONTROLLER DIMENSIONS
1000 or more
•
1000 or more
Wireless type
or
ore
rm
0o )
20 (300
mo
re
(field Supplied parts)
ore
rm
0o
100
More than 90
(Srevice space)
Service space for ceiling installation
Note :
Do not install more than 3 receivers in
the vicinity of one another.
With 4 or more units, there is always
the possibility of malfunction
For R(Y)200KU /250KU
In case of single installation
In case of parallel installation
In case of set installation
Wired type
•REMOTE CONTROLLER DIMENSIONS
Pattern 1
•REMOTE CONTROLLER INSTALLATION PROCEDURE
A EXPOSED BODY, EXPOSED CORD B EXPOSED BODY, EMBEDDED CORD
17
CONDUIT
84
120
10
or more
117
38
Pattern 1
300 or more
42
STAPLE
Pattern 1
300 or more
10
or more
FRONT
SIDE
500 or more
10
or more
20 or more
FRONT
SIDE
500 or more
300 or more
10
or more
20 or more
10
or more
20 or more
FRONT
SIDE
FRONT
SIDE
10
or more
10
or more
600 or more
0~5
500 or more
10
or more
20 or more
900 or more
17
18
CORD
OUTLET
HOLE
23 28
Pattern 2
17
CONTROL BOX
C EXPOSED BODY, EMBEDDED CODE
46
100 or more
NOTE) 1. REMOTE CONTROLLER CORD AND STAPLE ARE NOT
ATTACHED. THEY ARE FIELD SUPPLIED PARTS.
50
or more
THROUGH HOLE
(fl12~fl16)
( DISTANCE BETWEEN
REMOTE CONTROLLER
AND CONTROL BOX )
SIZE
0.75~1.25 mm2
TOTAL LENGTH
500 m
100 or more
FRONT
SIDE
500 or more
The height of
obstacle is free
Pattern 3
10
or more
Pattern 2
300 or more
200
or more
124
FRONT
SIDE
500 or more
The height of obstacle is free
50
or more
400 or more
FRONT
SIDE
100 or more
FRONT
SIDE
500 or more
400 or more
KRC47-3A
136
18
FRONT
SIDE
10
or more
FRONT
SIDE
500 or more
20 or more
100 or more
100 or more
Pattern 3
50
or more
100 or more
FRONT
SIDE
500 or more
50
or more
50
or more
50
or more
100 or more
50
or more
100 or more
600 or more
50
or more
50
or more
FRONT
SIDE
500 or more
136
32
124
32
14
61
If the number of units is more than that shown in this manual.
take short circuit into account.
35.50
36
92
85
4
For the service space for front side. take the service space required for field piping into account.
FRONT
SIDE
SUCTION
SIDE
h1
For the service space. if the obstacle of height exceeds the above mentioned dimensions. half of the exceeded
dimensions shall be added to the standard service space.
When installing a unit. choose the most suitable one from this manual depending on actual conditions such as
walking passage and ventilation.
500 mm
3
h2
Front side 1500 mm
Suction side 500 mm
Side No (imitation)
81
81
58
19
Notes:
1
Obstacies height of (Pattern 1) and (Pattern 2) shall be as follows:
2
75
50
or more
300 or more
110
FRONT
SIDE
500 or more
50
or more
* Countries requiring EMC: Shield wire (insulated thickness: 1 mm or more)
KRC47-1A
25
FRONT
SIDE
500 or more
50
or more
(INSULATED THICKNESS: 1 mm OR MORE)
•REMOTE CONTROLLER
KRC47-2A/ KRC47-4A
20 or more
VINYL CORD WITH SHEATH OR CABLE
TYPE
17
10
or more
100 or more
10
or more
10
or more
SPECIFICATIONS OF CORD
•DIGITAL REMOTE CONTROLLER
Pattern 2
1500 mm
120
85
76
MEMO
77
78
Related documents
Daikin FA71FVEK Unit installation
Daikin FA71FVEK Unit installation