Download Carrier 58DFA Instruction manual
Transcript
7 BLWM CAP CFR DSS EAC-1 EAC-2 FU1 FU2 FL GV HFR IDM IDR ILK JB LS PCB PL1 PL2 PL4 PRS TRAN LEGEND ALS CAP BRN BLWM FU2 JB ILK NOTE #5 EAC-2 W EAC-1 HI L1 Y R NOTE #10 HFR TRAN CFR LO COM PR2 L2 PL2 BLK 1 2 WHT AUX. LIMIT SWITCH (OVER TEMP), SPST-(N.C.), MANUAL RESET BLOWER MOTOR CAPACITOR COOLING FAN RELAY, SPDT DRAFT SAFEGUARD SWITCH, SPST-(N.C.), MANUAL RESET ELECTRONIC AIR CLEANER CONNECTION (115VAC) ELECTRONIC AIR CLEANER CONNECTION (COMMON) FUSE, 3 AMP, AUTOMOTIVE BLADE TYPE FUSE, FIELD INSTALLED FUSIBLE LINK GAS VALVE, (REDUNDANT) HEATING FAN RELAY, SPST (N.O.) INDUCED DRAFT MOTOR INDUCER DRAFT RELAY, DPST-(N.O.) BLOWER DOOR INTERLOCK SWITCH, SPST-(N.O.) JUNCTION BOX LIMIT SWITCH (OVER TEMP), SPST-(N.C.), AUTO RESET PRINTED CIRCUIT BOARD (FURNACE CONTROL) 9-CIRCUIT CONNECTOR (PCB1) 2-CIRCUIT CONNECTOR (L1, L2) 5-CIRCUIT PLUG CONNECTOR (BLWM) PRESSURE SWITCH, SPDT TRANSFORMER (115VAC/24VAC) BRN GRN NOTE #4 PL4 4 3 RED 2 BLK 1 WHT C LO MED LO MED HI HI COM GRN WHT BLK FUSED DISCONNECT SWITCH (WHEN REQ'D) IDM RED WHT BLK WHT WHT (WHEN USED) NOTE #7 ALS BLU FL C LS DSS IDR 3AMP FUSE NOTE #8 FU1 PL1 1 4 7 2 5 8 3 6 9 GROUND SCREW REQ'D SEC-1 SEC-2 NC NO FIELD WIRING SCREW TERMINAL PLUG RECEPTACLE FIELD SPLICE EQUIPMENT GROUND FIELD GROUND C PCB NOTE #1 PRS JUNCTION TERMINAL PCB TERMINAL FACTORY POWER WIRING (120VAC) FACTORY CONTROL WIRING (120VAC) FIELD POWER WIRING (120VAC) CONDUCTOR ON PCB G BRN BLU BRN ORN Fig. 9—Unit Wiring Diagram NOTE #9 PR1 BLK PILOT BLK TH BLK GV MGV BLU RED TR WHT RED RED CONNECTION DIAGRAM YEL HFR L2 NOTE #1 PL1-6 FL CFR PRS EAC-2 PL1-4 COM IDR C DSS NOTE #10 4 3 2 1 C FU1 PR-1 TRAN 115VAC BLWM TH HFR PILOT IDR TR MGV GV TIME DELAY LOGIC PL1-8 SEC-2 PR-2 IDM SCHEMATIC DIAGRAM 3A SEC-1 24VAC FUSE NOTE#8 PL1-1 PL1-3 CAP LO MED LO MED HI HI COM PL4 NOTE#4 PL1-2 (WHEN USED) NOTE #7 ALS EAC-1 CFR EQUIPMENT GROUND TO 115V AC FIELD DISCONNECTIONS NOTE #5 PL1-9 NO NC LS IDR NOTE#10 L1 L2 A92176 NOTES: 1. INTERNALLY CONNECTED TO EQUIPMENT GROUND THROUGH MOUNTING SCREW. 2. IF ANY OF THE ORIGINAL EQUIPMENT WIRE IS REPLACED, USE WIRE RATED FOR 105° C. 3. BLOWER MOTOR (BLWM) & INDUCER MOTOR (IDM) CONTAIN AUTO-RESET THERMAL OVERLOAD SWITCH. 4. BLOWER MOTOR FACTORY SPEED SELECTIONS (PL4) ARE FOR AVERAGE CONDITIONS. SEE INSTALLATION INSTRUCTIONS FOR DETAILS ON OPTIMUM SPEED SELECTIONS. 5. USE ONLY COPPER WIRE BETWEEN THE DISCONNECT SWITCH AND THE FURNACE JUNCTION BOX (JB). 6. SYMBOLS ARE ELECTRICAL REPRESENTATIONS ONLY. 7. AUXILIARY LIMIT SWITCH (ALS) USED ON DOWNFLOW MODELS ONLY. 8. THE TRANSFORMER 24VAC WINDING IS PROTECTED BY A 3 AMP AUTOMOTIVE BLADE TYPE FUSE ON THE CONTROL BOARD. A 24VAC SHORT TO GROUND DURING INSTALLATION, CHECKOUT, OPERATION, SERVICE OR MAINTENANCE COULD CAUSE THIS FUSE TO OPEN. DO NOT REPLACE THE 3 AMP FUSE WITH ANY OTHER SIZE FUSE. 9. BLOWER MOTOR (BLWM) ADJUSTABLE OFF-DELAY. FACTORY SET: 120 SECS. CUT RESISTOR: 180 SECS. 10. WHEN CFR RELAY IS ENERGIZED, HFR RELAY IS ALSO ENERGIZED. 319593-401 REV. C C G W Y R PL1-7 L1 PL2 ILK