BLWM
CAP
CFR
DSS
EAC-1
EAC-2
FU1
FU2
FL
GV
HFR
IDM
IDR
ILK
JB
LS
PCB
PL1
PL2
PL4
PRS
TRAN
LEGEND
ALS
CAP
BRN
BLWM
FU2
JB
ILK
NOTE #5
EAC-2
W
EAC-1
HI
L1
Y
R
NOTE #10
HFR
TRAN
CFR
LO
COM
PR2 L2
PL2
BLK 1
2
WHT
AUX. LIMIT SWITCH (OVER TEMP), SPST-(N.C.),
MANUAL RESET
BLOWER MOTOR
CAPACITOR
COOLING FAN RELAY, SPDT
DRAFT SAFEGUARD SWITCH, SPST-(N.C.), MANUAL RESET
ELECTRONIC AIR CLEANER CONNECTION (115VAC)
ELECTRONIC AIR CLEANER CONNECTION (COMMON)
FUSE, 3 AMP, AUTOMOTIVE BLADE TYPE
FUSE, FIELD INSTALLED
FUSIBLE LINK
GAS VALVE, (REDUNDANT)
HEATING FAN RELAY, SPST (N.O.)
INDUCED DRAFT MOTOR
INDUCER DRAFT RELAY, DPST-(N.O.)
BLOWER DOOR INTERLOCK SWITCH, SPST-(N.O.)
JUNCTION BOX
LIMIT SWITCH (OVER TEMP), SPST-(N.C.), AUTO RESET
PRINTED CIRCUIT BOARD (FURNACE CONTROL)
9-CIRCUIT CONNECTOR (PCB1)
2-CIRCUIT CONNECTOR (L1, L2)
5-CIRCUIT PLUG CONNECTOR (BLWM)
PRESSURE SWITCH, SPDT
TRANSFORMER (115VAC/24VAC)
BRN
GRN
NOTE #4
PL4
4
3 RED
2
BLK
1
WHT
C
LO
MED LO
MED HI
HI
COM
GRN
WHT
BLK
FUSED DISCONNECT
SWITCH (WHEN REQ'D)
IDM
RED
WHT
BLK
WHT
WHT
(WHEN USED)
NOTE #7
ALS
BLU
FL
C
LS
DSS
IDR
3AMP
FUSE
NOTE #8
FU1
PL1 1 4 7
2 5 8
3 6 9
GROUND
SCREW
REQ'D
SEC-1
SEC-2
NC
NO
FIELD WIRING SCREW TERMINAL
PLUG RECEPTACLE
FIELD SPLICE
EQUIPMENT GROUND
FIELD GROUND
C
PCB
NOTE #1
PRS
JUNCTION
TERMINAL
PCB TERMINAL
FACTORY POWER WIRING (120VAC)
FACTORY CONTROL WIRING (120VAC)
FIELD POWER WIRING (120VAC)
CONDUCTOR ON PCB
G
BRN
BLU
BRN
ORN
Fig. 9—Unit Wiring Diagram
NOTE #9
PR1
BLK
PILOT
BLK
TH
BLK
GV
MGV
BLU
RED
TR
WHT
RED
RED
CONNECTION
DIAGRAM
YEL
HFR
L2
NOTE #1
PL1-6
FL
CFR
PRS
EAC-2
PL1-4
COM
IDR
C
DSS
NOTE #10
4
3
2
1
C
FU1
PR-1
TRAN
115VAC
BLWM
TH
HFR
PILOT
IDR
TR
MGV GV
TIME
DELAY
LOGIC
PL1-8
SEC-2
PR-2
IDM
SCHEMATIC
DIAGRAM
3A
SEC-1 24VAC
FUSE
NOTE#8
PL1-1
PL1-3
CAP
LO
MED LO
MED HI
HI
COM
PL4
NOTE#4
PL1-2
(WHEN USED)
NOTE #7
ALS
EAC-1
CFR
EQUIPMENT GROUND
TO 115V AC FIELD DISCONNECTIONS
NOTE #5
PL1-9
NO
NC
LS
IDR
NOTE#10
L1
L2
A92176
NOTES:
1. INTERNALLY CONNECTED TO EQUIPMENT GROUND THROUGH MOUNTING SCREW.
2. IF ANY OF THE ORIGINAL EQUIPMENT WIRE IS REPLACED, USE WIRE RATED FOR
105° C.
3. BLOWER MOTOR (BLWM) & INDUCER MOTOR (IDM) CONTAIN AUTO-RESET
THERMAL OVERLOAD SWITCH.
4. BLOWER MOTOR FACTORY SPEED SELECTIONS (PL4) ARE FOR AVERAGE
CONDITIONS. SEE INSTALLATION INSTRUCTIONS FOR DETAILS ON OPTIMUM
SPEED SELECTIONS.
5. USE ONLY COPPER WIRE BETWEEN THE DISCONNECT SWITCH AND THE
FURNACE JUNCTION BOX (JB).
6. SYMBOLS ARE ELECTRICAL REPRESENTATIONS ONLY.
7. AUXILIARY LIMIT SWITCH (ALS) USED ON DOWNFLOW MODELS ONLY.
8. THE TRANSFORMER 24VAC WINDING IS PROTECTED BY A 3 AMP AUTOMOTIVE
BLADE TYPE FUSE ON THE CONTROL BOARD. A 24VAC SHORT TO GROUND
DURING INSTALLATION, CHECKOUT, OPERATION, SERVICE OR MAINTENANCE
COULD CAUSE THIS FUSE TO OPEN. DO NOT REPLACE THE 3 AMP FUSE
WITH ANY OTHER SIZE FUSE.
9. BLOWER MOTOR (BLWM) ADJUSTABLE OFF-DELAY. FACTORY SET: 120 SECS.
CUT RESISTOR: 180 SECS.
10. WHEN CFR RELAY IS ENERGIZED, HFR RELAY IS ALSO ENERGIZED.
319593-401 REV. C
C
G
W
Y
R
PL1-7
L1
PL2
ILK