Download Armor 801 Service manual
Transcript
Installation & Operation Manual Ratings HLW Model Number Note: Change “N” to “L” for L.P. gas models. CSA Input Modulation Btu/hr Water Content Gallons Water Connections Gas Connections (Note 2, 3) Vent/Air Size (Note 1) AWN151PM 30,000 - 150,000 1.3 1-1/4" 1/2" 3"/3" AWN200PM 40,000 - 199,999 1.7 1-1/4" 1/2" 3"/3" AWN286PM 57,000 - 285,000 2.4 2" 3/4" 4"/4" AWN400PM 80,000 - 399,999 3.4 2" 1" 4"/4" AWN501PM 100,000 - 500,000 4.2 2" 1" 4"/4" AWN601PM 120,000 - 600,000 4.2 2" 1" 4"/4" AWN701PM 140,000 - 700,000 5.0 2" 1" 6"/4" AWN801PM 160,000 - 800,000 5.7 2" 1" 6"/4" NOTICE Maximum allowed working pressure is located on the rating plate. Notes: 1. Armor water heaters require special gas venting. Use only the vent materials and methods specified in the Armor Installation and Operation Manual. UNIT EQUIPPED FOR 2. Standard Armor water heaters are equipped to operate from sea level to 4,500 feet only with no adjustments. The water heater will de-rate by 4% for each 1,000 feet above sea level up to 4,500 feet. HIGH ALTITUDE 3,000 FT TO 12,000 FT 3. High altitude Armor water heaters are equipped to operate from 3,000 to 12,000 feet only with no field adjustments. The water heater will de-rate by 2% for each 1,000 feet above 3,000 feet. High altitude models are manufactured with a different control module for altitude operation, but the operation given in this manual remains the same as the standard models. A high altitude label (as shown in FIG. A) is also affixed to the unit. 4. The manual reset high limit provided with the Armor is listed to UL353. The auto reset high limit is listed to ANSI Z21.87. Figure A High Altitude Label Location 7