SiBE12-713 Troubleshooting 5.25 Insufficient Gas Remote Controller Display U0 Outdoor Unit LED Display A5 11 21 34 44 Method of Malfunction Detection Gas shortage detection I: Gas shortage is detected by checking the input current value and the compressor running frequency. If the gas is short, the input current is smaller than the normal value. Gas shortage detection II: Gas shortage is detected by checking the discharge temperature and the opening of the electronic expansion valve. If the gas is short, the discharge temperature tends to rise. Malfunction Decision Conditions Gas shortage detection I (typical value): The following conditions continue for 7 minutes. DC current ≤ 0.035 × output frequency + 0.5 Output frequency > 55 (Hz) Gas shortage detection II: The following conditions continue for 80 seconds. Target opening of the electronic expansion valve ≥ 450 (pulse) Cooling: discharge temperature > 255 / 256 × target discharge temperature +20 (°C) Heating: discharge temperature > 255 / 256 × target discharge temperature +40 (°C) If a gas shortage error takes place 4 times straight, the system will be shut down. The error counter will reset itself if this or any other error does not occur during the following 60-minute compressor running time (total time). Supposed Causes Refrigerant shortage (refrigerant leakage) Poor compression performance of compressor Discharge pipe thermistor disconnected, or indoor unit or outdoor unit heat exchanger thermistor disconnected, room or outside air temperature thermistor disconnected Stop valve closed Electronic expansion valve defective Service Diagnosis 271