Download 601-273E - NSG 3060 User Manual english.indd

Transcript
1
NSG 3060
EMC TEST SYSTEM
USER MANUAL
601-273E
NSG 3060
EMC TEST SYSTEM
USER MANUAL
NSG 3060 EMC test system
CONTENTS
1
2
2.1 3
3.1
3.2 3.3 3.4
3.5 3.6 3.7 4
4.1 4.2 4.3 4.4 4.5 4.6 4.7 5
5.1 5.2 5.3 6
6.1 6.1.1 6.1.2 6.1.3 Explanation of symbols
Introduction
General description
Standards and applications
ESD test
Burst test
Combination wave and ring wave test
Telecommunication wave test
Mains quality test
Magnetic fields with mains frequency (option)
Pulsed magnetic fields (option)
Safety instructions
General
Installation
Installation of an EUT power switch
Applicable safety standards
Test execution
User warnings - Generator
Dangers concerning the EUT
First steps
Installation of the NSG 3060 system
Connecting the test system to the ground reference plane
Mounting in a 19” rack
Mainframe description
Front panel
EUT output connection
Reference ground connector
Surge output sockets
9
10
10
12
12
12
13
14
14
14
15
16
16
17
18
18
19
20
21
22
23
24
24
25
25
25
26
27
6.1.4 Burst output socket
6.1.5 Indicator LEDs
6.1.6 Touch screen and user interface
6.2 Rear panel
6.2.1 Mains power input
6.2.2 AC EUT mains input
6.2.3 DC EUT input
6.2.4 Ground connection point
6.2.5 System interface connector 25 pin D sub
6.2.6 Synchro-Bus system
7
The standard user interface (SUI)
7.1 Main menu
7.2 System window
7.3 General settings
7.4 Equipment
7.5 Communication
7.6 Monitoring
7.6.1 EUT supply voltage, EUT supply frequency
7.6.2 Test action at EUT fail input
7.6.3 EUT power supply by EUT fail input
7.6.4Exit
7.6.5 EUT on
7.6.6 Ok
7.7 SD-card properties
7.7.1 Viewing the current SUI version
7.7.2 Updating SUI software via the SD-card
7.8 Language
8
Setting test parameters
8.1 The red menu bar
8.2 The bottom bar
8.2.1 Load user test
8.2.2 Load standard test
8.2.3 Save test
8.3 Burst generator setting
8.3.1 Test configuration with power line coupling
8.3.2 Test configuration with external coupling
8.3.3 Burst parameters window
27
27
27
28
28
29
30
31
31
32
34
35
36
36
39
39
42
42
42
43
43
43
43
43
44
45
48
49
49
53
53
55
58
61
61
61
62
8.3.4 8.3.5 8.3.6 8.3.7 8.3.8 8.3.9 8.3.10 8.3.11 8.3.12 8.4 8.4.1 8.4.2 8.4.3
8.4.4 8.4.5 8.4.6 8.4.7 8.4.8 8.4.9 8.5 8.5.1 8.5.2 8.5.3 8.5.4 8.5.5 8.5.6 8.5.7 8.5.8 8.5.9
8.5.10
8.6 8.6.1
8.6.2
8.6.3
8.6.4
8.6.5
8.6.6
Voltage
Frequency
Phase
Coupling
Burst time
Repetition time
Test duration
Burst generator technical data
Derating
Combination wave (Surge) – parameter setting
Test configuration for power line coupling
Test configuration for external coupling
Voltage
Impedance
Phase
Coupling
Repetition time
Test duration
Surge generator technical data
Ring wave (RW)
Test configuration for power line coupling
Test configuration for external coupling
Ring wave parameters
Voltage
Impedance
Phase
Coupling
Repetition time
Test duration
Technical data ring wave generator
Telecom wave test
Voltage
Impedance
Phase
Coupling
Repetition time
Test duration
63
63
63
63
64
65
65
65
66
70
70
70
72
72
73
73
77
77
77
77
78
78
78
79
79
79
79
82
82
82
83
84
84
84
85
85
85
5
6
8.7
8.7.1
8.7.2
8.7.3
8.7.4
8.7.5
8.7.6
8.7.7
8.7.8
8.8
8.9 8.10
8.10.1
8.10.2
8.10.3
8.10.4
8.11
8.11.1
8.11.2
8.12
9
9.1 9.2 9.3 9.4 9.5 10 11 11.1 11.2 11.3 11.4 11.5 12 13 13.1 13.2 Mains power quality (PQT)
Sample graphs of dips/interrupts
Mains power quality generator
Voltage U Var
Phase
Repetition time
T-Event
Test duration
Dips and interrupts characteristics
Variation test (-4-11) - automatic procedure
Power magnetic field testing (-4-8) - automatic procedure
Pulsed magnetic field testing (-4-9)
The optional magnetic field loop antenna INA 701 and INA 702
Pulse wave shape adapter INA 753
Generator setting
Technical data pulsed magnetic field test
Power magnetic field test (-4-8) -automatic procedure
Automatic magnetic field option MFO 6502
Technical data power magnetic field test
Standard test parameter
Description of the 25 pin D-Sub signals
Interlock
Trigger to scope output signal
Synchronization (Sync) signal: Output signal
Pulse enable / next step input
EUT fail input
Coupling network CDN 3061
Maintenance and function check
General
Cleaning
Function check
Calibration
Warranty
Declaration of conformity (CE)
Technical data
Dimensions/weight
Options
NSG 3060 EMC test system
86
87
87
88
88
88
88
88
89
89
91
91
92
93
94
94
95
95
95
96
109
109
110
110
110
111
112
114
114
114
115
115
116
117
118
118
118
13.3 13.4 13.5
14 15 Accessories for IEC/EN 61000-4-11
Accessories for IEC/EN 61000-4-8/-4-9
Accessories for IEC/EN 61000-4-4/-4-5
System description
Addresses
119
119
120
122
123
7
8
WARNING - Lethal danger from high voltages and the
risk of radiating illegal electromagnetic interference.
This system must be used only for EMC test purposes
as specified in these operating instructions.
The NSG 3060 must be installed and used only by authorized and trained EMC specialists.
Personnel fitted with a heart pacemaker may not
operate the instrument and must not be in the vicinity
of the test setup while it is in operation.
When the system is used in conjunction with options,
accessories or other equipment the safety instructions
concerning those devices must also be observed.
NSG 3060 EMC test system
1 EXPLANATION OF SYMBOLS
Please take note of the following explanations of the symbols used in order
to achieve the optimum benefit from this manual and to ensure safety during
operation of the equipment.
The following symbol draws your attention to a circumstance where nonobservation of the warning could lead to inconvenience or impairment in the
performance.
Example:
This connection must not be confused with the Equipment under Test (EUT) power input.
The following symbol draws your attention to a circumstance where nonobservation of the warning could lead to component damage or danger to the
operating personnel.
Example:
Never connect or disconnect the EUT while the test
system is performing a test.
9
10
2 INTRODUCTION
2.1 General description
The NSG 3060 test system enables cable-borne EMC (electromagnetic compatibility) immunity tests to be carried out on electrical equipment intended
for household, office, light industrial or commercial use. The test system is a
concept from Teseq AG for electromagnetic immunity testing purposes and
fulfills the requirements to accomplish CE marking.
It is an open system, built on a modular principle that communicates through a
serial and standardized bus system and has open interfaces available. Operation is performed by means of standardized operator interfaces.
As a result of its modularity and the use of industry standards for the interfaces,
operating elements and expansion functions, the most widely varied instrument
configurations can be readily constructed from the basic building blocks. Single
function generators, customer-specific combinations, multifunction generators
for comprehensive test routines to product standards, generic standards and
basic standards, as well as combinations with special coupling devices are all
easily configurable.
A master controller in the NSG 3060 system architecture takes care of all the
“real-time” control functions and communicates with all the function modules
both within the instrument’s casing and external devices via an interbus link.
The system has a simple construction. All function units contain a slave controller. All these units are connected together through their slave controllers and
networked with the central master controller via a field bus (Interbus). Information concerning the special features and their adjustable parameters are stored
directly in the function modules. In addition to this bus system, the NSG 3060
system also has a further interface standard, Ethernet, with which the system
NSG 3060 EMC test system
can be controlled via single PC, a computer network or even via the Internet.
This modularity enables the function units to be re-combined in ever newer
instruments and subsystems. The function units can be readily expanded to
cope with new standards and new function units for new parameters can be
incorporated in existing systems.
To ensure optimal user and equipment safety, only industry-standard and correctly specified plugs and sockets are used throughout. High voltage outputs
are switch-protected.
11
12
3 STANDARDS AND APPLICATIONS
The NSG 3060 test system is designed primarily for cable-borne transient interference tests as specified in the European generic standards IEC/EN 61000-6-1
covering equipment for household, office and light industrial use, and IEC/EN
61000-6-2 for applications in industrial environments. The NSG 3040 generates
these tests in accordance with IEC/EN 61000-4-2, -4, -5, -11, -12 and -29. Accessories are available for generating optional tests to IEC/EN 61000-4-8 and -9,
and to ANSI/IEEE C.62.41.
The EU directive No. 89/336/EEC (for the assignment of the CE symbol) refers
to these standards and to this type of equipment.
3.1 ESD test
ESD tests (in accordance with IEC/EN 61000-4-2) must be performed with a
separate ESD simulator, such as the Teseq NSG 435, NSG 437 or NSG 438. The
standard calls for both air and contact discharges, and the simulator is supplied with special tips for each type of test. In the case of air discharges the
simulator is discharged by holding the tip close to the Equipment Under Test
(EUT). Then, while depressing the trigger, moving it closer to the target area
until a discharge occurs. Contact discharges occur with the tip of the simulator
in direct contact with EUT.
3.2 Burst test
Burst tests in compliance with IEC/EN 61000-4-4 simulate the high voltage/high
frequency interference pulses typically produced when an inductively loaded
switch is operated. Without countermeasures, such interference may occur
when a current through an electromagnetic device, e.g. motor, circuit breaker,
relay, fluorescent lamp, etc. is switched off.
This type of interference can affect other equipment in either of following two
ways. Firstly, the interference can be coupled directly into the target equipment
NSG 3060 EMC test system
via the mains power cable. The interference can be transmitted from the source
along the mains power cable connected to the target. Interference from the
mains can reach any other piece of equipment connected to the same power
source in a similar way, however this does not all have to occur in the same
section of a building.
Alternatively, the interference can be capacitively coupled into any target device
in the vicinity.
The system enables a test to be performed using both standardized coupling
methods. The EUT is connected to the mains power socket on the front panel
of the test system for the direct mains injection test. Capacitively coupled tests
require the interference to be superimposed onto the signal or data line cables
via an external coupling clamp that is connected to the burst output on the front
panel of the system.
3.3 Combination wave and ring wave test
The surge test, in compliance with IEC/EN 61000-4-5, ANSI C.62.41 and
IEC/EN 61000-4-12 Ed.2.0:2006. Duplicates high voltage/high energy interference as experienced with a lightning strike. Generally speaking the interference
finds its way into household equipment via the mains power supply.
This kind of interference can affect equipment in either of two ways. Firstly, the
interference can be coupled directly into the equipment via the mains supply.
The interference is conveyed directly from the source (e.g. lightning strike to
external power cables). Every item of equipment connected to this power
source will be affected by the interference pulses.
Alternatively, the pulses from the source of the interference or its associated
mains cables can be coupled into other equipment positioned nearby.
Surge pulse interference can also occur on signal and data lines through coupling effects and electrical discharges.
The system enables tests to be carried out using both coupling methods. The
EUT is connected to the mains power socket on the front panel of the test
system for direct mains injection tests. Externally coupled tests require the
13
14
interference to be superimposed onto signal/data line cables via an external
coupling unit that is connected to the surge output on the front panel of the
system.
3.4 Telecommunication wave test
The 10/700 µs telecom wave generator module is used to test ports intended
for connection to symmetrical communication lines.
The Telecom Surge Module TSM 3751 generates test pulse of 10/700 µs as
described in IEC/EN 61000-4-5:2005 and IEC 60060-1, ITU-K series, ANSI/IEEE
C62.41 and several EN standards and the safety standard of UL 1950. Since
tolerance can be taken into account, it will cover the 9/720 µs pulse given in
ANSI-TIA-968_B.
Therefore the pulse will fulfil the new IEC recommendation of open circuit
voltage of 10/700 µs and the short circuit current pulse measuring of 5/320 µs.
The test voltage satisfies the basic requirement of IEC up to 4 kV and surpasses
the UL1950 safety test recommendation of 7 KV.
3.5 Mains quality test
The mains quality test includes the simulation of dips and interruptsouts of the
mains power supply in accordance with IEC/EN 61000-4-11 and for DC power
supplies in accordance with IEC/EN 61000-4-29.
A voltage dip occurs when the supply voltage falls considerably below the
nominal level for a relatively short time, e.g. for a few cycles, whereas an interrupt means that the voltage falls to zero for a similar period.
3.6 Magnetic fields with mains frequency (option)
Mains frequency magnetic field tests, or, POWERM tests, involve the simulation
of the magnetic fields typically generated by the current flow in power supply
cables as specified in IEC/EN 61000-4-8. Such magnetic fields can affect the
operation of items of equipment that are sensitive to them. The NSG 3060
performs this test by causing a heavy current to flow in a magnetic field coil
such that the current and frequency produce a proportional field within the
coil parameters.
NSG 3060 EMC test system
The magnetic field coils, available as accessories, are connected to the magnetic field option (MFO) which, in turn, is connected to the system.
3.7 Pulsed magnetic fields (option)
Tests with pulsed magnetic fields, or PULSEM tests, simulate the type of interference produced by surge pulses as a result of lightning strikes to buildings
and other metallic structures such as freestanding masts, ground conductors,
grounding networks, etc. as specified in IEC/EN 61000-4-9. Magnetic fields of
this type can upset the operation of installations that find themselves within
such fields. The NSG 3060 erforms this test by causing a heavy current to flow
in a magnetic field coil such that the amplitude of the pulse current produce a
proportional field within the coil parameters.
The magnetic field coils, available as accessories, are connected to the surge
pulse output socket via an INA 753 pulse shaping network.
15
16
4 SAFETY INSTRUCTIONS
The NSG 3060 system and its accessories operate at high voltages.
Improper or careless operation can be fatal!
These operating instructions form an essential part of the equipment and must
be available to the operator at all times. The user must obey all safety instructions and warnings.
Neither Teseq AG, Luterbach, Switzerland, nor any of its subsidiary sales organizations can accept any liability for personal, material or consequential injury,
loss or damage that may result from improper use of equipment and accessories.
4.1 General
The NSG 3060 must be operated only by authorized and trained specialists.
The generator is to be used only for the purpose specified by the manufacturer.
The user is directly responsible for ensuring that the test setup does not cause
excessive radiated interference which could affect other instrumentation. The
test system itself does not produce any excessive EM radiation. However, the
injection of interference pulses into a EUT can result in it and/or its associated
cables radiating electromagnetic radiation. To avoid unwanted radiation, the
standards organizations recommend that the test setup be operated inside a
Faraday cage.
NSG 3060 EMC test system
WARNING - Because of its construction, the NSG 3060
is not suitable for use in an explosive atmosphere.
WARNING - Personnel fitted with a heart pacemaker
must neither operate the instrument nor approach the
test setup while a test is being executed.
Only approved accessories, connectors, adapters, etc. are to be used to ensure
safe operation.
WARNING - Connect the EUT only after the initial system
self test has finished.
4.2 Installation
The NSG 3060 test system conforms to protection class 1. Local installation
regulations must be respected to ensure the safe flow of leakage currents.
WARNING - Operation without a ground connection is
forbidden!
Two independent ground connections are necessary - one for the test system
and one for the EUT. These must be connected back to the local permanent
installation or to a fixed, permanent ground conductor.
Operate the equipment only in dry surroundings. Any condensation that occurs
must be allowed to evaporate before putting the equipment into operation. Do
not exceed the permissible ambient temperature or humidity levels. Use only
officially approved connectors and accessory items.
Ensure that a reliable return path for the interference current is provided
between the EUT and the generator. The ground reference plane and the ground
connections to the instruments, as described in the relevant test standards,
serve this purpose well.
17
18
The test system may only be opened by a qualified specialist upon specific
instruction given by the manufacturer. Since the instrument works, on principle, with two independent power supplies (one for the generator and one for
the EUT), the NSG 3060 must be disconnected from both sources before any
modifications to the test setup are undertaken. Besides the mains connections
themselves, certain components also operate at high voltages, and are not
provided with any form of extra protection against accidental contact.
4.3 Installation of an EUT power switch
The EUT input should be connected through a properly rated power switch
device, which should be located close to the test setup. In order to ensure easy
and quick access to the EUT power, the switch should be clearly and visibly
labeled as “EUT power ON/OFF”.
The in-house power distribution must be equipped with a proper circuit breaker
and an emergency off button as per IEC 61010-1:2001.
The test setup should only be accessible to trained personnel.
Dimensioning of the mains supply and rating of fuse protection of the AC or DC
power supply must conform with local electrical codes and EUT requirements.
Inappropriate arrangement, mounting, cabling or handling of the EUT or ground
can hamper or negate the effectiveness of the NSG 3040’s safety features.
4.4 Applicable safety standards
The NSG 3060 conforms to the safety requirements specified in IEC 348 and
offers all the features necessary for safe and efficient operation.
Development and manufacture is in compliance with ISO 9001.
The system complies with the safety requirements of IEC/EN 61010-1 (Safety
requirements for electrical equipment for measurement, control and laboratory
use).
NSG 3060 EMC test system
Like all mains-powered generators, the system is designed for high voltage
working safety in accordance with VDE 0104.
Interference immunity has been tested in accordance with EN 61326-1.
It is the user’s responsibility to ensure that the test rig does not emit excessive
electromagnetic interference (EMI) that might affect other equipment. The test
system itself does not produce any excessive radiation; however, the injection
of interference pulses into the EUT can result in the device and/or its associated
cables radiating EMI. To avoid radiating unwanted interference the standards
organzations recommend that the test setup be located in a Faraday cage.
Since the purpose of the test system is to produce interference signals for
interference immunity testing, the requirements in the IEC/EN 61000 series
concerning limiting the radiated EMI can only be complied with by operating
the test system inside a Faraday cage.
4.5 Test execution
WARNING - The test area must be organized so that
unauthorized persons do not have access during the
execution of a test. If a safety contact (Interlock) is used
as a means of access control to the test zone (e.g. a
Faraday cage), then an additional contact connected in
series is necessary to provide protection for parts of
the EUT that are likely to be touched accidentally.
During a test, the EUT together with its accessories and
cables are to be considered live at all times. The test
system must be stopped and the EUT supply disconnected before any work can be carried out on the EUT.
This can be achieved simply by opening the interlock
circuit.
The EUT is to be tested only in a protective cage or
under a hood which provides protection against electric
19
shock and all manner of other dangers pertaining to the
particular EUT (see: User warnings - Generator).
20
The user must observe safety instruction for all the
instruments and associated equipment involved in the
test setup.
Test setup configuration is to be strictly in compliance
with the methods described in the relevant standard to
ensure that the test is executed in a compliant manner.
4.6 User warnings - Generator
WARNING - Users must be aware of the following
dangers that can occur during testing:
Local burning, arcing, ignition of explosive gases.
EUT supply current surge caused by a flashover
or breakdown resulting from the superimposed high
voltage.
Disturbance of other, unrelated electronics, telecommunications, navigational systems and heart
pacemakers through unnoticed radiation of high
frequency energy.
In the test system the interference voltage,
corresponding to the level called for in the relevant
test specification, is superimposed also on the EUT’s
protective earth conductor. Earth contacts or pins
(e.g. as in German and French mains plugs) as well
as the EUT earth itself can therefore be at an elevated
voltage level that would make touching dangerous.
In many power connectors even the screws are
linked to the protective earth.
NSG 3060 EMC test system
4.7 Dangers concerning the EUT
WARNING - Users must be aware of the following
dangers that can occur during testing:
EUTs are often functional samples that have not yet
been subjected to safety tests. It is therefore pos sible that the EUT could be damaged by internal
overloads or may even start to burn.
As soon as the EUT shows signs of being disrupted
the test should be stopped and the power to the EUT
switched off.
Internal disruption of the electronics can result in
the interference voltage or the EUT supply voltage
being present on the EUT’s outer casing.
Electrical breakdown or arcing from connections
that are overstressed voltagewise during the test.
Explosion of components with fire or fragmentation
as a result of energy dissipated, e.g. from the resul tant supply current or ignition of vaporized plastic
materials.
Faulty behaviour by the EUT, e.g. a robot arm strikes
out or a temperature controller fails, etc.
21
22
5 FIRST STEPS
This chapter contains a short checklist with steps that should be taken before
the instrument is switched on and put into operation.
Check the packaging for signs of damage in transit. Any damage should be
reported immediately to the transportation company.
Lift the NSG 3060 test system out of its packaging by grasping of the mounted
grips.
Using the following list, check that all the items ordered have been delivered:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
NSG 3060 generator
CDN 306x coupling network
User manuals
2 HV surge cables Fischer/Fischer connector
1 HV burst cable SHV/SHV connector
1 system cable (connects the CDN to the NSG)
2 mains power cables for the test system
1 termination plug (interlock blind connector)
1 ground cable (to reference ground plane)
1 EUT power input connector with cable
1 EUT power output connector
WIN 3000 Remote control software (trial version)
Ethernet cable, typ: SFTP, CAT 5e, 2 m
Ordered options
Check the instrument for signs of transport damage. Any damage should be
reported to the transportation company immediately.
NSG 3060 EMC test system
5.1 Installation of the NSG 3060 system
The mains power voltage indicated on the instrument must correnspond with
the local supply voltage (mains voltage: 85–265 VAC, universal power unit, mains
frequency: 50–60 Hz).
Mains switch
Fuse-holder with fuses 2 x 3.1.5 AT
Mains power input
Mains switch, fuse holder and power input
To replace a fuse:
1) Disconnect the mains cable
2) Pull the fuse holder out of the connector
3) Remove the damaged fuse(s)
4) Insert 1 or 2 x 3.15 AT fuses
5) Replace the fuse holder
6) Plug the mains cable into a power outlet with a solid ground connection
7) Note the polarity of all input and output connections
8) Place the test system so that there is sufficient free space around the
cooling air inlets on both sides and behind the fan outlet on the rear panel
9) Switch the system on and operate as instructed in this manual
23
24
5.2 Connecting the system to the ground reference plane
As mentioned in the standard, the generator must be placed on a ground reference plane which is connected to ground. A good high frequency ground
connection between the test system and the ground reference plane (GRP) is
absolutely essential for performing burst tests correctly.
Connect the ground terminal on the front panel of the NSG 3060 to the ground
reference, plane using the link and bolts supplied. If a CDN is connected please
refer to section “Reference ground connector”.
5.3 Mounting in a 19” rack
When the NSG 3060 test system is combined with other equipment, it can be
useful to mount the instrument in a 19“ rack. The unit is 19” wide and 7U in
height (an additional 5U is required for the CDN 3061). An optional rack mount
kit is available.
NSG 3060 EMC test system
6 MAINFRAME DESCRIPTION
25
The 3060 housing NSG is specially designed for EMC applications and is EMC
approved.
Burst
output
6.1 Front panel
Surge low output
Start/Stop/Pause button
Surge high output
Color touch screen
LEDs
Reference ground
connector ground point
Surge low input
Surge high input
Wheel
Wheel sensitivity keys
LEDs
Burst input
EUT output
Reference ground
connector
NSG 3060 front panel
6.1.1 EUT output connection
This is the power output connection for the EUT.
An EUT mains power connector is included with the system. The connector
contains a phase pin (L: Live), Neutral pin (N) and a ground pin for connection of
the EUT. The pins in the connector must be correctly wired to the corresponding
conductors in the EUT power cable.
If the test system is connected to a DC power source as supply for the EUT, the
user must ensure that the polarity at this connector corresponds with that at
the EUT power connector.
26
N
L
EUT output connection
Note: For DC power supply L = positive (+), N = negative (-).
The pins in the connector are designed for a maximum current of 16 A.
WARNING - Never attempt to connect or disconnect an
EUT while a test is being performed.
6.1.2 Reference ground connector
This terminal provides a solid reference ground connection point to the test
system. If a CDN is connected then the ground strap must be connected from
the CDN to the ground reference plane. There is no need to connect the ground
connector from the generator itself, since the burst connector provides the
reference ground from the generator to the CDN.
Reference ground connector
Reference ground connector
The NSG 3060 can be efficiently connected to the GRP using the ground strap
supplied with the system.
This ground link must be used for burst tests to obtain reproducible test
results.
NSG 3060 EMC test system
6.1.3 Surge output sockets
These sockets (high, low) connects the surge output signal to a 1-phase or
3-phase coupling unit, or to a CDN (CDN 117/118) for data lines.
These coaxial sockets are also used to connect the generator to the optional
magnetic field coil for tests with pulsed magnetic fields.
The surge output is potential free (floating). The inner conductor of each connector is the surge high and surge low connection respectively, while the outer
conductor (screen) is connected to the NSG 3060’s ground point.
6.1.4 Burst output socket
This socket connects the instrument to a 1-phase or 3-phase CDN or to a burst
coupling clamp for capacitive coupled burst tests on data lines.
6.1.5 Indicator LEDs
The five indicator LEDs serve to show the most important test system conditions:
LED indicator
Function
Power on
Instrument / system in operation
Pulse
Shows the occurrence of a pulses or a test event
High voltage active
Shows that high voltage is present in the instrument
EUT-Power on
Indicates when the EUT power supply is present at
the EUT connector on the front panel
Error
Indicates that a system error has occurred
The LEDs switch on and off during the boot period and when errors occur.
6.1.6 Touch screen and user interface
The color 7” touch screen display controls include a wheel and 3 sensitivity keys
used to 1, 10 or 100 steps per wheel click. The Start, Stop, and Pause keys are
used to control the procedure.
All user interface function menus and sub-menus are described in chapter 7,
standard user interface.
27
28
6.2 Rear panel
System configured with NSG 3060 (top) with CDN 3061 (bottom).
Mains power on/off switch and fuse
holder
Mains power connection
Spare interface slot
Master controller, with Ethernet
connector
System interface connector
Ground connection point
System interface input
System interface output
Mains power connection, on/off switch
and fuse holder
Ground connection point
EUT power input
NSG 3060 rear panel
6.2.1 Mains power input
The mains input is the connection point for power to the NSG 3060.
NOTE - Do not confuse the Mains power input with the
EUT power input.
This input contains the mains power input connector and the mains fuses.
WARNING - Before operating the NSG 3060, make sure
that the voltage shown on the mains input module corresponds with the voltage of the local supply to which
the instrument will be connected, and that the fuses are
correctly rated (2 x 3.15 AT).
NSG 3060 EMC test system
6.2.2 AC EUT mains input
The EUT mains input is the connection point for the power source which supplies power to the EUT. The 4-pin connector is a special 16 A type. A mating plug
with 2 m of cable for supplying the EUT from a normal mains outlet is included
with the system.
The connector is comprised of the pole contact (La, No.1), the variable voltage
pole contact (Lb, No.3), the neutral return contact (N, No.2) and the ground
connection to the EUT. The zero cross reference for synchronization purpose
is taken all the time from L to N.
1
4
4
1
2
3
2
3
AC EUT mains input
1 L = Phase black
2 N = Neutral blue
3 = Variable voltage pole red/or brown
4 = GND - Earth green/yellow
Wire colors and functions
Black:
Phase conductor
La Pin 1
Blue:
Neutral return
Pin 2
Red or brown:
Variable voltage pole
Lb Pin 3
Green / yellow:
Ground conductor
Pin 4
29
30
30
Operating current
25
20
Wire 2.5 mm2
15
Wire 1.5 mm2
10
Wire 1.0 mm2
5
20
40
60
80
100
120
°C
Ambient temperature
The additional variable voltage pole contact (Lb, No.3) enables a variac or alternative AC source, or a DC source to be connected for PQT tests. In this way
the voltage at the phase (L) line at the EUT output connector can be varied in
relation with the voltage at this contact.
WARNING - Pulse overshoot spikes of up to 900 V can
occur on these power lines. Such voltages can, under
certain circumstances, destroy power supplies. It is the
user’s responsibility to provide adequate protection at
the source input.
6.2.3 DC EUT input
For DC voltages: L = positive (+), N = negative (-)
In DC applications, the positive and negative lines are to be connected to La
and N respectively. The polarity at this EUT power input connector must be the
same as at the EUT output connector.
The connector’s ground contact must be connected to a good, solid ground
point.
NSG 3060 EMC test system
Capacitors in the coupler can cause ground leakage
currents of up to 4 A the EUT power supply network.
The test system must therefore be properly grounded
and powered from a supply that is not protected by a
residual current detector (RCD).
The power source to this connector provides the power for the EUT. Burst and
surge interference signals are coupled into this supply line internally. Power is
also delivered via this route for PQT (mains quality) testing purposes.
6.2.4 Ground connection point
Like the reference ground connector on the front panel, this ground terminal
provides a solid connection point to the NSG 3060’s chassis ground.
6.2.5 System interface connector 25 pin D sub
Pin #
Sync.line Signal
Remark
Working direction
7
Sync0
Mains
synchronization
Mains voltage passes
From a coupling
through the zero crossing
network
point with rising signal level
5
Sync1
Interlock
Puts the NSG 3060 into an
idle state. The «Error» LED
lights in this state
From each controller/
to interlock circuit
6
Sync2
EUT fail
EUT reports a fault to the
NSG 3060 software. The
test is stopped
From EUT to master
controller
18
Sync3
Trigger to
oscilloscope
External device receives
the Trigger-to-Scope signal
from the generator
To/from the active
function module, the
slave controller and
master controller
17
Sync4
Pulse enable
External device stops the
test run
From external device
to the slave and
master controllers
31
32
Pin #
Sync.line Signal
Remark
Working direction
4
Sync5
Freely definable sync bus
signal
Freely definable, for
later options
16
Sync6
Freely definable sync bus
signal
Freely definable, for
later options
3
Sync7
2, 8,
15, 20
1, 9
14, 21
19
All
others
Reserved
Internal usage
(debug mode)
GND
Sync bus ground return
+ 24 V
Interbus +24 V supply
Interlock return
Interlock return line
Interbus lines
See chapter “System interface connector functions”, for more detail.
6.2.6 Synchro-Bus system
This connection includes external device control and interlock capability. If the
NSG is used only as a stand alone unit, the termination connector needs to be
plugged otherwise the unit will not start.
All connected accessories will be detected automatically. Written tests are
linked with this accessories so if other accessory is connected, it may get an
error if the test contains not the suitable accessories.
Any automated CDN and complementary automated equipment like variac, step
transformer etc. need to be linked together. Thereby the termination connector
needs to be moved to the system output plug of the last unit of the system.
Since time-critical information might not be transferred quick enough (transmission time for one message frame takes about 20 ms), an additional bus called
the synchro-bus is used instead where speed matters. The master controller,
NSG 3060 EMC test system
together with the function units in the same instrument, can access this bus.
The controller also makes this bus available to other instruments via a connector
on the rear panel.
The interfaces for the interbus, interlock and synchro-bus are bundled together
in a sub-miniature D-connector. These three interfaces are looped through from
one instrument to another.
Signal
Remark
Working direction
Mains synchronization
Mains voltage passes through the zero
crossing point with rising signal level
From coupling network
Interlock
Connects / interrupts HV supply and
EUT power relay (2 wires)
From each controller to
interlock circuit
EUT fail
The NSG 3060 software can stop a test
run if a fault caused by the test procedure occurs in the EUT and is reported
From EUT to master
controller
Watchdog
The controller watchdog puts this signal To the function module
on the bus when it is overlooked by its
to which an error signal
controller (to avoid software error)
applies
Global start trigger
with delay function
Sync1 to Sync3
Any function unit or external instrument
To/from the active
can generate this signal, or an external
function module, the
instrument receives a trigger-to-scope
SC and MC
signal
Three freely definable synchronization
bus signals
Freely definable, for
later options
33
34
7 THE STANDARD USER INTERFACE
(SUI)
The NSG 3060 Standard User Interface (SUI) consists of
– A 7” color touch panel
– A wheel for setting parameters
– A wheel sensitivity keys labeled 1, 10, and 100 to denote the units
– A Start key (show symbol) to start tests
– A Stop key (show symbol) to stop tests
– A Pause key (show symbol) to pause tests
NSG 3060 touch screen, keys and wheel
CAUTION – Never use a metal, sharp or pointed tool for
touching the panel. Use a soft towel for cleaning. Never
use aggressive cleaning liquids.
As soon the unit is powered and switched on, the boot procedure starts (approx.
30 seconds) and the Start menu is displayed.
NSG 3060 EMC test system
35
SUI boot-up screen
7.1 Main menu
Main menu
The main menu is displayed following boot-up. The main menu shows the possible pulses or tests which are available to the user, depending on the NSG
3060’s configuration. Faded generator icons (Telecom 10/700 us pulse and
voltage variation) mean, that the generator is configured to generate those
pulses but the proper unit is not connected.
The empty buttons are reserved for future applications.
In the red bar there are two buttons, “System” and “Reset Interlock”. Touching
the Reset interlock button will close the interlock. The interlock must be closed
before starting a test.
36
7.2 System window
Touch the “System” button to display the “System” window:
System window
The “System” window displays 6 buttons: General, Equipment, Communication,
Monitoring, SD-card properties and language. In the red bar there are two
buttons: Factory settings and exit.
FACTORY SETTINGS
Touch the “Factory settings” button to reset the properties associated with each
of the buttons in the “system” window to the original factory settings.
EXIT
Touch the “Exit” button to return to the main menu.
REMOTE
Touch “Remote” button to enter remote controlled screen. No inputs via touch
panel are possible. The NSG can now be controlld via WIN 3000 remote control
software. Touch “Exit” on screen and in WIN 3000 to use NSG manually.
7.3 General settings
Touch the “General” button to display one of the following windows:
General settings window with no optional hardware (CDN, variac, etc.) connected.
NSG 3060 EMC test system
37
General settings window with optional EUT switch connected
General settings window with optional automated variac connected
Beeper volume
During the surge test there is a beep sound to alert the user. Touch the “beeper
volume button” (“On” in the example) to switch the sound on and off.
The red vertical bar on the right side of the General settings window displays 4
buttons: “Exit”, “EUT OFF/ON”, “Factory Settings”, and “OK”.
EXIT
Touch the “Exit” button to return to the system window without saving settings.
38
EUT OFF/ON
When the NSG 3060 is powered on, the EUT power is automatically set to “OFF”.
Touch the “EUT OFF/ON” button to turn power to the EUT on or off.
FACTORY SETTINGS
Touch the “Factory settings” button to reset the properties associated with each
of the buttons in the General settings window to the original factory settings.
OK
Touch the “OK” button to save all settings and return to the system window.
Interlock action
Touch the “Interlock action button” (“EUT Power on” in the example) to keep
EUT power on when the interlock is activated, or to have it automatically shut
off (EUT Power off) when the interlock is activated.
Expert mode
Touch the “expert mode” button (“Off” in the example) to “Active” to change
parameters during a running test. When the button is set to “Off” parameters
can be changed only when the NSG 3060 is in stop mode. Expert mode only;
available for burst pulse (FFT).
Voltage Uin
This button is used only when an optional VAR 6502 or VAR 3005 variac is
connected to the NSG 3060. The value entered in this field is the voltage measured at the mains socket and is used as the 100% reference point for voltage
variation tests.
Touch the “voltage Uin” button (‘230” in the example). Use the wheel or keypad
to set the input voltage.
Uin setting will be saved and is valid for all following tests. Uin are changeable
via WIN 3000 (dialoge) to be used in sequence mode.
NSG 3060 EMC test system
7.4 Equipment
Equipment window
Touch the “Equipment” button to access a list of all internal and external generator modules, including firmware versions, serial numbers, calibration dates and
certificate numbers.
The red vertical bar on the right of the equipment window displays three
buttons: “Exit”, “Up” and “Down”.
EXIT
Touch the “Exit” button to return to the system window.
UP/DOWN
If the system includes more than 5 modules, touch the “Up” and “Down” arrows
to scroll through the list.
7.5 Communication
Communication window
39
40
Touch the “Communication” button to view and enter the network address
information required to integrate the NSG 3060 into a local area network or
connect it to a PC.
By touch the IP address-, SubNet-, Port- or Gateway-field the key board will
appear and the new numbers can be added. To enter a new address only the
number key and the dot may be used.
After touching “ENTER” the keypad will close and the new setting are saved.
The “Delete” key will delete all text entered. The backspace button (<--) will
delete the last letter entered. Touch the “Cancel” button to return to the test
parameter window without saving the file.
IP address
An IP address (Internet protocol address) is a unique address that certain electronic devices use identify and communicate with each other on a computer
network utilizing the Internet Protocol standard (IP). Any participating network
device must have its own unique address. Touch the “IP address” button to
enter the IP address. A red frame will be displayed around the field. Enter the
IP address using the wheel or keypad.
Subnet
A subnet is a logical grouping of connected network devices which is used to
partition networks into segments. Devices on a subnet are share a contiguous
range of IP address numbers.
A subnet mask defines the boundaries of an IP subnet and hides the network
address portion of an IP address. For example, if a network has a base IP
address of 192.168.0.0 and has a subnet mask of 255.255.255.0, then any data
going to an IP address outside of 192.168.0.X will be sent to that network’s
gateway.
The correspondence between subnet masks and IP address ranges follows
defined mathematical formulas, by assigning a value of 1 to every digit in the
network address portion of the binary IP address. These masked digits are not
permitted to change when assigning IP addresses to devices on the local area
network.
NSG 3060 EMC test system
Touch the “SubNet” button to enter the subnet mask. A red frame will be displayed around the field. Enter the subnet mask using the wheel or keypad.
Gateway
A gateway is a node on a network that serves as an entrance to another
network. In enterprises, the gateway is the computer that routes the traffic
from a workstation to the outside network that is serving the Web pages. In
homes, the gateway is the ISP that connects the user to the internet
In enterprises, the gateway node often acts as a proxy server and a firewall. The
gateway is also associated with both a router, which use headers and forwarding tables to determine where packets are sent, and a switch, which provides
the actual path for the packet in and out of the gateway.
The gateway address is usually set at 0.0.0.0. Touch the “Gateway” button to
enter the gateway address. A red frame will be displayed around the field. Enter
the gateway address using the wheel or keypad.
Port
Network ports can be either physical or virtual connection points. The NSG 3060
has a physical Ethernet port that allows it to be connected to a PC or router.
The port address for the NSG 3060 should be set to 1025. Touch the “Port”
button to enter the port number. A red frame will be displayed around the field.
Enter the port number using the wheel or keypad.
MAC address
Media Access Control (MAC) technology provides a unique identification and
access control for devices on an IP network. This address can not be changed.
Media Access Control assigns a unique number, the MAC address, to each
network adapter. The MAC address for the NSG 3040 network interface card,
displayed in the communication screen, is unique to that card and cannot be
changed.
41
42
7.6 Monitoring
Monitoring window
Touch the “Monitoring” button to view EUT power input parameters, and to
control test activity and EUT power input in the event of EUT failure.
7.6.1 EUT supply voltage, EUT supply frequency
The EUT supply voltage/EUT supply frequency fields display the actual EUT
voltage/frequency when the AC EUT input supply is connected and EUT power
is switched “On”. When the input supply is not connected and/or the EUT is
switched off, these fields will display 0 V and 0 Hz.
Thereby the EUT (AC) input supply must be connected and the EUT power has
to be switched “On”. Otherwise the screens show 0 V and 0 Hz.
7.6.2 Test action at EUT fail input
Touch the Test action at EUT fail input button (“Stop” in the example) to specify
the test action taken if the EUT fail signal is deledted.
When the button is set to “Stop” and the EUT fails, the test stops. The test can
be restarted by pressing the Start key on the front panel.
When the button is set to “Pause” and the EUT fails, the test goes into pause
mode. The test can be continued by pressing the “Start” key on the front panel.
When the button is set to “CONT.”, the test will continue even if the EUT stops
functioning.
NSG 3060 EMC test system
7.6.3 EUT power supply at EUT fail input
Touch the EUT power supply at EUT fail Input button (“Off” in the example) to
specify the action taken if an EUT fail signal is generated.
When the button is set to “On” EUT power stays on after the EUT fail signal is
generated.
When the button is set to “Off” EUT power shuts down when the EUT fail signal
is generated.
7.6.4 Exit
Touch the “Exit” button to return to the system window without saving
changes.
7.6.5 EUT on
This button displays the EUT input power status.
7.6.6 Ok
Touch the ”Ok” button to save changes and return to the system window.
7.7 SD-card properties
This feature is not yet implemented.
SD-card properties window
The NSG 3060 includes an integrated SD-card slot which can be used to download software updates.
43
44
7.7.1 Viewing the current SUI version
The current SUI software version is displayed in the equipment detail window.
To access this window.
1. Touch the system button in the main menu to display the system window.
2. Touch the equipment button to display the equiment detail list.
System button in the main menu
Equipment button in the system window
Identifies the SUI version
Equipment detail list with SUI software version displayed
NSG 3060 EMC test system
7.7.2 Updating SUI software via the SD-card
To change the SUI software, first switch off the generator and remove all power
cords and cables. Open the top housing cover of the generator as described
below.
WARNING - Before opening the generator make sure
that it is turned OFF and disconnected from all power
and signal cables!
To open the NSG 3060, the user must first remove the sides panels. Each
side panel has 4 snap fixtures which will separate when outward pressure is
applied.
1. Pull outward on the indentation in the front of the side panel.
A blunt tool which will not scratch the paint on the panel may be used.
2. Pull outward to separate the panel from the snap fixtures.
3. Remove the upper screws on both sides of the generator cover.
4. Remove the NSG 3060 cover. The SD-card slot is located at the right front of
the generator, in back of the front panel.
5. Press the SD-card to release it. Remove the card from the slot. To install a
new SD-card, proceed to step 7.
6. To download new software from a PC to the SD card, insert the card in the
SD port of the PC and copy the software to the SD card. The file name must
remain SUI3000AP.EXE. Remove the SD card from the PC.
7. Insert the SD-card in the NSG 3060. Follow steps 1 - 4 in reverse to replace
the generator cover and side panels.
8. Restart the NSG 3060. The new software version will boot automatically
and may be verified in the equipment detail window (see section 7.7.1).
45
46
Removing the NSG 3060 side panels and cover
The SD-card is placed on the upper right position.
NSG 3060 SD-card slot
NSG 3060 EMC test system
47
Removing the SD-card
Windows explorer displaying the SUI program filename (SUI3000AP.EXE) on the SD-card
(removable disk (F:))
NOTE: Do not change the SUI program filename.
48
7.8 Language
Language selector window
Touch the “Language” button to open the language selector window. The SUI
software can be displayed in English, German, French, Japanese or Chinese.
(Note: Only English is available at this time).
The NSG 3060 will automatically reboot if the language is changed.
OK
Touch the “OK” button to save all settings and return to the system window.
EXIT
Touch the “Exit” button to return to the system window without saving settings.
NSG 3060 EMC test system
8 SETTING TEST PARAMETERS
The main menu displays a button for every type of test that can be performed
by the NSG 3060. Buttons for tests that are not available on the system as
configured are grayed out.
The user can set parameters for available tests and create new tests in the test
parameter window.
Figure 8.1 shows the test parameter window for burst tests. While the input
fields differ for each type of test, the red side bar and bottom bar remain the
same.
Red bar
Bottom bar
Example of the burst test window, showing the red bar and bottom bar.
8.1 The red menu bar
EXIT
Touch the “Exit” button to return to the system window without saving settings.
49
50
EUT OFF/EUT ON
Touch the “EUT Off/EUT On” button to switch EUT power off or on. Note: the EUT
can work only in combination with an automated accessory, such as a variac,
step transformer or automated CDN.
RAMP VALUE
The “Ramp value” button is active only if a rampable parameter in the test
window is selected. All rampable parameters are identified by a small gray
ramp icon. This icon will turn red when a parameter is ramped.
Ramping window for voltage parameter
Ramping mode
Start Stop
Step
Touch the “Ramping mode” button (“Static” in the
example) to change the ramping mode from static to
linear. In linear mode the user can set Start, Stop
and Step values.
Touch the “Start” button (“200 V” in the example). A red
frame is displayed around the field. Enter the Start
value using either the wheel or the keypad.
Touch the “Stop” button (“4800 V” in the example). A
red frame is displayed around the field. Enter the Stop
value using either the wheel or the keypad.
Touch the “Step” button (“1 V” in the example). A red
frame is displayed around the field. Enter the Step
value using either the wheel or the keypad.
NSG 3060 EMC test system
Step delay
Touch the “Step delay” button (“1” in the example). A
red frame is displayed around the field. Enter the Step
Delay value using either the wheel or the keypad
Touch the “Unit” button (“s” in the example) to set the step delay unit.
The step delay depens on pulses and the minimum
repetition rates.
OK
Touch the “OK” button to save all settings and return to the test parameter
window.
EXIT
Touch the “Exit” button to return to the test parameter window without saving
settings.
SHOW STEPS
Touch the “Show Steps” button to view, change the order of, or delete individual
test steps. The show step window displays individual test steps in the order
that they will be executed.
UP/DOWN
Use the “UP” and “DOWN” arrows on the right side of the Show Step window
to change the test step order. Touch a line number to select a step. A
red frame is displayed around the selected step. Touch the “UP” button
to move the step up in the list. Touch the “DOWN” button to move the step
down in the list.
DEL
Touch a line number to select a step. A red frame is displayed around
the selected step. Touch the “DEL” button to delete the step.
OK
Touch the “OK” button to save all settings and return to the test
parameter window.
EXIT
Touch the “Exit” button to return to the Test parameter window without
saving settings.
51
52
ADD STEP
Multi-step tests can be programmed manually in the test parameters window
using the “Add Step” button.
Touch the “Add Step” button create a new step with the values currently displayed in the Test parameters window The user can program a maximum of
10 test steps.
When the first test step is programmed, “TEST 1/X” is displayed in the upper
right corner, and the step can no longer be changed from the Test parameters
window.
To change a step, the user must first delete it using the “Show Step” button,
then use “Add Step” to re-enter the step.
Refer to sections 8.3 - 8.9 for detailed information on setting parameters for
specific types of tests.
EXPERT MODE
The “Expert Mode” button can be used only if “Expert Mode” is set to “On” in
the System/General settings window (see section 7.3) Expert Mode is a fast,
effective method of activating critical threshold values.
Touch the “Expert Mode” button to manually adjust test parameters using the
wheel while a test is in progress.
“Expert Mode” only for burst pulse
The “Expert Mode” allows the user to change parameters during a running test
if this mode is set “Active” in the system setting. For safety reasons in the in the
burst menu the expert mode needs to be activated as well.
The “Expert Mode” can be activated only for the following parameter:
Volt (please note, the voltage change is only possible
if the polarity is set to Neg. or Pos.)
Frequency
Phase
Burst time
NSG 3060 EMC test system
53
A selected test can be started. During run mode the changeable parameter can
be touched, the value window is highlighted with a red frame, like the voltage
frame shown in the examples above. The value can now be changed via wheel
and by pressing again the “START” button, the value will be accepted and on
the pulse output the new value is displayed.
8.2 The bottom bar
Following functions are not available in this version:
8.2.1 LOAD USER TEST
Touch the “Load User Test” button to display a list of all test files that have
been created and saved by the user. Only files for the selected test type are
displayed. Figure 8.5 shows the load user test window with several burst tests
displayed.
The user can scroll through the tests by touch the “UP” and “DOWN” arrows on
the right side of the screen to scroll through the tests.
Touch the button to the left of the test name to select it. A red border is displayed around the selected test. Figure 8.6 shows the Load User Test window
with a test selected.
Touch the “OK” button to load the test and return to the test parameter
window.
54
Touch the “Delete” button to delete a saved test. A window asking the user to
confirm or cancel this action will be displayed (see figure 8.7). Touch “OK” to
delete the file, or “Cancel” to cancel this action.
NOTE: Once a test has been deleted it cannot be restored.
Load user test window
Delete test confirmation window
NSG 3060 EMC test system
55
Delete test confirmation window
8.2.2 LOAD STANDARD TEST
The NSG 3060 includes European generic standards from the IEC/EN 61000-4-x
and ANSI/IEEEE C62.41 which are conform to many standard derivates and
product standards.
Depending on selected pulse the appropriate IEC or ANSI standard test can be
selected. A complete list can be found in section “Standard test parameter”.
Following standard tests are in the SUI
Burst, IEC 61000-4-4; 2009 Ed2 and ANSI
1-Phase power lines level 1 up to level 4
3-Phase power lines level 1 up to level 4
Capacitive coupling clamp lines level 1 up to level 4
Combination wave, IEC 61000-4-5 2005_Ed_2
1-Phase power lines L-N coupling level 1 up to level 4
1-Phase power lines L-PE coupling level 1 up to level 4
1-Phase power lines N-PE coupling level 1 up to level 4
3-Phase power lines Lx-Lx coupling level 1 up to level 4
3-Phase power lines Lx-PE coupling level 1 up to level 4
DC-Line L-N coupling level 1 up to level 4
Unshielded unsymmetrical I/O lines level 1 up to level 4
Unshielded symmetrical communication lines level 1 up to level 4
56
Combination wave, ANSI C62.54, 2002
1-Phase EUT, Basic 1, Location Cat. A1 up to Cat. A3
1-Phase EUT, Basic 2, Location Cat. A1 up to Cat. A3
3-Phase EUT, Basic 1, Location Cat. A1 up to Cat. A3
3-Phase EUT, Basic 2, Location Cat. A1 up to Cat. A3
3-Phase EUT, Basic 3, Location Cat. A1 up to Cat. A3
3-Phase EUT, Basic 4, Location Cat. A1 up to Cat. A3
Ring wave, IEC 61000-4-12,
1-Ph Power Lines L-N, major feeder line, 12 Ω, level 1 up to level 4
1-Ph Power Lines L-PE, major feeder line, 12 Ω, level 1 up to level 4
1-Ph Power Lines N-PE, major feeder line, 12 Ω, level 1 up to level 4
1-Ph Power Lines L-N, outlet line, 30 Ω, level 1 up to level 4
1-Ph Power Lines L-PE, outlets line, 30 Ω, level 1 up to level 4
1-Ph Power Lines N-PE, outlets line, 30 Ω, level 1 up to level 4
3-Ph Power Lines Lx-Lx, major feeder line 12 Ω, level 1 up to level 4
3-Ph Power Lines Lx-Lx, outlets line, 30 Ω, level 1 up to level 4
3-Ph Power Lines Lx-PE, Comm. Mode, major feeder line 12 Ω, level 1 up to
level 4
3-Ph Power Lines Lx-PE, Comm. Mode, outlets lines, 30 Ω, level 1 up to level 4
DC Lines, L1=Pos.; N=Neg. 12 Ω, level 1 up to level 4
DC Lines, L1=Pos.; N=Neg. 30 Ω, level 1 up to level 4
Unshielded, unsymmetrical I/O lines, level 1 up to level 4
Unshielded symmetrical lines, communication lines, level 1 up to level 4
Ring wave, ANSI C.62.45,2002
1-Phase EUT, Basic 1, Location Cat. A1 up to Cat.A3, 12 Ω
1-Phase EUT, Basic 1, Location Cat. A1 up to Cat.A3, 30 Ω
1-Phase EUT, Basic 2, Location Cat. A1 up to Cat.A3, 12 Ω
1-Phase EUT, Basic 2, Location Cat. A1 up to Cat.A3, 30 Ω
NSG 3060 EMC test system
3-Phase EUT, Basic 1, Location Cat. A1 up to Cat.A3, 12 Ω
3-Phase EUT, Basic 1 Location Cat. A1 up to Cat.A3, 30 Ω
3-Phase EUT, Basic 2, Location Cat. A1 up to Cat.A3, 12 Ω
3-Phase EUT, Basic 2, Location Cat. A1 up to Cat.A3, 30 Ω
3-Phase EUT, Basic 3, Location Cat. A1 up to Cat.A3, 12 Ω
3-Phase EUT, Basic 3, Location Cat. A1 up to Cat.A3, 30 Ω
3-Phase EUT, Basic 4, Location Cat. A1 up to Cat.A3, 12 Ω
3-Phase EUT, Basic 4, Location Cat. A1 up to Cat.A3, 30 Ω
Telecom pulse, IEC 61000-4-5 2005_Ed_2
Symmetrical operated all lines to PE, level 1 up to level 4
Shielded I/O communication lines, level 1 up to level 4
Power magnetic field, IEC 61000-4-8 2001_Ed_1.1
50 HZ CF 9.8, level 1 up to level 4
60 HZ CF 9.8, level 1 up to level 4
Pulsed magnetic field, IEC 61000-4-9 2001_Ed_1.1
CF 0.98, level 3 up to level 5
Dip and Interrupts for AC power lines, IEC 61000-4-11 2002_Ed_2
50 Hz, AC Power Lines, Class 2, Dips, 0%, 0.5 Cycle dips up to 25 Cycle
60 Hz, AC Power Lines, Class 2, Dips, 0%, 0.5 Cycle dips up to 30 Cycle
50 Hz, AC Power Lines, Class 3, Dips, 0%, 0.5 Cycle dips up to 250 Cycle
60 Hz, AC Power Lines, Class 3, Dips, 0%, 0.5 Cycle dips up to 300 Cycle
50 Hz, AC Power Lines, Class 2, Short interruption, 0%, 250 Cycle dips
50 Hz, AC Power Lines, Class 3, Short interruption, 0%, 250 Cycle dips
60 Hz, AC Power Lines, Class 2, Short interruption, 0%, 300 Cycle dips
60 Hz, AC Power Lines, Class 3, Short interruption, 0%, 300 Cycle dips
57
58
50Hz Voltage variation
60Hz Voltage variation
Dips and interrupts for DC lines, IEC 61000-4-29 2000
DC Voltage Dips 40%, 0.01 s up to 1 s
DC Voltage Dips, 70%, 0.01 s up to 1 s
DC voltage interruption, 0%, 0.001 s up to 1 s
DC voltage variation, 85%, 0.1 s up to 10 s
DC voltage variation, 120%, 0.1 s up to 10 s
DC voltage variation, 80%, 0.1 s up to 10 s
8.2.3 SAVE TEST
The “Save Test” button is used to save the current test to a file for later use.
Touch the “Save Test” button. A keyboard is displayed. Touch the individual keys
to enter a file name in the black bar above the keyboard.
The “Delete” key will delete all text entered. The backspace button (<--) will
delete the last letter entered. Touch the “Enter” button to save the file under
the name entered.
All letters and numbers, as well as hyphens, spaces and dots, can be used in
file names. The maximum file name is 40 characters, including spaces.
The system automatically generates a file extension to identify the type of test.
For example, all burst tests will are given the extension .EFT.
Touch the “Cancel” button to return to the test parameter window without
saving the file.
NSG 3060 EMC test system
59
Save Test keyboard
Keyboard with filename entered
KEYPAD
Touch the “Keypad” button to display a numeric keypad. The Keypad button is
active only when the user has selected a parameter that requires a numeric
entry.
Touch individual numbers to enter them, touch “C” to clear an entry, and touch
“Enter” to enter the value in the field. After touching “Enter” the keypad will
close.
60
Keypad
SHOW GRAPHICS
Touch the “Show Graphics” button to display waveforms, coupling diagrams
and other graphical information for the selected test.
Touch the “More” button to view additional information.
Touch the “Back” button to view previous graphics.
Touch the “Exit” button to return to the Test parameters window.
Example burst pulse graph
NSG 3060 EMC test system
8.3 Burst parameter setting
The generation of high voltage bursts and high frequency pulses is part of
the EFT/burst package test required in the international standard EN/IEC
61000-4-4.
The test NSG 3060 generates bursts of interference that simulate the interference that is generated when inductively loaded switches are operated. With
their very steep rising and falling edges, these interference pulses spread over
a frequency spectrum of over 300 MHz and may occur wherever electrical
currents are switched off in connection with motors, circuit breakers, relays,
fluorescent lamps, etc. Therefore, nearly all the relevant standards concerning
the testing of electronic equipment require the performance of burst tests.
8.3.1 Test configuration with power line coupling
In a power line coupling test, the NSG 3060 generates the interference signal,
which is superimposed on the EUT power signal.
8.3.2 Test configuration with external coupling
In an externally coupled test, the interference signal is delivered through the NSG
3060’s coaxial burst output connector on the front panel and fed to an external
coupling clamp. The signal is then applied to signal or data line cables.
The same SHV type connector may also be used for connection of a 3-phase
CDN or for a CDN suitable for 1-phase >16 A and all other CDNs.
NOTE - A Teseq CAS 3025 calibration set must be used
with a minimum 400 MHz digital oscilloscope to accurately verify the EFT pulse parameters.
61
62
Single pulse
Pulse burst
V
100%
90%
V
50%
10%
t
tr
tp
≤ 20%
Burst wave shape and timing definitions
tr = 5 ns ± 30%
tp = 50 ns ± 30% into 50 Ω
tp = 50 –15 ns / +100 ns into 1000 Ω
8.3.3 Burst parameters window
Burst parameter setting window
NSG 3060 EMC test system
tBurst
trep
1
f
Burst
t
8.3.4 Voltage
Touch the “Polarity” button (ALT in the example) to select test polarity. Polarity
values are: positive (POS), negative (NEG), or alternating (ALT).
On odd pulse number there will be one pulse less in negative then in positive.
Positive pulse will be first executed.
Touch the “Voltage” button (200 V in the example) to enter the test voltage. A
red frame is displayed around the field. The voltage value may be entered using
the wheel or the keypad.
8.3.5 Frequency
Touch the “Frequency” button (5 in the example) to set the test frequency. A
red frame is displayed around the field. The frequency value may be entered
using the wheel or the keypad.
Touch the units button (KHz in the example) to set the frequency unit. Frequency
values are Hz and KHz.
8.3.6 Phase
Touch the Synch/Asynch button (Asynch in the example) to activate the synchronization of test pulses to the EUT mains frequency.
When this button is set to Asynch, the phase value button ( --- in the example)
will display ‘---’. When this button is set to Synch, the user must also set the
phase value.
To set the phase value, touch the phase value button. A red frame is displayed
around the field. The phase value may be entered using the wheel or the
keypad.
The value is in degree units and may range from 0 to 359.
8.3.7 Coupling
Touch the “Coupling mode” button (IEC COUPLING in the example) to select
BURST OUTPUT, MANUAL CDN, ANSI COUPLING or IEC COUPLING.
63
64
Burst output
Burst output must be selected if an external capacitive coupling clamp (e.g.
CDN 8014/8015) is connected to the NSG 3060.
Manual CDN
The factory setting for manual CDN is the same as for burst output.
ANSI and IEC coupling
In burst testing it does not matter if ANSI or IEC coupling mode is selected, since
the ANSI standard refers to IEC/EN 61000-4-4. Touch the coupling line selection
field (L1, N, PE in the example) to display the coupling selection window.
Touch the individual “high output coupling line” buttons (L, N, and PE in the
example) to select an open or closed relay.
The “Low output” field (Ref. ground in the example) is always fixed.
Touch “OK” to enable the coupling selection and close the window.
Touch “Cancel” to close the window without saving the coupling selection.
Touch “Show Graphics” to display a graphical example of the coupling selection.
Coupling selection window
Note: Burst coupling is always to HF reference ground.
8.3.8 Burst time
Touch the “burst time” button (15 in the example) to set the burst time. A red
frame is displayed around the field. The burst time may be entered using the
wheel or the keypad.
NSG 3060 EMC test system
Touch the “units” button (ms in the example) to set the time unit. Time units are
s, ms, µs and spikes.
8.3.9 Repetition time
Touch the “Repetition time” button (300 in the example) to set the test repetition time. A red frame is displayed around the field. The repetition time may be
entered using the wheel or the keypad.
Touch the “units” button (ms in the example) to set the time unit. Time units
are s and ms.
8.3.10 Test duration
Touch the “Test Duration” button (120 in the example) to set the test duration time. A red frame is displayed around the field. The duration time may be
entered using the wheel or the keypad.
Touch the “units” button (s in the example) to set the time unit. Time units are
s, min, h and cont (continuous).
8.3.11 Burst generator technical data
ParameterValue
Pulse amplitude: ± 200 V to 4.8 kV (in 1 V steps) - open circuit
± 100 V to 2.4 kV (50 Ω matching system)
Voltage step:
1 V/ 10 V / 100 V
Polarity:
Positive / negative / alternate
Frequency:
Hz: 100 ... 99’999
kHz: 1 ... 1’000
Phase:
Asynchronous, synchronous 0° to 359º (in 1º steps)
Coupling:
ANSI / IEC / external / manual
Burst time:
μs: 1 ... 99’999
ms: 1 ... 99’999
s:
1 ... 1’999
Spike: 1 ... 1000
65
66
Repetition time:
Test duration:
ms: 1 ... 99’999
s:
1 ... 4’200 (70 min)
s:
1 ... 99’999
min: 1 ... 99’999
h: 1 ... 1’000
Continuous
8.3.12 Derating
Some parameter combinations will not be accepted due to the power limitation
of the HV power supply. The following error message will be displayed when an
invalid combination of parameters is entered:
Invalid parameter error message
The following graphs show the relationship between voltage, trep, tburst and
frequency, and show the range of possible parameter combinations that can
be used in testing.
Each graph includes two voltage settings which are shown in different line thicknesses in relation to the trep values given for 20, 10, 5, 2, 1, 0.5, 0.2 and 0.1 ms.
The appropriate trep value (bold trep for the bold line) are labeled on the border
of the graph. Combinations of values that are below the line are allowed.
NSG 3060 EMC test system
Tburst [ms]
0,01
100
0.1
1
10
100
1000
0.1 ms
10000
0.5 ms
0.2 ms
1 ms
100000
5 ms
2 ms
10 ms
20 ms
1000
4,8 kV
10000
Fburst [Hz]
4 kV
100000
1000000
-0.1 s
0.2 s
0.5 s
1s
2s
5s
10 s
20 s
TREP

67
Tburst [ms]
NSG 3060 EMC test system
0.01
100
0.1
1
10
100
1000
3,0 kV
10000
Fburst [Hz]
2,0 kV
100000
2s
1s
0,2 s
1000000
0,1 s
0,1 s
0,2 s
0,5 s
0,5 s
1s
2s
5s
10 s
5s
10 s
20 s
20 s
TREP
68
1000
10000

Tburst [ms]
0,01
100
0.1
1
10
100
1000
10000
100000
1000
1,0 kV
Fburst [Hz]
10000
>500
100000
2s
5s
0,2 s
0,1 s
1s
0,5 s
2s
1000000
0,1 s
0,2 s
1s
0,5 s
5s
10 s
20 s
20 s
TREP

69
70
8.4 Combination wave (Surge) parameter setting
The surge test generates high voltage pulses as specified in the international
standards EN/IEC 61000-4-5 and ANSI C62.41.
8.4.1 Test configuration for power line coupling
Test pulses are injected directly into the EUT power supply lines as they pass
through the mains CDN 306x. The EUT obtains its power from the EUT power
outlet on the front panel of the CDN where the mains voltage has the interference signal superimposed on it.
8.4.2 Test configuration for external coupling
In this mode, the interference pulses are switched to the surge Hi and Lo output
sockets on the front panel, to which an external data line signal coupler can be
connected. By using such an external signal coupler it is possible to superimpose the interference signal, as specified in the standards, on communication
cables and other kinds of data lines.
The same coaxial HV output sockets may also be used for connection to all
other CDNs.
1.0
0.8
0.5
T2
0.3
0.1
T
T1
t
max 30%
Front time T1 = 1.67 x T = 1.2 µs ± 30%
Time to half value T2 = 50 µs ± 20%
Wave shape of open circuit voltage (1.2/50 μs), wave shape definition according to
IEC/EN 61000-4-5.
NSG 3060 EMC test system
71
1.0
0.8
0.5
T2
0.3
0.1
t
T
T1
max 30%
Front time T1 = 1.25 x T 8 = µs ± 20%
Time to half value: T2 = 20 µs ± 20%
Wave shape of short circuit current (8/20 μs), wave shape definition according to
IEC/EN 61000-4-5.
WARNING - Using improper equipment when measuring
surge pulses can result in personal injury or equipment
damage.
NOTE - Teseq recommends using a Teseq MD 200 or MD
200A differential probe in combination with a Teseq INA
6560 Fischer-to-banana adapter for surge pulse verification.
72
CW Parameter window
8.4.3 Voltage
Touch the “polarity” button (ALT in the example) to select test polarity. Polarity
values are: positive (POS), negative (NEG), or alternating (ALT).
On odd pulse number there will be one pulse less in negative then in positive.
Positive pulse will be first executed.
Touch the “voltage” button (200 V in the example) to enter the test voltage. A
red frame is displayed around the field. The voltage value may be entered using
the wheel or the keypad.
8.4.4 Impedance
Touch the “impedance” button (2 ohms in the example), it will repetitively
change between 2 and 12 Ω.
NSG 3060 EMC test system
8.4.5 Phase
Touch the “Synch/Asynch” button (Asynch in the example) to activate the synchronization of test pulses to the EUT mains frequency.
When this button is set to Asynch, the “phase value” button ( --- in the example)
will display ‘---’. When this button is set to Synch, the user must also set the
phase value.
To set the phase value, touch the “phase value” button. A red frame is displayed
around the field. The phase value may be entered using the wheel or the keypad.
The value is in degree units and may range from 0 to 359. Synch mode is only
available if the EUT power is switched on.
8.4.6 Coupling
Touch the “coupling mode” button (ANSI COUPLING in the example) to select
SURGE OUTPUT, MANUAL CDN, ANSI COUPLING or IEC COUPLING.
Surge output
Select SURGE OUTPUT when a pulse is to be applied directly to the EUT; for
example, in component testing of non-powered EUTs.
Manual CDN
This setting will compensate the loss of an external manual CDN such as the
CDN 3083 or CDN 117. The internal impedance will be reduced by 0.37 Ω.
ANSI coupling
When ANSI COUPLING is selected the window. The appropriate coupling network (1- or 3-phase) is displayed automatically, depending on the type of CDN
connected to the NSG 3060.
73
74
ANSI coupling selection window
EUT supply
Touch the “EUT supply” button (1-phase in the example) to select a 1-, 2-, or
3-phase EUT supply mode.
NOTE - The EUT supply selection must match the EUT
supply input on the rear panel of the CDN and the connections to the EUT from the front panel of the CDN.
Otherwise, the coupling path setting will be switched
incorrectly.
Coupling
Touch the coupling button (suppl. in the example) to select basic, supplemental, or diagnostic coupling mode. These modes are identical to those defined
in the ANSI standard. Different coupling options are displayed depending on
the EUT supply mode selected.
NSG 3060 EMC test system
Basic 1
Low
Basic 2
High
Low
L
L
N
N
PE
PE
Supplemental 1
Low
Supplemental 2
High
Low
L
L
N
N
PE
PE
Diagnostic 1
Low
High
Diagnostic 2
High
Low
L
L
N
N
PE
PE
ANSI coupling modes for a 1-phase CDN
High
High
75
76
High/low
The coupling path will be shown by open or closed relay signs. The relay buttons ae not selectable, they are for information only.
By touching the “OK” button the selected coupling will be activated. With
“cancel” it will close the window without saving the coupling selection. By
touching the button “Show Graphics” it will illustate a graphical setting.
IEC coupling
When IEC coupling is selected the window in figure below displayed.
Touch the individual “High” and “Low output coupling” buttons (L, N, and PE in
the example), to select an open or closed relay.
Touch “OK” to enable the coupling selection and close the window.
Touch “Cancel” to close the window without saving the coupling selection.
Touch “Show Graphics” to display a graphical example of the coupling selection.
IEC coupling selection window
NSG 3060 EMC test system
8.4.7 Repetition time
Touch the “Repetition time” button (60 in the example) to set the test repetition
time. A red frame is displayed around the field. The repetition time may be
entered using the wheel or the keypad.
Touch the “units” button (s in the example) to set the time unit. Time units are
s and min.
8.4.8 Test duration
Touch the “Test Duration” button (10 in the example) to set the test duration
time. A red frame is displayed around the field. The duration time may be
entered using the wheel or the keypad.
Touch the “units” button (pulse in the example) to set the unit. Unit values are
pulse and cont (continuous).
8.4.9 Surge generator technical data
Parameter
Pulse voltage (open circuit): Pulse current (short circuit):
Impedance: Polarity: Phase synchronization: Coupling: Pulse repetition:
Test duration: Value
± 200 V to 6.6 kV (in 1 V steps)
± 100 A to 3.3 kA
2 / 12 Ω
Positive / negative / alternate
Asynchronous, synchronous 0° to 359º
(in 1º steps)
ANSI / IEC / external / manual
10* .... 600 s (in 1 sec steps)
1 .... 10 min.
1 to 9999 pulses
Continuous
* Repetition rate depends on voltage:
200 to 4400 V = 10 s repetition time
4401 to 6600 V = 20 s repetition time
8.5 Ring wave (RW)
The ring wave is specified in the ANSI IEEE Std C62.41.2, 2002 and
IEC/EN 61000-4-12.
77
78
8.5.1 Test configuration for power line coupling
The test pulse is injected directly into the EUT power supply lines as they pass
through the CDN of the test system. The EUT obtains its power from the EUT
power outlet on the CDN of the test system where the voltage has the interference signal superimposed on it.
8.5.2 Test configuration with external coupling
Hereby the interference pulses are brought out to the Hi and Lo output sockets
on the front panel to which an external coupler can be connected.
8.5.3 Ring wave parameters
UII
100 %
90 %
T
10 %
t
T1
T1 Rise time
T Oscillation period
The open-circuit voltage waveform is defined by the following parameters:
Rise time: 0.5 μs
Ringing frequency: 100 kHz
Note: No short-circuit current waveform is specified for the 100 kHz ring wave.
Because the purpose of the ring wave is not to provide high-energy stress to
the EUT, the precise specification of the current waveform is unnecessary.
NSG 3060 EMC test system
79
Ring wave parameter window
8.5.4 Voltage
Touching the “Volt” field, it will come up with a red frame to indicate the selected
parameter being ready for change. The value can be changed either with the
red wheel or using the keypad.
Touching the prefix repetitively it will change from Alternate to Positive and
Negative.
On odd pulse number there will be one pulse less in negative then in positive.
Positive pulse will be first executed.
8.5.5 Impedance
Touching the Impedance field, it will repetitively change between 12, 30 and
200 Ω.
8.5.6 Phase
Touching the Phase field, it will come up with a red frame to indicate the selected
parameter being ready for change. The value can be changed either with the red
wheel or using the keypad. Touching the Synch / Asynch button it will change
repetitively. In synch mode the angle can be changed either with the red wheel
or using the keypad. Synch mode is only available if a CDN is connected and if
the EUT power (AC) is switched on.
8.5.7 Coupling
Touching the coupling prefix repetitively it will change from surge output,
manual CDN, ANSI coupling and IEC coupling.
80
Surge output
The surge output selection will activate the HV surge pulse output. This selection is used if pulse need to applied directly to an EUT like for testing of nonenergized EUTs, socalled component testing.
Manual CDN
The factory settings for this selection is equal the surge output. But it is possible to compensate the loss of an external manual CDN’s. To do so, the CDN
hast to be sent with the unit to a Teseq facility for modification.
ANSI coupling
Touching the coupling line selection it will come up with a window. The appropriate coupling network (1-phase or 3-phase) is automatically given by the
selected CDN. The 2-phase selection can be done only if a three phase coupler
is connected. It is possible to use a three phase coupler also as a single phase
CDN. Make sure, that the EUT connector on the CDN does match accordingly.
1-phase ANSI coupling possibilities
NSG 3060 EMC test system
EUT supply
Set the EUT supply in mode: 1-phase, 2-phase or 3-phase.
Make sure, that the EUT connector on the CDN does match accordingly the
EUT supply selection.
EUT supply selection has to be in line with the connected
EUT supply input at the rear of the automated CDN
otherwise the coupling path setting will be switched
incorrect.
Coupling
The coupling mode can be set via multiple button touch between basic, supplemental and diagnostic. Those wording are equal to the ANSI standard. Depending on selected EUT supply mode different coupling mode level are selected.
For the ANSI coupling path.
High/low
The coupling path will be shown by open or closed relay signs. The relay buttons
are not selectable, they are for information only.
By touching the “OK” button the selected coupling will be activated. With
“cancel” it will close the window without saving the coupling selection. By
touching the button “Show Graphics” it will illustrate a graphical setting.
IEC coupling
IEC coupling is not recommended for ring wave, however it can be selected by
touching the coupling line selection it will come up with a window. The desired
line to ground or lines to ground can be set as well as line to line coupling. The
coupling paths will be shown as open or closed relay signs. With touching the
“OK” button the selected coupling will be taken. With “cancel” it will close the
window without saving the coupling selection. With touching the button “Show
Graphics” it will show a graphical setting.
81
82
8.5.8 Repetition time
Touching the “Repetition Time” field, it will come up with a red frame to indicate
the selected parameter being ready for change. The value can be changed
either with the red wheel or using the keypad.
Touching the units repetitively will change from s to min.
8.5.9 Test duration
Touching the “Test Duration” field, it will come up with a red frame to indicate
the selected parameter being ready for change. The value can be changed
either with the red wheel or using the keypad.
Touching the units repetitively it will change from Pulse to Continuous.
8.5.10 Technical data ring wave generator
Parameter Value
Pulse voltage (open circuit): ± 200 V to 6.6 kV (in 1 V steps)
Pulse current (short circuit): ±16.6 to ±550 A, ± 10%, (12 Ω)
±6.6 to ±220 A, ± 10%, (30 Ω)
Impedance: 12 Ω / 30 Ω / 200 Ω
Polarity: Positive / negative / alternate
Phase synchronization:
Asynchronous, synchronous 0° to
359º (in 1º steps)
Coupling: ANSI / IEC / external / manual
Pulse repetition: 10* .... 600 s (in 1 s steps)
1 .... 10 min.
Test duration: 1 to 9999 pulses
Continuous
* Repetition rate depends on voltage:
200 to 4400 V = 10 s repetition time
4401 to 6600 V = 20 s repetition time
NSG 3060 EMC test system
8.6 Telecom wave test
The telecom wave test, in compliance with IEC/EN 61000-4-5:2005 and IEC
60060-1, ITU–K series, ANSI/IEEE C62.41 and the safety standard of UL 1950 is
used to test port of symmetrical driven communication lines.
The same purpose will cover the 9/720 µs pulse given in ANSI-TIA-968-B which
is also part of the modules thanks to the tolerance of pulse given in the standard
mentioned above it can be cover by 10/700 µs pulse.
U
1.0
B
0.9
0.5
T2
A
0.3
0.1
0.0
t
T
O1
T1
Front time T1 = 1.67 x T = 10 µs ± 30%
Time to half value T2 = 700 µs ± 20%
Waveform of open-circuit voltage (10/700 µs) (waveform defination according
to IEC 80060-1).
ll/max
1.0
0.9
T2
0.5
0.1
0.0
t
O1
T
T1
Front time T1 = 1.25 x T = 5 µs ± 20%
Time to half value T2 = 320 µs ± 20%
83
84
WARNING - If a CDN is connected, the voltage can
not be set higher than 6.6 kV this for safety reason to
prevent damages to the CDN. To set the 7 kV range on
the telecom pulse, the CDN system cable needs to be
disconnected and the HV output of the Generator has
to be disconnect from the CDN.
Telecom parameter window
8.6.1 Voltage
Touching the “Repetition Time” field, it will come up with a red frame to indicate
the selected parameter being ready for change. The value can be changed
either with the red wheel or using the keypad.
8.6.2 Impedance
Touch the “impedance” button (15 ohms in the example), it will repetitively
change between 15 and 40 Ω.
8.6.3 Phase
Since telecom pulse always is injected asynchronous into telecommunication
it may stay always to “Asynch”. But it is possible that in some rear cases a
synchronisation to the power is needed for investigation purpose, so the phase
angle can be set.
Touch the “Synch/Asynch” button (Asynch in the example) to activate the synchronization of test pulses to the EUT mains frequency.
NSG 3060 EMC test system
When this button is set to Asynch, the “phase value” button ( --- in the example)
will display ‘---’. When this button is set to Synch, the user must also set the
phase value.
To set the phase value, touch the “phase value” button. A red frame is displayed
around the field. The phase value may be entered using the wheel or the keypad.
The value is in degree units and may range from 0 to 359. Synch mode is only
available if the EUT power is switched on.
8.6.4 Coupling
Touch the “coupling mode” button SURGE OUTPUT, or MANUAL CDN.
Surge output
Select SURGE OUTPUT when a pulse is to be applied directly to the EUT; for
example, in component testing of non-powered EUTs.
Manual CDN
This setting will compensate the loss of an external MANUAL CDN such as the
CDN 3083 or CDN 117/118. The internal impedance will be reduced by 0.37 Ω.
8.6.5 Repetition time
Touch the “Repetition time” button (60 in the example) to set the test repetition time. A red frame is displayed around the field. The repetition time may
be entered using the wheel or the keypad. Touch the “units” button (s in the
example) to set the time unit. Time units are s and min. Touching the units
repetitively will change from s to min.
8.6.6 Test duration
Touch the “Test Duration” button (10 in the example) to set the test duration
time. A red frame is displayed around the field. The duration time may be
entered using the wheel or the keypad.
Touch the “units” button (pulse in the example) to set the unit. Unit values are
PULSE and CONT (continuous).
85
86
Parameter Value
Pulse voltage (open circuit): ± 200 V to 7.7 kV (in 1 V steps)
Pulse current (short circuit):
± 13.3 A to 513.3 A
Impedance: 15 / 40 Ω
Polarity: Positive / negative / alternate
Phase synchronization: Asynchronous, (synchronous 0° to
359º in 1º steps)
Coupling: external / manual
Pulse repetition: 20* to 30 s, up to 600 s
(in 1 sec steps)
Test duration: 1 to 9999 pulses
Continuous
* Repetition rate depends on voltage:
200 to 4400 V = 20 s repetition time
4401 to 7700 V = 30 s repetition time
8.7 Mains power quality (PQT)
The PQT test involves the emulation of mains voltage dips and brief interruptions as specified in the international standard EN/IEC 61000-4-11.
The generator causes disturbances on the EUT supply line that is brought out
to the EUT power outlet socket of the 1-phase CDN. A dip have occurred when
the nominal voltage falls by a significant amount during a certain number of
cycles. The standard specifies dips of 20, 30 and 60% (i.e. the voltage falls to
80, 70 and 40% of the nominal level respectively).
An external variable transformer (variac), transformer with taps or a DC power
source is to be fed into the appropriate pins of an extra input socket for freely
selectable voltage dips.
An interruption occurs when the supply voltage disappears completely for a
certain number of cycles (or falls to a value less than 5% of its nominal voltage).
NOTE - Dips and interrupts appear on the phase (L)
line only.
NSG 3060 EMC test system
8.7.1 Sample graphs of dips/interrupts
87
u
70%
0
5
t (cycles)
10
a) Voltage dip 30%
u
40%
0
u
10
t (cycles)
b) Voltage dip 60%
t (cycles)
c) Voltage dip 100%
8.7.2 Mains power quality generator
PQT Parameter window
88
8.7.3 Voltage U Var
If no automatic variac or automatic transformer being connected, then the
voltage dips or interrupts will always occur to 0%. Touching the units repetitively
it will change from % to Volts.
If a manual voltage source being connected, then the dips/interrupts level will
follow the manually set voltage at the EUT input.
8.7.4 Phase
Touching the “Phase” field, it will come up with a red frame to indicate the
selected parameter being ready for change. The value can be modified either
with the red wheel or using the keypad. Touching the “Synch/Asynch” button
it will change repetitively. In synch mode the angle can be modified either with
the red wheel or using the keypad. Synch mode is only available along with a
automated CDN and if the EUT power (AC) is switched on.
8.7.5 Repetition time
Touching the “Repetition Time” field, it will come up with a red frame to indicate
the selected parameter being ready for change. The value can be modified
either with the red wheel or by using the keypad.
Touching the units repetitively will change from s, min, cycle, μs to ms.
8.7.6 T-Event
Touching the “T-Event” field, it will come up with a red frame to indicate the
selected parameter being ready for change. The value can be modified either
with the red wheel or using the keypad.
Touching the units repetitively will change from ms, s, cycle, ¹⁄10 cycle or μs.
8.7.7 Test duration
Touching the “Test Duration” field, it will come up with a red frame to indicate
the selected parameter being ready for change. The value can be modified
either with the red wheel or using the keypad.
Touching the units repetitively will change from Pulse, Continuous, s to min.
NSG 3060 EMC test system
8.7.8 Dips and interrupts characteristics
ParameterValue
Dips & interrupts:
From EUT voltage input to 0 V; 0% (1)
Uvar with optional variac:
up to 265 V or up to 115% of Uin
16 A max. ±10%
Uvar step transformer: 0%; 40%; 70%; 80%
Peak inrush current capability: >500 A (at 230 V)
Switching times: 1 to 5 μs (100 Ω load)
Phase synchronization: Asynchronous, synchronous 0° to 359º
(in 1º steps)
Repetition time: µs:
40 ... 99’999
ms:
1 ... 99’999
s:
1 ... 1’999
min:
1 ... 35
cycle:
1 ... 99’999
Event time (T-Event):
µs:
20 ... 99’999
ms:
1 ... 99’999
s:
1 ... 1’999
cycle:
1 ... 300
¹⁄ 10 cycle: 1 ... 3’000
Test duration: s:
1 ... 99’999
min:
1 ... 70’000
pulse:
1 ... 99’999
Continuous
(1) Effective minimal dip voltage ~8 V. As specified in IEC 61000-4-11, chapt. 5.1 a test voltage
level from 0% to 20% of the rated voltage is considered as a total interruption.
8.8. Variation test (-4-11) – automatic procedure
Parameter
Uvar with optional variac:
Phase synchronization: Repetition time: Value
up to 265 V (in 1 V steps) or
up to 115% of Uin (in 1% steps)
asynchronous, synchronous, 0° to 359°
(in 1° steps)
1000 ms to 35 min.
1 to 99’999 cycles
89
90
Decreasing time Td: Time at reduced voltage Ts:
Increasing time Ti: Test duration:
abrupt
1 ms to 5’000 ms
1 s to 5 s
1 to 250 cycles for 50 Hz
1 to 300 cycles for 60 Hz
10 ms to 10’000 ms
1 s to 10 s
1 to 250 cycles for 50 Hz
1 to 300 cycles for 60 Hz
10 ms to 5’000 ms
1 s to 5 s
1 to 250 cycles for 50 Hz
1 to 300 cycles for 60 Hz
1 s to 99’999 s
1 min. to 70’000 min.
1 to 99’999 pulse
Continous
Automatic accessories for power quality test
All automated standard accessories for PQT test provides a convenient means
of reducing the incoming supply voltage. It is required for power quality testing
(PQT) and is fully compliant with the latest revision of IEC/EN 61000-4-11
(2004).
Once detected, the functions are available in the user interface software. Its
fully automatic controlled, driven from NSG 3060.
With the step transformer INA 6502 the Uvar settings 0% – 40% – 70% – 80%
will appear.
Connecting the single variac VAR 3005-S16 or VAR 6501 the settings of Uvar
will be possible in volts or % of Uin. Therefore Uin needs to be set first in the
“General” settings menu. Uin in this case is the actual input voltage of the
single variac.
Connecting the double variac VAR 3005-D16 or VAR 6502 it is important that
Uin in the “General” setting needs to be set first before entering the variation
screen. The value of Uin is variable with the double variac.
NSG 3060 EMC test system
For proper operation of the plug and play detection
mechanisms it is strongly recommended to power
on first the accessory and then the NSG 3060 main
frame.
Powering on the NSG 3060 main frame before the accessories may result in non-detection of accessories.
8.9 Power magnetic field testing (-4-8) – automatic procedure
Parameter
AC field: Frequency: Coil factor:
Test duration:
Value
1 to 40 A/m (in 1 A/m steps)
50 Hz / 60 Hz
0.01 to 99.99
1 to 9’999 pulses; continuous
8.10 Pulsed magnetic field testing (-4-9)
Tests with pulsed magnetic fields simulate the type of field produced by surge
pulses such as those occurring during lightning strokes on buildings and other
metallic structures such as free-standing masts, lightning conductors, earth
networks, etc.
The NSG 3060 in conjunction with the pulse wave shape adaptor and a
loop antenna it generates these fields in accordance with the IEC 61000-4-9
standard by inducing a surge current into magnetic field loop.
It is recommended for the user to stay away (at least
a few meters) from the loop antenna while magnetic
fields are generated. Also keep away magnetic field sensitive devices and items such as credit cards – magnetic
key cards etc… which might be influenced by the field.
91
92
8.10.1 The optional magnetic field loops INA 701 and INA 702
Tests with mains frequency according IEC/EN 61000-4-8, in conjunction with
the MFO 6501/6502 option, and pulsed magnetic fields are performed using the
magnetic field loops designed for NSG 3060.
These are rectangular loops measuring 1 x 1m and are suitable for test objects
with dimensions up to 0.6 x 0.6 x 0.5m (l x w x h). For the pulsed magnetic field
test two types of loop can be supplied:
The INA 701 is a coil with a factor of 0.89. It enables field strengths up to 3.6A/m
for mains frequency fields 50 or 60Hz when used with the MFO 6501 or MFO
6502 current sources option and 1200A/m for pulsed magnetic fields.
NSG 3060 EMC test system
The INA 702 is a 1 x 1m loop - 11 turns – coil factor 9.8 - when fitted with the
power plug. It enables the generation of field strengths of up to 40A/m for
mains frequency fields 50 or 60Hz when used with the MFO 6501 or MFO 6502
current sources option.
The INA 702 becomes a single turn loop when fitted with the pulse plug, which
allows the generation of pulsed field strengths up to 1200A/m, where the
current is generated by surge generator.
8.10.2 Pulse wave shape adapter INA 753
In order to meet the pulse waveform required by IEC 61000-4-9, the wave shape
adapter INA 753 needs to be used with NSG 3060 and the INA 701 or 702 loop
antennas.
The pulse wave shape adapter INA 753 is a standard accessory for the NSG
3060. It provides a convenient means for interconnecting the surge generator
output with the loop antennas INA 701 or 702 and insures that the generated
pulsed magnetic field has the wave shape as specified in the application standard.
The control is fully automatic, driven from the NSG. The user will setup his tests
directly in A/m, the internal software makes the calculation and drives the
combination wave pulse moduel to generate the right current.
Two safety banana plugs provide a convenient means to connect the loop
antenna; two Fischer HV plugs allow connection to Surge Hi and Lo outputs of
NSG 3060.
93
94
The field generated in the loop antenna is directly proportional to the current
flowing through it:
Field strength (A/m) H = Cf x I
Where H is the generated field Cf the coil factor and I the current generated by
the combination wave pulse module.
8.10.3 Generator setting
Generally surge generators get set by voltage, the current they deliver will
depend on the load impedance. In this case the load consists of the loop
antenna plus the wave shape adapter which is fix and stable. So there is a direct
relationship between the generator voltage setting and the current delivered
to the load.
As the current in the loop antenna and the generated field (coil factor) are
proportional, there will be a direct relationship between the surge generator’s
voltage setting and the generated field.
In case an INA 702 loop antenna is used, the termination
plug labelled “Pulse“ needs to be used.
8.10.4 Technical data pulsed magnetic field test
Parameter
Pulsed field:
Polarity: Repetition time:
Impedance: Coil factor:
Test duration:
Phase synchronization:
NSG 3060 EMC test system
Value
1 to 1200 A/m (in 1 A/m steps), higher
possible with lower coil factor
positive / negative / alternate
10 s to 10 min. (in 1 s steps)
2Ω
0.35 to 99.99 in 0.01 step
1 to 9’999 pulses
Continuous
Asynchronous, synchronous 0 to 359°
(in 1° steps)
8.11 Power magnetic field test (-4-8) - automatic procedure
Mains frequency magnetic fields simulate the kind of stray fields that occur
around current carrying power supply lines.
The optional MFO can be connected to the NSG 3060 using the convenient user
interface for easy test setting.
The automated MFO together with the INA 701 or 702 loop antenna generates
test conditions in accordance with the IEC 61000-4-8 standard by inducing a
strong current into a magnetic field loop.
8.11.1 Automatic magnetic field option MFO 6502
The automatic current generator type MFO 6502 (magnetic field option) is a
standard accessory for the Teseq NSG 30xx series
It is required for magnetic field testing for fields up to 40 A/m.
MFO 6502 is designed to drive INDUCTIVE LOADS ONLY,
as magnetic field loops. Connecting capacitive loads
will destroy the Instrument
For more information refer to the MFO manual.
8.11.2 Technical data power magnetic field test
Parameter
Field strength:
Frequency: Coil factor:
Test duration:
Value
1 to 99999 mA/m (in 1 mA/m steps)
1 to 100 A/m (in 1 A/m steps)
50 Hz / 60 Hz
0.01 to 99.99 (in 0.01 steps)
1 to 9’999 s
1 to 166 min
Continuous
95
96
8.12 Standard test parameter
Basic Standard, IEC 61000-4-4 2004_Ed_2
File name implemented
ANSI-IEC 1PH POWER LINES LEVEL 1
ANSI-IEC 1PH POWER LINES LEVEL 2
ANSI-IEC 1PH POWER LINES LEVEL 3
ANSI-IEC 1PH POWER LINES LEVEL 4
ANSI-IEC 3PH POWER LINES LEVEL 1
ANSI-IEC 3PH POWER LINES LEVEL 2
ANSI-IEC 3PH POWER LINES LEVEL 3
ANSI-IEC 3PH POWER LINES LEVEL 4
ANSI-IEC CAP.COUPL. LEVEL 1
ANSI-IEC CAP.COUPL. LEVEL 2
ANSI-IEC CAP.COUPL. LEVEL 3
ANSI-IEC CAP.COUPL. LEVEL 4
Test step Voltage
1/2
500 V
Polarity
±
Frequency Phase Coupling
5 kHz
Asynch L, N, PE
Burst time Rep. time Test duration
15 ms
300 ms
120 s
2/2
500 V
±
100 kHz
Asynch L, N, PE
750us
300 ms
120 s
1/2
1000 V
±
5 kHz
Asynch L, N, PE
15 ms
300 ms
120 s
2/2
1000 V
±
100 kHz
Asynch L, N, PE
750us
300 ms
120 s
1/2
2000 V
±
5 kHz
Asynch L, N, PE
15 ms
300 ms
120 s
2/2
2000 V
±
100 kHz
Asynch L, N, PE
750us
300 ms
120 s
1/2
4000 V
±
5 kHz
Asynch L, N, PE
15 ms
300 ms
120 s
2/2
4000 V
±
100 kHz
Asynch L, N, PE
750us
300 ms
120 s
1/2
500 V
±
5 kHz
Asynch L1, L2, L3, N, PE 15 ms
300 ms
120 s
2/2
500 V
±
100 kHz
Asynch L1, L2, L3, N, PE 750us
300 ms
120 s
1/2
1000 V
±
5 kHz
Asynch L1, L2, L3, N, PE 15 ms
300 ms
120 s
2/2
1000 V
±
100 kHz
Asynch L1, L2, L3, N, PE 750us
300 ms
120 s
1/2
2000 V
±
5 kHz
Asynch L1, L2, L3, N, PE 15 ms
300 ms
120 s
2/2
2000 V
±
100 kHz
Asynch L1, L2, L3, N, PE 750us
300 ms
120 s
1/2
4000 V
±
5 kHz
Asynch L1, L2, L3, N, PE 15 ms
300 ms
120 s
2/2
4000 V
±
100 kHz
Asynch L1, L2, L3, N, PE 750us
300 ms
120 s
1/2
250 V
±
5 kHz
Asynch Burst output
15 ms
300 ms
120 s
2/2
250 V
±
100 kHz
Asynch Burst output
750us
300 ms
120 s
1/2
500 V
±
5 kHz
Asynch Burst output
15 ms
300 ms
120 s
2/2
500 V
±
100 kHz
Asynch Burst output
750us
300 ms
120 s
1/2
1000 V
±
5 kHz
Asynch Burst output
15 ms
300 ms
120 s
2/2
1000 V
±
100 kHz
Asynch Burst output
750us
300 ms
120 s
1/2
2000 V
±
5 kHz
Asynch Burst output
15 ms
300 ms
120 s
2/2
2000 V
±
100 kHz
Asynch Burst output
750us
300 ms
120 s
Basic Standard, IEC 61000-4-4
2004_Ed_2
File nam e im plem ented
ANSI-IEC 1PH POWER LINES LEVEL 1
ANSI-IEC 1PH POWER LINES LEVEL 2
ANSI-IEC 1PH POWER LINES LEVEL 3
ANSI-IEC 1PH POWER LINES LEVEL 4
ANSI-IEC 3PH POWER LINES LEVEL 1
ANSI-IEC 3PH POWER LINES LEVEL 2
ANSI-IEC 3PH POWER LINES LEVEL 3
ANSI-IEC 3PH POWER LINES LEVEL 4
ANSI-IEC CAP.COUPL. LEVEL 1
ANSI-IEC CAP.COUPL. LEVEL 2
ANSI-IEC CAP.COUPL. LEVEL 3
ANSI-IEC CAP.COUPL. LEVEL 4
Burst
tim e
15 ms
Rep.
tim e
300 ms
Test
duratio
n
120 s
2/2
Frequenc
Voltage Polarity y
Phase Coupling
500 V
5 kHz
Asynch L, N, PE
±
500 V
100 kHz
Asynch L, N, PE
±
750us
300 ms
120 s
1/2
1000 V
±
5 kHz
Asynch L, N, PE
15 ms
300 ms
120 s
2/2
1000 V
±
100 kHz
Asynch L, N, PE
750us
300 ms
120 s
1/2
2000 V
±
5 kHz
Asynch L, N, PE
15 ms
300 ms
120 s
2/2
2000 V
±
100 kHz
Asynch L, N, PE
750us
300 ms
120 s
1/2
4000 V
±
5 kHz
Asynch L, N, PE
15 ms
300 ms
120 s
2/2
4000 V
±
100 kHz
Asynch L, N, PE
750us
300 ms
120 s
1/2
500 V
±
5 kHz
Asynch L1, L2, L3, N, PE 15 ms
300 ms
120 s
2/2
500 V
±
100 kHz
Asynch L1, L2, L3, N, PE 750us
300 ms
120 s
1/2
1000 V
±
5 kHz
Asynch L1, L2, L3, N, PE 15 ms
300 ms
120 s
2/2
1000 V
±
100 kHz
Asynch L1, L2, L3, N, PE 750us
300 ms
120 s
1/2
2000 V
±
5 kHz
Asynch L1, L2, L3, N, PE 15 ms
300 ms
120 s
2/2
2000 V
±
100 kHz
Asynch L1, L2, L3, N, PE 750us
300 ms
120 s
1/2
4000 V
±
5 kHz
Asynch L1, L2, L3, N, PE 15 ms
300 ms
120 s
2/2
4000 V
±
100 kHz
Asynch L1, L2, L3, N, PE 750us
300 ms
120 s
1/2
250 V
±
5 kHz
Asynch Burst output
15 ms
300 ms
120 s
2/2
250 V
±
100 kHz
Asynch Burst output
750us
300 ms
120 s
1/2
500 V
±
5 kHz
Asynch Burst output
15 ms
300 ms
120 s
2/2
500 V
±
100 kHz
Asynch Burst output
750us
300 ms
120 s
1/2
1000 V
±
5 kHz
Asynch Burst output
15 ms
300 ms
120 s
2/2
1000 V
±
100 kHz
Asynch Burst output
750us
300 ms
120 s
1/2
2000 V
±
5 kHz
Asynch Burst output
15 ms
300 ms
120 s
2/2
2000 V
±
100 kHz
Asynch Burst output
750us
300 ms
120 s
Test
step
1/2
NSG 3060 EMC test system
Basic Standard, IEC 61000-4-5
File name implemented
97
Test step
Voltage
Polarity
Impedance
Phase
Coupling
Rep. time
Test duration
IEC 1PH POWER LINES L-N LEVEL 1
1/1
500 V
±
2
0°- 270°/90°
L -> N
60 s
10 pulse
IEC 1PH POWER LINES L-N LEVEL 2
1/2
500 V
±
2
0°- 270°/90°
L -> N
60 s
10 pulse
2/2
1000 V
±
2
0°- 270°/90°
L -> N
60 s
10 pulse
1/3
500 V
±
2
0°- 270°/90°
L -> N
60 s
10 pulse
2/3
1000 V
±
2
0°- 270°/90°
L -> N
60 s
10 pulse
3/3
2000 V
±
2
0°- 270°/90°
L -> N
60 s
10 pulse
1/4
500 V
±
2
0°- 270°/90°
L -> N
60 s
10 pulse
2/4
1000 V
±
2
0°- 270°/90°
L -> N
60 s
10 pulse
3/4
2000 V
±
2
0°- 270°/90°
L -> N
60 s
10 pulse
4/4
4000 V
±
2
0°- 270°/90°
L -> N
60 s
10 pulse
IEC 1PH POWER LINES L-N LEVEL 3
IEC 1PH POWER LINES L-N LEVEL 4
IEC 1PH POWER LINES L-PE LEVEL 1
1/1
500 V
±
12
0°- 270°/90°
L -> PE
60 s
10 pulse
IEC 1PH POWER LINES L-PE LEVEL 2
1/2
500 V
±
12
0°- 270°/90°
L -> PE
60 s
10 pulse
2/2
1000 V
±
12
0°- 270°/90°
L -> PE
60 s
10 pulse
1/3
500 V
±
12
0°- 270°/90°
L -> PE
60 s
10 pulse
2/3
1000 V
±
12
0°- 270°/90°
L -> PE
60 s
10 pulse
3/3
2000 V
±
12
0°- 270°/90°
L -> PE
60 s
10 pulse
1/4
500 V
±
12
0°- 270°/90°
L -> PE
60 s
10 pulse
2/4
1000 V
±
12
0°- 270°/90°
L -> PE
60 s
10 pulse
3/4
2000 V
±
12
0°- 270°/90°
L -> PE
60 s
10 pulse
4/4
4000 V
±
12
0°- 270°/90°
L -> PE
60 s
10 pulse
IEC 1PH POWER LINES N-PE LEVEL 1
1/1
500 V
±
12
0°- 270°/90°
N -> PE
60 s
10 pulse
IEC 1PH POWER LINES N-PE LEVEL 2
1/2
500 V
±
12
0°- 270°/90°
N -> PE
60 s
10 pulse
2/2
1000 V
±
12
0°- 270°/90°
N -> PE
60 s
10 pulse
1/3
500 V
±
12
0°- 270°/90°
N -> PE
60 s
10 pulse
2/3
1000 V
±
12
0°- 270°/90°
N -> PE
60 s
10 pulse
3/3
2000 V
±
12
0°- 270°/90°
N -> PE
60 s
10 pulse
1/4
500 V
±
12
0°- 270°/90°
N -> PE
60 s
10 pulse
2/4
1000 V
±
12
0°- 270°/90°
N -> PE
60 s
10 pulse
3/4
2000 V
±
12
0°- 270°/90°
N -> PE
60 s
10 pulse
4/4
4000 V
±
12
0°- 270°/90°
N -> PE
60 s
10 pulse
IEC 1PH POWER LINES L-PE LEVEL 3
IEC 1PH POWER LINES L-PE LEVEL 4
IEC 1PH POWER LINES N-PE LEVEL 3
IEC 1PH POWER LINES N-PE LEVEL 4
98
Basic Standard, IEC 61000-4-5
File name implemented
Test step
Voltage
Polarity
Impedance
Phase
Coupling
Rep. time
Test duration
IEC 1PH POWER LINES L-N LEVEL 1
1/1
500 V
±
2
0°- 270°/90°
L -> N
60 s
10 pulse
IEC 1PH POWER LINES L-N LEVEL 2
1/2
500 V
±
2
0°- 270°/90°
L -> N
60 s
10 pulse
2/2
1000 V
±
2
0°- 270°/90°
L -> N
60 s
10 pulse
1/3
500 V
±
2
0°- 270°/90°
L -> N
60 s
10 pulse
2/3
1000 V
±
2
0°- 270°/90°
L -> N
60 s
10 pulse
3/3
2000 V
±
2
0°- 270°/90°
L -> N
60 s
10 pulse
1/4
500 V
±
2
0°- 270°/90°
L -> N
60 s
10 pulse
2/4
1000 V
±
2
0°- 270°/90°
L -> N
60 s
10 pulse
3/4
2000 V
±
2
0°- 270°/90°
L -> N
60 s
10 pulse
4/4
4000 V
±
2
0°- 270°/90°
L -> N
60 s
10 pulse
IEC 1PH POWER LINES L-PE LEVEL 1
1/1
500 V
±
12
0°- 270°/90°
L -> PE
60 s
10 pulse
IEC 1PH POWER LINES L-PE LEVEL 2
1/2
500 V
±
12
0°- 270°/90°
L -> PE
60 s
10 pulse
2/2
1000 V
±
12
0°- 270°/90°
L -> PE
60 s
10 pulse
1/3
500 V
±
12
0°- 270°/90°
L -> PE
60 s
10 pulse
2/3
1000 V
±
12
0°- 270°/90°
L -> PE
60 s
10 pulse
3/3
2000 V
±
12
0°- 270°/90°
L -> PE
60 s
10 pulse
1/4
500 V
±
12
0°- 270°/90°
L -> PE
60 s
10 pulse
2/4
1000 V
±
12
0°- 270°/90°
L -> PE
60 s
10 pulse
3/4
2000 V
±
12
0°- 270°/90°
L -> PE
60 s
10 pulse
4/4
4000 V
±
12
0°- 270°/90°
L -> PE
60 s
10 pulse
IEC 1PH POWER LINES L-N LEVEL 3
IEC 1PH POWER LINES L-N LEVEL 4
IEC 1PH POWER LINES L-PE LEVEL 3
IEC 1PH POWER LINES L-PE LEVEL 4
IEC 1PH POWER LINES N-PE LEVEL 1
1/1
500 V
±
12
0°- 270°/90°
N -> PE
60 s
10 pulse
IEC 1PH POWER LINES N-PE LEVEL 2
1/2
500 V
±
12
0°- 270°/90°
N -> PE
60 s
10 pulse
2/2
1000 V
±
12
0°- 270°/90°
N -> PE
60 s
10 pulse
1/3
500 V
±
12
0°- 270°/90°
N -> PE
60 s
10 pulse
2/3
1000 V
±
12
0°- 270°/90°
N -> PE
60 s
10 pulse
3/3
2000 V
±
12
0°- 270°/90°
N -> PE
60 s
10 pulse
1/4
500 V
±
12
0°- 270°/90°
N -> PE
60 s
10 pulse
2/4
1000 V
±
12
0°- 270°/90°
N -> PE
60 s
10 pulse
3/4
2000 V
±
12
0°- 270°/90°
N -> PE
60 s
10 pulse
4/4
4000 V
±
12
0°- 270°/90°
N -> PE
60 s
10 pulse
IEC 1PH POWER LINES N-PE LEVEL 3
IEC 1PH POWER LINES N-PE LEVEL 4
NSG 3060 EMC test system
IEC 3PH POWER LINES LX-LX LEVEL 1
1/6
500 V
±
2
0°- 270°/90°
L1 -> N
60 s
10 pulse
2/6
500 V
±
2
0°- 270°/90°
L2 -> N
60 s
10 pulse
3/6
500 V
±
2
0°- 270°/90°
L3 -> N
60 s
10 pulse
4/6
500 V
±
2
0°- 270°/90°
L1 -> L2
60 s
10 pulse
5/6
500 V
±
2
0°- 270°/90°
L1 -> L3
6/6
500 V
±
2
0°- 270°/90°
L2 -> L3
60 s
10 pulse
1/6
1000 V
±
2
0°- 270°/90°
L1 -> N
60 s
10 pulse
2/6
1000 V
±
2
0°- 270°/90°
L2 -> N
60 s
10 pulse
3/6
1000 V
±
2
0°- 270°/90°
L3 -> N
60 s
10 pulse
4/6
1000 V
±
2
0°- 270°/90°
L1 -> L2
60 s
10 pulse
5/6
1000 V
±
2
0°- 270°/90°
L1 -> L3
60 s
10 pulse
6/6
1000 V
±
2
0°- 270°/90°
L2 -> L3
60 s
10 pulse
1/6
2000 V
±
2
0°- 270°/90°
L1 -> N
60 s
10 pulse
2/6
2000 V
±
2
0°- 270°/90°
L2 -> N
60 s
10 pulse
3/6
2000 V
±
2
0°- 270°/90°
L3 -> N
60 s
10 pulse
4/6
2000 V
±
2
0°- 270°/90°
L1 -> L2
60 s
10 pulse
5/6
2000 V
±
2
0°- 270°/90°
L1 -> L3
60 s
10 pulse
6/6
2000 V
±
2
0°- 270°/90°
L2 -> L3
60 s
10 pulse
1/6
4000 V
±
2
0°- 270°/90°
L1 -> N
60 s
10 pulse
2/6
4000 V
±
2
0°- 270°/90°
L2 -> N
60 s
10 pulse
3/6
4000 V
±
2
0°- 270°/90°
L3 -> N
60 s
10 pulse
4/6
4000 V
±
2
0°- 270°/90°
L1 -> L2
60 s
10 pulse
5/6
4000 V
±
2
0°- 270°/90°
L1 -> L3
60 s
10 pulse
6/6
4000 V
±
2
0°- 270°/90°
L2 -> L3
60 s
10 pulse
1/4
500 V
±
12
0°- 270°/90°
L1 -> PE
60 s
10 pulse
2/4
500 V
±
12
0°- 270°/90°
L2 -> PE
60 s
10 pulse
3/4
500 V
±
12
0°- 270°/90°
L3 -> PE
60 s
10 pulse
4/4
500 V
±
12
0°- 270°/90°
N -> PE
60 s
10 pulse
1/4
1000 V
±
12
0°- 270°/90°
L1 -> PE
60 s
10 pulse
2/4
1000 V
±
12
0°- 270°/90°
L2 -> PE
60 s
10 pulse
3/4
1000 V
±
12
0°- 270°/90°
L3 -> PE
60 s
10 pulse
4/4
1000 V
±
12
0°- 270°/90°
N -> PE
60 s
10 pulse
1/4
2000 V
±
12
0°- 270°/90°
L1 -> PE
60 s
10 pulse
2/4
2000 V
±
12
0°- 270°/90°
L2 -> PE
60 s
10 pulse
3/4
2000 V
±
12
0°- 270°/90°
L3 -> PE
60 s
10 pulse
4/4
2000 V
±
12
0°- 270°/90°
N -> PE
60 s
10 pulse
1/4
4000 V
±
12
0°- 270°/90°
L1 -> PE
60 s
10 pulse
2/4
4000 V
±
12
0°- 270°/90°
L2 -> PE
60 s
10 pulse
3/4
4000 V
±
12
0°- 270°/90°
L3 -> PE
60 s
10 pulse
4/4
4000 V
±
12
0°- 270°/90°
N -> PE
60 s
10 pulse
IEC DC LINES L-N LEVEL 1
1/1
500 V
±
2
Asynch
L1 -> N
60 s
10 pulse
IEC DC LINES L-N LEVEL 2
1/2
500 V
±
2
Asynch
L1 -> N
60 s
2/2
1000 V
±
2
Asynch
L1 -> N
60 s
10 pulse
1/3
500 V
±
2
Asynch
L1 -> N
60 s
10 pulse
2/3
1000 V
±
2
Asynch
L1 -> N
60 s
10 pulse
3/3
2000 V
±
2
Asynch
L1 -> N
60 s
10 pulse
1/4
500 V
±
2
Asynch
L1 -> N
60 s
10 pulse
2/4
1000 V
±
2
Asynch
L1 -> N
60 s
10 pulse
3/4
2000 V
±
2
Asynch
L1 -> N
60 s
10 pulse
4/4
4000 V
±
2
Asynch
L1 -> N
60 s
10 pulse
IEC 3PH POWER LINES LX-LX LEVEL 2
IEC 3PH POWER LINES LX-LX LEVEL 3
IEC 3PH POWER LINES LX-LX LEVEL 4
IEC 3PH POWER LINES LX-PE LEVEL 1
IEC 3PH POWER LINES LX-PE LEVEL 2
IEC 3PH POWER LINES LX-PE LEVEL 3
IEC 3PH POWER LINES LX-PE LEVEL 4
IEC DC LINES L-N LEVEL 3
IEC DC LINES L-N LEVEL 4
60 s
10 pulse
10 pulse
99
100
IEC UNSH. UNSYMM. I-O LINES LEVEL 1
1/1
500 V
±
2
Asynch
Surge Output
60 s
10 pulse
IEC UNSH. UNSYMM. I-O LINES LEVEL 2
1/2
500 V
±
2
Asynch
Surge Output
60 s
10 pulse
2/2
1000 V
±
2
Asynch
Surge Output
60 s
10 pulse
1/3
500 V
±
2
Asynch
Surge Output
60 s
10 pulse
2/3
1000 V
±
2
Asynch
Surge Output
60 s
10 pulse
3/3
2000 V
±
2
Asynch
Surge Output
60 s
10 pulse
1/4
500 V
±
2
Asynch
Surge Output
60 s
10 pulse
2/4
1000 V
±
2
Asynch
Surge Output
60 s
10 pulse
3/4
2000 V
±
2
Asynch
Surge Output
60 s
10 pulse
4/4
4000 V
±
2
Asynch
Surge Output
60 s
10 pulse
IEC UNSH. SYMM. COMM. LINES LEVEL 1
1/1
500 V
±
2
Asynch
Surge Output
60 s
10 pulse
IEC UNSH. SYMM. COMM. LINES LEVEL 2
1/2
500 V
±
2
Asynch
Surge Output
60 s
10 pulse
2/2
1000 V
±
2
Asynch
Surge Output
60 s
10 pulse
1/3
500 V
±
2
Asynch
Surge Output
60 s
10 pulse
2/3
1000 V
±
2
Asynch
Surge Output
60 s
10 pulse
3/3
2000 V
±
2
Asynch
Surge Output
60 s
10 pulse
1/4
500 V
±
2
Asynch
Surge Output
60 s
10 pulse
2/4
1000 V
±
2
Asynch
Surge Output
60 s
10 pulse
3/4
2000 V
±
2
Asynch
Surge Output
60 s
10 pulse
4/4
4000 V
±
2
Asynch
Surge Output
60 s
10 pulse
IEC UNSH. UNSYMM. I-O LINES LEVEL 3
IEC UNSH. UNSYMM. I-O LINES LEVEL 4
IEC UNSH. SYMM. COMM. LINES LEVEL 3
IEC UNSH. SYMM. COMM. LINES LEVEL 4
Basic Standard, IEC 61000-4-5 2005_Ed_2
File name implemented
Test step
Voltage
Polarity
Impedance
Phase
Coupling
Rep. time
Test duration
SYMM. OPERATED ALL LINES TO PE LEVEL 1
1/1
500 V
±
15
Asynch
Surge Output
60 s
10 pulse
SYMM. OPERATED ALL LINES TO PE LEVEL 2
1/2
500 V
±
15
Asynch
Surge Output
60 s
10 pulse
2/2
1000 V
±
15
Asynch
Surge Output
60 s
10 pulse
1/3
500 V
±
15
Asynch
Surge Output
60 s
10 pulse
2/3
1000 V
±
15
Asynch
Surge Output
60 s
10 pulse
3/3
2000 V
±
15
Asynch
Surge Output
60 s
10 pulse
1/4
500 V
±
15
Asynch
Surge Output
60 s
10 pulse
2/4
1000 V
±
15
Asynch
Surge Output
60 s
10 pulse
3/4
2000 V
±
15
Asynch
Surge Output
60 s
10 pulse
4/4
4000 V
±
15
Asynch
Surge Output
60 s
10 pulse
SHIELDED IO COMM LINES LEVEL 1
1/1
500 V
±
15
Asynch
Surge Output
60 s
10 pulse
SHIELDED IO COMM LINES LEVEL 2
1/2
500 V
±
15
Asynch
Surge Output
60 s
10 pulse
2/2
1000 V
±
15
Asynch
Surge Output
60 s
10 pulse
1/3
500 V
±
15
Asynch
Surge Output
60 s
10 pulse
2/3
1000 V
±
15
Asynch
Surge Output
60 s
10 pulse
3/3
2000 V
±
15
Asynch
Surge Output
60 s
10 pulse
1/4
500 V
±
15
Asynch
Surge Output
60 s
10 pulse
2/4
1000 V
±
15
Asynch
Surge Output
60 s
10 pulse
3/4
2000 V
±
15
Asynch
Surge Output
60 s
10 pulse
4/4
4000 V
±
15
Asynch
Surge Output
60 s
10 pulse
SYMM. OPERATED ALL LINES TO PE LEVEL 3
SYMM. OPERATED ALL LINES TO PE LEVEL 4
SHIELDED IO COMM LINES LEVEL 3
SHIELDED IO COMM LINES LEVEL 4
NSG 3060 EMC test system
Basic Standard, IEC 61000-4-12 2006_Ed_2
File name implemented
IEC 1-PH M. FEEDER LINE L-N LEVEL 1
Rep. time
60 s
Test duration
10 pulse
1/2
250 V
±
12
0°- 270°/90°
L -> N
60 s
10 pulse
2/2
500 V
±
12
0°- 270°/90°
L -> N
60 s
10 pulse
1/3
250 V
±
12
0°- 270°/90°
L -> N
60 s
10 pulse
2/3
500 V
±
12
0°- 270°/90°
L -> N
60 s
10 pulse
3/3
1000 V
±
12
0°- 270°/90°
L -> N
60 s
10 pulse
1/4
250 V
±
12
0°- 270°/90°
L -> N
60 s
10 pulse
2/4
500 V
±
12
0°- 270°/90°
L -> N
60 s
10 pulse
3/4
1000 V
±
12
0°- 270°/90°
L -> N
60 s
10 pulse
4/4
2000 V
±
12
0°- 270°/90°
L -> N
60 s
10 pulse
IEC 1-PH POWER LINE L-N LEVEL 1
1/1
250 V
±
30
0°- 270°/90°
L -> N
60 s
10 pulse
IEC 1-PH POWER LINE L-N LEVEL 2
1/2
250 V
±
30
0°- 270°/90°
L -> N
60 s
10 pulse
2/2
500 V
±
30
0°- 270°/90°
L -> N
60 s
10 pulse
1/3
250 V
±
30
0°- 270°/90°
L -> N
60 s
10 pulse
2/3
500 V
±
30
0°- 270°/90°
L -> N
60 s
10 pulse
3/3
1000 V
±
30
0°- 270°/90°
L -> N
60 s
10 pulse
1/4
250 V
±
30
0°- 270°/90°
L -> N
60 s
10 pulse
2/4
500 V
±
30
0°- 270°/90°
L -> N
60 s
10 pulse
3/4
1000 V
±
30
0°- 270°/90°
L -> N
60 s
10 pulse
4/4
2000 V
±
30
0°- 270°/90°
L -> N
60 s
10 pulse
IEC 1-PH M. FEEDER LINE L-PE LEVEL 1
1/1
500 V
±
12
0°- 270°/90°
L -> PE
60 s
10 pulse
IEC 1-PH M. FEEDER LINE L-PE LEVEL 2
1/2
500 V
±
12
0°- 270°/90°
L -> PE
60 s
10 pulse
2/2
1000 V
±
12
0°- 270°/90°
L -> PE
60 s
10 pulse
1/3
500 V
±
12
0°- 270°/90°
L -> PE
60 s
10 pulse
2/3
1000 V
±
12
0°- 270°/90°
L -> PE
60 s
10 pulse
3/3
2000 V
±
12
0°- 270°/90°
L -> PE
60 s
10 pulse
1/4
500 V
±
12
0°- 270°/90°
L -> PE
60 s
10 pulse
2/4
1000 V
±
12
0°- 270°/90°
L -> PE
60 s
10 pulse
3/4
2000 V
±
12
0°- 270°/90°
L -> PE
60 s
10 pulse
4/4
4000 V
±
12
0°- 270°/90°
L -> PE
60 s
10 pulse
IEC 1-PH M. FEEDER LINE L-N LEVEL 2
IEC 1-PH M. FEEDER LINE L-N LEVEL 3
IEC 1-PH M. FEEDER LINE L-N LEVEL 4
IEC 1-PH POWER LINE L-N LEVEL 3
IEC 1-PH POWER LINE L-N LEVEL 4
IEC 1-PH M. FEEDER LINE L-PE LEVEL 3
IEC 1-PH M. FEEDER LINE L-PE LEVEL 4
Test step Voltage
1/1
250 V
Polarity
±
Impedance Phase
Coupling
12
0°- 270°/90°
L -> N
101
102
IEC 1-PH POWER LINE L-PE LEVEL 1
1/1
500 V
±
30 ohm
0°- 270°/90°
L -> PE
60 s
10 pulse
IEC 1-PH POWER LINE L-PE LEVEL 2
1/2
500 V
±
30 ohm
0°- 270°/90°
L -> PE
60 s
10 pulse
2/2
1000 V
±
30 ohm
0°- 270°/90°
L -> PE
60 s
10 pulse
1/3
500 V
±
30 ohm
0°- 270°/90°
L -> PE
60 s
10 pulse
2/3
1000 V
±
30 ohm
0°- 270°/90°
L -> PE
60 s
10 pulse
3/3
2000 V
±
30 ohm
0°- 270°/90°
L -> PE
60 s
10 pulse
1/4
500 V
±
30 ohm
0°- 270°/90°
L -> PE
60 s
10 pulse
2/4
1000 V
±
30 ohm
0°- 270°/90°
L -> PE
60 s
10 pulse
3/4
2000 V
±
30 ohm
0°- 270°/90°
L -> PE
60 s
10 pulse
4/4
4000 V
±
30 ohm
0°- 270°/90°
L -> PE
60 s
10 pulse
IEC 1-PH M. FEEDER LINE N-PE LEVEL 1
1/1
500 V
±
12
0°- 270°/90°
N -> PE
60 s
10 pulse
IEC 1-PH M. FEEDER LINE N-PE LEVEL 2
1/2
500 V
±
12
0°- 270°/90°
N -> PE
60 s
10 pulse
2/2
1000 V
±
12
0°- 270°/90°
N -> PE
60 s
10 pulse
1/3
500 V
±
12
0°- 270°/90°
N -> PE
60 s
10 pulse
2/3
1000 V
±
12
0°- 270°/90°
N -> PE
60 s
10 pulse
3/3
2000 V
±
12
0°- 270°/90°
N -> PE
60 s
10 pulse
1/4
500 V
±
12
0°- 270°/90°
N -> PE
60 s
10 pulse
2/4
1000 V
±
12
0°- 270°/90°
N -> PE
60 s
10 pulse
3/4
2000 V
±
12
0°- 270°/90°
N -> PE
60 s
10 pulse
4/4
4000 V
±
12
0°- 270°/90°
N -> PE
60 s
10 pulse
IEC 1-PH POWER LINE N-PE LEVEL 1
1/1
500 V
±
30 ohm
0°- 270°/90°
N -> PE
60 s
10 pulse
IEC 1-PH POWER LINE N-PE LEVEL 2
1/2
500 V
±
30 ohm
0°- 270°/90°
N -> PE
60 s
10 pulse
2/2
1000 V
±
30 ohm
0°- 270°/90°
N -> PE
60 s
10 pulse
1/3
500 V
±
30 ohm
0°- 270°/90°
N -> PE
60 s
10 pulse
2/3
1000 V
±
30 ohm
0°- 270°/90°
N -> PE
60 s
10 pulse
3/3
2000 V
±
30 ohm
0°- 270°/90°
N -> PE
60 s
10 pulse
1/4
500 V
±
30 ohm
0°- 270°/90°
N -> PE
60 s
10 pulse
2/4
1000 V
±
30 ohm
0°- 270°/90°
N -> PE
60 s
10 pulse
3/4
2000 V
±
30 ohm
0°- 270°/90°
N -> PE
60 s
10 pulse
4/4
4000 V
±
30 ohm
0°- 270°/90°
N -> PE
60 s
10 pulse
1/6
250 V
±
12
0°- 270°/90°
L1 -> N
60 s
10 pulse
2/6
250 V
±
12
0°- 270°/90°
L2 -> N
60 s
10 pulse
3/6
250 V
±
12
0°- 270°/90°
L3 -> N
60 s
10 pulse
4/6
250 V
±
12
0°- 270°/90°
L1 -> L2
60 s
10 pulse
5/6
250 V
±
12
0°- 270°/90°
L1 -> L3
60 s
10 pulse
6/6
250 V
±
12
0°- 270°/90°
L2 -> L3
60 s
10 pulse
1/6
500 V
±
12
0°- 270°/90°
L1 -> N
60 s
10 pulse
2/6
500 V
±
12
0°- 270°/90°
L2 -> N
60 s
10 pulse
3/6
500 V
±
12
0°- 270°/90°
L3 -> N
60 s
10 pulse
4/6
500 V
±
12
0°- 270°/90°
L1 -> L2
60 s
10 pulse
5/6
500 V
±
12
0°- 270°/90°
L1 -> L3
60 s
10 pulse
6/6
500 V
±
12
0°- 270°/90°
L2 -> L3
60 s
10 pulse
1/6
1000 V
±
12
0°- 270°/90°
L1 -> N
60 s
10 pulse
2/6
1000 V
±
12
0°- 270°/90°
L2 -> N
60 s
10 pulse
3/6
1000 V
±
12
0°- 270°/90°
L3 -> N
60 s
10 pulse
4/6
1000 V
±
12
0°- 270°/90°
L1 -> L2
60 s
10 pulse
5/6
1000 V
±
12
0°- 270°/90°
L1 -> L3
60 s
10 pulse
6/6
1000 V
±
12
0°- 270°/90°
L2 -> L3
60 s
10 pulse
1/6
2000 V
±
12
0°- 270°/90°
L1 -> N
60 s
10 pulse
2/6
2000 V
±
12
0°- 270°/90°
L2 -> N
60 s
10 pulse
3/6
2000 V
±
12
0°- 270°/90°
L3 -> N
60 s
10 pulse
4/6
2000 V
±
12
0°- 270°/90°
L1 -> L2
60 s
10 pulse
5/6
2000 V
±
12
0°- 270°/90°
L1 -> L3
60 s
10 pulse
6/6
2000 V
±
12
0°- 270°/90°
L2 -> L3
60 s
10 pulse
IEC 1-PH POWER LINE L-PE LEVEL 3
IEC 1-PH POWER LINE L-PE LEVEL 4
IEC 1-PH M. FEEDER LINE N-PE LEVEL 3
IEC 1-PH M. FEEDER LINE N-PE LEVEL 4
IEC 1-PH POWER LINE N-PE LEVEL 3
IEC 1-PH POWER LINE N-PE LEVEL 4
IEC 3-PH M. FEEDER LINE LX-LX LEVEL 1
IEC 3-PH M. FEEDER LINE LX-LX LEVEL 2
IEC 3-PH M. FEEDER LINE LX-LX LEVEL 3
IEC 3-PH M. FEEDER LINE LX-LX LEVEL 4
NSG 3060 EMC test system
IEC 3-PH POWER LINE LX-LX LEVEL 1
IEC 3-PH POWER LINE LX-LX LEVEL 2
IEC 3-PH POWER LINE LX-LX LEVEL 3
IEC 3-PH POWER LINE LX-LX LEVEL 4
IEC 3-PH M. FEEDER LINE LX-PE LEVEL 1
IEC 3-PH M. FEEDER LINE LX-PE LEVEL 2
IEC 3-PH M. FEEDER LINE LX-PE LEVEL 3
IEC 3-PH M. FEEDER LINE LX-PE LEVEL 4
IEC 3-PH POWER LINE LX-PE LEVEL 1
IEC 3-PH POWER LINE LX-PE LEVEL 2
IEC 3-PH POWER LINE LX-PE LEVEL 3
IEC 3-PH POWER LINE LX-PE LEVEL 4
1/6
250 V
±
30
0°- 270°/90°
L1 -> N
60 s
10 pulse
2/6
250 V
±
30
0°- 270°/90°
L2 -> N
60 s
10 pulse
3/6
250 V
±
30
0°- 270°/90°
L3 -> N
60 s
10 pulse
4/6
250 V
±
30
0°- 270°/90°
L1 -> L2
60 s
10 pulse
5/6
250 V
±
30
0°- 270°/90°
L1 -> L3
60 s
10 pulse
6/6
250 V
±
30
0°- 270°/90°
L2 -> L3
60 s
10 pulse
1/6
500 V
±
30
0°- 270°/90°
L1 -> N
60 s
10 pulse
2/6
500 V
±
30
0°- 270°/90°
L2 -> N
60 s
10 pulse
3/6
500 V
±
30
0°- 270°/90°
L3 -> N
60 s
10 pulse
4/6
500 V
±
30
0°- 270°/90°
L1 -> L2
60 s
10 pulse
5/6
500 V
±
30
0°- 270°/90°
L1 -> L3
60 s
10 pulse
6/6
500 V
±
30
0°- 270°/90°
L2 -> L3
60 s
10 pulse
1/6
1000 V
±
30
0°- 270°/90°
L1 -> N
60 s
10 pulse
2/6
1000 V
±
30
0°- 270°/90°
L2 -> N
60 s
10 pulse
3/6
1000 V
±
30
0°- 270°/90°
L3 -> N
60 s
10 pulse
4/6
1000 V
±
30
0°- 270°/90°
L1 -> L2
60 s
10 pulse
5/6
1000 V
±
30
0°- 270°/90°
L1 -> L3
60 s
10 pulse
6/6
1000 V
±
30
0°- 270°/90°
L2 -> L3
60 s
10 pulse
1/6
2000 V
±
30
0°- 270°/90°
L1 -> N
60 s
10 pulse
2/6
2000 V
±
30
0°- 270°/90°
L2 -> N
60 s
10 pulse
3/6
2000 V
±
30
0°- 270°/90°
L3 -> N
60 s
10 pulse
4/6
2000 V
±
30
0°- 270°/90°
L1 -> L2
60 s
10 pulse
5/6
2000 V
±
30
0°- 270°/90°
L1 -> L3
60 s
10 pulse
6/6
2000 V
±
30
0°- 270°/90°
L2 -> L3
60 s
10 pulse
1/4
500 V
±
12
0°- 270°/90°
L1 -> PE
60 s
10 pulse
2/4
500 V
±
12
0°- 270°/90°
L2 -> PE
60 s
10 pulse
3/4
500 V
±
12
0°- 270°/90°
L3 -> PE
60 s
10 pulse
4/4
500 V
±
12
0°- 270°/90°
N -> PE
60 s
10 pulse
1/4
1000 V
±
12
0°- 270°/90°
L1 -> PE
60 s
10 pulse
2/4
1000 V
±
12
0°- 270°/90°
L2 -> PE
60 s
10 pulse
3/4
1000 V
±
12
0°- 270°/90°
L3 -> PE
60 s
10 pulse
4/4
1000 V
±
12
0°- 270°/90°
N -> PE
60 s
10 pulse
1/4
2000 V
±
12
0°- 270°/90°
L1 -> PE
60 s
10 pulse
2/4
2000 V
±
12
0°- 270°/90°
L2 -> PE
60 s
10 pulse
3/4
2000 V
±
12
0°- 270°/90°
L3 -> PE
60 s
10 pulse
4/4
2000 V
±
12
0°- 270°/90°
N -> PE
60 s
10 pulse
1/4
4000 V
±
12
0°- 270°/90°
L1 -> PE
60 s
10 pulse
2/4
4000 V
±
12
0°- 270°/90°
L2 -> PE
60 s
10 pulse
3/4
4000 V
±
12
0°- 270°/90°
L3 -> PE
60 s
10 pulse
4/4
4000 V
±
12
0°- 270°/90°
N -> PE
60 s
10 pulse
1/4
500 V
±
30
0°- 270°/90°
L1 -> PE
60 s
10 pulse
2/4
500 V
±
30
0°- 270°/90°
L2 -> PE
60 s
10 pulse
3/4
500 V
±
30
0°- 270°/90°
L3 -> PE
60 s
10 pulse
4/4
500 V
±
30
0°- 270°/90°
N -> PE
60 s
10 pulse
1/4
1000 V
±
30
0°- 270°/90°
L1 -> PE
60 s
10 pulse
2/4
1000 V
±
30
0°- 270°/90°
L2 -> PE
60 s
10 pulse
3/4
1000 V
±
30
0°- 270°/90°
L3 -> PE
60 s
10 pulse
4/4
1000 V
±
30
0°- 270°/90°
N -> PE
60 s
10 pulse
1/4
2000 V
±
30
0°- 270°/90°
L1 -> PE
60 s
10 pulse
2/4
2000 V
±
30
0°- 270°/90°
L2 -> PE
60 s
10 pulse
3/4
2000 V
±
30
0°- 270°/90°
L3 -> PE
60 s
10 pulse
4/4
2000 V
±
30
0°- 270°/90°
N -> PE
60 s
10 pulse
1/4
4000 V
±
30
0°- 270°/90°
L1 -> PE
60 s
10 pulse
2/4
4000 V
±
30
0°- 270°/90°
L2 -> PE
60 s
10 pulse
3/4
4000 V
±
30
0°- 270°/90°
L3 -> PE
60 s
10 pulse
4/4
4000 V
±
30
0°- 270°/90°
N -> PE
60 s
10 pulse
103
104
IEC DC LINES L-N 12 R LEVEL 1
1/1
500 V
±
12
Asynch
L1 -> N
60 s
10 pulse
IEC DC LINES L-N 12 R LEVEL 2
1/2
500 V
±
12
Asynch
L1 -> N
60 s
10 pulse
2/2
1000 V
±
12
Asynch
L1 -> N
60 s
10 pulse
1/3
500 V
±
12
Asynch
L1 -> N
60 s
10 pulse
2/3
1000 V
±
12
Asynch
L1 -> N
60 s
10 pulse
3/3
2000 V
±
12
Asynch
L1 -> N
60 s
10 pulse
1/4
500 V
±
12
Asynch
L1 -> N
60 s
10 pulse
2/4
1000 V
±
12
Asynch
L1 -> N
60 s
10 pulse
3/4
2000 V
±
12
Asynch
L1 -> N
60 s
10 pulse
4/4
4000 V
±
12
Asynch
L1 -> N
60 s
10 pulse
IEC DC LINES L-N 30 R LEVEL 1
1/1
500 V
±
30
Asynch
L1 -> N
60 s
10 pulse
IEC DC LINES L-N 30 R LEVEL 1
1/2
500 V
±
30
Asynch
L1 -> N
60 s
10 pulse
2/2
1000 V
±
30
Asynch
L1 -> N
60 s
10 pulse
1/3
500 V
±
30
Asynch
L1 -> N
60 s
10 pulse
2/3
1000 V
±
30
Asynch
L1 -> N
60 s
10 pulse
3/3
2000 V
±
30
Asynch
L1 -> N
60 s
10 pulse
1/4
500 V
±
30
Asynch
L1 -> N
60 s
10 pulse
2/4
1000 V
±
30
Asynch
L1 -> N
60 s
10 pulse
3/4
2000 V
±
30
Asynch
L1 -> N
60 s
10 pulse
4/4
4000 V
±
30
Asynch
L1 -> N
60 s
10 pulse
IEC UNSH. UNSYMM. I-O LINES LEVEL 1
1/1
500 V
±
12
Asynch
60 s
10 pulse
IEC UNSH. UNSYMM. I-O LINES LEVEL 2
1/2
500 V
±
12
Asynch
Surge
Output
Surge
Output
Surge
2/2
1000 V
±
12
Asynch
1/3
500 V
±
12
Asynch
2/3
1000 V
±
12
Asynch
3/3
2000 V
±
12
Asynch
1/4
500 V
±
12
Asynch
2/4
1000 V
±
12
Asynch
3/4
2000 V
±
12
Asynch
4/4
4000 V
±
12
Asynch
IEC UNSH. SYMM. COMM. LINES LEVEL 1
1/1
500 V
±
12
Asynch
IEC UNSH. SYMM. COMM. LINES LEVEL 2
1/2
500 V
±
12
Asynch
2/2
1000 V
±
12
Asynch
1/3
500 V
±
12
Asynch
2/3
1000 V
±
12
Asynch
3/3
2000 V
±
12
Asynch
1/4
500 V
±
12
Asynch
2/4
1000 V
±
12
Asynch
3/4
2000 V
±
12
Asynch
4/4
4000 V
±
12
Asynch
IEC DC LINES L-N 12 R LEVEL 3
IEC DC LINES L-N 12 R LEVEL 4
IEC DC LINES L-N 30 R LEVEL 1
IEC DC LINES L-N 30 R LEVEL 1
IEC UNSH. UNSYMM. I-O LINES LEVEL 3
IEC UNSH. UNSYMM. I-O LINES LEVEL 4
IEC UNSH. SYMM. COMM. LINES LEVEL 3
IEC UNSH. SYMM. COMM. LINES LEVEL 4
60 s
10 pulse
Output
Surge
Output
Surge
60 s
10 pulse
60 s
10 pulse
Output
Surge
Output
Surge
60 s
10 pulse
60 s
10 pulse
Output
Surge
Output
Surge
60 s
10 pulse
60 s
10 pulse
Output
Surge
Output
60 s
10 pulse
60 s
10 pulse
60 s
10 pulse
Surge
Output
Surge
Output
Surge
60 s
10 pulse
Output
Surge
Output
Surge
60 s
10 pulse
60 s
10 pulse
Output
Surge
Output
Surge
60 s
10 pulse
60 s
10 pulse
Output
Surge
Output
Surge
60 s
10 pulse
60 s
10 pulse
Output
Surge
Output
60 s
10 pulse
60 s
10 pulse
Coil Factor
Basic Standard, IEC 61000-4-8 2001_Ed_1.1
Field
1 A/m
Frequency
50 Hz
Test
duration
60 s
IEC 60HZ CF 9.8 LEVEL 1
1 A/m
60 Hz
60 s
9.8
IEC 50HZ CF 9.8 LEVEL 2
3 A/m
50 Hz
60 s
9.8
IEC 60HZ CF 9.8 LEVEL 2
3 A/m
60 Hz
60 s
9.8
IEC 50HZ CF 9.8 LEVEL 3
10 A/m
50 Hz
60 s
9.8
IEC 60HZ CF 9.8 LEVEL 3
10 A/m
60 Hz
60 s
9.8
IEC 50HZ CF 9.8 LEVEL 4
30 A/m
50 Hz
60 s
9.8
IEC 60HZ CF 9.8 LEVEL 4
30 A/m
60 Hz
60 s
9.8
File name implemented
IEC 50HZ CF 9.8 LEVEL 1
NSG 3060 EMC test system
Test step
9.8
Basic Standard, IEC 61000-4-9 2001_Ed_1.1
File name implemented
105
Test step
Field
Polarity
IEC LEVEL 3
1/2
100 A/m
IEC LEVEL 4
1/2
IEC LEVEL 5
1/2
Pulses
V to A/m Ratio
+/-
Rep. Time
10 s
10
0.98
300 A/m
+/-
20 s
10
0.98
1000 A/m
+/-
20 s
10
0.98
106
Basic Standard, IEC 61000-4-11 2002_Ed_2
File name implemented
IEC 50HZ CLASS 2 DIPS 0PC 0.5 CYCLE
IEC 60HZ CLASS 2 DIPS 0PC 0.5 CYCLE
IEC 50HZ CLASS 2 DIPS 0PC 1 CYCLE
IEC 60HZ CLASS 2 DIPS 0PC 1 CYCLE
IEC 50HZ CLASS 2 DIPS 70PC 25 CYCLE
IEC 60HZ CLASS 2 DIPS 70PC 30 CYCLE
Phase
Rep. time T-Event (ts)
10 s
10 ms
0°-315°/45°
10 s
8333 us
0°-315°/45°
0°-315°/45°
10 s
1 cycle
0°-315°/45°
10 s
1 cycle
0°-315°/45°
10 s
25 cycle
0°-315°/45°
10 s
30 cycle
Test duration
3 pulses
3 pulses
3 pulses
3 pulses
3 pulses
3 pulses
IEC 50HZ
IEC 60HZ
IEC 50HZ
IEC 60HZ
IEC 50HZ
IEC 60HZ
IEC 50HZ
IEC 60HZ
IEC 50HZ
IEC 60HZ
CLASS 3 DIPS 0PC 0.5 CYCLE
CLASS 3 DIPS 0PC 0.5 CYCLE
CLASS 3 DIPS 0PC 1 CYCLE
CLASS 3 DIPS 0PC 1 CYCLE
CLASS 3 DIPS 40PC 10 CYCLE
CLASS 3 DIPS 40PC 12 CYCLE
CLASS 3 DIPS 70PC 25 CYCLE
CLASS 3 DIPS 70PC 30 CYCLE
CLASS 3 DIPS 80PC 250 CYCLE
CLASS 3 DIPS 80PC 300 CYCLE
0°-315°/45°
0°-315°/45°
0°-315°/45°
0°-315°/45°
0°-315°/45°
0°-315°/45°
0°-315°/45°
0°-315°/45°
0°-315°/45°
0°-315°/45°
10 s
10 s
10 s
10 s
10 s
10 s
10 s
10 s
10 s
10 s
10 ms
8333 us
1 cycle
1 cycle
10 cycle
12 cycle
25 cycle
30 cycle
250 cycle
300 cycle
3 pulses
3 pulses
3 pulses
3 pulses
3 pulses
3 pulses
3 pulses
3 pulses
3 pulses
3 pulses
IEC 50HZ
IEC 60HZ
IEC 50HZ
IEC 60HZ
CLASS 2 S.INT. 0PC 250CYCLE
CLASS 2 S.INT. 0PC 300CYCLE
CLASS 3 S.INT. 0PC 250CYCLE
CLASS 3 S.INT. 0PC 300CYCLE
0°
0°
0°
0°
10 s
10 s
10 s
10 s
250 cycle
300 cycle
250 cycle
300 cycle
3 pulses
3 pulses
3 pulses
3 pulses
40%
40%
40%
40%
40%
70%
70%
70%
70%
70%
10 s
10 s
10 s
10 s
10 s
10 s
10 s
10 s
10 s
10 s
0.01 s
0.03 s
0.1 s
0.3 s
1s
0.01 s
0.03 s
0.1 s
0.3 s
1s
3 pulses
3 pulses
3 pulses
3 pulses
3 pulses
3 pulses
3 pulses
3 pulses
3 pulses
3 pulses
0
0
0
0
0
0
0
10 s
10 s
10 s
10 s
10 s
10 s
10 s
0.001 s
0.003 s
0.01 s
0.03 s
0.1 s
0.3 s
1s
3 pulses
3 pulses
3 pulses
3 pulses
3 pulses
3 pulses
3 pulses
Uvar
File name implemented
IEC DCV DIPS 10MS (40PC)
IEC DCV DIPS 30MS (40PC)
IEC DCV DIPS 100MS (40PC)
IEC DCV DIPS 300MS (40PC)
IEC DCV DIPS 1S (40PC)
IEC DCV DIPS 10MS (70PC)
IEC DCV DIPS 30MS (70PC)
IEC DCV DIPS 100MS (70PC)
IEC DCV DIPS 300MS (70PC)
IEC DCV DIPS 1S (70PC)
IEC DCV
IEC DCV
IEC DCV
IEC DCV
IEC DCV
IEC DCV
IEC DCV
INTERRUPTION 1MS (0PC)
INTERRUPTION 3MS (0PC)
INTERRUPTION 10MS (0PC)
INTERRUPTION 30MS (0PC)
INTERRUPTION 100MS (0PC)
INTERRUPTION 300MS (0PC)
INTERRUPTION 1S (0PC)
IEC DCV
IEC DCV
IEC DCV
IEC DCV
IEC DCV
VARIATION 100MS (85PC)
VARIATION 300MS (85PC)
VARIATION 1S (85PC)
VARIATION 3S (85PC)
VARIATION 10S (85PC)
85%
85%
85%
85%
85%
10 s
10 s
10 s
10 s
10 s
0.1 s
0.3 s
1s
3s
10 s
3 pulses
3 pulses
3 pulses
3 pulses
3 pulses
IEC DCV
IEC DCV
IEC DCV
IEC DCV
IEC DCV
VARIATION 100MS (120PC)
VARIATION 300MS (120PC)
VARIATION 1S (120PC)
VARIATION 3S (120PC)
VARIATION 10S (120PC)
120%
120%
120%
120%
120%
10 s
10 s
10 s
10 s
10 s
0.1 s
0.3 s
1s
3s
10 s
3 pulses
3 pulses
3 pulses
3 pulses
3 pulses
IEC DCV
IEC DCV
IEC DCV
IEC DCV
IEC DCV
VARIATION 100MS (80PC)
VARIATION 300MS (80PC)
VARIATION 1S (80PC)
VARIATION 3S (80PC)
VARIATION 10S (80PC)
80%
80%
80%
80%
80%
10 s
10 s
10 s
10 s
10 s
0.1 s
0.3 s
1s
3s
10 s
3 pulses
3 pulses
3 pulses
3 pulses
3 pulses
NSG 3060 EMC test system
107
Basic Standard, IEC 61000-4-11 2002_Ed_2
File name implemented
IEC 50HZ VOLTAGE VARIATION
IEC 60HZ VOLTAGE VARIATION
Uvar
70%
70%
Phase
0°
0°
Rep. time
10 s
10 s
T-Event (ts)
1 cycle
1 cycle
T-Decrease
(td)
abrupt
abrupt
T-Increase (ti)
25 cycle
30 cycle
Test duration
3 pulses
3 pulses
ANSI C.62.45_ 2002, Combination w ave
File name implemented
ANSI 1-PH BASIC 1 CAT. A1
Voltage
2000V
Polarity
±
ANSI 1-PH BASIC 1 CAT. A2
4000 V
±
ANSI 1-PH BASIC 1 CAT. A3
6000 V
±
ANSI 1-PH BASIC 2 CAT. A1
2000V
ANSI 1-PH BASIC 2 CAT. A2
4000 V
ANSI 1-PH BASIC 2 CAT. A3
Impedance
2
Phase
0°- 270°/90°
Coupling
L, N -> PE
Rep. time Test duration
10 s
10 pulse
2
0°- 270°/90°
L, N -> PE
20 s
10 pulse
2
0°- 270°/90°
L, N -> PE
20 s
10 pulse
±
2
0°- 270°/90°
L -> N
10 s
10 pulse
±
2
0°- 270°/90°
L -> N
20 s
10 pulse
6000 V
±
2
0°- 270°/90°
L -> N
20 s
10 pulse
ANSI 3-PH BASIC 1 CAT. A1
2000V
±
2
0°- 270°/90°
L1, L2, L3, N -> PE
10 s
10 pulse
ANSI 3-PH BASIC 1 CAT. A2
4000 V
±
2
0°- 270°/90°
L1, L2, L3, N -> PE
20 s
10 pulse
ANSI 3-PH BASIC 1 CAT. A3
6000 V
±
2
0°- 270°/90°
L1, L2, L3, N -> PE
20 s
10 pulse
ANSI 3-PH BASIC 2 CAT. A1
2000V
±
2
0°- 270°/90°
L2 -> L1
10 s
10 pulse
ANSI 3-PH BASIC 2 CAT. A2
4000 V
±
2
0°- 270°/90°
L2 -> L1
20 s
10 pulse
ANSI 3-PH BASIC 2 CAT. A3
6000 V
±
2
0°- 270°/90°
L2 -> L1
20 s
10 pulse
ANSI 3-PH BASIC 3 CAT. A1
2000V
±
2
0°- 270°/90°
L3 -> L2
10 s
10 pulse
ANSI 3-PH BASIC 3 CAT. A2
4000 V
±
2
0°- 270°/90°
L3 -> L2
20 s
10 pulse
ANSI 3-PH BASIC 3 CAT. A3
6000 V
±
2
0°- 270°/90°
L3 -> L2
20 s
10 pulse
ANSI 3-PH BASIC 4 CAT. A1
2000V
±
2
0°- 270°/90°
L1 -> L3
10 s
10 pulse
ANSI 3-PH BASIC 4 CAT. A2
4000 V
±
2
0°- 270°/90°
L1 -> L3
20 s
10 pulse
ANSI 3-PH BASIC 4 CAT. A3
6000 V
±
2
0°- 270°/90°
L1 -> L3
20 s
10 pulse
108
ANSI C.62.45_ 2002, Ring w ave
File name implemented
Voltage Polarity Impedance Phase
Coupling
Rep. time Test duration
ANSI 1-PH BASIC 1 CAT. A1 12R LN-PE
2000V
±
12
0°- 270°/90°
L, N -> PE
10 s
10 pulse
ANSI 1-PH BASIC 1 CAT. A2 12R LN-PE
4000 V
±
12
0°- 270°/90°
L, N -> PE
20 s
10 pulse
ANSI 1-PH BASIC 1 CAT. A3 12R LN-PE
6000 V
±
12
0°- 270°/90°
L, N -> PE
20 s
10 pulse
ANSI 1-PH BASIC 1 CAT. A1 30R LN-PE
2000V
±
30
0°- 270°/90°
L, N -> PE
10 s
10 pulse
ANSI 1-PH BASIC 1 CAT. A2 30R LN-PE
4000 V
±
30
0°- 270°/90°
L, N -> PE
20 s
10 pulse
ANSI 1-PH BASIC 1 CAT. A3 30R LN-PE
6000 V
±
30
0°- 270°/90°
L, N -> PE
20 s
10 pulse
ANSI 1-PH BASIC 2 CAT. A1 12R LN-PE
2000V
±
12
0°- 270°/90°
L -> N
10 s
10 pulse
ANSI 1-PH BASIC 2 CAT. A2 12R LN-PE
4000 V
±
12
0°- 270°/90°
L -> N
20 s
10 pulse
ANSI 1-PH BASIC 2 CAT. A3 12R LN-PE
6000 V
±
12
0°- 270°/90°
L -> N
20 s
10 pulse
ANSI 1-PH BASIC 2 CAT. A1 30R LN-PE
2000V
±
30
0°- 270°/90°
L -> N
10 s
10 pulse
ANSI 1-PH BASIC 2 CAT. A2 30R LN-PE
4000 V
±
30
0°- 270°/90°
L -> N
20 s
10 pulse
ANSI 1-PH BASIC 2 CAT. A3 30R LN-PE
6000 V
±
30
0°- 270°/90°
L -> N
20 s
10 pulse
ANSI 3-PH BASIC 1 CAT. A1 12R L1L2L3N-PE
2000V
±
12
0°- 270°/90° L1, L2, L3, N -> PE
10 s
10 pulse
ANSI 3-PH BASIC 1 CAT. A1 12R L1L2L3N-PE
4000 V
±
12
0°- 270°/90° L1, L2, L3, N -> PE
20 s
10 pulse
ANSI 3-PH BASIC 1 CAT. A1 12R L1L2L3N-PE
6000 V
±
12
0°- 270°/90° L1, L2, L3, N -> PE
20 s
10 pulse
ANSI 3-PH BASIC 1 CAT. A1 30R L1L2L3N-PE
2000V
±
30
0°- 270°/90° L1, L2, L3, N -> PE
10 s
10 pulse
ANSI 3-PH BASIC 1 CAT. A1 30R L1L2L3N-PE
4000 V
±
30
0°- 270°/90° L1, L2, L3, N -> PE
20 s
10 pulse
ANSI 3-PH BASIC 1 CAT. A1 30R L1L2L3N-PE
6000 V
±
30
0°- 270°/90° L1, L2, L3, N -> PE
20 s
10 pulse
ANSI 3-PH BASIC 2 CAT. A1 12R L2-L1
2000V
±
12
0°- 270°/90°
L2 -> L1
10 s
10 pulse
ANSI 3-PH BASIC 2 CAT. A1 12R L2-L1
4000 V
±
12
0°- 270°/90°
L2 -> L1
20 s
10 pulse
ANSI 3-PH BASIC 2 CAT. A1 12R L2-L1
6000 V
±
12
0°- 270°/90°
L2 -> L1
20 s
10 pulse
ANSI 3-PH BASIC 2 CAT. A1 30R L2-L1
2000V
±
30
0°- 270°/90°
L2 -> L1
10 s
10 pulse
ANSI 3-PH BASIC 2 CAT. A1 30R L2-L1
4000 V
±
30
0°- 270°/90°
L2 -> L1
20 s
10 pulse
ANSI 3-PH BASIC 2 CAT. A1 30R L2-L1
6000 V
±
30
0°- 270°/90°
L2 -> L1
20 s
10 pulse
ANSI 3-PH BASIC 3 CAT. A1 12R L3-L2
2000V
±
12
0°- 270°/90°
L3 -> L2
10 s
10 pulse
ANSI 3-PH BASIC 3 CAT. A1 12R L3-L2
4000 V
±
12
0°- 270°/90°
L3 -> L2
20 s
10 pulse
ANSI 3-PH BASIC 3 CAT. A1 12R L3-L2
6000 V
±
12
0°- 270°/90°
L3 -> L2
20 s
10 pulse
ANSI 3-PH BASIC 3 CAT. A1 30R L3-L2
2000V
±
30
0°- 270°/90°
L3 -> L2
10 s
10 pulse
ANSI 3-PH BASIC 3 CAT. A1 30R L3-L2
4000 V
±
30
0°- 270°/90°
L3 -> L2
20 s
10 pulse
ANSI 3-PH BASIC 3 CAT. A1 30R L3-L2
6000 V
±
30
0°- 270°/90°
L3 -> L2
20 s
10 pulse
ANSI 3-PH BASIC 4 CAT. A1 12R L1-L3
2000V
±
12
0°- 270°/90°
L1 -> L3
10 s
10 pulse
ANSI 3-PH BASIC 4 CAT. A1 12R L1-L3
4000 V
±
12
0°- 270°/90°
L1 -> L3
20 s
10 pulse
ANSI 3-PH BASIC 4 CAT. A1 12R L1-L3
6000 V
±
12
0°- 270°/90°
L1 -> L3
20 s
10 pulse
ANSI 3-PH BASIC 4 CAT. A1 30R L1-L3
2000V
±
30
0°- 270°/90°
L1 -> L3
10 s
10 pulse
ANSI 3-PH BASIC 4 CAT. A1 30R L1-L3
4000 V
±
30
0°- 270°/90°
L1 -> L3
20 s
10 pulse
ANSI 3-PH BASIC 4 CAT. A1 30R L1-L3
6000 V
±
30
0°- 270°/90°
L1 -> L3
20 s
10 pulse
NSG 3060 EMC test system
9 DESCRIPTION OF THE 25 PIN D-SUB
SIGNALS
9.1 Interlock
Between Pin 5 (hi) and Pin 2, 8, 15, 20 (low).
This connection is an integral part of the interlock safety circuit. If a number
of units are incorporated in a system, then these connections can be “daisychained” together to form a single safety circuit. If no external interlock circuit
is required then the shorting connection must be made by using the terminator
connector supplied. Otherwise pulse generation in the system will be inhibited.
A built in circuit breaker enables the EUT power supply also to be switched off,
while the interlock function only blocks the generation of pulses or any other
ongoing test resp.
The interlock is a safety function to ensures the following:
The interlock forms a bus to which all instruments in a system are
connected.
The interlock feature can be connected to external safety devices (door
contacts, test enclosure hoods, etc.).
If any part of the interlock circuit is interrupted, all the generator modules
are inhibited from producing or switching high voltages. Additionally the
power supply to the EUT can be switched off too.
Activation of this safety feature is reported to the master controller.
The master controller is also notified when the interlock facility is reset.
Once the interruption is over and the re-instatement of the interlock has
been acknowledged, then power to the EUT is restored.
109
110
Activation of the interlock function is achieved without the help of microprocessors and software. This ensures that the safety feature is not affected or
hindered in the event of a program crash.
9.2 Trigger to scope output signal
Between Pin 18 (hi) and Pin 2, 8, 15, 20 (low)
Inactive state: at 24 V, in the active state: < 2.4 V
Note: The trigger signal has generally a duration of approx. 50 μs e.g. for surge
testing. In case of bursts its width shall change according to the length of the
event. During PQT testing (supply voltage variations) the width of the trigger
signal shall change according to the duration of the voltage dip or interrupts.
9.3 Synchronization (Sync) signal: Output signal
Between pin 7 (hi) and pin 2, 8, 15, 20 (low)
Inactive state: at 24 V; in the active state: < 2.4 V
The sync signal consists of a level that goes low for each cycle of the mains
frequency. The reference is the signal at the power supply input (“EUT supply
IN”). The position (timewise) of the sync signal corresponds to the specified
phase angle (converted into time, irrespective of the supply frequency).
The sync signal is only active while an AC test is in progress and Fsync is set to sync.
9.4 Pulse enable / next step input
Between pin 17 (hi) and pin 2, 8, 15, 20 (low)
Input open = inactive; input shorted = active
If this input is activated during a test run the test is halted (exactly the same
as the pause function in the control software). The test will continue to run as
soon as the input is made inactive again.
If the input is already active before a test is implemented then the test cannot
start.
NSG 3060 EMC test system
9.5 EUT fail input
Between pin 6 (hi) and pin 2, 8, 15, 20 (low)
Input open = inactive; input shorted = active
This connection serves as a control input that can be activated externally.
The EUT can activate this input if it is capable of reporting a disturbance effect
caused during an EMC test. Such events are time/date stamped by the system
and are stored together with the current test parameters for subsequent use
in a test report if required.
111
112
10
COUPLING NETWORK CDN 3061
Parameter
Instrument supply:
Decoupling attenuation:
Standard-conform pulse:
Mains decoupling:
Connections:
EUT supply:
EUT VAC:
EUT VDC:
EUT current:
EFT (burst):
Value
85...265 VAC
Remanent pulse 15% max.
Mains side crosstalk 15% max.
1.2/50 μs up to 6.6 kV
8/20 μs up to 3.3 kA
1.5 mH
Pulse input(s) from generator
Cable connector for EUT supply input
and output
Power inlet for CDN
1-phase (P / N / PE)
50 to 270 V rms, 50/60 Hz
(Phase - Neutral), 400 Hz max.
0 to 270 VDC
1 x 16 A rms continuous
over heat protected
1 x 25 A rms for 30 min
Standard coupling all lines to HF reference ground GND
IEC/EN 61000-4-4 and ANSI (IEEE)
C62.41 L, N, PE à GND
Any lines and combination to ref GND:
L à GND
N à GND
PE à GND
L,N à GND
L, PE à GND
N,PE à GND
NSG 3060 EMC test system
Combination wave pulse:
Line to line (2 Ω)
L à N / L à PE / N à PE
IEC/EN 61000-4-5 Lines to ground (12 Ω)
L à PE / N à PE / L, N à PE
Combination wave & ring wave: ANSI (IEEE) C62.41
Basic 1 & 2 L, N à PE & L à N
Supplemetal 1 & 2 N à PE & L à PE
Diagnostic 1 & 2 N, PE à L & L, PE à N
Ring wave:
IEC/EN 61000-4-12
12 / 30 Ω
L à N / L à PE / N à PE
L à PE / N à PE / L, N à PE
PQT:
IEC/EN 61000-4-11/-4-29
Dips & interrupts to phase L
113
114
11
MAINTENANCE AND FUNCTION
CHECK
11.1 General
Inside the test system there are no adjustable elements accessible to the user
neither for calibration nor for maintenance purpose.
The housing of the test system must not be opened (exceptional for SW update
via SD-card). Should any maintenance or adjustment become necessary, the
whole test system, together with an order or fault report, should be sent in to
a Teseq service center.
Maintenance by the user is restricted to cleaning the outer housing, performing
a function check and verification of the pulse parameters.
The only exception concerns the exchange of modules
or the upgrading of the system with new modules. In
such cases the instructions accompanying the modules
are to be strictly observed.
11.2 Cleaning
In general a moist cloth is sufficient for cleaning the outer housing, including the touch panel. If necessary add a small amount of a mild, non-foaming
household cleanser.
No chemicals (acid, etc) should be used for cleaning purposes.
Before beginning to clean the test system ensure that it is switched off and
the mains power cable is unplugged from the supply.
NSG 3060 EMC test system
11.3 Function check
The safety measures described previously must be
strictly observed while carrying out a function check.
As soon as the test system is switched on the Power-LED should light up. If
this is not the case then please check the mains power connection to the test
system as well as the fuses, voltage selector and any other cabling.
The instrument automatically carries out a diagnostic routine once it has been
successfully switched on.
The generator cannot perform any test while the interlock circuit is open.
Pulse generation can be observed at the output connectors by means of an
oscilloscope. This is a practical way to check that the system is functioning
correctly but should never be used for reference or calibration purposes.
Do not connect the oscilloscope directly in order not to
exceed its max. input voltage.
Teseq recommends the use of a HV differential probe
type MD 200 or MD 200A along with the INA 6560 safety
banana adapter as well as CAS 3025 and MD 300. (See
paragraph: Options).
11.4 Calibration
The combination of high voltages and high frequencies in a single pulse makes
the calibration of EMC pulse generators particularly demanding and difficult.
Teseq has one of the few accredited test laboratories in Europe that is in the
position to undertake calibrations in this specialized field.
115
116
11.5 Warranty
Teseq grants a warranty of 2 years on this test system, effective from the date
of purchase.
During this period, any defective components part will be repaired or replaced
free of charge or, if necessary, the test system will be replaced by another of
equivalent value. The decision regarding the method of reinstating the functional capability is at the sole discression of Teseq.
Excluded from the warranty is damage or consequential damage caused
through negligent operation or use as well as the replacement of parts subject
to degradation.
The warranty is rendered invalid by any intervention on the part of the customer
or a third party.
The faulty items have to be returned in their original packaging.
Teseq accept no responsibility for damage in transit.
NSG 3060 EMC test system
12
DECLARATION OF CONFORMITY (CE)
The equipment is CE-certificated. The following standards apply:
Type of standard
Standard
number
Remark
Safety requirements for electrical equipment for use
in measurement, control, regulation and laboratory
applications
Product family
standard
EN 61010
Generic standard
Electromagnetic compatibility (EMC); generic standard for interference radiation; Part 6.3 for residential,
EN 61000-6-3
business and trade applications as well as small businesses
Generic standard
Electromagnetic compatibility (EMC); generic stanEN 61000-6-4 dard for interference radiation; Part 6.4 industrial applications
Generic standard
EN 61000-6-1
Electromagnetic compatibility (EMC); generic standard for interference immunity; Part 6.1 for residential,
business and trade applications as well as small businesses
Generic standard
EN 61000-6-2
Electromagnetic compatibility (EMC); generic stadard
for interference immunity; Part 6.2 for industrial applications
Product family
standard
EN 60326-1
Electrical equipment for measurements, control and
laboratory use
The requirements cannot be fulfilled in some cases. (The true purpose of an
interference generator is to produce interference signals. Emission limitations
can therefore only be complied with if the equipment is operated inside a
Faraday cage).
Deviations from the requirements are stated and explained in the appendix to
the conformity declaration.
The interference immunity has been tested successfully as per EN 61326-1.
117
118
13
TECHNICAL DATA
13.1 Dimensions/weight
Parameter
Dimensions NSG 3060:
Weight NSG 3060:
Dimensions CDN 3061-C16:
Weight CDN 3061-C16:
Value
W: 449 mm (17.7”)
H: 310 mm (12.9”; 7 HU)
D: 565 mm (22.2”)
22 kg (48.5 lb) approx.
W: 449 mm (17.7”)
H: 221.5 mm (8.7”; 5 HU)
D: 565 mm (22.2”)
20 kg (44 lb) approx.
13.2 Options
Parameter
CAS 3025:
MD 200A:
MD 300:
INA 166:
INA 167:
NSG 3060 EMC test system
Value
Burst/EFT verification set
High voltage differential probe
Current probe
Rack mounting 5 HU
Rack mounting 7 HU
13.3 Accessories for IEC/EN 61000-4-11
ParameterValue
INA 6501:
Manual step transformer, 16 Arms,
0/40/70/80%
INA 6502:
Automatic step transformer, 16 Arms,
0/40/70/80%
VAR 3005-S16:
Automatic single variable transformer,
16 Arms
VAR 3005-D16:
Automatic double variable transformer,
16 Arms
13.4 Accessories for IEC/EN 61000-4-8/-4-9
ParameterValue
MFO 6501:
Magnetic field option, manual for -4-8
MFO 6502:
Magnetic field option, automatic for -4-8
INA 701:
Magnetic field loop 1 x 1 m
– for AC with MFO max. 4 A/m (-4-8)
– for surge* max. 1200 A/m (-4-9)
INA 702:
Magnetic field loop 1 x 1 m
– for AC with MFO max. 40 A/m (-4-8)
– for surge* max. 1200 A/m (-4-9)
INA 703:
Magnetic field coil 1 x 1 m;
max. 330 A/m -4-8
INA 3251:
Cable to interconnect INA 703 with
MFO 6501 OR 6502
INA 752:
Pulse shape adapter for -4-9
*) INA 752 needed to surge generator
119
120
13.5 Accessories for IEC/EN 61000-4-4/-4-5
ParameterValue
CDN 3061-C16-PQM
Automated 1-phase coupler for
EFT/Burst (4.8 kV), Surge (6.6 kV) and
Dips, Interrupts and Variations with
EUT supply up to 270 V / 16 A
CDN 3061-C16
Automated 1-phase coupler for
EFT/Burst (4.8 kV) & Surge (6.6 kV) with
EUT supply up to 270 V / 16 A
CDN 3063-S16
Automated 1-phase coupler for Surge
(6.6 kV) with EUT supply up to 270 V/ 16 A
CDN 3063-B32
Automated 3-phase coupler for
EFT/Burst (4.8 kV) only with EUT supply
up to 480 V / 32 A
CDN 3063-C32
Automated 3-phase coupler for
EFT/Burst (4.8 kV) and Surge (6.6 kV)
with EUT supply up to 480 V / 32 A
CDN 3063-S32
Automated 3-phase coupler for Surge
(6.6 kV) only (combination and ring wave)
with EUT supply up to 480 V / 32 A
CDN 3063-S63
Automated 3-phase coupler for Surge
(6.6 kV) only (combination and ring wave)
with EUT supply up to 480 V / 63 A
CDN 3063-S100
Automated 3-phase coupler for Surge
(6.6 kV) only (combination and ring wave)
with EUT supply up to 480 V / 100 A
CDN 3083-B100
Manual 3-phase coupler for EFT/Burst
(8 kV) only with EUT supply up to
690 VAC (1000 VDC) / 100 A
CDN 3083-B200
Manual 3-phase coupler for EFT/Burst
(8 kV) only with EUT supply up to
690 VAC (1000 VDC) / 200 A
CDN 3083-S100
Manual 3-phase coupler for Surge
(8 kV) only (combination and ring wave)
with EUT current up to 100 A
CDN 3083-S200M
Manual 3-phase coupler for Surge
(8 kV) only (combination and ring wave)
with EUT current up to 200 A
NSG 3060 EMC test system
121
CDN 117/118:
CDN HSS-2
CDN 3425
Coupling networks for signal / data
lines (surge)
Coupling network for 2 kV surge pulse
1.2 / 50 μs IEC/EN 61000-4-5 on
unshielded symmetrical high speed
telecom lines (Ethernet)
Burst EFT capacitive coupling clamp for
data line coupling per IEC 61000-4
122
14
SYSTEM DESCRIPTION
Description:
Housing:
Mains on/off:
Indicator LED’s on
front panel:
Safety functions:
Ambient conditions:
Self-test:
Relevant safety
standards:
Relevant EMC
standards:
Test system for EMC tests with mains-borne interference in accordance with the EN 61000-6-1 and 2
standards for burst, surge and mains quality tests.
Operation via touch-screen or software-wise via a PC
link Ethernet TCP/IP interface. Pulse output to external
coupling networks. Housing for bench-top or rack
use.
Bench-top housing made of metal with moulded
plastic front panel.
Supplementary rack-mounting kit.
On/off switch on rear panel of the instrument
Power on:
LED, yellow
Pulse:
LED, green
High voltage active: LED, red
EUT Power on:
LED, green
Error:
LED, red
Main fuses, interlock, EUT fail input
+5° to 40°C, 20 to 80% relative humidity (non-condensing), 68–106 kPa atmospheric pressure
Routines for functional self-test
IEC 61010-1 safety requirements for electrical
equipment used for measurement and control
purposes as well as laboratory use
IEC/EN 61000-6-1 and 2; generic standards for electromagnetic interference immunity
NSG 3060 EMC test system
Headquarters
Teseq AG
4542 Luterbach, Switzerland
T + 41 32 681 40 40
F + 41 32 681 40 48
sales @ teseq.com
www.teseq.com
Manufacturer
Teseq AG
4542 Luterbach, Switzerland
T + 41 32 681 40 40
F + 41 32 681 40 48
sales @ teseq.com
China
Teseq Company Limited
T + 86 10 8460 8080
F + 86 10 8460 8078
chinasales @ teseq.com
France
Teseq Sarl
T + 33 1 39 47 42 21
F + 33 1 39 47 40 92
francesales @ teseq.com
Germany
Teseq GmbH
T + 49 30 5659 8835
F + 49 30 5659 8834
desales @ teseq.com
Japan
Teseq K.K.
T + 81 3 5725 9460
F + 81 3 5725 9461
japansales @t eseq.com
Singapore
Teseq Pte Ltd.
T + 65 6846 2488
F + 65 6841 4282
singaporesales @ teseq.com
Switzerland
Teseq AG
T + 41 32 681 40 50
F + 41 32 681 40 48
sales @ teseq.com
Taiwan
Teseq Ltd.
T + 886 2 2917 8080
F + 886 2 2917 2626
taiwansales @ teseq.com
UK
Teseq Ltd.
T + 44 845 074 0660
F + 44 845 074 0656
uksales @ teseq.com
USA
Teseq Inc.
T + 1 732 417 0501
F + 1 732 417 0511
Toll free +1 888 417 0501
usasales @ teseq.com
© September 2013 Teseq®
Specifications subject to change
without notice. Teseq® is an ISOregistered company. Its products are
designed and manufactured under
the strict quality and environmental
requirements of the ISO 9001. This
To find your local partner within document has been carefully checked.
Teseq®’s global network, please go to However, Teseq® does not assume
www.teseq.com
any liability for errors or inaccuracies.