6.4 Comparison for Upper and Lower Limits
„ I/O Allocation
The I/O numbers in the timing chart and program are shown on the condition that the first
word number of the unit is 10. Actual I/O numbers allocated to the analog input unit are
determined by the first word number.
CH0
CH1
CH2
CH3
*1 Comparison execution relay
Y103
Y113
Y123
Y133
*2 Upper limit comparison relay
X111
X131
X151
X171
*3 Lower limit comparison relay
X112
X132
X152
X172
*4 Comparison execution flag
X113
X133
X153
X173
„ Configuration
Name
Default
Setting range and description
Not
execute
Select the desired function to be used.
Upper/Lower limit comparison
Upper limit comparison ON
level
K0
Set the upper limit to turn ON the output flag at the time of using
the upper/lower limit comparison function.
Upper/Lower limit comparison
Upper limit comparison OFF
level
K0
Set the upper limit to turn OFF the output flag at the time of using
the upper/lower limit comparison function.
Upper/Lower limit comparison
Lower limit comparison OFF
level
K0
Set the lower limit to turn OFF the output flag at the time of using
the upper/lower limit comparison function.
Upper/Lower limit comparison
Lower limit comparison ON
level
K0
Set the lower limit to turn ON the output flag at the time of using
the upper/lower limit comparison function.
Function
setting
Upper limit /
Lower limit
comparison
Setting range: -31,250 to +31,250 (specified with a signed integer)
Setting range: -31,250 to +31,250 (specified with a signed integer)
Setting range: -31,250 to +31,250 (specified with a signed integer)
Setting range: -31,250 to +31,250 (specified with a signed integer)
(Note) Make the following level settings for upper/lower limit comparison.
Lower limit comparison ON level ≤ Lower limit comparison OFF level < Upper limit comparison OFF level ≤ Upper
limit comparison ON level
6-9