Download Programming manual
Transcript
Factory configuration Drive factory settings The Altivar 12 is factory-set for the most common operating conditions (motor rating according to drive rating): • Display: drive ready (rdY) motor stopped or motor frequency reference while running • Automatic adaptation of the deceleration ramp in the event of overvoltage on braking. • No automatic restarting after a detected fault is cleared • Logic inputs: - LI1: forward (2-wire transitional control) - LI2, LI3, LI4: no assignment • Logic output: LO1: no assignment • Analog input: AI1 (0 to + 5 V) speed reference • Relay R1: the contact opens in the event of a detected fault (or drive off) • Analog output AO1: no assignment Code Description Value page bFr Standard motor frequency 50 Hz 44 UnS Rated motor voltage 230 V 55 ACC Acceleration 3 seconds 62 dEC Deceleration 3 seconds 62 LSP Low speed 0 Hz 44 75 HSP High speed 50 Hz 76 Ctt Motor control type Standard U/F law 55 UFr IR compensation (law U/F) 100% 56 Ith Motor thermal current equal to nominal motor current (value determined by drive rating) 80 SdC1 Automatic DC injection current 0.7 x nominal drive current, for 0.5 seconds. 65 SFr Switching frequency 4 kHz 57 If the above values are compatible with the application, the drive can be used without changing the settings. Drive factory wiring diagram ATV12ppppM3 3-phase motor Source (1) R1 relay contacts, for remote indication of the drive status. (2) Internal + 24 V c. If an external source is used (+ 30 V c maximum), connect the 0 V of the source to the COM terminal, and do not use the + 24 V c terminal on the drive. (3) Reference potentiometer SZ1RV1202 (2.2 kΩ) or similar (10 kΩ maximum). (4) Forward BBV28581 04/2009 29