Download Taylor Programmable Controller Interface User`s Guide
Transcript
Taylor™ Programmable Controller Interface User’s Guide Chapter 2 Hardware and Software Requirements Internal Switches SC Controller PC devices connected by either single or redundant connections SC Interface Module Backup SC Controller Figure 2-10. SC Controller with Controller Redundancy SC Controller Serial Ports The serial ports of an SC Controller Subsystem are provided by the 6204B SC Control Module. Each SC Control Module has two redundant serial ports that are set up for RS-422/485 communication. If the PC or data highway uses a different protocol, a converter box must be provided. The maximum baud rate for communication at these ports is 9600. Serial communications are brought to the 6204B SC Control Module via connections to its corresponding 6254B Direct I/O Interface Module or 6229B Field Bus Interface Module. Both interface modules have four male serial connectors on the top portion of their front panels as shown in Figure 2-11. Connectors 1A and 1B are redundant connectors for port 1; connectors 2A and 2B are redundant connectors for port 2. Each connector has 15 pins with the pin designation shown in Table 2-7. 2-12 3BUR 000 254R0201