Download User Manual - Electrocomponents
Transcript
05/02 AWB2528-1423GB NET Network Changing the write repeat rate, time interval manually Every NET network connection automatically determines the number of stations which are active on the network, the baud rate which is used and the total number of bytes which are transmitted. The minimum time interval which a device requires is automatically determined using this data, to ensure that all devices can send their messages. If a time interval is to be increased, the value of the BUSDELAY: must be set greater than zero. Value “1” doubles the time interval, value “15” will increase it by a factor of 16. tpnew = tp x (1 + n) tpnew = new time interval tp = time interval determined by the network n = value on BUSDELAY h An extension of the time interval means that fewer messages (inputs, outputs, bit data, word data) are transferred per time unit. The reaction speed of the entire controller depends on the baud rate, the time interval and the quantity of transferred data. The smaller the amount of data transferred, the faster the reaction times of the system. h 190 An increase in the time interval is only useful during commissioning. To ensure that the data for the power flow direction is updated faster in the PC, a longer range for this data is created on the network within this time interval.