Download B2UC0002_Inst 24848502 21-11

Transcript
Burglar Alarm System
B2
1 2 3 4 5 6 7 8 9 10
12:30
Fri 03rd March
Partial
Armed
Disarmed
Installation instructions
21-11-2011 / 24848502
B2UC0002_Inst 24848502 21-11-11_GB.indd 1
21/11/11 16.17
2
B2UC0002_Inst 24848502 21-11-11_GB.indd 2
21/11/11 16.17
CONTENTS
Safety notes .................................................................................. 4
1- GENERAL SYSTEM INFORMATION
Page 5
General Diagram ....................................................................... 6
Devices that can be connected
to the Control Panel................................................................ 7
Absorption of the
system components ............................................................... 7
Technical characteristics
of the Control Panel B2UC0002...................................... 8
2- CONNECTION DIAGRAMS
Page 9
Connection of the devices
to the system bus ................................................................... 10
Connection
of the Power Supplier B2AL0001 ................................ 11
Connection of the GSM module or
generic loads to the Power Supplier ........................ 12
Connection of the sensors
to the modules B2MIA101 ............................................... 13
Connection of the sensors
to the modules B2MI0401 ................................................ 14
Connection of loads
to the module B2MO0201................................................ 16
Connection to the OH/GW gateway
with BXRS4201 Interface Module ............................... 17
Connection to the OH/GW gateway
with OH/RS422 Interface Module............................... 18
Connection to a PC with BXRS2301
Interface Module..................................................................... 19
Anti-tampering cover EBTAM ........................................ 20
3- INSTALLATION
Page 20
Anti-tampering cover EBTAM ........................................ 20
Connection of the
B2CTME01 metal container............................................. 21
Connection of the
B2CTPL01 plastic container ............................................ 21
Installation of the control Panel
B2UC0002..................................................................................... 22
Installing BXRS4201 and OH/RS422
Interface Module..................................................................... 23
Configuration of “Slave” Terminals ............................. 23
4- COMMISSIONING
Page 24
Introduction ............................................................................... 24
Commissioning of the system....................................... 25
Learning ........................................................................................ 26
Identification.............................................................................. 28
- Device identification ....................................................... 28
- Assigning a symbolic name
to the devices ...................................................................... 29
- Check module operation ............................................. 30
- State of the connected sensors ............................... 31
- Erasing a device ................................................................. 31
Device Test................................................................................... 33
- Input Test ................................................................................ 34
- Output Test............................................................................ 34
- Siren Test ................................................................................. 34
- Battery Test ............................................................................ 35
- Transmission Quality Test ............................................. 35
Date & Time Setting .............................................................. 36
Commissioning complete ............................................... 37
5- RESTORING FACTORY VALUES
Page 38
3
B2UC0002_Inst 24848502 21-11-11_GB.indd 3
21/11/11 16.17
Safety notes
 WARNING
•
•
•
•
•
•
•
•
•
•
•
•
Carefully read the instructions before starting installation. Perform work as specified by the manufacturer.
It is prohibited to use the product for purposes other than those specified or which are improper.
It is prohibited to tamper with or modify the product.
The removal of the labels on the card will void the guarantee.
Use original spare parts.
Installation, setting, commissioning and maintenance of the product must only be performed by qualified
technicians who have been properly trained in compliance with current standards. Installation of security systems is regulated and may be performed by persons who possess the legally required qualifications, including
compliance with accident prevention.
Operate in sufficiently lighted areas that are conducive to health and use tools, utensils and equipment that
are in good working order.
Upon completion of installation, always check for correct operation of the unit and the system as a whole.
Do not install the devices outdoors or in areas where they are exposed to seepage or splashes of water.
Handle the devices with care. They contain electronic parts that are fragile and sensitive to humidity.
Always disconnect the power supply before doing any work on the devices.
The electrical system must comply with current standards in the country of installation.
4
B2UC0002_Inst 24848502 21-11-11_GB.indd 4
21/11/11 16.17
GENERAL SYSTEM INFORMATION
General system information
1
5
B2UC0002_Inst 24848502 21-11-11_GB.indd 5
21/11/11 16.17
General Diagram
General system information
1
Infrared
sensor
B2IPPA01
Control Panel
B2UC0002
2 Relay output
module
B2MO0201
B
Keypad
BXTAIN01
C
D
Power supplier
B2AL0001
External siren
B2SEAL02
A
4-Input
module
B2MI0401
Infrared
key receiver
BXINIR
Powered
input
module
B2MIA101
Powered
generic
sensor
Infrared
key
BXKEIR01
The system bus allows:
• non-polarized connection of the devices;
• maximum wiring length of 800 metres (A+B+C+D in the figure) and a maximum distance of 400 metres between
the power supplier and the most distant device (B+D in the figure) (*);
• maximum current available for devices on bus 1 A (*).
• connection of a maximum of 32 devices which are part of the system with free typology.
(*)These distances can be achieved by adding the repeater modules B2RP0001 and B2RPAL01 not shown in the
drawing. If these devices are not present, the distance and current values shown are halved.
 WARNING
In order to obtain the best system performance, it is recommended that you use unshielded, non-polarized twisted pair with a minimum section of 0.5 mm2.
6
B2UC0002_Inst 24848502 21-11-11_GB.indd 6
21/11/11 16.17
Devices that can be connected to the Control Panel
Description
Recessed keypad
Passive infrared sensor
2 Relay output module
Powered 1 input module
Non-powered 4 input module
Self-powered external siren
Power supplier
Code
BXINIR
BXKEIR01
BXGM0001
BRP0001
BRPAL01
B2DTPA01
BXRS4201
OH/RS422
Description
IR key receiver that can be used only
with the key BXKEIR01
Infrared key
GSM communicator
BUS signal repeater module
Power supply repeater module
Volumetric detector
Interface module
Interface module
The BXIRI receiver can be integrated in the standard bodies listed in the table below.
Code
BXINIRMA
BXINIRLV
BXINIRLI
BXINIRTL
BXINIRPB
Model
Ticino Magic
Ticino Living
Ticino Living International
Ticino Living Light
Gewiss Play Bus
Code
BXINIRGB
BXINIRVN
BXINIRVB
BXINIRAN
BXINIRAB
Model
Gewiss 20
Vimar Idea black
Vimar Idea white
Ave Noir
Ave Blanque
1
General system information
Code
BXTAIN01
B2IPPA01
B2MO0201
B2MIA101
B2MI0401
B2SEAL02
B2AL0001
Absorption of the system components
DEVICES
Control Panel B2UC0002
Recessed keypad BXTAIN01
Passive infrared sensor B2IPPA01
2 Relay output module B2MO0201
Powered 1 input module B2MIA101
Non-powered 4 input module B2MI0401
Self-powered external siren B2SEAL02
Infrared key receiver BXINIR
GSM communicator BXGM0001
Volumetric detector B2DTPA01
Interface module BXRS4201 or Interface module OH/RS422
AVERAGE ABSORPTION
25 mA
22 mA
9 mA
12 mA
(without output load) 13 mA
3 mA
18÷100 mA
30 mA
110 mA
16 mA
50 mA
 WARNING
The sum of the current absorbed by the devices connected to the bus must not exceed the maximum current
available from the power supplier (500 mA).
7
B2UC0002_Inst 24848502 21-11-11_GB.indd 7
21/11/11 16.17
Technical characteristics of the Control Panel B2UC0002
General system information
1
Main power supply
• Power supply voltage
• Max current absorbed
The module can ONLY be powered by means of the system BUS
12÷35 V DC
30 mA
Mechanical characteristics
• Weight
• Dimensions (L x H x D)
• Container material
• Protection rating
Security Level II as per CEI 79-2
170 g
116x95x27 mm
ABS
IP30
Climatic characteristics
• Operating temperature
• Maximum relative humidity during operation
• Storage temperature
• Maximum relative humidity for storage
0 ÷ 40 °C
93% RH without condensation
-10 ÷ +50 °C
85% RH with no condensation
The touchscreen keypad as well as the supplementary keypad BXTAIN01 provides each user with more
than 1,000,000 combinations for the access code.
8
B2UC0002_Inst 24848502 21-11-11_GB.indd 8
21/11/11 16.17
CONNECTION DIAGRAMS
Connection diagrams
2
9
B2UC0002_Inst 24848502 21-11-11_GB.indd 9
21/11/11 16.17
Connection of the devices to the system BUS
An example of the connection of the keypad (BXTAIN01), expansion modules (B2MO0201, B2MI0401,
B2MIA101), siren (B2SEAL02), IR key receiver (BXINIR), sensor (B2IPPA01) and Control Panel (B2UC0002)
on the B2 BUS.
BUS
+
–
I1
T1
I3
T3
–3
I4
T4
–4
I1
T1
–1
I2
T2
–2
BUS
BUS
B2MIA101
B2MI0401
B2MO0201
BUS
+ 12 V
–
BXTAIN01
NC1
C1
NA1
NC2
C2
NA2
Connection diagrams
2
B2AL0001
M2
24 V
30 V
M1
BUS
+ 12 V
–
+
– BAT
TAMPER
M3
BUS
B2DTPA01
BUS
B2SEAL02
BUS
BXINIR
BUS
B2IPPA01
BUS
NO1
C1
NC1
NO2
C2
NC2
NO3
C3
NC3
NO4
C4
NC4
B2UC0002
10
B2UC0002_Inst 24848502 21-11-11_GB.indd 10
21/11/11 16.17
Connection of the Power Supplier B2AL0001
230 V
L
N
B2AL0001
M2
T
24 V
30 V
M1
BUS
 WARNING
+ 12 V
–
+
– BAT
TAMPER
M3
NO1
C1
NC1
NO2
C2
NC2
NO3
C3
NC3
NO4
C4
NC4
BB065
12 Vcc 7Ah
–
+
BB065
12 Vcc 7Ah
–
+
• The unit is powered at mains voltage, 230 V AC
- 50/60 Hz. Therefore, it must be provided with an
earth connection using the appropriate terminals.
Failure to connect all accessible metal parts to the
earth will make the unit unsafe to use.
• For the 230 V AC power supply, it is essential to
use a cable with double insulation (with double
sheath), as set forth in electrical safety standards.
• Use wire terminals for connection to the mains at
230V AC - 50/60 Hz.
• Protect the appliance using a suitable disconnection device to protect the power supply network
such as an easily accessible bi-polar switch (or
other).
• Use a cable passage hole only for the passage of
the cable for connection to the 230V AC - 50/60
Hz mains.
• The backup battery should only be replaced by
qualified personnel. Dispose of the unit in accordance with current standards. Use only sealed lead
batteries.
Connection diagrams
2
11
B2UC0002_Inst 24848502 21-11-11_GB.indd 11
21/11/11 16.17
Connection of the GSM module or generic loads to the Power Supplier
B2AL0001
M2
BXGM0001
2
24 V
30 V
M1
Connection diagrams
BUS LA
M1
BUS
BUS B2
+ 12 V
–
+
– BAT
M2
TAMPER
M3
NO1
C1
NC1
NO2
C2
NC2
NO3
C3
NC3
NO4
C4
NC4
B2AL0001
M2
24 V
30 V
U1
M1
BUS
+ 12 V
–
+
– BAT
TAMPER
U2
M3
U3
NA1
C1
NC1
NA2
C2
NC2
NA3
C3
NC3
NA4
C4
NC4
U4
Max 24Vcc
12
B2UC0002_Inst 24848502 21-11-11_GB.indd 12
21/11/11 16.17
Connection of the sensors to the modules B2MIA101
Connection for sensors with Normally Open or
Normally Closed contacts without balancing.
Connection for sensors with Normally Closed
contacts with Two Resistance Mode.
TAMPER
ALLARME
+
–
RFL=2.2K
RA=2.2K
Connection diagrams
2
TAMPER
ALLARME
+
–
B2MIA101
B2MIA101
BUS
+
–
I1
–1
BUS
+
–
I1
–1
Connection for sensors with Normally Closed
contacts with One Resistance Mode.
RFL=
2.2 K
TAMPER
ALLARME
+
–
B2MIA101
BUS
+
–
I1
–1
13
B2UC0002_Inst 24848502 21-11-11_GB.indd 13
21/11/11 16.17
Connection of the sensors to the modules B2MI0401
Connection of 4-wire magnetic contacts and wall/
fence-breaking sensors (RIN01).
2
Connection diagrams
CIO21-CIO23-CIP31-CPA31CSA31-CSP21-RIN01
Connection of magnetic contacts and wall/fencebreaking sensors (RIN02) with four terminals.
CSA11-CSA12-RIN02RVB02
ALLARME
TAMPER
B2MI0401
B2MI0401
BUS
I1
T1
–1
I2
T2
BUS
I1
T1
–1
I2
T2
Connection of 2-wire cable contacts for shutters.
CFSST
Connection of magnetic contacts with two terminals.
CSP01-CSP02
ALLARME
B2MI0401
B2MI0401
BUS
I1
T1
–1
I2
T2
BUS
I1
T1
–1
I2
T2
14
B2UC0002_Inst 24848502 21-11-11_GB.indd 14
21/11/11 16.17
Connection of the sensors to the modules B2MI0401
Connection of magnetic contacts with two wires.
2
Connection diagrams
CXP31-CIO22
B2MI0401
BUS
I1
T1
–1
I2
T2
BRAHMS CONTACTS AND SENSORS
CONTACTS FOR SHUTTERS AND BLINDS
CFSST
cable contact pre-wired two wires
MAGNETIC CONTACTS
CIO21
magnetic recessed with four wires
CIO22
magnetic recessed with two wires
CIO23
magnetic recessed with four wires
CIP31
magnetic recessed with four wires
CIPA31
magnetic contact for garage door with four wires
CSA11
surface mounted magnetic contact with four terminals
CSA12
surface mounted magnetic contact with four terminals
CSA31
surface mounted magnetic contact with four wires
CSP01
surface mounted magnetic contact with two terminals
CSP02
surface mounted magnetic contact with two terminals
CSP21
surface mounted magnetic contact with four wires
CXP31
surface mounted magnetic contact with two wires
VIBRATION SENSORS
RIN01
wall/fence breaking sensor with 4 wires
RIN02
wall/fence breaking sensor in box with four terminals
RVB02
glass-breaking sensors with 6 terminals
15
B2UC0002_Inst 24848502 21-11-11_GB.indd 15
21/11/11 16.17
Connection of loads to the module B2MO0201
Connection of the 2-Relay output module
B2MO0201 to a generic load (U1 and U2).
B2MO0201
Connection diagrams
22
2
NC1
C1
NA1
NC2
C2
NA2
1
BUS
Max 24Vcc
U1
U2
16
B2UC0002_Inst 24848502 21-11-11_GB.indd 16
21/11/11 16.17
Connection to the OH/GW gateway with BXRS4201 Interface Module
EXV00
22
$/
Connection diagrams
0,7+2
0
²
%
0
00
9$60+
6(&
²
9 + 18V –
9
9
+] 9 9$
230V
35,
%;56
2+*:
5;
5;²
7;
7;²
²
6
0
5
5²
7
7²
²
7;
7;²
5;
5;²
²
6
0
00
%;56
,QWHUIDFFLD56
&1
&1
0
&1
0
%8&
/$
&1
%86
2+$
0
/$
/$
0
%.
0
EXV%37
EXV%5$+06
17
B2UC0002_Inst 24848502 21-11-11_GB.indd 17
21/11/11 16.17
Connection to the OH/GW gateway with OH/RS422 Interface Module
Connection diagrams
22
EXV00
9$6
7;²
0
5;
5;²
²
6:
²
9 0
9
M2
2+56
MAX 150m
2+*:
0
6
7;
7;²
5;
5;²
²
6:
6
5
5²
7
7²
²
0
00
6
5;
5;²
7;
7;²
²
6:
M1
0DGHLQ,WDO\
2+56
&1
&1
0
&1
0
%8&
/$
&1
%86
2+$
0
/$
/$
0
%.
0
EXV%37
EXV%5$+06
18
B2UC0002_Inst 24848502 21-11-11_GB.indd 18
21/11/11 16.17
Connecting to a PC with BXRS2301 Interface Module
CN1
22
Cavo seriale
NON INCLUSO
per connessione a PC
Serial Cable
NOT INCLUDED
Cable serial
NO INCLUIDO
para conexión a PC
Connection diagrams
TX
Connessione
a centrali
BRAHMS B2 o C4
Connection for
control units
BRAHMS B2 ou C4
Conexión a
centrales
BRAHMS B2 o C4
–
RX
RS 232
p
5 4 3 2 1
F
9 8 7 6
RS 232
TX
RX
–
CN1
Connessione
a centrali
BRAHMS B2 o C4
Connection for
control units
BRAHMS B2 ou C4
Conexión a
centrales
BRAHMS B2 o C4
1 - DCD
2 - RX
3 - TX
4 - DTR
5 - GND
6 - DSR
7 - RTS
8 - CTS
9 - RI
Cavo seriale
NON INCLUSO
per connessione a PC
Serial Cable
NOT INCLUDED
Cable serial
NO INCLUIDO
para conexión a PC
19
B2UC0002_Inst 24848502 21-11-11_GB.indd 19
21/11/11 16.17
Anti-tampering cover EBTAM
The use of this cover (fig. 2) is indispensable if the modules are to be equipped with an anti-opening and antitampering device in order to achieve the Security Level II as per the Standard CEI 79-2.
Installation
3
INSTALLATION
The modules (B2MIA101, B2MI0401, B2MO0201) can be wall-mounted on a completely flat surface or mounted inside a junction box or even on a DIN rail (fig. 1). Remove the jumper present on the module and insert the
one present on the cover (fig. 3). Fix the protection to the module with the screws provided (fig. 4), being very
careful that, in the chosen position, the lever (A) of the protection’s microswitch is operated and the connection cable (B) between the cover and the module is not accidentally positioned between the two elements.
B
A
2
1
3
2
1
4
20
B2UC0002_Inst 24848502 21-11-11_GB.indd 20
21/11/11 16.17
Connection of the B2CTME01 metal container
ER
+
TBA
- +
12V
P
TAM
~
24V
Installation
3
Connection of the B2CTPL01 plastic container
ER
AT
+
P
TAM
B
- +
12V
~
24V
21
B2UC0002_Inst 24848502 21-11-11_GB.indd 21
21/11/11 16.17
Installation of the Control Panel B2UC0002
2
Installation
3
1
5
7
6
Open the unit by using a screwdriver in the slot (fig. 5). Fasten the base to the wall using the screws and plugs
provided or on a recessed box (fig. 6).
We recommend you install it on a flat surface, being careful not to over tighten screws.
Connect the wires of the twisted pair to the terminals of the provided connector and insert it on the printed
circuit (fig. 7). Close the unit.
After connecting the various system devices, connect the power supplier B2AL0001 to the local network.
22
B2UC0002_Inst 24848502 21-11-11_GB.indd 22
21/11/11 16.17
Installing BXRS4201 and OH/RS422 Interface Modules
6
5;
5;²
7;
7;²
²
6:
5;
5;²
7;
7;²
²
6
Should you wish to connect a Brahms B2 burglar-proof system to a Bpt home automation system, you need to
install module BXRS4201 or OH/RS422 (figure 8) using the purpose-provided CN1connector supplied
3
0DGHLQ,WDO\
%;56
,QWHUIDFFLD56
2+56
Installation
&1
&1
CN1
CN1
CN1
8
9
Configuration of “Slave” Terminals
An additional terminal in SLAVE configuration
can also be installed in a system. From a SLAVEconfigured terminal, it is possible to totally or
partially arm/disarm the system. No other terminal
function can be accessed. In order to operate in
SLAVE mode, a terminal should be configured as
shown in figure 10, setting dip-switch number 4 off.
Ļ
O
N1
2
3 4
10
23
B2UC0002_Inst 24848502 21-11-11_GB.indd 23
21/11/11 16.17
Introduction
System language
Commissioning
4
The objectives of the “Commissioning” are the
following:
- Setting the language of the system.
- Check that all the connections have be made correctly.
- Check that the Control Panel is able to communicate with all the system devices.
- Check the correct operation of each device.
- Set the main parameters of each device.
Thus this chapter will only illustrate the functions
regarding Commissioning; all other functions have
been intentionally omitted here and will be covered in the Installer Manual.
Detection of
all the System
devices
Not all the devices
have been detected
Learn
Make any changes
necessary
R
All the devices
have been detected
We recommend that you follow the procedure
illustrated to the side that summarizes the essential
steps for a correct “Commissioning”.
I I I
I
A B2UC0002 terminal can also be programmed
using the dedicated PCB2 software.
This programming software is a valid tool for the
quick configuration of the system and if necessary
for saving a copy of the structure.
NOTE. Using this software, you can also update
the firmware of the B2UC0002 terminals. We
recommend that the updating procedure only
be performed if it is strictly necessary, and in any
case ONLY by specialised Brahms technical staff.
I I I
Identify
Identify the devices making up
the system by assigning them
names reflecting their location
or use.
Inputs
State
No device
in alarm
TEST
Device
in alarm
Check
connections
and type of
balancing
Test
Input Test
Output Test
Alarm Test
Battery Test
Date and Time
Setting
1 2
END
24
B2UC0002_Inst 24848502 21-11-11_GB.indd 24
21/11/11 16.17
Commissioning of the system
When the system is started for the first time, after a
brief standby period (fig. 1), by pressing the appropriate icon it will be possible to choose the system
language.
Choose Language
DEU
ESP
ENG
FRA
ITA
The “Choose Language” window will appear
automatically when the system is turned on or
turned back on after a complete power outage.
POR
ESC
1 2 3 4 5 6 7 8 9 10
12:30
Fri 03rd March
Armed
Partial
Once you have chosen the system language, provide for automatic detection of the connected
devices.
(fig. 2).
Push the icon
A keypad will appear on which to enter the Installer
Code (which at the first start-up will be 5, 6, 7, 8, fig.
3) in order to access the Installer Menu (fig. 4).
Commissioning
4
Fig. 1
Disarmed
Fig. 2
Enter Code
1
2
3
4
5
6
7
8
Esc 9
0
OK
Fig. 3
25
B2UC0002_Inst 24848502 21-11-11_GB.indd 25
21/11/11 16.17
Installer Menu
S S S
I I I
S
I
S S S
I I I
Learn
View
Identify
Learning
P P P
Setting
1 2 3
4 5 6
7 8 9
0
MEM ORY
1 2
Learn
P P P
P
TEST
When the appropriate icon is pressed, the system
automatically detects the connected devices (fig.
4).
ESC
Fig. 4
4
Commissioning
Devices Detected
Start
devices detection?
OK
At this point, a list will appear with the number of
devices detected and a different icon for each type
of device (figg. 6, 7).
To scroll through the complete list of detected
devices, press the buttons
.
ESC
If a device is not recognized during this phase, it
may not have been connected correctly.
Fig. 5
Once the connection problems have been resolved,
the detection of the devices can be repeated by
simply pressing the icon R .
Devices Detected
A POWER SUPPLIER
UC CONTROL PANEL
In 4 IN MODULE
In 1 IN PW MODULE
12V
Out 2 OUT MODULE
IR
WALL IR SENSOR
01
01
01
01
02
03
R
Pressing the icon ESC, we will now return to the
“Installer Menu” (fig. 8).
ESC
Fig. 6
26
B2UC0002_Inst 24848502 21-11-11_GB.indd 26
21/11/11 16.17
On the following pages we will analyze ONLY the
items of the “Installer Menu” which are useful for
properly carrying out the commissioning (fig. 8).
Devices Detected
01
03
03
EXT. SIREN
IR RECEIVER
SUPPLEMENTARY KEYPAD
Learn
Learn devices
I I I
I
I I I
Identify
Devices Detection
ESC
R
TEST Device Test
Fig. 7
1 2
Date & Time Setting
4
S S S
I I I
S
I
I I I
Learn
Identify
P P P
P
S S S
View
P P P
Setting
MEM ORY
1 2
Commissioning
Installer Menu
TEST
1 2 3
4 5 6
7 8 9
0
Learn
ESC
Learning
Pressing the icon “Learn” allows you to repeat the
detection of the connected devices (fig. 9).
Fig. 8
Devices Detected
Start
devices detection?

OK
ESC
Before proceeding with the commissioning,
it is important that all the devices are recognized by the system
Fig. 9
27
B2UC0002_Inst 24848502 21-11-11_GB.indd 27
21/11/11 16.17
Devices Detection
In
In
In
In
In
ID: 022228237 V:0.1
DEL
Power Supplier
A PW. OUT 01.1
A PW. OUT 01.2
A PW. OUT 01.3
A PW. OUT 01.4
ID: 02228296 V:0.1
A
ESC
OK
DEL
Devices Detection
01
OUT Module
OUT Module 01.1
Out 2 OUT Module 01.2
ID: 022228259 V:0.1
DEL
Devices Detection
In
12V
12V 1 IN PW Mod 01.1
Commissioning
IR
Sensore IR Par.
IR
Wall IR 01.1
ESC
OK
DEL
Devices Detection
EXT Siren 01.1
ESC
OK
01
Rec. Keypad
REC Keypad 01.1
ID: 022228226 V:0.1
DEL
ID: 022228333 V:0.1
ESC
OK
DEL
ESC
OK
Fig. 10
Devices Detection
In
In
In
In
In
4
4
4
4
4
IN
IN
IN
IN
IN
I I I
Identification
By pressing the appropriate icon, we will now proceed
with the identification of the devices.
During this phase of the commissioning, we can
identify, name and program the components of the
burglar alarm system.
To facilitate the identification of each individual
device and its outputs or inputs, numbered progressively, these will now appear in a list divided
over several pages (fig. 10).
To scroll through the pages containing the list of
devices, use the icons
.
Devices Detection
01
Ext. Siren
01
ID: 022228632 V:0.1
ID: 022228382 V:0.1
DEL
ESC
OK
Devices Detection
01
1 IN PW Module
In
4
ESC
OK
Out 2
ESC
OK
I
Identify
Out 2
ID: 022228233 V:0.1
DEL
01
Devices Detection
01
IR Receiver
IR Receiver 01.1
I I I
Devices Detection
01
4 IN Module
Mod 4 IN 01.1
Mod 4 IN 01.2
Mod 4 IN 01.3
Mod 4 IN 01.4
Module
Mod 01.1
Mod 01.2
Mod 01.3
Mod 01.4
01

In the event, once the siren has been recognized,
it is necessary to perform work on the installation
and on the wiring of the siren itself, (or branches
upstream from the siren), it is necessary to proceed
as follows in order to avoid the ’“Tamper Alarm”:
1- Erase the Siren(s) by pressing on the button DEL .
2- Carry out the necessary operations on the installation.
3- Perform the detection of the Siren(s) again and
recheck the setting.
DEVICE IDENTIFICATION
The icon
allows you to activate the LEDs and
buzzers present on the connected devices and
identify their position within the environment (fig.
11).
ID: 022228776 V:0.1
DEL
OK
ESC
Fig.11
28
B2UC0002_Inst 24848502 21-11-11_GB.indd 28
21/11/11 16.17
Consider a 4-input module as an example; the first
line (fig. 12) cannot be changed, it contains the
default name assigned by the system and represents
the type of device recognized.
Devices Detection
In
In
In
In
In
01
4 IN Module
Mod 4 IN 01.1
Mod 4 IN 01.2
Mod 4 IN 01.3
Mod 4 IN 01.4
ID: 022228237 V:0.1
DEL
ESC
OK
Fig.12
In
In
In
In
In
01
4 IN Module
Mod 4 IN 01.1
Mod 4 IN 01.2
Mod 4 IN 01.3
Mod 4 IN 01.4
ID: 022228237 V:0.1
DEL
ESC
OK
4
Commissioning
Devices Detection
ASSIGNING A SYMBOLIC NAME TO THE
DEVICES
The next lines on the page (fig. 13) represent each
of the 4 inputs to which an external sensor can be
connected; pressing on the text, an alphanumeric
keypad will appear which allows us to assign them
a name.
We recommend that you use a symbolic name that
identifies their position, for example garage 01.1, or
that identifies their use, for example Gas detector
(fig. 14).
Press OK to confirm the selections made before
exiting from the screen with ESC.
Fig.13
Once these operations have been carried out for
all the connected devices, whether these are entry
panels, outputs, sirens, IR receivers or what have
you, we will have a precise picture of the location of
each component and/or its function.
Enter Zone Name
Garage 01.1
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V W X
Y
Z
'
.
-
0
1
4
5
6
7
8
CAP
2
OK
3
DEL BkSp
9
ESC
It is advisable that you carry out the identification operations carefully, as the names
assigned to the devices during this phase will
help you to recognize them during the setting
phase as well.
Fig.14
29
B2UC0002_Inst 24848502 21-11-11_GB.indd 29
21/11/11 16.17
Devices Detection
IR
Sensore IR Par.
IR
Wall IR 01.1
01
CHECK MODULE OPERATION
We will now consider as an example another device
recognized by the system during detection, and
we will analyze the column indicated by the arrow
(fig. 15).
Clicking on this icon, we act on the state of the
device as follows:
On
ID: 022228632 V:0.1
DEL
In Test state
Fig. 15
With the device in test state we can perform maintenance on the installation while keeping it active
but avoiding the effective sounding of the alarm
sirens; the activation of the devices, however, will be
indicated in the “Event Log”.
4
Commissioning
Off
ESC
OK
Devices Detection
IR
Sensore IR Par.
IR
Wall IR 01.1
01
The second column (fig. 16) cannot be changed
from the display, as it shows the effective state of
the connected device:
Alarm
ID: 022228823 V:0.1
DEL
OK
Tamper
ESC
Fault
Fig. 16
Press OK to confirm the selections made before
exiting from the screen with ESC.

- The state of the devices set during this phase (On,
Off, in Test State) become a permanent state
which cannot be modified by the User.
- In order to avoid false alarms or malfunctioning,
it is recommended to turn Off
all the unconnected inputs.
30
B2UC0002_Inst 24848502 21-11-11_GB.indd 30
21/11/11 16.17
Devices Detection
In
In
In
In
In
4 IN Module
Mod 4 IN 01.1
Mod 4 IN 01.2
Mod 4 IN 01.3
Mod 4 IN 01.4
01
STATE OF THE CONNECTED SENSORS
During this commissioning phase, it is important
that none of the connected inputs are in a state
of alarm; otherwise, it is necessary to check that
the connection is correct and consistent with the
“Type of Balancing” parameter for each input;
in order to do this, just press on the icon of the
device in alarm (fig. 17) in order to access the window “Input Setting” (fig. 18).
ID: 022228456 V:0.1
OK
ESC
Fig. 17
Input Setting
The first line of the “Input Setting” page contains
the name that we have assigned to the input during the identification phase (this name, however,
can also be changed from this window using the
procedures described previously).
4 IN Module 01.4
01 Area
Burglar Alarm
NC contact
Entry Delay=000
Exit Delay =000
OK
From this window it is possible to access all the setting functions, but for the commissioning we will
limit ourselves only to the parameters necessary
for correct recognition of the inputs by the control
panel, referring to the setting manual for further
information.
4
Commissioning
DEL
ESC
Fig. 18
Devices Detection
IR
Sensore IR Par.
IR
Wall IR 01.1
01
ERASING A DEVICE
In the event you must remove a device, just press
the button DEL (fig. 19) and confirm the selection
so that the device is no longer recognized by the
system.
ID: 022228632 V:0.1
DEL
OK
ESC
Fig. 19
31
B2UC0002_Inst 24848502 21-11-11_GB.indd 31
21/11/11 16.17
Input Setting
4 IN Module 01.4
01 Area
Burglar Alarm
NC contact
Entry Delay=000
Exit Delay =000
ESC
OK
On the fourth line (fig. 20), of the “Input Setting”
page, pressing the icons
allows you to
identify the correct type of balancing for the input
in question.
The available options are:
NC contact (Normally Closed)
NO contact (Normally Open)
One Resistance Mode
Two Resistance Mode
Vibration Sensor
Rolling Shutter Sensor
For the types of balancing defined as “Vibration
Sensor” and “Rolling Shutter Sensor”, you will also
have to set the pulse length, pulse number and
time interval (fig. 22); to access these parameters,
press on the icon
(fig. 21).
Fig. 20
4
Commissioning
Input Setting
For the other types of balancing, we will be able to
set “Tamper” and “Gong” (fig. 22).
4 IN Module 01.4
01 Area
Burglar Alarm
Rolling Shutter Sensor
Entry Delay=000
Exit Delay =000
The correctness of the connections and balancing can be checked from the inputs, by purposely
triggering the alarms and checking that they are
recognized correctly by the Control Panel.
ESC
OK
Fig. 21
This phase of the commissioning can be considered completed when, returning to the “Devices
Detection” window, none of the devices are in a
state of alarm.
Press OK to confirm the selections made before
exiting from the screen with ESC.
Input Setting
4 IN Module 01.4
Tamper OFF
Pulse Lenght
Pulse Number
Time Interval
=000
=000
=000
OK
ESC
Fig. 22
32
B2UC0002_Inst 24848502 21-11-11_GB.indd 32
21/11/11 16.18
Installer Menu
S S S
I I I
S
I
I I I
Learn
Identify
S S S
View
Device Test
P P P
Setting
MEM ORY
1 2
TEST
P P P
P
TEST
1 2 3
4 5 6
7 8 9
0
From the “Installer Menu” (fig. 23), pressing the icon
“Test” will take us to the “Test Menu” (fig. 24) that
allows us to test the correct operation of the connected devices.
Each individual test available is analyzed below.
ESC
Fig. 23
Commissioning
4
Test Menu
In In
Out Out
In In
12V
Out Out
12V
ESC
Fig. 24
33
B2UC0002_Inst 24848502 21-11-11_GB.indd 33
21/11/11 16.18
In In
Input Test
In
4 IN MOD 01.1
In
4 IN MOD 01.2
In
4 IN MOD 01.4
WALL IR SENSOR 01
IR
IR
12V
In In
12V
WALL IR SENSOR 02
ESC
INPUT TEST
Only the inputs that are in a state of alarm will
appear in this window (fig. 25).
Thus, by materially activating the inputs, we can
check their correct operation, name and location.
If the balancing of the inputs has been set correctly
and the inputs are not effectively activated, this
window must be empty.
Fig. 25
4
Out Out
Commissioning
Input Test
PW.
A PW.
A PW.
A PW.
Out MOD. 2OUT
Out MOD. 2OUT
A
01/1
01/2
01/3
01/4
01/1
01/2
Out Out
On
Off
On
Off
On
Off
ESC
Fig. 26
OUTPUT TEST
All the connected outputs will appear in this window, with the icon in the right column (fig. 26) on
Off.
By pressing the pen provided on the icon Off, the
state of the output will change to On and the output will be activated in order to allow us to check
its operation.
When exiting from the window by pressing the icon
ESC, any outputs that may have been left active will
automatically be deactivated.
Siren Test
EXT. SIREN 01
EXT. SIREN 02
On
Off
SIREN TEST
The legend “On” or “Off” next to the name of the
device acts as a switch (fig. 27).
By simply pressing on the legend we can turn the
sirens on or off.
ESC
Fig. 27
34
B2UC0002_Inst 24848502 21-11-11_GB.indd 34
21/11/11 16.18
Battery Test
A
BATTERY TEST
PW.
01
EXT. SIREN 02
By simply pressing on the name of the device, we
will be informed about the state of the battery
housed inside the device (figg. 28, 29).
ESC
Fig. 28
4
Commissioning
Battery Test
Battery CHARGED
ESC
Fig. 29
Transmission Speed
IR
IR
IR
IR
Bedroom Sensor
Bathroom Sensor
Kitchen Sensor
Garage Sensor
OK
9
8
9
8
ESC
TRANSMISSION QUALITY TEST
Pressing the appropriate icon, a list of the inputs
will appear with a numerical value next to each that
indicates the speed and quality of communication
between the Control Panel and the device, on a
scale from 1 to 10 (fig. 30).
If the value is less than 7, check that the length of the
connection is within the limits indicated in the section
“General system information”.
Fig. 30
35
B2UC0002_Inst 24848502 21-11-11_GB.indd 35
21/11/11 16.18
Date & Time Setting
Hours
18
1 2
55
ESC
OK
Fig. 31
Date & Time Setting
From the “Installer Menu”, pressing the appropriate
icon will take us to the window for the Date and
Time Setting.
Set the correct time by selecting the area to be
modified (fig. 31) and using the arrows on the side.
Proceed in the same manner to set the date after
having pressed the arrow at the bottom of the window (fig. 32) which allows access to the appropriate
screen (fig. 33).
Press OK to confirm the selections made before
exiting from the screen with ESC.
Commissioning
4
Date & Time Setting
Hours
19
58
ESC
OK
Fig. 32
Date & Time Setting
Date
Gio
17
Month-Year Gen
08
OK
ESC
Fig. 33
36
B2UC0002_Inst 24848502 21-11-11_GB.indd 36
21/11/11 16.18
Commissioning complete
At this point the commissioning can be considered as completed, and the system is ready to operate.
It is possible to arm the system, trigger the alarms and check that all the devices respond correctly.
For the system activation and deactivation procedures, refer to the “User Manual”.
Commissioning
4
37
B2UC0002_Inst 24848502 21-11-11_GB.indd 37
21/11/11 16.18
Restoring factory values
Should it be necessary to restore the default values, proceed as follows:
- With the system turned on, remove the terminal (figure 1) from its fixing base WITHOUT cutting off the power
supply (figure 2) (the system will go into sabotage mode).
2
1
2
1
- Hold down the central key (figure 3) and concurrently switch dip-switch number 2 OFF (figure 4).
- After approximately 5 seconds, switch the dip-switch back ON and release the central key (figure 3).
1 2 3 4 5 6 7 8 9 10
12:30
Ven 03
Parziale
Inserito
Ļ
Restoring factory values
5
Marzo
Spento
O
N1
3
2
3 4
4
- Attach the terminal back onto its wall fixing base.
38
B2UC0002_Inst 24848502 21-11-11_GB.indd 38
21/11/11 16.18
- At this stage, the terminal will automatically display the device recognition menu (figure 5) and will proceed
with detecting devices (figure 6).
Devices Detected
Devices Detected
A POWER SUPPLIER
Start
devices detection?
UC CONTROL PANEL
In 4 IN MODULE
Wait....
In 1 IN PW MODULE
12V
Out 2 OUT MODULE
IR
OK
Fig. 5
ESC
WALL IR SENSOR
R
01
01
01
01
02
03
ESC
Fig. 6
Restoring factory values
5
39
B2UC0002_Inst 24848502 21-11-11_GB.indd 39
21/11/11 16.18
BPT Spa
Centro direzionale e Sede legale
Via Cornia, 1/b
33079 Sesto al Reghena (PN) - Italia
http://www.bpt.it - mailto: [email protected]
40
B2UC0002_Inst 24848502 21-11-11_GB.indd 40
21/11/11 16.18