Download PLC-5 Programmable Controllers / Selection Guide
Transcript
6 / 2011 www.klinkmann.com Select Network Communications 27 The PLC BASIC Module occupies one slot in the 1771 I/O chassis and runs user-written BASIC and C programs. These programs are independent of your PLC-5 controller and provide an easy and fast interface between a PLC-5 controller, 1771 backplane, and RS-232, -422, or -485 devices. The module can also communicate with a remote SLC controller or remote device on the DH-485 network through a DH-485 port. Cat. No. Function Comm. Rate 1771-DB Provides an interface between a PLC-5 controller, 1771 backplane, and RS-232, -422, or -485 devices Configurable, • 2 ports for RS-232, Place in the local I/O depending on -422, or -485 chassis serial protocol • 1 port for DH-485 Connections Design Considerations Cable • Data Highway 1770-CD • RS-232 1770-CG or Modem Interface Cable 1770-CP Power Dissipation, Max 4W Backplane Current Load 0.75 A (with 1747-PIC) 0.65 A The communication controller modules, 1771-KE and 1771-KF, link intelligent RS-232-C devices to Data Highway. Both of these modules provide a choice of two protocols on the RS-232-C link - full-duplex and half-duplex. These modules perform the same functions, however their mounting styles and power supply requirements are different. Cat. No. Function Comm. Rate Connections Design Considerations 1771-KE Provides an interface between RS-232-C devices and Data Highway link with both full-duplex and half-duplex protocols • Data Highway 57 Kbps • RS-232-C from 110 to 19 Kbps Data Highway, RS-232 Place in the local I/O chassis. Power source is the 1771 I/O chassis power supply. 1771-KF Provides an interface between RS-232-C devices and Data Highway link with both full-duplex and half-duplex protocols • Data Highway 57 Kbps • RS-232-C from 110 to 19 Kbps Data Highway, RS-232 Cable Power Dissipation, Max 6.3 W • Data Highway 1770-CD • RS-232 1770-CG or Modem Interface Cable 1770-CP Includes mounting • Data Highway 6.3 W bracket for external 1770-CD mounting or in a standard • RS-232 industrial enclosure 1770-CG or (NEMA Type 12 or Modem similar). Power source is Interface Cable user-supplied (1771-P2 or 1770-CP similar). Backplane Current Load 1.2 A 1.2 A Publication 1785-SG001B-EN-P - June 2006