Download 1 Features
Transcript
• Outdoor Units • R-410A • RZQS-B7V3 1 A i ny Uk 3 S Vr 7 o BAt o0- i dS1 l Qt4 pZu- R•OS • 1 Outdoor units for pair, twin, triple, double twin application The Sky Air Inverter is developed for use in shops, restaurants and small offices. This innovative Daikin unit provides a more comfortable environment and offers great savings in energy consumption to shop and office owners. • During start up, the room can be cooled down or heated very quickly. Once the temperature in the room has reached its set point, the low power operation starts to save energy. • Daikin outdoor units are neat and sturdy and can be mounted easily on a roof or terrace or simply placed against an outside wall. • The use of inverter type outdoor units results in an air conditioning system with a high energy efficiency and very low sound level • Outdoor units are fitted with either a swing or scroll compressor, renowned for low noise and high energy efficiency • An inverter driven compressor allows the capacity to be adjusted precisely to match variations in room and outside temperatures. • A special acryl precoated fin for anti-corrosion treatment on the heat exchanger ensures greater resistance against severe weather conditions. 1 1 Features • Split Sky Air • Outdoor Units • Outdoor Units • R-410A • RZQS-B7V3 2 Specifications 2-1 NOMINAL CAPACITY AND NOMINAL INPUT For combination indoor units + outdoor units Condition 2 Nominal input For combination indoor units + outdoor units Condition 2 Nominal input For combination indoor units + outdoor units Condition 2 Nominal input For combination indoor units + outdoor units Condition 2 Nominal input For combination indoor units + outdoor units 2-2 Casing Indoor Units R ZQS7 1B7V3B RZQS100B7 V3 B RZQS125B7V3B FCQ71B7V3B FCQ100B7V3B FCQ125B7V3B 3 1 Cooling Standard capacity Heating Standard capacity Cooling Standard Heating Standard EER Nominal COP Nominal Energy Cooling Labeling Heating Directive Annual energy consumption Indoor Units Cooling Standard capacity Heating Standard capacity Cooling Standard Heating Standard EER Nominal COP Nominal Energy Cooling Labeling Heating Directive Annual energy consumption Indoor Units Cooling Standard capacity Heating Standard capacity Cooling Standard Heating Standard EER Nominal COP Nominal Energy Cooling Labeling Heating Directive Annual energy consumption Indoor Units Cooling Standard capacity Heating Standard capacity Cooling Standard Heating Standard EER Nominal COP Nominal Energy Cooling Labeling Heating Directive Annual energy consumption kW 7.10 10.00 12.50 kW 8.00 11.20 14.00 kW kW 2.46 2.61 2.89 3.07 C D 3.83 3.47 2.61 3.23 D C 4.14 4.52 3.02 3.10 B D kWh kW 1230 FBQ71B7V3B 7.10 1915 FBQ100B7V3B 10.00 2070 FBQ125B7V3B 12.50 kW 8.00 11.20 14.00 kW kW 2.52 2.40 2.82 3.33 C 3.83 3.47 2.61 3.23 D C 4.40 4.24 2.84 3.30 C kWh kW 1260 FHQ71BUV1B 7.10 1915 FHQ100BUV1B 10.00 2200 FHQ125BUV1B 12.50 kW 8.00 11.20 14.00 kW kW 2.53 2.84 2.81 2.82 C 4.15 3.99 2.41 2.81 E D 4.58 4.96 2.73 2.82 D kWh kW 1265 FAQ71BUV1B 7.10 2075 FAQ100BUV1B 10.00 2290 FDQ125B7V3B 12.50 kW 8.00 11.20 14.00 kW kW 2.53 2.61 2.81 3.01 C D 4.08 3.73 2.45 3.00 E D 4.45 4.08 2.81 3.43 C B kWh 1265 2040 2225 R ZQS7 1B7V3B RZQS100B7 V3 B RZQS125B7V3B TECHNICAL SPECIFICATIONS Colour Material 2 Ivory W hite Painted galvanised steel • Split Sky Air • Outdoor Units 2 • Outdoor Units • R-410A • RZQS-B7V3 2 Specifications 2-2 TECHNICAL SPECIFICATIONS Dimensions 1 Unit Packing 2 Weight Heat Exchanger Unit Packed Unit Dimensions Tube type Fin Fan Motor Fan Compressor Operation Range Cooling Cooling Heating Sound Level (Night quiet) Refr iger ant Refr iger ant Oil 3 mm mm mm mm mm mm kg kg mm Length Nr of Rows Fin Pitch mm Nr of Passes Face m² Area Nr of Stages Sound Pr essur e Type Char ge Control Nr of Circuits Type Char ged Volume RZQS71B7V3B RZQS100B 7V3B RZQS125B7 V3 B 770 900 320 900 980 420 68 72 857 2 1.40 3 0.641 770 900 320 900 980 420 68 72 857 2 1.40 3 0.641 1345 900 320 1475 980 420 106 111 857 2 1.40 5 1.131 34 34 Hi- XSS(8) W F fin Anti-corrosion treatment (PE) Propeller Horizontal 1 61.3 61.7 60 Type Tr eatment Type Dischar ge direction Quantity Air Flow Rate Cooling (nominal at Heating 230V) Motor Quantity Model Speed Steps (nominal) Cooling Heating Motor Output Quantity Motor Model Type Heating Sound Level (nominal) Height W idth Depth Height W idth Depth Motor Output Crankcas e Heater Min Max Min Max Sound Power Sound Pressure Sound Pressure m³/min m³/min rpm rpm W W 1 54.5 48.1 1 KFD-325-70-8A 8 8 818 920 715 920 70 70 1 1 2YC63BXD 2YC63BXD Her metically sealed swing compressor 2 99.0 100.0 1 2 1800 8 782 767 70 1 JT100G-VD Hermetically sealed scroll compressor 2200 1800 W 33 °CDB °CDB °CWB °CWB dBA - 5.0 46.0 -15.0 15.5 65.0 -5.0 46.0 - 15.0 15.5 67.0 -5.0 46.0 -15.0 15.5 67.0 dBA 49.0 51.0 51.0 dBA 51.0 55.0 53.0 dBA 43.0 45.0 45.0 kg 2.80 l 1 Daphne FVC50K 0.8 • Split Sky Air • Outdoor Units R-410A 2.80 Expansion valve ( electr onic type) 1 Daphne FVC50K 0.8 4.3 1 Daphne FVC68D 1.0 • Outdoor Units • R-410A • RZQS-B7V3 2 2-2 Specifications TECHNICAL SPECIFICATIONS Piping connections Liquid ( OD) Quantity Type Diameter (OD) Gas Quantity Type Diameter (OD) Drain Quantity Type Diameter (OD) Piping Length Minimum Maximum Equivalen t Chargele ss Additional Refrigerant Charge Installation Maximum height difference Max. internunit level difference Heat Insulation mm mm 9.52 15.9 1 Flare connection 15.9 9.52 1 26 m m m 5 30 40 5 50 70 5 50 70 m 30 30 30 kg/m 1 2 3 26 see installation manual 4PW32097-1 m 15 30 30 m 0.5 0.5 0.5 Hz V Minimum V Maximum V Cur rent Z-max List Recomended fuses A Wiring For Power Remark connections Supply For connection Remark with indoor Power Supply Intake Notes 3 15.9 mm Item Quantity Item Quantity Name Phase Frequency Voltage Voltage range 1 3 Hole 26 ELECTRICAL SPECIFICATIONS Power Supply RZQS125B7V3B 1 Flare connection 9.52 3 Notes 2-3 RZQS100B7 V3 B 1 1 Defrost Method Defrost Control Capacity Control Method Safety Devices Standard Accessories R ZQS7 1B7V3B Both liquid and gas pipes Pressur e equalising Sensor for outdoor heat exchanger temperature Inverter controlled High pressure switch Fan motor thermal protector Fuse Tie- wr aps 2 2 2 Installation manual 1 1 1 Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperatur e : 35°CDB Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB R ZQS7 1B7V3B 1 50 230 20 RZQS100B7 V3 B V3 1 50 230 -10% +10% Complies to EN6100-3-3 20 see installation manual 4PW32097-1 RZQS125B7V3B 1 50 230 32 see installation manual 4PW32097-1 Outdoor unit only See separate drawings for electrical data Power supply to the FDQ indoor unit is separate • Split Sky Air • Outdoor Units 4 • Outdoor Units • R-410A • RZQS-B7V3 3 Electrical data RZQ71-125BV3 Unit combination Indoor unit Outdoor unit 1 FCQ71BV3 FCQ35BV3x2 FFQ35BV3x2 FBQ71BV3 FBQ35BV3x2 FHQ71BV3 FHQ35BV3x2 FAQ71BV3 FCQ100BV3 FCQ50BV3x2 FCQ35BV3x3 FFQ50BV3x2 FFQ35BV3x3 FBQ100BV3 FBQ50BV3x2 FBQ35BV3x3 FHQ100BV3 FHQ50BV3x2 FHQ35BV3x3 FAQ100BV3 FCQ125BV3 FCQ60BV3x2 FCQ50BV3x3 FCQ35BV3x4 FFQ60BV3x2 FFQ50BV3x3 FFQ35BV3x4 FBQ125BV3 FBQ60BV3x2 FBQ50BV3x3 FBQ35BV3x4 FHQ125BV3 FHQ60BV3x2 FHQ50BV3x3 FHQ35BV3x4 FDQ125BV3 3 Power supply Voltage range MCA Hz-volts RZQS71BV3 RZQS71BV3 RZQS71BV3 RZQS71BV3 RZQS71BV3 RZQS71BV3 RZQS71BV3 RZQS71BV3 RZQS100BV3 RZQS100BV3 RZQS100BV3 RZQS100BV3 RZQS100BV3 RZQS100BV3 RZQS100BV3 RZQS100BV3 RZQS100BV3 RZQS100BV3 RZQS100BV3 RZQS100BV3 RZQS125BV3 RZQS125BV3 RZQS125BV3 RZQS125BV3 RZQS125BV3 RZQS125BV3 RZQS125BV3 RZQS125BV3 RZQS125BV3 RZQS125BV3 RZQS125BV3 RZQS125BV3 RZQS125BV3 RZQS125BV3 RZQS125BV3 RZQS125BV3 TOCA MFA Comp. MSC RLA OFM kW IFM FLA kW FLA Max. 50Hz253V Min. 50Hz207V Max. 50Hz253V Min. 50Hz207V Max. 50Hz253V Min. 50Hz207V 3D055645 SYMBOLS MCA TOCA MFA MSC RLA OFM IFM FLA kW NOTES : Min. Circuit Amps (A) : Total Over Current Amps (A) : Max. Fuse Amps (See note 7) (A) : MSC means the max. current during the starting of compressor. (A) : Rated Load Amps (A) : Outdoor Fan Motor (A) : Indoor Fan Motor : Full Load Amps : Fan Motor Rated Output (kW) 1 2 3 4 5 6 7 8 5 RLA is based on the following conditions: Power supply: 50Hz 230V Cooling Heating Indoor temperature 27°CDB/19°CWB Indoor temperature 20.0°CDB Outdoor temperature 35°CDB Outdoor temperature 7.0°CDB/6.0°CWB TOCA means the total value of each OC set Voltage range Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed operation range limits Maximum allowable voltage unbalance between phases is 2% MCA represents maximum input current., MFA represents capacity which may accept MCA (next lower standard fuse rating, min.15A) Select wire size based on the larger value of MCA or TOCA MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker) For more details concerning conditional connections, see http://extranet.daikineurope.com, select ’’E-Data Books’’. Finally, click on the document title of your choice. • Split Sky Air • Outdoor Units • Outdoor Units • R-410A • RZQS-B7V3 4 Options 3 Available option for RZQS71-125BV3 Kit name Name of option RZQS71B7V3B Central drain plug Refrigerant branch piping RZQS100B7V3B RZQS125B7V3B KKPJ5F180 Twin 4 KHRQ22M20TA Triple - Double twin - Demand adapter kit 1 KHRQ127H - KHRQ22M20TA (3x) KRP58M51 3TW26739-1C • Split Sky Air • Outdoor Units 6 • Outdoor Units • R-410A • RZQS-B7V3 5 Capacity tables 5-1 Combination table Possible combinations and standard capacity for twin, triple and double twin application Possible indoor combination 1 Simultaneous operation 5 Outdoor models Twin Triple Out Out In In In In RZQS71BV3 35-35 (KHRQ22M20TA7) RZQS100BV3 50-50 (KHRQ22M20TA7) 35-35-35 (KHRQ127H7) RZQS125BV3 60-60 (KHRQ22M20TA7) 50-50-50 (KHRQ127H7) Double twin Out In In In In In 35-35-35-35 (3x KHRQ22M20TA7) 3TW29069-1 NOTES 7 1 Possible indoor units: FCQ35-125B, FFQ35-60BV, FHQ35-125B, FBQ35-125B, FAQ71-100B, FDQ125B 2 Individual indoor capacities are not given because the combinations are for simultaneous operation (=indoor units installed in same room). 3 When different indoor models are used in combination, designate the infrared remote controller that is equipped with the most functions as the main unit. In note 1 are the indoor units mentioned in order of the possible function (most functions are on FCQ, less functions are on FAQ). 4 Between brackets are the required Refnet kits mentioned, that are necessary to install the combination. • Split Sky Air • Outdoor Units • Outdoor Units • R-410A • RZQS-B7V3 5 Capacity tables 5-2 Cooling capacity tables 3 RZQS71BV3 Cooling Coefficient of power input. (-) 1 5 Capacity range Rated point Cooling capacity (kW) Cooling capacity 230V [50Hz] Indoor EWB Outdoor temp. (°CDB) EDB (°C) (°C) 16.0 18.0 19.0 19.5 22.0 24.0 22 25 27 27 30 32 TC (kW) 6.47 7.43 7.58 7.66 8.05 8.37 25 SHC (kW) 4.39 4.82 4.80 4.79 4.73 4.66 CPI (-) 0.76 0.83 0.84 0.84 0.85 0.85 TC (kW) 6.46 7.20 7.35 7.43 7.81 8.12 30 SHC (kW) 4.43 4.72 4.71 4.70 4.64 4.58 CPI (-) 0.89 0.91 0.91 0.91 0.92 0.93 TC (kW) 6.66 6.95 7.10 7.17 7.55 7.85 35 SHC (kW) 4.62 4.61 4.60 4.59 4.54 4.48 CPI (-) 0.99 1.00 1.00 1.00 1.01 1.02 TC (kW) 6.39 6.67 6.82 6.89 7.26 7.55 40 SHC (kW) 4.49 4.47 4.46 4.46 4.41 4.35 CPI (-) 1.09 1.10 1.10 1.10 1.11 1.12 3D055646 NOTES SYMBOLS 1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 7.5 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. (Pair) Model AFR (BF) FCQ71B 18 (0.10) FBQ71B 19 (0.11) FHQ71B 17 (0.10) FAQ71B 19 (0.08) 10. Rated power input of each model is tabulated below. (Pair) Model Cooling Heating FCQ71B 2.46 2.61 FBQ71B 2.52 2.40 FHQ71B 2.53 2.85 FAQ71B 2.53 2.61 • Split Sky Air • Outdoor Units AFR: BF: EWB: EDB: TC: SHC: PI: CPI: (m3/min) Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input. (°CWB) (°CDB) (kW) (kW) (kW) (-) Caution: TC and SHC are shown by kW (Multi) Model AFR (BF) FCQ35Bx2 14x2 (0.16x2) FFQ35Bx2 10x2 (0.25x2) FBQ35Bx2 11.5x2 (0.15x2) FHQ35Bx2 13x2 (0.2x2) FCQ35Bx2 2.59 2.75 FFQ35Bx2 2.61 2.70 FBQ35Bx2 2.57 2.47 FHQ35Bx2 2.66 2.85 (Multi) Model Cooling Heating 8 • Outdoor Units • R-410A • RZQS-B7V3 5 Capacity tables 5-2 Cooling capacity tables RZQS100BV3 1 5 Coefficient of power input. (-) Cooling Capacity range Rated point Cooling capacity (kW) Cooling capacity 400V [50Hz] Indoor Outdoor temp. (°CDB) EWB EDB (°C) (°C) 16.0 18.0 19.0 19.5 22.0 24.0 22 25 27 27 30 32 TC (kW) 9.12 10.5 10.7 10.8 11.3 11.8 25 SHC (kW) 6.19 6.78 6.76 6.75 6.66 6.57 CPI (-) 0.76 0.83 0.84 0.84 0.85 0.85 TC (kW) 9.10 10.1 10.4 10.5 11.0 11.4 30 SHC (kW) 6.25 6.65 6.63 6.62 6.54 6.45 CPI (-) 0.89 0.91 0.91 0.91 0.92 0.93 TC (kW) 9.38 9.79 10.0 10.1 10.6 11.1 35 SHC (kW) 6.51 6.49 6.48 6.47 6.39 6.30 CPI (-) 0.99 1.00 1.00 1.00 1.01 1.02 TC (kW) 9.00 9.40 9.60 9.71 10.2 10.6 40 SHC (kW) 6.32 6.30 6.29 6.28 6.21 6.13 CPI (-) 1.09 1.10 1.10 1.10 1.11 1.12 3D055647 NOTES SYMBOLS 1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb 3 SHC* = 0.02 x AFR (m /min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 7.5 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. (Pair) AFR: BF: EWB: EDB: TC: SHC: PI: CPI: (m3/min) Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input. (°CWB) (°CDB) (kW) (kW) (kW) (-) Caution: TC and SHC are shown by kW (Twin) Model AFR (BF) FCQ100B 28 (0.16) FBQ100B 27 (0.20) FHQ100B 24 (0.14) FAQ100B 23 (0.10) Model AFR (BF) FCQ50Bx2 14x3 (0.16x3) FFQ50Bx2 10x3 (0.25x3) FBQ50Bx2 11.5x3 (0.15x3) FHQ50Bx2 13x3 (0.2x3) Model AFR (BF) FCQ35Bx3 15x2 (0.16x2) FFQ35Bx3 12x2 (0.16x2) FBQ35Bx3 14x2 (0.15x2) FHQ35Bx3 13x2 (0.1x2) FCQ50Bx2 3.83 3.65 FFQ50Bx2 3.83 3.54 FBQ50Bx2 3.83 3.58 FHQ50Bx2 4.15 3.99 (Triple) 10. Rated power input of each model is tabulated below. (Pair) Model Cooling Heating (Twin) FCQ100B 3.83 3.47 FBQ100B 3.83 3.47 FHQ100B 4.15 3.99 FAQ100B 4.08 3.73 FCQ35Bx3 3.83 3.65 FFQ35Bx3 3.83 3.54 FBQ35Bx3 3.83 3.58 FHQ35Bx3 4.15 3.99 (Triple) Model Cooling Heating 9 • Split Sky Air • Outdoor Units Model Cooling Heating • Outdoor Units • R-410A • RZQS-B7V3 5 Capacity tables 5-2 Cooling capacity tables 3 RZQS125BV3 Cooling Coefficient of power input. (-) 1 5 Rated point Capacity range Cooling capacity (kW) Cooling capacity 400V [50Hz] Indoor Outdoor temp. (°CDB) EWB EDB (°C) (°C) 16.0 18.0 19.0 19.5 22.0 24.0 22 25 27 27 30 32 TC (kW) 11.4 13.1 13.3 13.5 14.2 14.7 25 SHC (kW) 7.73 8.48 8.45 8.44 8.33 8.21 CPI (-) 0.76 0.83 0.84 0.84 0.85 0.85 TC (kW) 11.4 12.7 12.9 13.1 13.8 14.3 30 SHC (kW) 7.81 8.32 8.29 8.28 8.18 8.06 CPI (-) 0.89 0.91 0.91 0.91 0.92 0.93 TC (kW) 11.7 12.2 12.5 12.6 13.3 13.8 35 SHC (kW) 8.14 8.12 8.09 8.08 7.99 7.88 CPI (-) 0.99 1.00 1.00 1.00 1.01 1.02 40 SHC (kW) 7.90 7.88 7.86 7.85 7.76 7.67 TC (kW) 11.3 11.8 12.0 12.1 12.8 13.3 CPI (-) 1.09 1.10 1.10 1.10 1.11 1.12 3D055649A NOTES SYMBOLS 1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb 3 SHC* = 0.02 x AFR (m /min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 7.5 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. AFR: BF: EWB: EDB: TC: SHC: PI: CPI: (m3/min) Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input. (°CWB) (°CDB) (kW) (kW) (kW) (-) Caution: TC and SHC are shown by kW (Twin) (Pair) Model AFR (BF) FCQ125B 31 (0.07) FBQ125B 35 (0.14) FHQ125B 30 (0.13) FDQ125B 45 (0.25) FCQ50Bx3 15x3 (0.16x3) FFQ50Bx3 12x3 (0.16x3) FBQ50Bx3 14x3 (0.15x3) FHQ50Bx3 13x3 (0.1x3) 10. Rated power input of each model is tabulated below. (Pair) Model Cooling Heating FFQ60Bx2 15x2 (0.11x2) FBQ60Bx2 19x2 (0.11x2) FHQ60Bx2 17x2 (0.2x2) Model AFR (BF) FCQ35Bx4 14x4 (0.16x4) FFQ35Bx4 10x4 (0.25x4) FBQ35Bx4 11.5x4 (0.15x4) FHQ35Bx4 13x4 (0.2x4) FCQ60Bx2 4.36 4.76 FFQ60Bx2 4.41 4.42 FBQ60Bx2 4.48 4.42 FHQ60Bx2 4.76 4.92 FCQ35Bx4 4.36 4.76 FFQ35Bx4 4.41 4.42 FBQ35Bx4 4.48 4.42 FHQ35Bx4 4.76 4.92 (Twin) FCQ125B 4.14 4.52 FBQ125B 4.40 4.24 FHQ125B 4.58 4.96 FDQ125B 4.45 4.08 FCQ50Bx3 4.36 4.76 FFQ50Bx3 4.41 4.42 FBQ50Bx3 4.48 4.42 FHQ50Bx3 4.76 4.92 (Triple) Model Cooling Heating FCQ60Bx2 18x2 (0.1x2) (Double twin) (Triple) Model AFR (BF) Model AFR (BF) Model Cooling Heating (Double twin) • Split Sky Air • Outdoor Units Model Cooling Heating 10 • Outdoor Units • R-410A • RZQS-B7V3 5 Capacity tables 5-3 Heating capacity tables RZQS71BV3 1 5 Coefficient of power input. (-) Heating Rated point Capacity range Heating capacity (kW) Heating capacity Indoor EDB TC (kW) 5.68 5.67 5.67 5.66 5.66 5.65 (°C) 16.O 18.O 20.0 21.O 22.O 24.0 230V [50Hz] −10 CPI (-) 1.12 1.16 1.21 1.23 1.25 1.30 TC (kW) 6.22 6.21 6.20 6.20 6.19 6.19 −5 CPI (-) 1.17 1.22 1.27 1.29 1.32 1.36 Outdoor temp. (°CWB) 0 TC CPI (kW) (-) 6.75 1.23 6.74 1.28 6.74 1.33 6.73 1.35 6.73 1.38 6.72 1.43 6 TC (kW) 8.02 8.01 8.00 8.00 7.99 7.98 10 CPI (-) 0.92 0.96 1.00 1.02 1.04 1.08 TC (kW) 8.64 8.62 8.61 8.61 8.60 8.59 CPI (-) 0.97 1.01 1.05 1.07 1.09 1.13 3D055646 NOTES SYMBOLS 1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m3/min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 7.5 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. (Pair) Model AFR (BF) FCQ71B 18 (0.10) FBQ71B 19 (0.11) FHQ71B 17 (0.10) FAQ71B 19 (0.08) 10. Rated power input of each model is tabulated below. (Pair) Model Cooling Heating 11 FCQ71B 2.46 2.61 FBQ71B 2.52 2.40 FHQ71B 2.53 2.85 FAQ71B 2.53 2.61 • Split Sky Air • Outdoor Units AFR: BF: EWB: EDB: TC: SHC: PI: Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input. CPI: (m3/min) (°CWB) (°CDB) (kW) (kW) (kW) (-) Caution: TC and SHC are shown by kW (Multi) Model AFR (BF) FCQ35Bx2 14x2 (0.16x2) FFQ35Bx2 10x2 (0.25x2) FBQ35Bx2 11.5x2 (0.15x2) FHQ35Bx2 13x2 (0.2x2) FCQ35Bx2 2.59 2.75 FFQ35Bx2 2.61 2.70 FBQ35Bx2 2.57 2.47 FHQ35Bx2 2.66 2.85 (Multi) Model Cooling Heating • Outdoor Units • R-410A • RZQS-B7V3 5 Capacity tables 5-3 Heating capacity tables 3 RZQS100BV3 Heating Coefficient of power input. (-) 1 5 Capacity range Rated point Heating capacity (kW) Heating capacity 400V [50Hz] Indoor EDB −10 TC (kW) 7.91 7.90 7.89 7.89 7.88 7.87 (°C) 16.O 18.O 20.0 21.O 22.O 24.0 CPI (-) 1.07 1.11 1.15 1.17 1.20 1.24 TC (kW) 8.66 8.65 8.64 8.63 8.63 8.62 −5 Outdoor temp. (°CWB) 0 TC CPI (kW) (-) 9.41 1.17 9.39 1.22 9.38 1.27 9.38 1.29 9.37 1.32 9.36 1.36 CPI (-) 1.12 1.16 1.21 1.23 1.26 1.30 6 TC (kW) 11.2 11.2 11.2 11.2 11.2 11.2 10 CPI (-) 0.92 0.96 1.00 1.02 1.04 1.08 TC (kW) 12.1 12.1 12.1 12.1 12.0 12.0 CPI (-) 0.97 1.01 1.05 1.07 1.09 1.13 3D055647 NOTES SYMBOLS 1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb 3 SHC* = 0.02 x AFR (m /min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 7.5 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. AFR: BF: EWB: EDB: TC: SHC: PI: (m3/min) Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input. CPI: (°CWB) (°CDB) (kW) (kW) (kW) (-) Caution: TC and SHC are shown by kW (Twin) (Pair) Model AFR (BF) FCQ100B 28 (0.16) FBQ100B 27 (0.20) FHQ100B 24 (0.14) FAQ100B 23 (0.10) Model AFR (BF) FCQ35Bx3 14x3 (0.16x3) FFQ35Bx3 10x3 (0.25x3) FBQ35Bx3 11.5x3 (0.15x3) FHQ35Bx3 13x3 (0.2x3) Model AFR (BF) FCQ50Bx2 15x2 (0.16x2) FFQ50Bx2 12x2 (0.16x2) FBQ50Bx2 14x2 (0.15x2) FHQ50Bx2 13x2 (0.1x2) FCQ50Bx2 3.83 3.65 FFQ50Bx2 3.83 3.54 FBQ50Bx2 3.83 3.58 FHQ50Bx2 4.15 3.99 (Triple) 10. Rated power input of each model is tabulated below. (Pair) Model Cooling Heating (Twin) FCQ100B 3.83 3.47 FBQ100B 3.83 3.47 FHQ100B 4.15 3.99 FAQ100B 4.08 3.73 FCQ35Bx3 3.83 3.65 FFQ35Bx3 3.83 3.54 FBQ35Bx3 3.83 3.58 FHQ35Bx3 4.15 3.99 Model Cooling Heating (Triple) Model Cooling Heating • Split Sky Air • Outdoor Units 12 • Outdoor Units • R-410A • RZQS-B7V3 5 Capacity tables 5-3 Heating capacity tables RZQS125BV3 1 5 Coefficient of power input. (-) Heating Capacity range Rated point Heating capacity (kW) Heating capacity Indoor EDB TC (kW) 9.76 9.74 9.73 9.73 9.72 9.71 (°C) 16.O 18.O 20.0 21.O 22.O 24.0 230V [50Hz] −10 CPI (-) 1.11 1.15 1.20 1.22 1.24 1.29 TC (kW) 10.7 10.7 10.7 10.6 10.6 10.6 −5 CPI (-) 1.16 1.21 1.26 1.28 1.31 1.35 Outdoor temp. (°CWB) 0 TC CPI (kW) (-) 11.6 1.22 11.6 1.27 11.6 1.32 11.6 1.34 11.6 1.37 11.5 1.42 6 TC (kW) 14.0 14.0 14.0 14.0 14.0 14.0 10 CPI (-) 0.92 0.96 1.00 1.02 1.04 1.08 TC (kW) 15.1 15.1 15.1 15.1 15.1 15.0 CPI (-) 0.97 1.01 1.05 1.07 1.09 1.13 3D0455649A NOTES SYMBOLS 1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. On the figure the mark j show the max. at standard conditions. On the figure the mark Q show rated capacity and rated coefficient of power input. However the max. capacity is not guaranteed, except at standard condition. 3. On the tables Q show rated capacity and rated coefficient of power input. 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb 3 SHC* = 0.02 x AFR (m /min.) x (1−BF) x (DB*−EDB) Add SHC* to SHC. 5. Capacities are based on following conditions: Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating) Corresponding refrigerant piping length : 7.5 m Level difference :0m 6. Coefficient of power input is the percentage when the rated valve is defined as 1.00. 7. The value contains less than 5% error acording to indoor unit type. 8. Heating capacity include the drop of frost formation. 9. Air flow rate and BF are tabulated below. CPI: (m3/min) Air flow rate Bypass factor Entering wet bulb temp. Entering dry bulb temp. Total cooling/heating capacity Sensible heating capacity Power input (comp.+indoor+outdoor fan motor) Coefficient of power input. (°CWB) (°CDB) (kW) (kW) (kW) (-) Caution: TC and SHC are shown by kW Triple Pair Model AFR (BF) FCQ125B 31 (0.07) FBQ125B 35 (0.14) FHQ125B 30 (0.13) FDQ125B 45 (0.25) Model AFR (BF) FCQ50Bx3 15x3 (0.16x3) FFQ50Bx3 12x3 (0.16x3) FBQ50Bx3 14x3 (0.15x3) FHQ50Bx3 13x3 (0.1x3) Model AFR (BF) FCQ60Bx2 18x2 (0.1x2) FFQ60Bx2 15x2 (0.11x2) FBQ60Bx2 19x2 (0.11x2) FHQ60Bx2 17x2 (0.2x2) FCQ35Bx4 14x4 (0.16x4) FFQ35Bx4 10x4 (0.25x4) FBQ35Bx4 11.5x4 (0.15x4) FHQ35Bx4 13x4 (0.2x4) FCQ60Bx2 4.36 4.76 FFQ60Bx2 4.41 4.42 FBQ60Bx2 4.48 4.42 FHQ60Bx2 4.76 4.92 FCQ35Bx4 4.36 4.76 FFQ35Bx4 4.41 4.42 FBQ35Bx4 4.48 4.42 FHQ35Bx4 4.76 4.92 Double twin Twin 10. Rated power input of each model is tabulated below. Pair Model Cooling Heating Model Cooling Heating Model AFR (BF) Triple FCQ125B 4.14 4.52 FBQ125B 4.40 4.24 FHQ125B 4.58 4.96 FDQ125B 4.45 4.08 FCQ50Bx3 4.36 4.76 FFQ50Bx3 4.41 4.42 FBQ50Bx3 4.48 4.42 FHQ50Bx3 4.76 4.92 Twin 13 AFR: BF: EWB: EDB: TC: SHC: PI: Model Cooling Heating Double twin • Split Sky Air • Outdoor Units Model Cooling Heating • Outdoor Units • R-410A • RZQS-B7V3 5 Capacity tables 5-4 Capacity correction factor RZQS71-125BV3 3 Capacity in function of field piping length for non-inverter 1 5 Capacity (%) Field piping length (m) Cooling Heating • Split Sky Air • Outdoor Units 3TW29069-3 14 • Outdoor Units • R-410A • RZQS-B7V3 6 Dimensional drawing & centre of gravity 6-1 Dimensional drawing unit (mm) RZQS71-100BV3 Hole for anchor bolt 4-M12 1 2 3 4 5 6 7 8 1 6 Gas pipe connection J15.9 flare Liquid pipe connection - J9.5 flare Service port (in the unit) Grounding terminal M5 (in switch box) Refrigerant piping intake Power supply wiring intake (knock out hole J34) Control wiring intake (Knock out hole J27) Drain outlet 3TW25144-1A unit (mm) RZQS125BV3 Hole for anchor bolt 4-M12 1 2 3 4 5 6 7 8 Gas pipe connection J15.9 flare Liquid pipe connection - J9.5 flare Service port (in the unit) Electronic connection and grounding terminal MS (in switch box) Refrigerant piping intake Power supply wiring intake (knock out hole J34) Control wiring intake (Knock out hole J27) Drain outlet 3TW26071-1 15 • Split Sky Air • Outdoor Units • Outdoor Units • R-410A • RZQS-B7V3 6 Dimensional drawing & centre of gravity 6-2 Centre of gravity 3 RZQS71-100BV3 1 6 4TW26069-3 RZQS125BV3 4TW26079-3 • Split Sky Air • Outdoor Units 16 • Outdoor Units • R-410A • RZQS-B7V3 7 Piping diagram RZQS71-100BV3 Electronic expansion valve 1 One way valve One way valve 7 Heat exchanger Filter Service port 5/16″ One way valve One way valve Capillary tube Solenoid valve Receiver Strainer Heat exchanger 4-way valve Muffler Low pressure sensor Muffler One way valve Field piping J9.5 C1220T-0 Service port 5/16″ Filter Field piping J15.9 C1220T-0 Compressor High pressure switch Indoor unit Outdoor unit Heating Cooling Stop valve (with service port 5/16’ flare) O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe 3TW26735-1 RZQS125BV3 One way valve One way valve One way valve Heat exchanger Filter One way valve One way valve Solenoid valve Capillary tube Capillary tube Receiver Electronic expansion valve Strainer Capillary tube Service port 5/16″ Heat exchanger 4-way valve Filter Low pressure switch High pressure switch Muffler Field piping J9.5 C1220T-0 Service port 5/16″ Filter Field piping J15.9 C1220T-0 Compressor Indoor unit Outdoor unit Stop valve (with service port 5/16’ flare) O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe 17 • Split Sky Air • Outdoor Units Heating Cooling 3TW26745-1 • Outdoor Units • R-410A • RZQS-B7V3 7 Piping diagram 3 RZQS71-100BV3 Electronic expansion valve One way valve 1 One way valve Heat exchanger 7 Heat exchanger Filter Service port 5/16″ One way valve One way valve Capillary tube Solenoid valve Field piping Filter Receiver Field piping Strainer Indoor unit 4-way valve Muffler Low pressure sensor Muffler Heat exchanger One way valve Branch duct connection Field piping J9.5 Service port 5/16″ Option Field piping J15.9 Compressor High pressure switch Outdoor unit Field piping Filter Field piping Stop valve (with service port 5/16’ flare) Indoor unit Heating Cooling Note: 1. The pipes between the branch and the indoor units should have the same size as the indoor connections. 3TW26735-2 O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe RZQS125BV3 One way valve One way valve One way valve One way valve One way valve Heat exchanger Filter Solenoid valve Capillary tube Electronic expansion valve Capillary tube Strainer Receiver Field piping Filter Heat exchanger Capillary tube Field piping Service port 5/16″ Indoor unit 4-way valve Filter Low pressure switch High pressure switch Muffler Heat exchanger Branch duct connection Service port 5/16″ Field piping J9.5 C1220T-0 Option Field piping J15.9 Compressor C1220T-0 Outdoor unit Field piping Filter Indoor unit Heating Cooling Field piping Stop valve (with service port 5/16’ flare) Note: 1. The pipes between the branch and the indoor units should have the same size as the indoor connections. O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe • Split Sky Air • Outdoor Units 3TW26745-2 18 • Outdoor Units • R-410A • RZQS-B7V3 7 Piping diagram RZQS100BV3 Indoor unit Electronic expansion valve Heat exchanger 1 7 Stop valve (with service port 5/16’ flare) One way valve One way valve One way valve One way valve Filter Service port 5/16″ Field piping Filter Heat exchanger Capillary tube Field piping Capillary tube Solenoid valve Indoor unit Heat exchanger Receiver Strainer Field piping J9.5 4-way valve C1220T-0 Muffler Field piping Filter Field piping Low pressure switch Muffler Field piping J15.9 C1220T-0 Service port 5/16″ Indoor unit Heat exchanger Branch duct connection (Option) Compressor High pressure switch Outdoor unit Note: 1. The pipes between the branch and the indoor units should have the same size as the indoor connections. Heating Cooling Field piping Filter Field piping 3TW29075-1 O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe RZQS125BV3 Indoor unit Heat exchanger One way valve One way valve Stop valve (with service port 5/16’ flare) Filter Heat exchanger Filter One way valve Solenoid valve Field piping One way valve One way valve Capillary tube Field piping Capillary tube Indoor unit Electronic expansion valve Receiver Heat exchanger Strainer Capillary tube Service port 5/16″ 4-way valve Field piping J9.5 C1220T-0 Field piping Filter Filter Field piping Low pressure switch High pressure switch Muffler Field piping J15.9 Indoor unit C1220T-0 Service port 5/16″ Heat exchanger Branch duct connection Compressor Option Outdoor unit Field piping Filter Field piping Note: 1. The pipes between the branch and the indoor units should have the same size as the indoor connections. O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe 19 • Split Sky Air • Outdoor Units Heating Cooling 3TW26745-3 • Outdoor Units • R-410A • RZQS-B7V3 7 Piping diagram 3 RZQS125BV3 Heat exchanger Indoor unit 1 One way valve One way valve 7 One way valve Field piping Filter Field piping Heat exchanger Indoor unit Heat exchanger One way valve Filter One way valve Capillary tube Field piping J9.5 Solenoid valve Electronic expansion valve Capillary tube Receiver Field piping J15.9 4-way valve Field piping Heat exchanger Indoor unit Capil ary tube Service port 5/16″ Field piping Filter Strainer Branch duct connection Field piping J9.5 Filter Low pressure High pressure switch sensor C1220T-0 Option Service port 5/16″ Field piping J15.9 Muffler C1220T-0 Compressor Field piping Filter Heat exchanger Field piping Outdoor unit Heating Cooling Indoor unit Field piping J9.5 Field piping J15.9 Stop valve (with service port 5/16’ flare) Field piping Filter Note: 1. The pipes between the branch and the indoor units should have the same size as the indoor connections. Field piping O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe • Split Sky Air • Outdoor Units 3TW26755-4 20 • Outdoor Units • R-410A • RZQS-B7V3 8 Wiring diagram 8-1 Wiring diagram RZQS71-100BV3 Indoor L N : Live : Neutral : Field wiring : Protective earth (screw) : Wire clamp : Terminal : Connector 8 NOTE 1. 1 Outdoor : Relay connector Colours BLK: Black / ORG: Orange / BLU: Blue / WHT: White / RED: Red / YLW:Yellow / BRN: Brown / GRN: Green ON OFF NOTES: 1. Refer to the optional manual, for connection wiring to X6A. 2. Confirm the method of setting the selector switches (DS1) by service manual. When the unit is shipped by factory all switches are set to be off. El. comp. assy front A1P A2P BS1 C1-C2-C3 DS1 F1U HAP (A1P) HAP (A2P) H1P (A1P) Printed circuit board Printed circuit board (INV) Push button switch (forced def. / pump down) Capacitor Dip switch Fuse (T6, 3A/250V) Light emitting diode (service monitor green) Light emitting diode (service monitor green) Light emitting diode (service monitor red) K1M(A2P) K1R(A1P) K2R(A1P) K2R(A2P) L1R M1C M1F PS Q1DI R1-R2 R1T Magnetic contactor Magnetic relay (Y1S) Magnetic relay (Y2S) Magnetic relay Reactor Motor compressor Motor fan Power circuit Earth leakage breaker (30mA) Resistor Thermistor (air) R2T R3T R4T R5T S1PH S1NPL RC TC V1R Thermistor (coil) Thermistor (discharge pipe) Thermistor (suction pipe) Thermistor (power module) Pressure switch (high) Pressure sensor (low) Signal receiver circuit Signal transmission circuit Power module V2R-V3R V1T X6A X1M Y1E Y1S Y2S Z1C, Z2C Z3C, Z4C Z1F View A Diode module IGBT Connector (Option) Terminal strip Expansion valve 4-way valve Solenoid valve Noise filter Noise filter (with surge absorber) 2TW26736-1B RZQS125BV3 Indoor Outdoor : Live : Neutral : Field wiring : Protective earth (screw) : Wire clamp : Terminal : Connector NOTE 1. L N : Relay connector Colours BLK: Black / ORG: Orange / BLU: Blue / WHT: White / RED: Red / YLW:Yellow / BRN: Brown / GRN: Green ON OFF NOTES: 1. Refer to the optional manual, for connection wiring to X6A. 2. Confirm the method of setting the selector switches (DS1) by service manual. When the unit is shipped by factory all switches are set to be off. El. comp. assy front A1P A2P BS1 C1-C2-C3 DS1 E1HC F1U F2U F3U HAP (A1P) HAP (A2P) H1P (A1P) 21 Printed circuit board Printed circuit board (INV) Push button switch (forced def. / pump down) Capacitor Dip switch Crankcase heater Fuse (T 6,3A/250V) Fuse Fuse (B 5A/250V) Light emitting diode (service monitor green) Light emitting diode (service monitor green) Light emitting diode (service monitor red) K1M(A2P) K1R(A1P) K2R(A1P) K3R(A1P) K4R (A1P) L1R M1C M1F PS Q1DI R1-R2 R1T Magnetic contactor Magnetic relay (Y1S) Magnetic relay Magnetic relay (E1HC) Magnetic relay (Y2S) Reactor Motor compressor Motor fan Power circuit Earth leakage breaker (30mA) Resistor Thermistor (air) • Split Sky Air • Outdoor Units R2T R3T R4T R5T S1PH S1NPL TC V1R Thermistor (coil) Thermistor (discharge pipe) Thermistor (suction pipe) Thermistor (power module) Pressure switch (high) Pressure sensor (low) Signal transmission circuit Power module V2R-V3R V1T X6A X1M Y1E Y1S Y2S Z1C, Z2C Z3C, Z4C Z1F Z1F View A Reactor box Diode module IGBT Connector (Option) Terminal strip Expansion valve 4-way valve Solenoid valve Noise filter Noise filter Noise filter (with surge absorber) 2TW26746-1 • Outdoor Units • R-410A • RZQS-B7V3 9 Sound data 9-1 Sound pressure spectrum 3 Sound pressure level (dB) RZQS71BV3 - Heating Sound pressure level (dB) RZQS71BV3 - Cooling 3TW29067-1A 1 9 3TW29067-2A Octave band center frequency (Hz) NOTES 1 2 3 4 Octave band center frequency (Hz) NOTES Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa 1 2 3 4 Measuring location (discharge side) Measuring location (discharge side) Sound pressure level (dB) RZQS100BV3 - Heating Sound pressure level (dB) RZQS100BV3 - Cooling Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa 3TW29077-1A Octave band center frequency (Hz) 3TW29077-2A NOTES 1 2 3 4 Octave band center frequency (Hz) NOTES Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa 1 2 3 Measuring location (discharge side) • Split Sky Air • Outdoor Units 4 Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa Measuring location (discharge side) 22 • Outdoor Units • R-410A • RZQS-B7V3 9 Sound data 9-1 Sound pressure spectrum 9 Sound pressure level (dB) 1 RZQS125BV3 - Heating Sound pressure level (dB) RZQS125BV3 - Cooling 3TW29087-1A Octave band center frequency (Hz) 3TW29087-2A NOTES 1 2 3 4 23 Octave band center frequency (Hz) NOTES Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa 1 2 3 Measuring location (discharge side) • Split Sky Air • Outdoor Units 4 Data is valid at free field condition Data is valid at nominal conditions. dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic pressure 0dB = 20μPa Measuring location (discharge side) • Outdoor Units • R-410A • RZQS-B7V3 9 Sound data 9-2 Sound power spectrum 3 Sound power level (dB) RZQS100BV3 Sound power level (dB) RZQS71BV3 3TW29067-3 1 9 Octave band center frequency (Hz) 3TW29077-3 NOTES 1 2 3 Octave band center frequency (Hz) NOTES dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic intensity 0dB = 10E-6μW/m2 Measured according to ISO 3744 1 2 3 dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic intensity 0dB = 10E-6μW/m2 Measured according to ISO 3744 Sound power level (dB) RZQS125BV3 3TW29087-3 Octave band center frequency (Hz) NOTES 1 2 3 dB(A) = A-weighted sound pressure level (A-scale according to IEC) Reference acoustic intensity 0dB = 10E-6μW/m2 Measured according to ISO 3744 • Split Sky Air • Outdoor Units 24 • Outdoor Units • R-410A • RZQS-B7V3 10 Installation 10 - 1 Installation method RZQS71∼125BV3 A. Non stacked installation Legend 1 Suction side obstacle 10 Discharge side obstacle Left side obstacle Right side obstacle Top side obstacle Obstacle is present In these cases, close the bottom of the installation frame to prevent discharged air from being bypassed. In these cases, only 2 units can be installed. This situation is not allowed. Figures between ( ) indicate the dimensions only for the 100-125-140 class models. B. Stacked installation 1. Obstacles exist in front of the outlet side 2. Obstacles exist in front of the air inlet Do not stack more than one unit. About 100mm is required as the dimension for laying the upper outdoor unit’s drain pipe. Get the portion A sealed so that air from the outlet does not bypass. C. Multiple-row installation 1. Installation of one unit per row 2. Installing multiple units (2 units or more) in lateral connection per row Relation of dimensions of H, A, and L are shown in the table below. L≤H H<L L 0 < L ≤ 1/2 H 1/2 H < L Installation impossible A 150 (250) 200 (300) 3TW26739-4 25 • Split Sky Air • Outdoor Units • Outdoor Units • R-410A • RZQS-B7V3 10 Installation 10 - 2 Refnet pipe systems 3 1 10 • Split Sky Air • Outdoor Units 26 Inlet Inlet Inlet Inlet Inlet Inlet Inlet Outlet Outlet Inlet Inlet Outlet Outlet Outlet Outlet Outlet Outlet Inlet Inlet Inlet Inlet Outlet Outlet Outlet Outlet Outlet Outlet Outlet Outlet Outlet Outlet Outlet Outlet Outlet Outlet Outlet Outlet Outlet Outlet Outlet Suction gas side junction Inlet Inlet Inlet Inlet Outlet Inlet Discharge gas side junction Inlet Outlet Inlet Outlet Outlet Outlet Outlet Outlet Outlet Outlet Outlet Outlet Outlet Outlet Outlet Outlet Outlet Outlet Liquid side junction KHR22A10T KHR22A16T KHR22A30T KHR22A64T KHR22A75T KHR25A16T KHR25A30T KHR25A64T KHR25A75T • Split Sky Air • Outdoor Units KHR928A4T Others - Insulator - Installation manual - Insulator - Pipe reducers (suction) J15.9-J12.7 J25.4-J19.1-J15.9-J12.7 J31.8-J34.9 (3x) J38.1-J41.3 J31.8-J34.9-J41.3 - Pipe reducers (discharge) J12.7-J9.5 J19.1-J15.9 J31.8-J25.4 - Pipe reducers (liquid) J19.1-J15.9-J12.7 J12.7-J9.5-J6.4 - Installation manual - Insulator - Pipe reducers (suction) J15.9-J12.7 - Pipe reducers (discharge) J12.7-J9.5 - pipe reducers (liquid) J9.5-J6.4 - Installation manual - Insulator - Pipe reducers (suction) J25.4-J19.1 - Pipe reducers (discharge) J12.7-J9.5 J19.1-J15.9 - Installation manual - Insulator - Installation manual - Insulator - Pipe reducers (suction) J25.4-J19.1-J15.9 J31.8-J34.9 (3x) J38.1-J41.3 J31.8-J34.9-J41.3 - Pipe reducers (liquid) J19.1-J15.9-J12.7 J12.7-J9.5-J6.4 - Installation manual - Insulator - Pipe reducer (suction) J15.9-J12.7 - Pipe reducer (liquid) J9.5-J6.4 - Installation manual - Insulator - Pipe reducer (suction) J25.4-J19.1 - Installation manual - Insulator - Installation manual - Insulator - Installation manual KHR22A10H 4 branches KHR22A16H 8 branches KHR22A30H 8 branches KHR22A64H 8 branches 27 KHR25A16H 6 branches Inlet Inlet Inlet Inlet Inlet Inlet Inlet Outlet Liquid side header Outlet Outlet Outlet Outlet Outlet Outlet Discharge gas side header Inlet Inlet Inlet Inlet Inlet Inlet Suction gas side header Others 2TW21559-10B - Insulator - Pinched pipes - Installation manual - Pipe reducerd (suction) J15.9-J12.7 J31.8-J34.9-J41.3 J25.4-J19.1-J15.9-J12.7 - pipe reducers (liquid) J19.1-J15.9-J12.7 J12.7-J9.5-J6.4 - Pipe reducers (discharge) J12.7-J9.5 J19.1-J15.9 J31.8-J25.4 - Insulator - Pinched pipes - Installation manual - Insulator - Pinched pipes - Installation manual - Insulator - Pinched pipes - Installation manual - Pipe reducer (suction) J31.8-J34.9J41.3 - Insulator - Pinched pipes - Installation manual - Insulator - Pinched pipes - Installation manual - Insulator - Pinched pipes - Installation manual 1 KHR25A30H 8 branches 10 KHR25A64H 8 branches RZQS71-125BV3 • Outdoor Units • R-410A • RZQS-B7V3 Installation 10 - 2 Refnet pipe systems 10 • Outdoor Units • R-410A • RZQS-B7V3 11 Operation range 3 RZQS71-100-125-140BV3 Model name Cooling RZQS71BV3 1 RZQS100BV3 Indoor temp. (°CWB) 11 Operation range Allowable range of operation (warming-up) Heating Outdoor temp. (°CWB) Allowable range of operation (pull-down) Operation range Outdoor temp. (°CDB) RZQS125BV3 Indoor temp. (°CDB) Notes: - Depending on operation and installation conditions, the indoor unit can change over to freeze-up operation (indoor de-icing). - To reduce the freeze-up operation (indoor de-icing) frequency, it is recommended to install the outdoor unit in a location not exposed to wind. • Split Sky Air • Outdoor Units 3TW29063-1 28