Download Installation, Operation & Service Manual

Transcript
System Control
Installation, Operation &
Service Manual
WARNING
Improper installation, adjustment, alteration, service
or maintenance can result in death, injury or property
damage. Read the installation and operation
manuals thoroughly before installing or servicing
this equipment.
Installation must be done by an electrician qualified
in the installation of control systems for heating
equipment.
Installer
Please take the time to read and understand
these instructions prior to any installation.
Installer must give a copy of this manual to the owner.
Owner
Keep this manual in a safe place to provide your
serviceman with information should it become
necessary.
Roberts-Gordon
Roberts-Gordon Canada Inc.
1250 William Street
P.O. Box 44
Buffalo, New York 14240-0044
Telephone: 716.852.4400
Fax: 716.852.0854
Toll Free: 800.828.7450
241 South Service Road West
Grimsby, Ontario L3M 1Y7 Canada
Telephone: 905.945.5403
Fax: 905.945.0511
http://www.rg-inc.com
© Copyright 2000 Roberts-Gordon
Roberts-Gordon
Oxford Street
Bilston, West Midlands WV14 7EG UK
Telephone: +44 (0) 1902 494425
Fax:
+44 (0) 1902 403200
10091601NA
Rev B
06/00
TABLE OF CONTENTS
TABLE OF FIGURES
1. Introduction .............................................................. 1
®
1.1 What is a ROBERTS GORDON
System Control..................................................1
1.2 General Requirements...................................... 1
1.3 Check Installation Materials.............................. 1
1.4 Safety ................................................................1
2. Specifications .......................................................... 2
2.1
2.2
2.3
2.4
2.5
2.6
2.7
Material Specification........................................
Electrical Specification ......................................
Pump Specifications ........................................
Burner Electrical Ratings ..................................
Outside Air Supply Blower ................................
Indicator Lights ................................................
Terminal Block Guide........................................
2
2
2
2
2
2
2
Figure 1
Figure 2
Figure 3
Figure 4
Figure 5
Panel Layout.......................................................... 2
Terminal Block Guide ............................................ 2
System Control Cover Detail ................................ 3
Mounting Hole Layout............................................ 3
External Wiring Diagram
EP 100 and EP 201 120V 1ph Pump .................. 4
Figure 6 External Wiring Diagram
EP 301 120V 1ph Pump ...................................... 5
Figure 7 External Wiring Diagram EP 203 and EP 303
230V 3ph Pumps .................................................. 6
Figure 8 External Wiring Diagram 120V 1ph Pump with ......
Outside Air Blower.................................................. 7
Figure 9 System Control Troubleshooting Chart.................. 8
Figure 10 System Control Internal Components
Diagram .................................................................. 9
3. Installation Instructions .......................................... 3
3.1 Preparation ......................................................
3.2 Installing the System Control Panel..................
3.3 Select the External Wiring Diagram for
the Installation ..................................................
3.4 Important Voltage Selection..............................
3
3
3
3
4. Typical External Wiring Diagrams .......................... 4
4.1 External Wiring Diagram EP 100 and
EP 201 120V 1ph Pump .................................. 4
4.2 External Wiring Diagram EP 301 120V
1ph Pump ........................................................ 5
4.3 External Wiring Diagram EP 203 and EP 303
230V 3ph Pump ................................................ 6
4.4 Outside Air Blower External Wiring....................7
5. Troubleshooting ...................................................... 8
5.1 Sequence of Operation .................................... 8
6. Replacement Parts .................................................. 9
6.1 Replacement Parts List .................................... 9
6.2 Replacement Parts Instructions ......................10
7. The ROBERTS GORDON® System Control
Warranty....................................................................11
© 2000
All rights reserved. No part of this work covered by the copyrights herein may be reproduced
or copied in any form or by any means - graphic, electronic, or mechanical, including
photocopying, recording, taping or information storage and retrieval systems - without the
written permission of Roberts-Gordon.
Printed in the U.S.A.
SECTION
SECTION 1: INTRODUCTION
1.1
1.3.4
The cable used for all wiring must be rated for line
voltage up to 250V.
Failure to follow these instructions will result in
death or electrical shock.
The system control, burners, pump and outside
air blower must be electrically grounded in accordance with the National Electrical Code®
ANSI/NFPA 70 - latest revision.
Before proceeding with the installation of the
ROBERTS GORDON® System Control, check the
following points:
1.3
CHECK INSTALLATION MATERIALS
1.3.1
Thermostats
Only use 24V thermostats with the ROBERTS
GORDON® System Control. Do not use "power
stealing" 24V thermostats. ROBERTS GORDON®
offers a selection of low voltage thermostats
approved for use with the system control.
The thermostats measure the air temperature in
the building. It is important that the thermostat is
located in an area within the heated zone at occupant level. Do not place thermostat in an area
shaded from the low-intensity, infrared heating
system.
Proving switch must be installed on all ROBERTS
GORDON® systems to ensure safety and operation.
System will not operate without proving switch.
Failure to follow these instructions can result in product
damage.
1.4
SAFETY
Your Safety is Important to Us! This symbol is used throughout the manual to notify you of possible fire, electrical or burn
hazards. Please pay special attention
when reading and following the warnings.
WARNING
Installation, Service and Annual Inspection of
controller must be done by an electrician qualified
in the installation of control systems for heating
equipment.
Installation, Service and Annual Inspection must be
done by a contractor qualified in the installation and
service of gas-fired heating equipment.
Read this manual carefully before installation,
operation, or service of this equipment.
Failure to follow these instructions can result in
death, injury or property damage.
Electrical Installation Materials
A 1ph 16A, 120V power supply to the control
panel must be installed in accordance with the
most current National Electrical Code®, local
codes and any site specific diagrams.
Total load powered by the panel must not exceed
16A. Loads totaling more than 16A must be powered from an additional power supply circuit by
the use of a load relay package.
1.3.3
CAUTION
GENERAL REQUIREMENTS
Failure to comply with the installation instructions
will invalidate the limited warranty set out on
Page 11, Section 7.
1.3.2
Vacuum Proving Switch
A vacuum proving switch (P/N 90430600), preset
at 1.7" w.c. is required for installation on the inlet
of the pump. This switch is required to interlock
the operation of the pump with the control panel.
The System Control is capable of giving four
zones of temperature control. The control will give
power output to one pump.
1.2
INTRODUCTION
the pump. The load relay package is required with
the blower. See Page 7, Section 4, Figure 8, for
wiring detail.
WHAT IS A ROBERTS GORDON® SYSTEM
CONTROL?
The ROBERTS GORDON® System Control is an
electronic controller designed for the control of
CORAYVAC® and VANTAGE® EV systems.
1:
Outside Air Supply Blower
For optimum heater performance and safe heating conditions, inspect and maintain heater(s)
before every heating season and as necessary.
Also, know and maintain heater clearances to
combustibles, see heater Installation, Operation
and Service manual for further details. If you
require additional manuals, contact your
ROBERTS GORDON® independent distributor or
Roberts-Gordon at (716) 852-4400 or (800) 8287450 in the U.S., (905) 945-5403 in Canada or at
www.rg-inc.com.
If used, the optional outside air blower is to be
controlled in parallel with the pump. The blower
incorporates a pressure switch which must be
wired in series with the vacuum proving switch on
1
SYSTEM CONTROL INSTALLATION MANUAL
SECTION 2: SPECIFICATIONS
SYSTEM CONTROL
Quality in Any Language
TM
LINE POWER
PUMP POWER
PROVING SWITCH
ZONE 1
ZONE 2
ZONE 3
ZONE 4
U.S.A.
Canada
U.K.
Internet




1.716.852.4400
1.905.945.5403
+44 (0) 1902 494425
www.rg-inc.com
WARNING: Disconnect from electrical supply before removing this cover
FIGURE 1 - Panel Layout
2.1
2.6
MATERIAL SPECIFICATION
Enclosure Material: ABS (UL 94-5VA Rated)
Weight:
1.1 lbs
Dimensions:
7.9" x 11.4" x 2.4"
(199 x 290 x 62 mm)
Protection:
Rating IP20
2.2
Pump Relay:
Thermostats:
2.3
16A 120V 50/60Hz
Single pole 4.4A 120V AC
(resistive)
Single pole 12A 120V AC
(resistive) 1HP motor rated.
Low voltage 12V DC
3. PROVING SWITCH, when lit, indicates that
the proving switch is closed.
4. ZONE, when lit, indicates which zone relay
is on.
2.7
TERMINAL BLOCK GUIDE
Page 2, Section 2, Figure 2 is a guide to the terminal abbreviations.
Ground
Ground connection
for burners
and pump
current:
3ph
N/A
3.0A
4.2A
BURNER ELECTRICAL RATINGS
CORAYVAC® burners: 120V, 60Hz, 1ph 0.2A
VANTAGE® EV burners: 120V, 60Hz, 1ph 0.2A
2.5
2. PUMP POWER, when lit, indicates the relay
for power to the pump is energized.
PUMP SPECIFICATIONS
Full load
1ph
EP 100 pump 1/3HP:
4.8A
EP 200 series pumps 3/4HP:
6.6A
EP 300 series pumps 1-1/2 HP: 16.0A
2.4
1. LINE POWER, when lit, indicates supply on
to the panel.
ELECTRICAL SPECIFICATION
Supply:
Zone Relay:
INDICATOR LIGHTS (PAGE 2, SECTION 2,
FIGURE 1)
G
N
L
PUMP
Z1
Z2
OUTSIDE AIR SUPPLY BLOWER
Z3
2.2A Run (Full load current) at 120V, 60Hz,
1ph, 2.2A
Z4
T1
T2
T3
T4
PS
2
N
L
N
L
N
L
N
L
N
L
C
C
C
C
C
Ground
Neutral
Live
Power
Supply
Pump Live
& Neutral
Zone1 Burners
Live & Neutral
Zone 2 Burners
Live & Neutral
Zone 3 Burners
Live & Neutral
Zone 4 Burners
Live & Neutral
Thermostats
12V DC output
Proving Switch
FIGURE 2 - Terminal Block Guide
SECTION
SECTION 3: INSTALLATION
3.2.6
Installation of the System Control and the associated external electrical wiring must be completed
by an electrician qualified in the installation of control systems for heating equipment.
3.1
4 x DIA. 0.2" (5mm)
6.85"
(174 mm)
Before installing the System Control, observe the
following:
Ensure that you have a copy of the site layout for
the project that identifies clearly the separate
zones.
3.1.2
Read Page 1, Section 1.3 carefully to ensure the
correct installation materials are available.
3.2
INSTALLING THE SYSTEM CONTROL PANEL
3.2.1
3.2.2
INSTALLATION
Fit the cable plate, provided with the System
Control Panel, in the slot at the top of the System
Control panel.
PREPARATION
3.1.1
3:
10.7" (272 mm)
FIGURE 4 - Mounting Hole Layout
3.3
SELECT THE EXTERNAL WIRING DIAGRAM
FOR THE INSTALLATION
Choose a mounting location for the System
Control. It is advisable to choose a visible location
near the pump.
3.3.1
Use Page 4, Section 4, Figure 5 for the external
wiring of the burners, thermostats and pressure
switch.
Remove the cover of the System Control by
removing the four securing screws.
3.3.2
Use the table below to select the correct pump
external wiring diagram.
Pump
EP 100
EP 201
EP 301
EP 203
EP 303
See Page 3, Section 3, Figure 3 for cover detail.
Pry the clip off using a flat blade screw driver in the
groove (3). This will reveal the securing screw (2).
Repeat this for each corner of the cover.
Roberts-Gordon provides, at an additional cost,
the following IEC contactor and enclosure
required for the EP 301 pump, the part numbers
are listed below.
1
2
3
5
For 120V AC Connection
Description
P/N
10050006
Contactor 120V AC EP 301 1ph
10001705 Contactor IEC 16A 120V AC
10001001 Enclosure IEC metal 8” x 5” x 5”
Nema 1
Roberts-Gordon provides, at an additional cost,
the following IEC contactor and overload starter
package required for 3ph pumps, the contents are
listed below:
4
ITEM
1
2
3
4
5
PN
10000701
10000700
NA
NA
10090500
Supply Voltage Page Section Figure
120V 1ph
4
4
5
120V 1ph
4
4
5
120V 1ph
5
4
6
230V 3ph
6
4
7
230V 3ph
6
4
7
DESCRIPTION
CLIP COVER PLASTIC
SCREW M3X22 PAN HD BZP
LEVER SLOT
SECURING SCREW HOLE
SYSTEM CONTROL LID ASSEMBLY
FIGURE 3 - System Control Cover Detail
3.2.3
Disconnect the ribbon cable from the System
Control panel board. Place the cover and the hardware in a safe place for refitting after the external
wiring connections have been made.
3.2.4
Position the mounting hole location of the System
Control per Figure 4, Section 3.
3.2.5
Remove the knockouts required for the conduit
entry into the System Control panel.
P/N
Description
10050001
Starter 120V AC EP 203/303 3ph
10001001 Enclosure IEC metal 8" x 5" x 5"
Nema 1
10001701 Contactor IEC 9A 120V AC
10001706 Overload IEC 1.6-5.0A 3ph
3.3.3 If an outside air blower is to be used with any of
the above options, see Page 7, Section 4, Figure
8, or the external wiring diagram.
3.4
IMPORTANT: VOLTAGE SELECTION
The System Control can be used with either 115V
or 230V single phase. Ensure the voltage selector switch is set to 115V. See Page 9, Section 6,
Figure 10, ITEM 2.
3
SYSTEM CONTROL INSTALLATION MANUAL
SECTION 4: TYPICAL EXTERNAL WIRING DIAGRAMS
Pump
All burners must be
connected to Ground
(Not shown)
Zone 1 Zone 2 Zone 3 Zone 4
Low voltage thermostats
located in heated zone
Zone Zone Zone Zone
4
1
2
3
120V
1ph
60HZ
Pressure switch
located at pump
120V
1ph
60HZ
12V DC
Low voltage must
be enclosed within
the slotted cable
trunking fitted inside
the controller
L
Z4
C
Z3
PS
Z2
C
Z1
T4
PUMP
C
N L
T3
NL
C
NL
T2
N L
C
N L
T1
L
Ground
N
Ground
G
N
System Controller
FIGURE 5 - External Wiring Diagram ROBERTS GORDON® EP 100 and EP 201 120V 1ph Pump
4.1
EP 100 OR EP 201 120V 1PH PUMP
EXTERNAL WIRING DIAGRAM
The external wiring diagram above shows the connections for four zones of system burners. System
burners can be either CORAYVAC® or VANTAGE®
EV.
The zones are connected to a single pump. The
external wiring diagram above shows connection
to an EP 100 or EP 201 pump.
4
4.1.1
External wiring connection details
The cable used for all the wiring must be rated for
line voltage up to 250V.
The low voltage circuit conforms with Class 2 separation of circuit requirements. National Electrical
Codes® for wiring class 2 low voltage circuits must
be followed. Disconnect electrical supply before
servicing.
SECTION
EP 301
Pump
IEC contactor
P/N 10050006
rated for the
EP 301 pump
motor
6
120V
1ph
60 Hz
5
All burners must be
connected to Ground
(Not shown)
Low voltage thermostats
located in heated zone
2
M
N
1
Zone Zone Zone
1
2
3
L
Zone
4
Individual supply
for pump rated for
total full load current
(See Page 2, Section 2.3
for details)
Pressure switch
located at pump
L
12V DC
Z4
C
Z3
PS
Z2
C
Z1
T4
PUMP
C
NL
T3
NL
C
NL
T2
NL
C
NL
T1
L
N
N
Ground
4
3
G
Ground
TYPICAL EXTERNAL WIRING DIAGRAMS
Zone 1 Zone 2 Zone 3 Zone 4
The power supply for each
pump must be separate
from the controller supply
120V
1ph
60 Hz
Never directly connect the
controller relay terminals to the
pump motor.
4:
System Control
FIGURE 6 - External Wiring Diagram ROBERTS GORDON® EP 301 120V 1ph Pump
4.2
EP 301 120V 1PH EXTERNAL WIRING
DIAGRAM
The external wiring diagram above shows the connections for four zones of system burners. System
burners can be either CORAYVAC® or VANTAGE®
EV.
The zones are connected to a single pump. The
external wiring diagram above shows connection
to an EP 301 1ph motor.
4.2.1
External wiring connection details
The cable used for all the wiring must be rated for
line voltage up to 250V.
The low voltage circuit conforms with Class 2 separation of circuit requirements. National Electrical
Codes® for wiring class 2 low voltage circuits must
be followed. Disconnect electrical supply before
servicing.
5
SYSTEM CONTROL INSTALLATION MANUAL
3ph
Pump
All burners must be
connected to Ground
(Not shown)
Zone 1 Zone 2
Motor starter
Zone 3 Zone 4
OL
230V
3ph
60HZ
M
Pressure switch
located at pump
12V DC
L
Z3
Z4
T1
C
Z2
PS
Z1
C
PUMP
T4
NL
C
NL
T3
NL
C
NL
T2
NL
C
N
L
Ground
Zone
4
120V
1ph
60HZ
N
120V
1ph
60HZ
Zone Zone Zone
3
1
2
G
L3
L2
L1
Ground
Low voltage thermostats
located in heated zone
System Control
FIGURE 7 - External Wiring Diagram EP 203 and EP 303 230V 3ph Pump
4.3
EP 203 OR EP 303 230V 3PH PUMP
EXTERNAL WIRING DIAGRAM
The external wiring diagram above shows the connections for four zones of system burners. System
burners can be either CORAYVAC® or VANTAGE®
EV.
The zones are connected to a single pump. The
external wiring diagram above shows connection
to an EP 203 or EP 303 3ph pump.
6
4.3.1
External Wiring Connection Details
The cable used for all the wiring must be rated for
line voltage up to 250V.
The low voltage circuit conforms with Class 2 separation of circuit requirements. National Electrical
Codes® for wiring class 2 low voltage circuits must
be followed. Disconnect electrical supply before
servicing.
SECTION
Typical wiring for Load Relay
Package (P/N 05023000)
Outside Air
Blower
Live out to the
outside air
blower
Coil connections
to Pump L & N
Outputs from
Control Panel
4:
TYPICAL EXTERNAL WIRING DIAGRAMS
All burners must be
connected to Ground
(Not shown)
Pump
Zone Zone Zone Zone
1
2
3
4
Live in
Low voltage thermostats
located in heated zone
Pressure switch
located at pump
Relay Receptacle
Back Plate
L
Z3
Z4
C
Z2
PS
Z1
C
PUMP
T4
NL
C
NL
T3
NL
C
NL
T2
NL
C
N
T1
Ground
12V DC
L
Ground
120V
1ph
60HZ
Pressure switch
located at outside
air blower
120V
1ph
60HZ
N
120V
1ph
60HZ
CR
G
N
L
Zone Zone Zone Zone
4
1
2
3
System Control
FIGURE 8 - External wiring diagram ROBERTS GORDON® EP 100 or EP 201 120V 1ph Pump with outside air blower
4.4
OUTSIDE AIR BLOWER EXTERNAL WIRING
DIAGRAM
The external wiring diagram above shows the connections for four zones of system burners. System
burners can be either CORAYVAC® or VANTAGE®
EV.
The zones are connected to a single pump. The
external wiring diagram above shows connection
to an EP 100 or EP 201 1ph motor. The diagram
also shows the connection via a load relay to the
optional outside air blower.
4.4.1
External Wiring Connection Details
The cable used for all the wiring must be rated for
line voltage up to 250V.
The low voltage circuit conforms with Class 2 separation of circuit requirements. National Electrical
Codes® for wiring class 2 low voltage circuits must
be followed. Disconnect electrical supply before
servicing.
7
SYSTEM CONTROL INSTALLATION MANUAL
SECTION 5: TROUBLESHOOTING
5.1
SEQUENCE OF OPERATION
a.
On demand for heat, the panel will send power to
the pump. The pump will begin operation.
b.
Once vacuum is established, the vacuum proving
switch at the pump will close.
c.
The panel sends power to the burners. The burners will go through a 45 second purge and cycle
time.
Is the line power indicator
on? See Page 2,
Section 2, Figure 1.
No
Check the power supply
to the system control
panel. Is it on?
Yes
No
d.
Once flame is established, the heater will remain
in operation until such time as either a lockout
condition occurs or the heating is turned off by
the thermostat.
e.
After the heating is turned off, the pump will
continue operation for 2 minutes, post purge.
Check the fuse. Is
it OK? See Page 9,
Section 6, Figure 10,
(ITEM 1)
Check the low voltage fuse.
Is it OK? See Page 9,
Yes Section 6, Figure 10,
(ITEM 4)
No
No
Replace fuse with
P/N 10000202.
Rectify power supply
problem.
Check if the ribbon cable
Yes is securely located
at both ends.
Replace fuse with
P/N 10000202.
Yes
Adjust thermostat set
point to call for heat.
Does the pump
come on?
Check the voltage selector,
is it set to 115V? See
No Page 9, Section 6,
Yes
Figure 10, (ITEM 2)
No
Set the selector to 115 V.
Is external wiring to the
pump OK?
Yes
Is the correct overload
selected for the
pump?
See Page 2, Section 2.3.
No
No
Rectify.
Fit the correct overload.
Yes
Refer to burner troubleshooting in either the
CORAYVAC ® or
VANTAGE ® EV
Installation, Operation and
Service Manuals.
Yes
Does the zone light
come on?
Is the thermostat connected
to the correct terminal at the
Yes system control. See Page 4,
Section 4, Figure 5.
Does the proving switch
No light come on? See Page 2,
Section 2, Figure 1.
Yes
No
Is external wiring to the
proving switch OK?
No
Yes
No
Refer to burner troubleshooting in either the
CORAYVAC ® or
VANTAGE ® EV
Installation, Operation and
Service Manuals.
Contact Roberts-Gordon.
at
www.rg-inc.com
Rectify.
Yes
Do the burners in the
zone come on?
No
Is external wiring to the
zone OK? See Page 4,
Section 4, Figure 5.
Yes
No
Rectify.
Yes
Troubleshoot ends.
Contact Roberts-Gordon.
at
www.rg-inc.com
FIGURE 9 - System Control Troubleshooting Chart
8
Has the system been
commissioned?
Yes
Refer to burner troubleshooting in either the
CORAYVAC ® or
VANTAGE ® EV
Installation, Operation and
Service Manuals.
Refer to the burner start up
®
No instructions in either the CORAYVAC
or VANTAGE® EV Installation, Operation
and Service Manuals.
Rectify.
SECTION
6:
REPLACEMENT PARTS
SECTION 6: REPLACEMENT PARTS
WARNING
Use only genuine ROBERTS GORDON ® replacement parts.
Use of parts not specified by Roberts-Gordon voids warranty.
Ground
NL
NL
NL
NL
PUMP
Z1
Z2
Z3
Z4
C
C
C
C
C
NL
T1
T2
T3
T4
PS
L
N
G
Failure to follow these instructions can result in death, injury
or property damage.
1
ROBERTS GORDON®
System Controller
PN 10090100
2
3
4
5
FIGURE 10 - System Control Internal Components Diagram
6.1
REPLACEMENT PARTS LIST
Part Number
Description
1. 10000202
Fuse Anti Surge 500mA
2. NA
Voltage Selector Switch
3. NA
Transformer
4. 10000202
Fuse Anti Surge 500mA
5. 10000200
Fuse Fast Blow 315mA
6. 10000702
Cable Entry Plate not shown
7. 10000703
Clip Cover and Screw (4 pack)
not shown
9
SYSTEM CONTROL INSTALLATION MANUAL
6.2
REPLACEMENT PARTS INSTRUCTIONS
6.2.4
WARNING
This fuse protects the System Control circuit
board.
Electrical Shock Hazard
If the fuse needs replacing, the following steps
must be taken.
Disconnect electrical supply before
performing service or maintenance.
Turn off the power to the System Control.
Remove the clips and screws from the cover panel
and remove the cover of the System Control. See
Page 3, Section 3.2.2 for details.
Failure to follow these instructions will
result in death or electrical shock.
6.2.1
Disconnect the ribbon cable from the Main Board
only, leaving the ribbon attached to the cover.
10000202 Fuse Anti Surge 500mA
This fuse protects the System Control from power
surges, lightning and incorrect wiring.
Locate the fuse (Page 9, Section 6, Figure 10,
ITEM 4) and remove the fuse with a fuse pulling
tool.
If the fuse needs replacing, the following steps
must be taken.
Turn off the power to the System Control.
Replace with a new fuse rated to 500mA anti
surge.
Remove the clips and screws from the cover and
remove the cover of the System Control. See
Page 3, Section 3.2.2 for details.
Reconnect the ribbon cable to the Main Board and
replace cover.
Disconnect the ribbon cable from the Main Board
only, leaving the ribbon attached to the cover.
Locate the fuse (Page 9, Section 6, Figure 10,
ITEM 1) and remove the fuse with a fuse pulling
tool.
Replace with a new fuse rated at 500mA anti
surge.
Reconnect the ribbon cable to the Main Board and
replace cover.
6.2.2
Voltage Selector Switch
The voltage selector switch must display 115V for
use in North America.
6.2.3
10000202 Fuse Anti Surge 500mA
6.2.5
10000200 Fuse Fast Blow 315mA
This fuse protects the inputs connected to the
System Control circuit board.
If the fuse needs replacing, the following steps
must be taken:
Turn off the power to the System Control.
Remove the clips and screws from the cover panel
and remove the cover of the System Control. See
Page 3, Section 3.2.2 for details.
Disconnect the ribbon cable from the Main Board
only, leaving the ribbon attached to the cover.
Transformer
Locate the fuse (Page 9, Section 6, Figure 10,
ITEM 5) and remove the fuse with a fuse pulling
tool.
The transformer on the board cannot be replaced.
Replace with a new fuse rated to 315mA fast blow.
Reconnect the ribbon cable to the Main Board and
replace cover.
10
SECTION
SECTION 7: THE ROBERTS GORDON®
SYSTEM CONTROL WARRANTY
ROBERTS-GORDON WILL PAY FOR:
For 36 months from the date of purchase by the original
consumer or 18 months from date of shipment by RobertsGordon, whichever occurs first: we will provide, free of
charge, replacement parts for any part of the ROBERTS
GORDON® System Control that fails because of a manufacturing or material defect.
ROBERTS GORDON® replacement parts are warranted for
the period of the original ROBERTS GORDON® System
Control Warranty.
ROBERTS-GORDON WILL NOT PAY FOR:
Service trips, service calls and labor charges.
Shipment of replacement parts.
Damage due to:
Failure to install, operate or maintain the ROBERTS
GORDON® System Control as directed in Installation,
Operation and Service Manual. You must follow
requirements printed in this manual.
Misuse, abuse, neglect or modification of the
ROBERTS GORDON® System Control in any way.
Improper service, use of replacement parts or accessories that are not specified by Roberts-Gordon.
Improper installation, or any relocation of the
ROBERTS GORDON® System Control after initial
installation.
Incorrect supply, accident, fire, flood, acts of God or
other casualty.
Use of the ROBERTS GORDON® System Control for
other than its intended purpose.
Use of the ROBERTS GORDON® System Control in a
corrosive atmosphere or any atmosphere containing
contaminants.
Shipping. Claim must be filed with carrier.
WARRANTY IS VOID IF:
7:
THE ROBERTS GORDON® SYSTEM CONTROL WARRANTY
READ YOUR OPERATION AND INSTALLATION
MANUALS
If you have questions about your ROBERTS GORDON®
System Control, contact your installing professional. Should
you need replacement parts or have additional questions,
call or write Roberts-Gordon:
U.S.A.
1250 William Street
P.O. Box 44
Buffalo, New York 14240-0044
Telephone: 716.852.4400
Fax: 716.852.0854
Canada
241 South Service Road, West
Grimsby, Ontario L3M 1Y7
Telephone: 905.945.5403
Fax: 905.945.0511
On the web at:
www.rg-inc.com
Roberts-Gordon's liability, and your exclusive remedy,
under this warranty or any implied warranty (including
the implied warranties of merchantability and fitness
for a particular purpose) is limited to providing replacement parts during the term of this warranty. Some jurisdictions do not allow limitations on how long an implied warranty lasts, so this limitation may not apply to you. There are
no rights, warranties or conditions, expressed or implied,
statutory or otherwise, other than those contained in this
warranty.
Roberts-Gordon shall in no event be responsible for
incidental or consequential damages or incur liability
for damages in excess of the amount paid by you for
the ROBERTS GORDON® System Control. Some jurisdictions do not allow the exclusion or limitation of incidental or
consequential damages, so this limitation or exclusion may
not apply to you. This warranty gives you specific legal
rights, and you may also have other rights which vary from
jurisdiction to jurisdiction.
You cannot prove original purchase date and required
annual maintenance history.
Roberts-Gordon shall not be responsible for failure to perform under the terms of this warranty if caused by circumstances out of its control, including but not limited to fire,
flood, strike, government or court orders, unavailability of
supplies, parts or power. No person is authorized to assume
for Roberts-Gordon any other warranty, obligation or liability.
The data plate and/or serial number are removed, defaced,
modified or altered in any way.
LIMITATIONS ON AUTHORITY OF REPRESENTATIVES:
®
The ROBERTS GORDON System Control is not installed
by a electrician qualified in the installation of control systems for heating equipment.
®
The ROBERTS GORDON System Control is transferred.
This warranty is nontransferable.
Roberts-Gordon is not permitted to inspect the damaged
controller and/or component parts.
No representative of Roberts-Gordon, other than an
Executive Officer, has authority to change or extend these
provisions. Changes or extensions shall be binding only if
confirmed in writing by Roberts-Gordon's duly authorized
Executive Officer.
11