Installation
CHLORIDE LINEAR Plus/RM
Common mains feeding
If UPS with backfeed protection shall be feeded from mains 1 only please
connect L (mains 2) with L1 (mains 1) and N (mains 2) with N (mains 1)
inside customers feeding distribution. Cable bridge between input terminals
of the UPS may not be connected.
Fig. 16: RM UPS 6 and 10 kVA and external isolation device (in this
example a magnetic contactor (MC)
Operation
If bypass thyristor is short (short circuit) and UPS runs in double conversion
mode (online) the following steps follow:
• the backfeed relay opens and
• the message „backfeed active“ is shown on the LCD panel