Download Injection Controller Program User Manual (for the FloBoss 107 and

Transcript
Injection Controller Program User Manual (FB107+ROC800)
Point Type 22/198: Injection Controller Configuration Parameters
Parm
#
Name
Access
System or
User Update
Data
Type
Length
Range
Default
Version
Description of functionality and
meaning of values
39
Meter Element Type
R/W
User
UINT8
1
0-4
0
1.06
Indicates the type of meter
element:
0 = Pulse Output
1 = Orifice
2 = V-Cone
3 = Accumulator
4 = Square Root DP Proportional
40
Output Units
R/W
User
UINT8
1
0-1
0
1.00
Selects the units of measure class
to use for input and output to the
calculation:
0 = English
1 = Metric
41
Water Density
R/W
User
FL
4
Any positive
floating point
number
1.0
1.00
Sets the value to use for density of
water in water calculations.
42
Water Density Units of
Measure
R/W
User
UINT8
1
0-3
3
1.00
Indicates the units of measure for
the water density input value:
0 = Kg/M3
1 = lb/ft3
2 = lb/BBL
3 = specific gravity
43
Steam Quality Source
Type
R/W
User
UINT8
1
0-1
0
1.00
Indicates the source of the steam
quality value (when applicable).
This is only used when the flow
calculation fluid type is 2-phase
saturated steam:
0 = use fixed value
1 = read value from TLP
44
Steam Quality Fixed Value
R/W
User
FL
4
0 - 100
100.0
1.00
Sets the fixed value to use for
steam quality in percentage. This
is only used when the flow
calculation fluid type is 2-phase
steam and steam quality source
type is “fixed value”.
Issued Aug-14