Download Lochinvar PUMP-REC-05 User's Manual

Transcript
PUMP
Recommendation
PUMP-Rec-05 Rev B
PUMP RECOMMENDATION FOR
COPPER-FIN 0495-0745 WATER HEATER
Pump Specifications
Part No.
ARM3044PAB
HorsePower
1/4
Flanges
2"
Valute Material
Bronze
Flange Material
Bronze
Vendor
Armstrong
Vendor Product Series
LS45
Orientation
Horizontal
Installation Specifications
Recommended for
Pump
Based on
Model Numbers
Maximum GPM
Copper-Fin Wtr Htr, CW(N,L) 0495-0745
Based on
55 GPM
Single Water Heater piped to Single Storage Tank
Based on
Minimum Pipe Diameter
Connecting piping
2"
Maximum 45 feet straight pipe with 6-Elbows, 2-Unions,2-Ball Valves and 1-Cold Water Inlet Tee
IMPORTANT: Read the Copper-fin 495-2065 Installation and Operation Manual. If the planned system exceeds
the pump capacity in flow and/or head see “Pump Curves-All Pumps” for alternate pumps and pump curves.
15-3/4”
A
12-1/2”
C
OIL PORT
20
TOTAL HEAD IN FEET
ARM3044PAB
Installation Type
15
LS-45
10
5
0
10
20
30
40
50
60
70
80
90
CAPACITY IN U.S. GALLONS PER MINUTE
10”
B
D
1
100
110
PUMP
Recommendation
PUMP-Rec-05
PUMP RECOMMENDATION FOR
COPPER-FIN 0986-2066 WATER HEATER
Pump Specifications
Part No.
ARM3024PAB
HorsePower
1/2
Flanges
2-1/2"
Valute Material
Brass
Flange Material
Brass
Vendor
Armstrong
Vendor Product Series
2B1050
Orientation
Horizontal
Installation Specifications
Recommended for
Pump
Based on
Model Numbers
Maximum GPM
Copper-Fin Wtr Htr, CW(N,L) 0986-2066
ARM3024PAB
Based on
90 GPM
Installation Type
Single Water Heater piped to Single Storage Tank
Based on
Minimum Pipe Diameter
Connecting piping
2-1/2"
Maximum 45 feet straight pipe with 6-Elbows, 2-Unions,2-Ball Valves and 1-Cold Water Inlet Tee
IMPORTANT: Read the Copper-fin 495-2065 Installation and Operation Manual. If the planned system exceeds
the pump capacity in flow and/or head see “Pump-REC-All Pumps” for alternate pumps and pump curves.
19-1/2”
A
16”
C
OIL PORT
B
11-1/2”
D
2